COMPARISON OF STATCOM AND TCSC ON VOLTAGE STABILITY USING MLP INDEX

Similar documents
VOLTAGE STABILITY IMPROVEMENT IN POWER SYSTEM BY USING STATCOM

Voltage Sag Mitigation in IEEE 6 Bus System by using STATCOM and UPFC

Power Quality Improvement Using Statcom in Ieee 30 Bus System

Overview of Flexible AC Transmission Systems

Enhancement of Voltage Stability Margin Using FACTS Controllers

Maintaining Voltage Stability in Power System using FACTS Devices

TRANSMISSION LOSS MINIMIZATION USING ADVANCED UNIFIED POWER FLOW CONTROLLER (UPFC)

Concepts And Application Of Flexible Alternating Current Transmission System (FACTS) In Electric Power Network

Computation of Sensitive Node for IEEE- 14 Bus system Subjected to Load Variation

Improving Power System Transient Stability by using Facts Devices

Implementation of FC-TCR for Reactive Power Control

PSAT Model- Based Voltage Stability Analysis for the Kano 330KV Transmission Line

Enhancement of Power Quality in Transmission Line Using Flexible Ac Transmission System

Steady State Voltage Stability Enhancement Using Shunt and Series FACTS Devices

Performance Analysis of Transmission Line system under Unsymmetrical Faults with UPFC

A SIMPLE CONTROL TECHNIQUE FOR UNIFIED POWER FLOW CONTROLLER (UPFC)

Simulation of Voltage Stability Analysis in Induction Machine

INTRODUCTION. In today s highly complex and interconnected power systems, mostly made up of thousands of buses and hundreds of generators,

A Review on Reactive Power Compensation Technologies

ELG4125: Flexible AC Transmission Systems (FACTS)

Power Flow Simulation of a 6-Bus Wind Connected System and Voltage Stability Analysis by Using STATCOM

Paper ID: EE19 SIMULATION OF REAL AND REACTIVE POWER FLOW ASSESSMENT WITH FACTS CONNECTED TO A SINGLE TRANSMISSION LINE

POWER SYSTEM OPERATION AND CONTROL USING FACTS DEVICES

Tiruchengode, Tamil Nadu, India

Implementation SVC and TCSC to Improvement the Efficacy of Diyala Electric Network (132 kv).

An Overview of Facts Devices used for Reactive Power Compensation Techniques

INSTALLATION OF CAPACITOR BANK IN 132/11 KV SUBSTATION FOR PARING DOWN OF LOAD CURRENT

POSSIBILITIES OF POWER FLOWS CONTROL

Optimal Placement of Distributed Generation for Voltage Stability Improvement and Loss Reduction in Distribution Network

STABILITY ANALYSIS OF DISTRIBUTED GENERATION IN MESH DISTRIBUTION NETWORK IN FREE AND OPEN SOURCE SOFTWARE

Modelling and Analysis of Thyristor Controlled Series Capacitor using Matlab/Simulink

Optimal placement of SVCs & IPFCs in an Electrical Power System

CHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM

Power Flow Control through Transmission Line with UPFC to Mitigate Contingency

A Transient Free Novel Control Technique for Reactive Power Compensation using Thyristor Switched Capacitor

Enhancement of Power System Stability Using Thyristor Controlled Series Compensator (TCSC)

Simulation of real and reactive power flow Assessment with UPFC connected to a Single/double transmission line

Systematic Survey for Role of Reactive Power Compensating Devices in Power System

An Approach for Formation of Voltage Control Areas based on Voltage Stability Criterion

Fuzzy Based Unified Power Flow Controller to Control Reactive Power and Voltage for a Utility System in India

Transient Stability Assessment and Enhancement in Power System

Contingency Ranking and Analysis using Power System Analysis. Toolbox (PSAT)

Enhancement of Voltage Stability Through Optimal Placement of TCSC

Performance of FACTS Devices for Power System Stability

Wind Power Plants with VSC Based STATCOM in PSCAD/EMTDC Environment

Reactive Power Management Using TSC-TCR

Adaptive Power Flow Method for Distribution Systems With Dispersed Generation

DESIGN AND SIMULATION OF UPFC AND IPFC FOR VOLTAGE STABILITY UNDER A SINGLE LINE CONTINGENCY: A COMPARATIVE STUDY

Management of Congestion in the Deregulated Energy Market

IMPACT OF THYRISTOR CONTROLLED PHASE ANGLE REGULATOR ON POWER FLOW

OPTIMAL Placement of FACTS Devices by Genetic Algorithm for the Increased Load Ability of a Power System

Okelola, M. O. Department of Electronic & Electrical Engineering, Ladoke Akintola University of Technology, P.M.B. 4000, Ogbomoso, Nigeria

Improvement In Reliability Of Composite Power System Using Tcsc, Upfc Of 6 Bus Rbts A Comparison

Multi-Line power Flow Control Using Interline Power Flow Controller (IPFC) in Power Transmission system

Dynamic Control of Grid Assets

Statcom Operation for Wind Power Generator with Improved Transient Stability

ABSTRACT I. INTRODUCTION. Nimish Suchak, VinodKumar Chavada, Bhaveshkumar Shah, Sandip Parmar, Vishal Harsoda

APPLICATION OF FACTS DEVICES FOR POWER SYSTEM TRANSIENT STABILITY ENHANCEMENT JOEL RUTTO SUTTER MASTER OF SCIENCE

Modeling and Simulation of TSR-based SVC on Voltage Regulation for Three-Bus System

Influence of Unified Power Flow Controller on Flexible Alternating Current Transmission System Devices in 500 kv Transmission Line

FACTS Device a Remedy for Power Quality and Power System Stability Problem: A Review

Recent Trends in Real and Reactive Power flow Control with SVC and STATCOM Controller for transmission line

USING FACTS STABILITY ANALYSIS OF AC TRANSMISSION LINE

ιπλωµατική Εργασία του φοιτητή του Τµήµατος Ηλεκτρολόγων Μηχανικών και Τεχνολογίας Υπολογιστών της Πολυτεχνικής Σχολής του Πανεπιστηµίου Πατρών

Grid Stability Analysis for High Penetration Solar Photovoltaics

The Optimal Location of Interline Power Flow Controller in the Transmission Lines for Reduction Losses using the Particle Swarm Optimization Algorithm

ATC Computation with Consideration of N-1 Contingency and Congestion Removal Using FACTS Devices

EPRLAB FAQ v1.0 Page 1 / 8 Copyright EPRLAB December 2015

Electric Power System Under-Voltage Load Shedding Protection Can Become a Trap

VOLTAGE STABILITY CONSTRAINED ATC COMPUTATIONS IN DEREGULATED POWER SYSTEM USING NOVEL TECHNIQUE

Improvement of Transmission Line Power Transfer Capability, Case Study

Transient Stability Improvement of a FSIG Based Grid Connected wind Farm with the help of a SVC and a STATCOM: A Comparison

APPLICATION OF STATCOM FOR STABILITY ENHANCEMENT OF FSIG BASED GRID CONNECTED WIND FARM

Electric Drives Lab PCC 8 EE-456C Electrical Simulation Lab PCC 9 EE-468C Project Workshop SEC

NTRODUCTIONTO FACTS CONTROLLERS Theory, Modeling, and Applications

THE IMPORTANCE OF INTEGRATING SYNCHRONOUS COMPENSATOR STATCOM IN WIND POWER PLANT CONNECTED INTO THE MEDIUM VOLTAGE GRID

Enhancement of Transient Stability and Dynamic Power Flow Control Using Thyristor Controlled Series Capacitor

International Journal Of Global Innovations -Vol.2, Issue.I Paper Id: SP-V2-I1-048 ISSN Online:

International Journal of Advance Engineering and Research Development. Automatic Power Factor Correction in EHV System

Modeling of Power System For Improving Stability Using Thyristor Controlled Series Capacitor

CHAPTER I INTRODUCTION

FACULTY OF ENGINEERING AND TECHNOLOGY DEPARTMENT OF EEE COURSE PLAN FOR B.TECH (EEE)

Index Terms: Dynamics, reactive power capability, time domain simulation, voltage stability,

POWER FACTOR CORRECTION USING SHUNT COMPENSATION

Power Quality and Power Interruption Enhancement by Universal Power Quality Conditioning System with Storage Device

Enhancement of Reliability Analysis for a 6-Bus Composite Power System using the Combination of TCSC & UPFC

Integration of Large Wind Farms into Electric Grids

Enhancement of voltage profile for IEEE-14 Bus System by Using STATIC-VAR Compensation (SVC) when Subjected to Various Changes in Load

Targeted Application of STATCOM Technology in the Distribution Zone

Study of FACTS Controllers and its Impact on Power Quality

Overview of a Special Publication on Transmission System Application Requirements for FACTS Controllers

Hamdy S. K. El-Goharey, Walid A. Omran, Adel T. M. Taha

International Journal of Advance Research in Engineering, Science & Technology

LOAD FLOW STUDIES WITH UPFC POWER INJECTION MODEL

ELECTRICAL POWER SYSTEMS 2016 PROJECTS

Load Flow Analysis with UPFC under Unsymmetrical Fault. Condition

Transient Stability Improvement of Squirrel Cage Induction Wind Turbine Generator using Plugging Mode

CONGESTION MANAGEMENT IN DEREGULATED POWER SYSTEM USING FACTS DEVICES

Benefits of HVDC and FACTS Devices Applied in Power Systems

International Journal of Advanced Research in Electrical, Electronics and Instrumentation Engineering. (An ISO 3297: 2007 Certified Organization)

Transcription:

COMPARISON OF AND TCSC ON STABILITY USING MLP INDEX Dr.G.MadhusudhanaRao 1. Professor, EEE Department, TKRCET Abstract: Traditionally shunt and series compensation is used to maximize the transfer capability of a transmission line. By using FACTS controllers one can control the variables such as voltage magnitude and phase angle at chosen bus and line impedance. There are five well known FACTS devices utilized by the utilities for this purpose. These FACTS devices are Static Var Compensator (SVC), Static Synchronous Compensator (), Thyristor Controlled Series Capacitor (TCSC), Static Synchronous Series Compensator (SSSC) and Unified Power Flow Controller (UPFC). The voltage collapse occurs when a system is loaded beyond its maximum loadability point. Many analysis methods have been proposed and currently used for the study of this problem. Most of these techniques are based on the identification of system equilibrium where the corresponding jacobians become singular. These equilibrium points are typically referred to as points of voltage collapse and can be mathematically associated to saddle-node bifurcation. The voltage collapse points are also known as maximum loadability points.. 1. INTRODUCTION Power Generation and Transmission is a complex process, requiring the working of many components of the power system in tandem to maximize the output. One of the main components to form a major part is the reactive power in the system. It is required to maintain the voltage to deliver the active power through the lines. Loads like motor loads and other loads require reactive power for their operation. To improve the performance of ac power systems, we need to manage this reactive power in an efficient way and this is known as reactive power compensation. There are two aspects to the problem of reactive power compensation: load compensation and voltage support. Load compensation consists of improvement in power factor, balancing of real power drawn from the supply, better voltage regulation, etc. of large fluctuating loads. Voltage support consists of reduction of voltage fluctuation at a given terminal of the transmission line. Two types of compensation can be used: series and shunt compensation. These modify the parameters of the system to give enhanced VAR compensation. In recent years, static VAR compensators like the have been developed. These quite satisfactorily do the job of absorbing or generating reactive power with a faster time response and come under Flexible AC Transmission Systems (FACTS). This allows an increase in transfer of apparent power through a transmission line, and much better stability by the adjustment of parameters that govern the power system i.e. current, voltage, phase angle, frequency and impedance. The voltage collapse occurs when a system is loaded beyond its maximum loadability point. Voltage collapse studies are carried * Dr.G.MadhusudhanaRao Professor, EEE Department, TKRCET out with the aim to maximize the loading capability of a particular transmission line. Traditionally shunt and series compensation is used to maximize the transfer capability of a transmission line. Many analysis methods have been proposed and currently used for the study of this problem. Most of these techniques are based on the identification of system equilibrium where the corresponding jacobians become singular. These equilibrium points are typically referred to as points of voltage collapse and can be mathematically associated to saddle-node bifurcation. The voltage collapse points are also known as maximum loadability points By using FACTS controllers one can control the variables such as voltage magnitude and phase angle at chosen bus and line impedance. There are five well known FACTS devices utilized by the utilities for this purpose. These FACTS devices are Static Var Compensator (SVC), Static Synchronous Compensator (), Thyristor-Controlled Series Capacitor (TCSC), Static Synchronous Series Compensator (SSSC) and Unified Power Flow Controller (UPFC). Each of them has its-own characteristics and limitations. II. MAXIMUM LOADING POINT The voltage collapse occurs when a system is loaded beyond its maximum loadability point. All voltage stability studies carried out for the proposed studies consist on obtaining the maximum loadability margin and the voltage profiles for the given system considering critical contingencies, which is a typical procedure for voltage stability and transfer capability studies in power systems. Many analysis methods have been proposed and currently used for the study of this problem. Most of these techniques are based on the identification of system equilibrium where the 63

