COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN

Similar documents
Effective November 2016 Supersedes February 2012 (S )

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN

COOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN

COOPER POWER SERIES. Fused loadbreak elbow connector installation instructions. Loadbreak Apparatus Connectors MN650014EN

Effective November 2016 Supersedes September 1998 (S )

COOPER POWER SERIES. QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit A26 installation instructions

Effective June 2016 New Issue

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

COOPER POWER SERIES. ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions. Fusing Equipment MN132017EN

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

COOPER POWER SERIES. RTE EL-BAY-O-NET FUSE Re-Fusing Instructions. Fusing Equipment MN132024EN

COOPER POWER SERIES. Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions. Fusing Equipment MN132014EN

COOPER POWER SERIES. Edison Modular Fuse (EMF) Installation Instructions. Fusing Equipment MN132031EN

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN

COOPER POWER SERIES. S.T.A.R. Hot line voltage indicator installation instructions. Fault Indicators MN320011EN. Indicator boot.

COOPER POWER SERIES. Testing a motor capacitor on a voltage regulator procedure instructions. Voltage Regulators MN225064EN

COOPER POWER SERIES. UltraSIL polymer-insulated D-73P disconnect switches installation instructions. Switches MN008004EN

COOPER POWER SERIES. High-voltage primary bushings installation instructions. OEM Equipment MN800008EN

Effective March 2015 Supersedes S August 2012

COOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN

COOPER POWER SERIES. S.T.A.R. type LVR faulted circuit indicator installation instructions. Fault Indicators MN320005EN

COOPER POWER SERIES. KA1169R Closing Coil Transfer-Switch Accessory Operation. Reclosers MN280069EN

COOPER POWER SERIES. KA662R tank-lifting windlass assembly and installation instructions. Recloser Mountings MN280071EN

High-voltage primary bushings installation instructions

COOPER POWER SERIES. Expulsion fuse installation instructions. Capacitors MN230005EN. Effective November 2016 Supersedes November 2001 (S )

COOPER POWER SERIES. Pad-mounted Switchgear MN285019EN. Effective March 2017 Supersedes February 2007 (S )

COOPER POWER SERIES. Dielectric grease application to recloser cable instructions. Reclosers MN280070EN

COOPER POWER SERIES. Types 4H single-phase and 6H three-phase vacuum interrupter conversion kits. Reclosers MN280014EN

Type NR oil switch installation and operation instructions

COOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN

COOPER POWER SERIES. KA716L7001 adjustable control valve kit for Types L, E, 4E, V4E, and V4L reclosers installation and adjustment instructions

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN

Effective May 2017 Supersedes December 2004 (S )

COOPER POWER SERIES. KA146W5 single pole-mounting hanger; KA146W2 tank lifting windlass assembly and installation instructions. Reclosers MN280039EN

Effective May 2017 Supersedes January 2003 (S )

COOPER POWER SERIES. Surge arrester interchangeable fuse cutout combination installation instructions. Surge Arresters MN235004EN

COOPER POWER SERIES. Quick Connect Assembly (QCA) Retrofit Kit, General Electric Installation Instructions. Voltage Regulators MN225075EN

COOPER POWER SERIES. Mercury switch to microswitch retrofit kit KA349WE installation instructions. Reclosers MN280022EN

COOPER POWER SERIES. Electronic control battery testing, charging, and replacement instructions. Reclosers MN280074EN

S Voltage Regulators GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage. Standards

S Fault Indicators. S.T.A.R. Type TPR Faulted Circuit Indicator Installation Instructions. