Jeff Fehr, Senior Application Engineer. ACH550 Flux Optimization White Paper

Similar documents
Designing a Mechanically Adjustable Speed Drive for AC Motor Applications to Eliminate Vibrations Without Additional Harmonics

Código de rotor bloqueado Rotor bloqueado, Letra de código. Rotor bloqueado, Letra de código

AAFAME Presentation. Shermco Industries Inc. Drives and Automation Application, Sales and Service Manager, Irving Texas.

How to Select a Variable Frequency Drive Based on Load Characteristics

Understanding NEMA Motor Nameplates

PHYS 2212L - Principles of Physics Laboratory II

Permanent Magnet Synchronous Motor. High Efficiency Industrial Motors

Welcome to basics of drives training module, looking at process control and various control methods. To view the presenter notes as text, please

Components of Hydronic Systems

FAN ENGINEERING. Application Guide for Selecting AC Motors Capable of Overcoming Fan Inertia ( ) 2

Application Note CTAN #146

Table of Contents. Foreword...xiii. Chapter One Introduction, Objectives of the Guide...1

Drive Fundamentals. Motor Control Bootcamp May 15-18, Copyright 2015 Rockwell Automation, Inc. All Rights Reserved. PUBLIC CO900H

Pump ED 101. Variable, Fixed Speed Control - - Float Switch Activation. Introduction

Armature Reaction and Saturation Effect

30 top tips to tackle HVAC challenges No.09 - Energy efficiency

ASSESSMENT REGARDING THE FLUID EQUATION. W = PV (WORK = PRESSURE x VOLUME) AS IT RELATES TO THE WORKING CAPABILITY OF PRESSURISED FLUIDS APPLIED IN

Energy Savings Variable Frequency Drives and Cooling Tower Fan Motors

ELECTROPNEUMATIC POSITIONING SYSTEM CONTROL WITH THE LEGENDARY LOGO! PLC

Measurement of induction motor characteristics

Drives and Motor Sizing Made Easy. ABB Inc. October 23, 2014 Slide 1

Energy Saving Solutions Using Variable Frequency Drives

BROCHURE. ABB drives for HVAC applications ACH550, 1 to 550 Hp

Exercise 3. Battery Charging Fundamentals EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Charging fundamentals

Technical Guide No. 7. Dimensioning of a Drive system

Save Thousands of Dollars Per Year!

Project Summary Fuzzy Logic Control of Electric Motors and Motor Drives: Feasibility Study

Power Consumption Reduction: Hot Spare

Optimizing Airflow on Dust, Mist and Fume Collection Systems

Common recommendations

How to: Test & Evaluate Motors in Your Application

A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein.

Variable Speed Pumping

Pump & Motor Efficiency

Pump & Motor Efficiency

Introduction. Upon completion of AC Motors you should be able to: Explain the concepts of force, inertia, speed, and torque

Standard Drives A & D SD Application Note

ACH550 VARIABLE FREQUENCY DRIVES FOR HVAC APPLICATIONS

Application Notes. Calculating Mechanical Power Requirements. P rot = T x W

Realizing Energy Savings in Fan and Pump Systems using Variable Frequency Drives. Schaedler Yesco Expo 2012

G PULLAIAH COLLEGE OF ENGINEERING & TECHNOLOGY DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

IT 318 SUPPLEMENTARY MATERIAL CHAPTER 4

EMC Issues in Electric Drives

Overvoltage Suppression F7 Drive Software Technical Manual

CHAPTER 4 MODELING OF PERMANENT MAGNET SYNCHRONOUS GENERATOR BASED WIND ENERGY CONVERSION SYSTEM

ENERGY CONSERVATION IN AUTOMATIC FLUID FLOW CONTROL USING VARIABLE FREQUENCY DRIVE

VFD Best Practices: Getting the Most from Your VFD Investment

Automatic Energy Saving Control

C-BOA Tool. Comparison of Peak Demand Savings Estimation Methods. February 7, of 14

PUMP HEART OF PLUMBING SYSTEM V.SRINIVAS

Motor Performance Data for Electric Actuators Accutronix MX and L120 Series. Limitorque Actuation Systems

Variable Speed Drives in Electrical Energy Management. Course Content

ABB drives for HVAC applications ACH550, 1 to 550 Hp

The MICROMASTER has four modes of operation:

Is Your Factory Power Source Corrupting Your Product Testing? September 2015 Author: Steve Boegle Engineering Group Leader, Behlman Electronics

Permanent Magnet Motors for ESP Applications Updating the Track Record of Performance. Lorne Simmons VP Sales & Marketing

SECTION MOTORS AND VARIABLE FREQUENCY DRIVES

Efficient Variable Speed Pumping: A Low Cost Approach to Green Energy

Written By : Simon Teo B. ENG (HONS)

Central Station Air-Handling Units

ECET Industrial Motor Control. NEMA Ratings. National Electrical Manufacturers Association

Unidrive M600 High performance drive for induction and sensorless permanent magnet motors

You have probably noticed that there are several camps

Pretest Module 21 Units 1-3 AC Generators & Three-Phase Motors

For motors controlled

2. Draw the speed-torque characteristics of dc shunt motor and series motor. (May2013) (May 2014)

Industrial Motors. But first..servos!

SAMINCO ELECTRIC TRACTION DRIVES

Sizing gensets for motor starting A practical guide to understanding how motor-starting loads affect genset performance

Sensorless Vector Drives

MOTOR CONTROLLERS. STATE the function of motor controllers.

ELEN 236 DC Motors 1 DC Motors

Figure 1 Linear Output Hall Effect Transducer (LOHET TM )

BULLETIN BAQSOLO AQUAVAR SOLO CONSTANT PRESSURE CONTROLLERS FOR: 1Ø 3-WIRE MOTORS, 1Ø 2-WIRE CENTRIPRO MOTORS, 3Ø MOTORS

User s Manual. ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual

Application Note CTAN #234

Benefits of a Cooling Tower VFD Retrofit

AND LOAD PARAMETERS IMPORTANT MOTOR. Torque x Speed Constant. Horsepower= Mechanical Power Rating Expressed in either horsepower or watts

List of Tables: Page # Table 1: Emerson Commander SK VFD parameter settings 2. Table 2: Allen Bradly Power Flex 4M VFD parameter settings 3

CSDA Best Practice. Hi-Cycle Concrete Cutting Equipment. Effective Date: Oct 1, 2010 Revised Date:

Variable Frequency Drives

Solar Power Energy Harvesting Electrical Integration

NOW INTEGRATED WITH MLM DESIGNED FOR VAV DIFFUSER SYSTEMS LINEAR CHARACTERISTICS NO REGULAR MAINTENANCE REQUIRED PRESSURE SENSOR AND CONTROLLERS

Inverter control of low speed Linear Induction Motors

VSD Series II Variable Speed Micro Drives

It s What s Inside that Counts

Low Speed Control Enhancement for 3-phase AC Induction Machine by Using Voltage/ Frequency Technique

Motors and Variable Speed Drives for Pumps and Fans. Reid Hart, PE

WOB-L. PISTON Pumps and Compressors. 607/668/669/688/689 Series MODELS:

Single-Phase AC Induction Squirrel Cage Motors. Permanent Magnet Series Wound Shunt Wound Compound Wound Squirrel Cage. Induction.

Five Reasons for VFDs in HVAC Applications

Principles of iers (intelligent

CHAPTER THREE DC MOTOR OVERVIEW AND MATHEMATICAL MODEL

SMC -50 Technology and Control Advances

Chapter 7: DC Motors and Transmissions. 7.1: Basic Definitions and Concepts

Variable Frequency Drive Basics

AGN Unbalanced Loads

Electro-Proportional Terms and Definitions

QUALITY MISTING PUMPS

Full file at

Transcription:

Jeff Fehr, Senior Application Engineer ACH550 Flux Optimization White Paper

Table of Contents Executive Summary...3 Introduction...3 Problem Statement...4 ABB Solution...5 Implementation...6 Summary...6 2

Executive Summary This whitepaper discusses the methods used within the ABB ACH550 Variable Frequency Drive (VFD) to control the voltage/frequency output ratio. The variations in V/Hz ratios have an effect on system efficiency that can result in lower energy use. VFDs are used on many types of connected loads. When VFDs are used on systems with variable torque loads, i.e. fans and pumps, there are V/HZ ratios that may be used to improve system efficiency. Introduction ABB and other VFD manufactures have utilized various techniques within the software of VFDs to control the Voltage/Hertz ratio on the output. For constant-torque loads typically found in industrial applications, a linear V/Hz ratio is utilized to maintain full torque output from the motor at various motor speeds. However, when VFDs are used on variable-torque applications, a linear V/Hz ratio typically will provide the motor with a higher amount of voltage than is required to control the attached load. This type of load resulted in a V/Hz ratio, where the applied voltage is proportional to the square of the voltage applied to the motor when used on a ABB drive. This method reduces the output voltage to the motor greatly, which results in increased motor efficiency. ABB has determined that there is additional savings potential in variable-torque loads, if the output voltage is reduced further, when the load is lower than what is expected for a variable-torque load; example: an oversized motor (i.e. a 42 BHP load placed on a 50HP motor). The software calculation that has been implemented in the ACH550 is known as Flux Optimization. This optimization continually monitors the performance of the motor, as the load and speed changes. In addition, the power required by the fan or pump is proportional to the speed cubed. As shown by the graph below, a small reduction in the speed of the fan or pump results in a large reduction in power. 3

Problem Statement Flow and Power 100 80 60 40 20 HP Flow The Affinity Law states that the flow in a fan or pump application is proportional to the fan or pump speed. This results in a reduction in required motor horsepower by the cubed change in speed. (RPM 1 /RPM²) * FLOW 1 = FLOW 2 (RPM 1 /RPM²)³ * HP 1 = HP 0 0 20 40 60 Hertz This reduction is what makes the use of VFDs a substantial energy cost-savings method. Due to the fact that the HVAC system typically is sized for extreme outdoor temperature conditions that occur only a small percentage of the year, reducing the capacity and/ or flow of the HVAC system will control comfort and costs. There are multiple methods available to reduce the capacity of the HVAC system, each with some cost-savings capability. The use of a VFD however will result in the maximum cost savings. With the use of VFDs as a common practice within HVAC systems, manufacturers continually are developing new control methods to increase the efficiency of the system. The introduction of the squared V/Hz ratio reduced the amount of energy used in the motor to create the magnetization current on a variable-torque load. This voltage curve, however, assumes that the power requirements of the motor are exactly a cubed relationship to the speed of the motor. When the load falls below this level, there is an additional energy savings potential. This is achieved by reducing the voltage level to the motor to reduce the magnetization current. However, if the voltage level to the motor is reduced too much, the motor will begin to draw more current. When this occurs, all energy savings possibilities are lost and there is a possibility of overloading the motor. With this possibility, ABB has developed the Flux Optimization algorithm within the VFDs software, to provide, automatically, the motor with the optimum voltage for any operating speed and load. 4

ABB Solution Flux Optimization is standard function in the ACH550 and ACS550 variable frequency drives. This feature requires no complex programming or configuration of the drive, which makes implementation easy. The software program continuously monitors the performance of the motor, while adjusting the voltage delivered to the motor. With the change in voltage, the motor s magnetizing flux levels increase and decrease. The Flux Optimization program measures the flux-generating current and the torque- producing current. When operating in scaler mode, data stored in the motor data table is used to adjust the voltage applied to the motor. This continually adjusts the voltage output, as the torque and speed requirement of the motor changes. When the VFD is operated in Vector mode, the VFD will operate in much the same way, but it will use data measured during the ID run of the motor. Benefit 1 The first benefit of flux optimization is the reduction of the flux-producing current. This increases the overall efficiency of the VFD / motor package, by reducing the motor s current. ABB conducted several tests of a 3HP 1755RPM motor operated via an ACH550 VFD. The motor was run at three (3) set speeds, while the shaft load was varied from 20 100% of full load. The VFD input power consumption was measured approximately 100 times at each. The average of the power draw of the drive for each speed and load was graphed. Below is a chart representing the motor operating at 30 Hz from 0.3 to 1.5 HP. As shown, there is an increase in the amp draw at a given HP at the lighter loads of the VFD operating in Flux Optimization. At 1/3 HP, the flux optimization provided a 2.3% increase; and, at 1 HP, a 4.2% increase was measured. 1.65 1.45 1.25 Shaft Horsepower 1.05 0.85 0.65 Flux Off 30Hz Flux On 30Hz 0.45 0.25 0.5 1.5 2.5 Drive Input Amps Draw As the load was increased, the motor began to operate near the constant-torque mode. This created a large increase in efficiency, when using flux optimization. This was because the V/Hz ratio was set to the squared ratio, and the drive required additional flux to generate more torque. Flux Optimization has the ability to increase or decrease the magnetic flux in the motor to match the demand of the load. Benefit 2 As mentioned in the paragraph above, if you operate a motor above the variable torque curve, there is a possibility of greatly decreasing the efficiency of the motor. If the user had set the drive to the squared V/Hz with the Flux Optimization off, the motor would have the possibility of overheating. When Flux Optimization is enabled, the drive continually monitors the load, and adjusts the voltage applied to the motor as required. This will allow the V/Hz ratio to adjust towards the linear ratio, as required. This also will reduce the energy consumption of the system and protect the motor from over-heating. 5

Implementation By default, the ACH550 drive leaves the factory with the flux optimization enabled and a V/Hz ratio of squared selected. This has been geared to the HVAC market and its large use of variable torque loads. An ACS550, however, ships with Flux Optimization off and a linear V/Hz ratio. This has been set to accommodate large use of constant-torque loads in the industrial market. Summary The use of Flux optimization has the potential to increase the operation efficiency in variable-torque applications. This is determined by several variables during operation, such as; speed; load; type of motor and size of motor. Because of the nature of the variables involved, the exact energy savings cannot be calculated by ABB. However, test data has shown that there is a possibility of a 5% decrease in input power to the drive when Flux Optimization is enabled. Therefore, the use of Flux Optimization in the ACH550 drive is highly recommended. 6

Notes 7

Contact us ABB Inc. 16250 W. Glendale Drive New Berlin, WI 53151, United States Phone: (800) 752-0696 Fax: (262) 785-0397 www.abb.com LVD-PHWP13U-EN REV B. Effective 1/24/2011. Subject to change without notice.