Comparison Of Statcom And Tcsc On Voltage Stability Using Mlp Index corresponding jacobians become singular. These equilibrium points are typically referred to as points of voltage collapse and can be mathematically associated to saddle-node bifurcation. The voltage collapse points are also known as maximum loadability points improve the transient stability margins and to damp out the system oscillations due to these disturbances. Voltage instability is mainly associated with reactive power imbalance. The load ability of a bus in the power system depends on the reactive power support that the bus can receive from the system. As the system approaches the maximum loading point or voltage collapse point, both real and reactive power losses increase rapidly. Therefore, the reactive power supports have to be local and adequate. Usually, placing adequate reactive power support at the weakest bus enhances static-voltage stability margins. The weakest bus is defined as the bus, which is nearest to experiencing a voltage collapse. Equivalently, the weakest bus is one that has a large ratio of differential change in voltage to differential change in load (dv/dptotal). In static voltage stability, slowly developing changes in the power system occur that eventually lead to a shortage of reactive power and declining voltage. This phenomenon can be seen from the plot of the power transferred versus the voltage at receiving end. The plots are popularly referred to as P-V curve or Nose curve. As the power transfer increases, the voltage at the receiving end decreases. Eventually, the critical (nose) point, the point at which the system reactive power is short in supply, is reached where any further increase in active power transfer will lead to very rapid decrease in voltage magnitude. Before reaching the critical point, the large voltage drop due to heavy reactive power losses can be observed. The only way to save the system from voltage collapse is to reduce the reactive power load or add additional reactive power prior to reaching the point of voltage collapse III. AND TCSC is a shunt connected device, which controls the voltage at the connected bus to the reference value by adjusting voltage and angle of internal voltage source. is the Voltage-Source Inverter (VSI), which converts a DC input voltage into AC output voltage in order to compensate the active and reactive power needed by the system exhibits constant current characteristics when the voltage is low/high under/over the limit. This allows to delivers constant reactive power at the limits compared to SVC. One of the many devices under the FACTS family, a is a regulating device which can be used to regulate the flow of reactive power in the system independent of other system parameters. has no long term energy support on the dc side and it cannot exchange real power with the ac system. In the transmission systems, s primarily handle only fundamental reactive power exchange and provide voltage support to buses by modulating bus voltages during dynamic disturbances in order to provide better transient characteristics, Figure 1: Basic Structure of The AC circuit is considered in steady-state, whereas the DC circuit is described by the following differential equation, in terms of the voltage Vdc on the capacitor The power injection at the AC bus has the form P = V2G-kVdc- VGcos(θ- α)-kvdcvbsin(θ- α) Q = -V2B+kVdcVBcos(θ- α)-kvdcvgsin(θ- α) TCSC A TCSC is a capacitive reactance compensator, which consists of a series capacitor bank shunted by a thyristor controlled reactor in order to provide a smoothly variable series capacitive reactance. TCSC is the type of series compensator. The structure of TCSC is capacitive bank and the thyrister controlled inductive brunch connected in parallel. The principle of TCSC is to compensate the transmission line in order to adjust the line impedance, increase loadability, and prevent the voltage collapse. The characteristic of the TCSC depends on the relative reactance of the capacitor bank and thyristor branch. Even through a TCSC in the normal operating range in mainly capacitive, but it can also be used in an inductive mode. The power flow over a transmission line can be increased by controlled series compensation with minimum risk of subsynchronous resonance (SSR) TCSC is a second generation FACTS controller, which controls the impedance of the line in which it is connected by varying the firing angle of the thyristors. A TCSC module comprises a series fixed capacitor that is connected in parallel to a thyristor controlled reactor (TCR). A TCR includes a pair of anti-parallel thyristors that are connected in series with an 64

