www. ElectricalPartManuals. com INSTRUCTIONS TYPE HQS PHASE SELECTOR RELAY FOR INSTALLATION OPERATION MAINTENANCE APPLICATION

Similar documents
ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet

C. Figure 1. CA-16 Front View Figure 2. CA-16 Rear View

A - Add New Information C - Change Existing Information D - Delete Information. Page 7. Delete the fourth paragraph beginning CAUTION

L. Photo. Figure 2: Types CA-16 Relay (rear view) Photo. Figure 1: Types CA-16 Relay (front view)

B CW POWER RELAY

3.0 CHARACTERISTICS E Type CO-4 Step-Time Overcurrent Relay

ABB. Type CRQ Directional Negative Sequence Relay for Ground Protection B 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION CAUTION

2.0 CONSTRUCTION AND OPERATION 3.0 CHARACTERISTICS K. CO (HI-LO) Overcurrent Relay

Type CRN-1 Reverse Power Relay 50 and 60 Hertz

41-747G. Figure 1: Type DGF Relay without case (Photo)

P. Sub 4 184A404. Sub 3 876A220

TYPE KF UNDER-FREQUENCY RELAY A. Figure 1: Type KF Relay for 60 Hertz without Case. (Front & Rear View.) Front View Rear View

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E

ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065

COM Overcurrent Relay

INSTRUCTIONS. seconds. the tween the end of the bearing screw and the. top of the shaft. The moving contact is a small silver hemisphere

www. ElectricalPartManuals. com INSTRUCTIONS TYPE CO CONTACT MAKING AMMETER INSTALLATION OPERATION MAINTENANCE I.. L APPLICATION

4.0 OPERATION Type ITH-T Relay

TABLE I 60 CYCLE BURDEN OF THE CVD RELAY AT CONTINUOUS RATING

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA

2.0 CONSTRUCTION 3.0 OPERATION. SA-1 Generator Differential Relay - Class 1E 2.5 TRIP CIRCUIT

3. OPERATION 2.1. RESTRAINT CIRCUIT 2.6. INDICATING CIRCUIT 2.2. OPERATING CIRCUIT 2.7. SURGE PROTECTION CIRCUIT 2.3.

www. ElectricalPartManuals. com

UNION SERVICE SPECIFICATION NUMBER SU A

RELAYS HAVING NO KS DESIGNATIONS WARD LEONARD COMPANY, ALLEN-BRADLEY COMPANY AND WESTINGHOUSE CORPORATION REQUIREMENTS AND ADJUSTING PROCEDURES

INSTRUCTIONS. GEI-38974A Supersedes GEI INSTANTANEOUS CURRENT RELAY TYPE PJC2OA GENERALS ELECTRIC

ABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA. Non-Directional, Single Phase Adjustable Time Delay Device No.

A. Submit manufacturer's literature and technical data before starting work.

Horizontal Circuit Switchers

SL-6 & SL-6A. I UNION SWITCH & SIGNAL l[ml 645 Russell Street Batesburg, SC Service Manual Field and Shop Maintenance

TESCO THE EASTERN SPECIALTY COMPANY Date: 05/04/15 Canal Street and Jefferson Avenue Bristol, PA 19007

Horizontal Circuit Switchers

Florham Park, NJ USA Call (ASCO) for sales or service

CR193 Vacuum Limitamp* Contactors

section-page Table 1. Transfer switching device ratings. Conditional short circuit current

www. ElectricalPartManuals. com INSTRUCTIONS "INERTEEN AND OIL INSULATED FEEDER SWITCHES DESCRIPTION INSTALLATION MAINTENANCE

www. ElectricalPartManuals. com INS T R U c.t I 0 N S Westinghouse OPER.ATION MAINTENANCE INSTALLATION SWITCHBOARD INSTRUMENTS SIX-INCH CLASSIFICATION

STARTER SYSTEM TESTING 5.6

STARTER Mitsubishi Montero DESCRIPTION BENCH TESTING STARTER NO-LOAD TEST ELECTRICAL Mitsubishi Starters. Montero

Installation Sheet January, 2016 Supersedes February, 2013

Type SOQ Negative Sequence Time Overcurrent Relay

Instructions for Replacing

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

INTRODUCTION Principle

Florham Park, NJ USA Call (ASCO) for sales or service

STARTER SYSTEM TESTING 5.6

www. ElectricalPartManuals. com Instructions for Load Break Air Switch, Type LBF, for Power Centers

STARTING SYSTEMS 8B - 1 STARTING SYSTEMS CONTENTS

Instructions for De-Ion Air Circuit Breakers Types DM2R, DM2F

Limit Switches. Reference Information. Proper Application of Limit Switches General Information. Definition of Limit Switch Terms.

INSTRUCTIONS. GE Protection and Control. 205 Great Valley Parkway Malvern, PA UNDERVOL TAGE RELAYS TYPES: IAV54E IAV55C IAV54F IAV55F

3ATS & 3NTS J-design 600 A 3ADTS & 3NDTS A Transfer Switches. Installation Manual. Installation A DANGER. Table of Contents WARNING

Module 2 CONTROL SYSTEM COMPONENTS. Lecture - 4 RELAYS

SERVICE AND REPAIR PARTS NEMA SIZE 3, SINGLE POLE, NORMALLY OPEN, P/N SERIES NEMA SIZE 4, SINGLE POLE, NORMALLY OPEN, P/N SERIES

Crane Control Class 9055

www. ElectricalPartManuals. com MAGNETIC TIME RELAYS GENERAL. ELECTRIC INSTRUCTIONS *IC *Also identified with prefix CR instead of IC.

ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ Phone Fax

ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ Phone Fax

600 D 220 E 230 J Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO)

Electrical Machines-I (EE-241) For S.E (EE)

1. Take the cover off the relay, taking care to not shake or jar the relay or other relays around it.

SERVICE AND REPAIR PARTS NEMA SIZE 5, SINGLE POLE, NORMALLY OPEN, P/N SERIES NEMA SIZE 5A, SINGLE POLE, NORMALLY OPEN, P/N SERIES

BELT-DRIVEN ALTERNATORS

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

CHEC"'- INSTRUCTION UNION SWITCH & SIGNAL.. SWISSVALE, PA. DIVISION OF WESTINGHOUSE AIR BRAKE COMPANY

Disconnect & ByPass Switches

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

ELECTRICAL MAINTENANCE

FULL VOLTAGE STARTERS z SIZE 8 SERIES B CONSTRUCTION

CA Breaker Instruction Manual

UNIT 2. INTRODUCTION TO DC GENERATOR (Part 1) OBJECTIVES. General Objective

INSTRUCTIONS HAA 15A / 15B / 15C / 15D / 15E / 15F / 15G / 15H AUXILIARY CURRENT RELAYS

The galvanic separation of the primary or actuating circuit and the load circuits

Page 2 DS LOW VOLTAGE POWER CIRCUIT BREAKERS Digitrip Trip Unit Inside Wiring Guide Outside Wiring Guide Shutter Drawout Unit Position Indicator Escut

920 Remote Control Switches

www. ElectricalPartManuals. com INSTRUCTIONS INTERLOCKED MOTOR-DRIVEN OPERATING MECHANISM For No-Load Tap Changers DESCRIPTION OPERATION MAINTENANCE

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

FN-27 FLASHER RELAY SERVICE MANUAL 4519 * * * * * * * * * * * * * * * *

HGA. Hinged Armature Auxiliary. Hinged armature auxiliary relay to perform auxiliary functions in AC and DC circuits.

Installation Manual. E-design A Transfer Switches A

Instructions for Installation, Operation and Maintenance of Low Voltage Power Circuit Breakers Types DSII and DSLII

Product Specifications for Aluminum Vertical Break Switches

Bolted contact switches. Pringle switches

INSTRUCTIONS GEI-98305C UNDERVOLTAGE RELAY D-C. Type NGV18A GENERAL ELECTRIC

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

3143 Production Drive Fairfeild, Ohio Model HA Installation and Service Manual

Series 20 Installation Instructions

Industrial Control Transformers

Cutler-Hammer. Installation Instructions for the Digitrip OPTIM Pole Trip Unit Installation and Operation with L-Frame Series C Circuit Breakers

TECHNICAL GUIDE FOR PROXIMITY SENSORS DEFINITIONS YAMATAKE PROXIMITY SENSOR CATEGORIES

Operator s Manual Series ADTS Automatic Delayed Transition Transfer Switches 150 through 4000 amp. Rating Label. Nameplate A

Operator s Manual Series ATB Automatic Transfer & Bypass Isolation Switches 150, 260, and 400 amp sizes A. Rating Label.

Operator s Manual Series ATS Automatic Transfer Switches 30 through 4000 amp. Rating Label. Nameplate C TABLE OF CONTENTS

ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ Phone Fax

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 15 Troubleshooting Basic Controls

Design Standard. Purpose: Design Standard:

Chapter 22: Electric motors and electromagnetic induction

PV-250 Track Relay. Operating Values For Hz PV-250 Track Relay With 115 Volt Local 440 Turn Track Coil


Product Specifications for Phase Over Phase GOABS(r)

Transcription:

I. L. 41-610.2 INSTALLATION OPERATION MAINTENANCE INSTRUCTIONS TYPE HQS PHASE SELECTOR RELAY FOR TYPE HKB SINGLE-POLE CAUTION Before putting relays into service, remove all blocking which may have been inserted for the purpose of securing the parts during shipment, make sure that all moving parts operate freely, inspect the contacts to see that they are clean and close properly, and operate the relay to check the settings an d electrical connections. APPLICATION type HQS relay operates on negative and zero sequence currents to select the faulted phase when a single phase-to-ground fault occurs on the protected transmission line. zero sequence current is obtained from the neutral of the line current transformers, and the negative sequence current from an external three-phase filter supplied with the relay. CONSTRUCTION AND OPERATION type HQS relay consists of three phase selector elements, three contactor switches, and three operation indicators mounted in the type FT case of Figure 4. external threephase negative sequence filter is mounted in the case of Figure 3. Phase Selector phase selector element is similar to the type H directional elemfmt as used in the type HZ and HRK-P relays. primary of a small current transformer receives the zero sequence component of line current which causes a large current to flow in a one-turn movable aluminum secondary. Two other current coils are mounted on either side of a magnetic frame and these coils receive the negative sequence component of line current from an external filter. se zero and negative sequence elements are assembled at right angle to each NEW INFORMATION CARRIER RELAYING other with the one-turn loop in the air gaps of the path. negative sequence current coil flux interaction of the two fluxes produces torque and rotates the loop in a direction depending on the relative instantaneous direction of current flow in the two coils. An Isolantite arm extends from the moving loop and supports a rectangular silver contact which bridges two stationary contacts mounted on rither side of the loop. stationary contacts are silver on the lower end springs. conical surfaces mounted of vertically hanging contact separation is adjustable by a small screw near the upper end of the rigid stationary contact supporting arm. Onu of these supporting arms hangs parallel to 0ach of thr f'our stationary contacts. snt screw on the lower E'nd of this arm provides the contact follow adjustment. Two additional screws on the movement frame beneath the negative sequcjnce coil iron limit the movement of the loop. re are three of these phase selector elements, one for each of the three phases and designated S A, S B and S c for phases A, B and C respectively. sub numbers 2 and 0 indicate the negative and zero scqutmcc coils. Contactor Switch ' d-e. contact or switch in the relay is a small solenoid type switch. A cylindrical plunger with a silver disc mounted on its lower end moves in the core of the solenoid. As the plunger travels upward, the disc bridges three silver stationary contacts. coil is in series with the main contacts of the relay and with the trip coil of the br<'aker. '\llhen the relay contacts close, the coil becomes energized and closes the switch. EFFECTIVE DECEMBER 1948