Dr.G.MadhusudhanaRao inductor. In a TCSC, a metal oxide varistor (MOV) along with a bypass breaker is connected in parallel to the fixed capacitor for overvoltage protection. A complete compensation system may be made up of several of these modules. graphical user interfaces (GUIs) and a Simulink-based library provides an user friendly tool for network design. PSAT core is the power flow routine, which also takes care of state variable initialization. Once the power flow has been solved, further static and/or dynamic analysis can be performed. These routines are: 1. Continuation power flow; 2. Optimal power flow; 3. Small signal stability analysis; 4. Time domain simulations; 5. Phasor measurement unit (PMU) placement. V. RESULTS AND DISCUSSION Figure 2: Basic Structure of TCSC The principle of TCSC, in voltage stability enhancement is to control the transmission line impedance by adjust the TCSC impedance. The absolute impedance of TCSC, which can be adjusted in three modes: 1. Blocking mode: In the inserted mode with thyristor blocked, no current flows through the valve as the gate pulses are suppressed. In this mode, the TCSC reactance is the same as that the fixed capacitor. This mode is also termed as waiting mode. This mode is used to provide control and protective measures. The breaker is generally provided to remove TCSC from service when there are internal TCSC failure 2. By pass mode: The thyristor is operated in order to X L = XC. The current is in phase with TCSC voltage. In the bypass mode thyristors are gated for full conduction and the current flow in the reactor is continuous and sinusoidal. In this case the net reactance is slightly inductive because the susceptance of reactor is larger than that of the capacitor. This mode is mainly used for protecting the capacitor against the overvoltage (during transient overcurrents in the line). 3. Capacitive boost mode: : In vernier control mode, thyristors are gated in such a manner that a controlled amount of inductive current can be circulate through the capacitor thereby increasing effective capacitive/inductive reactance of the module IV. PSAT PSAT is a Matlab toolbox for electric power system analysis and control. The command line version of PSAT is also Octave compatible. PSAT includes power flow, continuation power flow, optimal power flow, small signal stability analysis and time domain simulation. All operations can be assessed by means of A 14-bus test system as shown in Figure 8 is used for voltage stability studies. PSAT [10] is power system analysis software, which has many features including power flow and continuation power flow. Using continuation power flow feature of PSAT, voltage stability of the test system is investigated. The behaviour of the test system with and without FACTS devices under different loading conditions is studied. The MLP index that is described in section 2 is used to compare the effects of the FACTS devices in static voltage stability. Voltage stability studies are performed from an initial base load case. The load has been increased gradually to an extent. is connected in parallel to the middle of the transmission line to regulate the voltage at chosen point by controlling the reactive power injection at that location based on the voltage-current curve of. Their steady-state model can be obtained from their V-I characteristics. At capacitive limit injects a fixed reactive power. At inductive limit absorbs a fixed reactive power. These devices can be effectively utilized if located at the most critical transmission line. TCSC is injected in a transmission line through a transformer connected in series with the system. The principle of TCSC is to compensate the transmission line in order to adjust the line impedance, increase loadability, and prevent the voltage collapse. The characteristic of the TCSC depends on the relative reactance of the capacitor bank and thyristor branch. Even through a TCSC in the normal operating range in mainly capacitive, but it can also be used in an inductive mode. The power flow over a transmission line can be increased by controlled series compensation with minimum risk of subsynchronous resonance (SSR). The conception of total power generated and losses are presented in table I. By applying the CPF for this test system, both voltage profiles in each bus and power flow in each line will change. In this system total generation, total power and total losses in MLP are shown in table II. According to this table, it can be seen that the capacity of CPF is more than that of the previous mode. 65

Comparison Of Statcom And Tcsc On Voltage Stability Using Mlp Index Table 1. Total power calculated after pf without facts Figure 3: PV curves for 14-bus test system without FACTS From the CPF results which are shown in the Figure 3, the buses 4, 5, 9 and 14 are the critical buses. Among these buses, bus 14 has the weakest voltage profile and thus we improved its profile with FACTS devices. Maximum loading point (MLP) or bifurcation point where the Jacobian matrix becomes singular occurs at max = 2.7699p.u Table.2: Total power calculated in MLP without FACTS Figure. 4. Voltage magnitude profile for 14-bus test system without compensation devices The best location for shunt reactive power compensation, as far as the improvement of static voltage stability margin is concerned, is the weakest bus of the system. The weakest bus of the system can be identified using tangent vector analysis as presented in [7]. Introducing shunt compensation devices at this bus will improve the MLP the most. In this simulation, bus 14 is the weakest of the system, introducing in this bus will increase the MLP to the maximum value. In order to get a rough estimate of reactive power support needed at the weakest bus and corresponding MLP, a synchronous compensator with no limit on reactive power was used at the weakest bus. Methodology to place series compensation devices is under investigation. However, insert the series compensation device at line 14-13 and then repeat the simulation. In table III the results of total power for and TCSC. According to the above table, total losses in MLP with TCSC are less than other devices and the real power generation in MLP with is more than that of other devices. The values of λmax of and TCSC are compared in Figure 6. Figure shows that has suitable result and is better than TCSC. 66

Dr.G.MadhusudhanaRao Table 3: The result of total power calculated in MLP with various FACTS device TOTAL GENERATION TCSC REAL POWER [p.u.] 16.5582 15.8081 REACTIVE POWER [p.u.] 26.5901 25.9616 The weakest bus (bus 14) of the system is located at the load area and it requires reactive power the most. Introducing reactive power at bus 14 or in its vicinity can improve voltage stability margin. To analyze of static voltage stability to survey contingencies of power system with Psat software. The continuation power flow for normal system manner is done that all generation units and lines are in the network and in fact no contingencies has occurred in system. Maximum Loading Point is λ max= 2.97 p.u. Table 4: MLP and Bus Voltage in case of contingencies without TOTAL LOAD REAL POWER [p.u.] 10.3359 10.1648 GENERATION UNIT OUTAGE BUS WITH MAXIMUM LOADING POINT REACTIVE POWER [p.u.] 2.0603 3.1946 BUS 2 5 0.7282 2.2 TOTAL LOSSES BUS 3 3 0.6235 1.8 REAL POWER [p.u.] 6.2223 5.6433 BUS 6 14 0.5283 1.6 REACTIVE POWER [p.u.] 24.5298 22.767 BUS 8 9 0.5913 2.2 3.2 3.1 able 4: MLP and Bus Voltage in case of contingencies with 3 2.9 2.8 2.7 GENERATION UNIT OUTAGE BUS WITH MAXIMUM LOADING POINT 2.6 2.5 Without FACTS TCSC BUS 2 14 0.9622 2.4 BUS 3 14 0.9537 2.0 Figure 5: MLP in and TCSC In IEEE 14-bus test system, shunt compensation device provides a higher MLP and a better voltage regulation compared to series compensation device. Shunt compensation device injects the reactive power at the connected bus but series compensation device inserts the reactive power at the connected line. The test system needs reactive power at the load bus more than the line. BUS 6 4 0.9853 2.6 BUS 8 3 0.9932 2.3 67

Comparison Of Statcom And Tcsc On Voltage Stability Using Mlp Index VI. CONCLUSION Static voltage stability assessment of the IEEE 14-bus test system with parallels and series FACTS devices using MLP index is studied. Using the continuation power flow with accurate model of the FACTS controllers the study was performed for test system. It is found that these controllers significantly increase the loadability margin of power systems. Parallel FACTS devices provide higher voltage stability margin than series FACTS devices. The test system requires reactive power the most at the weakest bus, which is located in the distribution level. Introducing reactive power at this bus using can improve loading margin the most. TCSC on the other hand, are series compensation devices, which inject reactive power through the connected line. This may not be effective when the system required reactive power at the load level. In case of contingencies, provides reactive power support and MLP and bus Voltage is higher than in the case of no. REFERENCES [1] V. Ajjarapu and C. Christy, The continuation power flow: a tool for steady state voltage stability analysis, IEEE Transactions on Power Systems, vol.7, no. 1, pp. 416 423, 1992 [2] R. Natesan and G. Radman, Effects of, SSSC and UPFC on Voltage Stability, Proceedings of the system theory thirty- Sixth southeastern symposium, 2004, pp. 546-550. [3] N. Talebi, M. Ehsan, S.M.T Bathaee, Effects of SVC and TCSC Control Strategies on Static Voltage Collapse Phenomena, IEEE Proceedings, Southeast Con, Mar 2004, pp. 161 168. [4] A. Kazemi, V. Vahidinasab and A. Mosallanejad, Study of and UPFC Controllers for Voltage Stability Evaluated by Saddle-Node Bifurcation Analysis, First International Power and Energy Coference PECon/IEEE, Putrajaya, Malaysia, November 28-29, 2006, pp. 191-195. [5] Arthit Sode-Yome, Nadarajah Mithulananthan and Kwang Y. Lee, Static Voltage Stability Margin Enhancement Using, TCSC and SSSC, IEEE/PES Transmission and Distribution Conference & Exhibition, Asia and pacific, Dalian Chine, 2005,pp. 1-6. [6] C. A. Cañizares, C. Cavallo, M. Pozzi, and S. Corsi, "Comparing Secondary Voltage Regulation and Shunt Compensation for Improving Voltage Stability and Transfer Capability in the Italian Power System," Electric Power Systems Research, Vol. 73, No. 1, pp 67-76, January,2005. [7] A. Sode-Yome and N. Mithulananthan, Comparison of shunt capacitor, SVC and in static voltage stability margin enhancement, International Journal of Electrical Engineering Education, UMIST, Vol. 41, No. 3, July 2004. 68