TYPE HQS RELAY : T; ; C - TO BASE TERMS. L o_o o_o_o_ FRONT VIEW WITH RELATIVE 1!'-ISTANTA.NEOUS POL.AR.ITY" THE 5.tt.. 5&. Sc M-"KE CONTACTS CLOSE. PM-To Rl:L,..Y CONTACTOR. SWITCH SHORT CIR.CUIT SWITCH Fig. 1-Intemal Schematic of the Type HQS Phase Selector Relay in the Type FT Case. Operation Indicator operation indicator coil connected in the trip circuit. is a small solenoid When the coil is energized, a spring-restrained armature releases the white target which ralls by gravity to indicate the completion or the trip circuit. indicator is reset rrom outside of the case by a push rod in the cover stud. Three Phase Negative Sequence Filter filter consists of three mutual reactors each with three windings connected as shown in Figure 2. With unbalanced three-phase current flowing in the input terminals, the output voltage and current will be proportional to the negative sequence components of the unbalanced input. detailed explanation of the filter is beyond the scope of this leaflet and is covered in catalog section 41-287 on the type CRS relay. 2 CHARACTERISTICS type H S relay is an auxiliary relay used in the carrier relaying scheme with the type HKB relay. minimum pick-up of the type Hqs relay and the filter is as follows: Polarizing Winding Turns 17 10 7 3 Minimum Pick-Up Amperes 1.0 1.3 1.55 2.37 Maximum 3Io Amperes 15.0 25.0 32.0 75.0 1 4 1 This is the total phase current Connections of Links to B,2 to 3, to A to B,2 to A 3 to B,4 to A 2 to A, 1 to 3, 4 to B passed thru the filter and relay to neutral with the other two phase currents zero. corresponding negative and zero sequence values are each 1/3 of the values given above. combining RELAYS IN TYPE FT CASE type FT cases are dust-proof enclosures relay elements and knife-blade test switches in the same case. This combination provides a compact flexible assembly easy to maintain, inspect, test and adjust. re are three main units of the type FT case: the case, cover, and chassis. case is an all welded steel housing containing the hinge half of the knife-blade test terminals for external connections. switches and the cover is a drawn steel frame with a clear window which fits over the front of the case with the switches closed. chassis is a frame that supports the relay elements and the contact jaw half of the test switches. This slides in and out of the case. electrical connections between the base and chassis are completed through the closed knife-blades. Removing Chassis To remove the chassis, first remove the cover by unscrewing the captive nuts at the corners. This exposes the relay elements and all the test switches for inspection and testing. next step is to open the test switches. Always open the elongated red

TYPE HQS RELAY ---_.:.:_'...=.L...::41-6lo.2 handle switches first before opening any of the black handle switches or the cam action latches. This opens the trip circuit to prevent accidental trip out. n open all the remaining switches. order of opening the remaining switches is not important. In opening the test switches they should be moved all the way back against the stops. With all the switches fully opened, grasp the two cam action latch arms and pull outward. This releases the chassis from the case. Using the latch arms as handles, pull the chassis out of the case. chassis can be set on a test bench in a normal upright position for test as well as on its back or sides for easy inspection and maintenance. After removing chassis may be blade portion of and the cover chassis. switch the chassis a duplicate inserted in the case or the the switches can be closed put in place without the chassis operated shorting located behind the current test switch prevents open circuiting the current transformers when the current type test switches are closed. When the chassis is to be put back in the case, the above procedure is to be followed in the reversed order. elongated red handle switch should not be closed until after the chassis has been latched in place and all of the black handle switches closed. Electrical CircuitJ Each terminal in the base connects thru a test switch to the relay elements in the chassis as shown on the internal schematic diagrams. numbers relay terminal is identified by marked on both the inside and outside of the base. test switch positions are identified by letters marked on the top and bottom surface of the moulded blocks. se letters can be seen when the chassis is removed from the case. relay are disconnected from the external circuit potential and control circuits thru the by opening the associated test switches. Opening the current test switch short-circuits the current transformer secondary and disconnects -one. side of the relay coil but leaves IIAUTU.. I.. RUCTORS ' j +/-- SEQUENCE NEGATIVE OUTPUT T R'MINJit\LS FRONT 'IIEW TERMINALS Fig. 2-Intemal Connections of the Three-Phase Negative Sequence Filter. the other side of the coil connected to the external circuit th the current test jack jaws. This circuit can be isolated by inserting the current test plug {without external connections), by inserting the ten circuit test plug, or by inserting a piece of insulating material approximately 1/3211 thick into the current test jack jaws. Both switches of the current test switch pair must be open when using the current test plug or insulating material in this manner to shortcircuit the current transformer secondary. A cover operated switch can be supplied with its contacts wired in ser ies with the trip circuit. This switch opens the trip circuit when the cover is removed. This switch can be added to the existing type FT cases at any time. Testing relays can be tested in service, in the case but with the external circuits isolateo or out of the case as follows: Testing in Service ammeter test plug can be inserted in the 3

TYPE HQS RELAY current test jaws after opening the knifeblade switch to check the current thru the relay. This plug consists of two conducting strips separated by an insulating strip. ammeter is connected to these strips by terminal screws and the leads are carried out thru holes in the back of the insulated handle. Voltages between the potential circuits can be measured conveniently by clamping #2 clip leads on the projecting clip lead lug on the contact jaw. Testing in Case With all blades in the full open position, the ten circuit test plug can be inserted in the contact jaws. This connects the relay elements to a set of binding posts and completely isolates the relay circuits from the external connections by means of an insulating barrier on the plug. external test circuits are connected to these binding posts. Thu plug is inserted in the bottom test jaws 4 with the binding posts up and in the top test switch jaws with the binding posts down. external t8st circuits may be made to the relay elements by #2 test clip leads instead of the test plug. v en connecting an external test circuit to the current elem8nts using clip leads, care should be taken to se8 that the current test jack jaws are op n so that the relay is completely isolated from the r;xternul circuits. Suggested means for isolating this circuit are outlined above under "Electrical Circuits. " Tusting Out of Case vlith the chassis removed from the base, relay elements may be tested by using the circuit test ten plug or by #2 test clip leads as described above. factory calibration is made with the chassis in the case and removing the chassis from the case will change the calibration values by a small percentage. is recommended that the relay be checked in position as a final check on calibration. INSTALLATION relays should be mounted on switchboard It panels or their equivalent in a location free from dirt, moisture, excessive vibration and heat. Mount the relay vertically by means of the two mounting studs. Either of these studs may be utilized for grounding the relay. electrical connections may be made direct to the terminals by means of screws for steel panel mounting or to terminal studs furnished with the relay for ebony-asbestos or slate panel mounting. terminal studs may pe easily removed or inserted by locking two nuts on the studs and then turning the proper nut with a wrench. external connections of both the relay and the filter are shown in the Carrier Current Schematic supplied with each terminal. for selective pole tripping ADJUSTMENTS AND MAINTENANCE proper adjustments to insure correct operation factory of this relay have been made at the and should not be disturbed after receipt by the customer. If the adjustments have been changed, the relay taken apart for repairs, or if it is desired to check the adjustments at regular maintenance periods, the instructions below should be followed. All contacts should be periodically cleaned with a fine file. 3#1002110 file is recommended for this purpose. use of abrasive material for cleaning contacts is not recommended, because of the danger of embedding small particles in the face of the soft silver and thus impairing the contact. Phase Selector Element Check tne free movement of each element with the relay in a vertical position to see that it is free from friction and properly centered. loop should assume a vertical position with the contacts open when the element is completely deenergized. With the loop in the neutral position determined by gravity, adjust both left-hand stationary contacts (front view) so that there is contact gap of.01011 between moving contact bridge and the stationary contacts. Adjust \ I L

TYPE HQS RELAY -21. L 4 1-6J o.2 the left hand back stop screws for.01011 contact deflection. Adjust the left stop which strikes against the loop so that is makes contact against the loop at the same time the moving contact deflects the stationary contact against the two back screws. Repeat these adjustments for the right hand contacts and stops. Connect terminals 25 and 24 together and pass 1 ampere, 60 cycles, from terminals 26 to 23. (This test is without the filter). moving should contact of the bottom element (Sc) move to the right and bridge the stationary contacts. Reverse the connections to terminals 25 and 26. left-hand contacts should now remain firmly closed. Raise the current to 15 amperes and make sure that the loop stop screws have the adjustment for minimum contact vibration. Repeat the tests on the middle element (S B ) by connecting terminals 22 and 25 together and passing current through terminals 21 and 26 and on the top element (S A ) by connecting terminals 25 and 20 together and passing current through terminals 19 and 26. Adjust the bearing screws of the moving loop so that there is about.010 inch end play. See that the loop does not bind or strike against the either end jewel. Contactor Switch iron or coil when pressed against Adjust the stationary core of the switch for a clearance between the stationary core and the moving core This can be most when the switch is picked up. conveniently done by turning the relay up-side-down.. Screw up the core screw until.the moving core starts rotating. Now, back off the core screw until the moving core stops rotating. where the play in the moving This indicates the point contact assembly is taken up, and where the moving core just separates from the stationary core screw. Back off the stationary core screw one turn beyond this point and lock in place. This prevents the moving core from striking and sticking to the stationary core because of residual magnetism. Adjust the contact clearance for 3/32 inch by means of the two 'Small nuts on either side of the Hicarta disc. switch should pick up at 1 amperp d-e. Test for sticking after 30 amperes d-e. have been passed thru the coil. coil resistance is approximately 1.0 ohms. Operation In'dicator Adjust the indicator to operate at 1.0 ampere d-e. gradually applied by loosening the two screws on the under side of the assembly, and moving the bracket forward or backward. If the two helical springs which reset the armature are replaced by new springs, they should be weakened slightly by stretching to obtain the 1 ampere calibration. coil resistance is approximately 0.16 ohm. Three-Phase Negative Sequence Filter filter is adjusted for balance at the factory and no furthpr adjustments or maintenance should be required. Fith balanced three phase currents of 10 amperes, 60 cycles, phase rotation A, B, C, introduced into the input terminals as marked on Figure 2, the voltage between the output terminals A', B', a high resisand C', should be zero. Use tance voltmeter for this check. Connect terminals A', B' and C' to terminals 20, 22 and 24 of the type HQS relay. Connect the relay terminals 19, 21 and 23 together. With balanced three-phase currents of 5 amperes, 60 cycles, phase rotation A, B, C applies to the filter input terminals A, B, C, and the neutral formed by connecting terminals A", B", and C" the voltage across the relay terminals 21 and 22, and 23 and 24 should be zero. Now, reverse the connections to the filter input terminals A and B and check the voltage now appearing across the relay terminals. se three voltages should be substantially 0.7 volt. RENEWAL PARTS Repair work can be done most satisfactorily at the factory. However, interchangeable parts can be furnished to the customers who are equipped for doing repair work. When ordering parts, always give the complete nameplate data. 5

. TYPE HQS RELAY -- 6 7 ---1.3- /4,-t :.1:!10-.32.SC.QEW.S ror "T'ERMINA6S I 0 l7p --------------- t<tt I+ tl,,,,.,,.. - JZ DIA, Mr4. J.IOI.. S (J!I-HOLfES) Fig. 3-0utline and Drilling Plan of the Three-Phase Negative Sequence Filter. PANEL LOC TION FOR PROJECTION TYPE. HTQ.- I 0 I 1,1: :IIJO al. G.It.. e -..., I "7 I PANEL I.OCI\TION SE.MI F\..US'r\ T'IPE M"TCi ' 2." WIT"' t.t.r "" 2.1. 'WITH ITUO.. 016--1 \STUDS O'R P'RQJ.. l TVPE MTG.! OIA. HOlE (Z.REQ.) I 1{ 18 MTG. STUO(Z. R'i.Q.) Fig. 4-0utline and Drilling Plan of the M20 Projection or Semi-Flush Type FT Flexitest Case.

WESTINGHOUSE ELECTRIC CORPORATION METER DIVISION NEWARK, N.J. Printed in U.S.A.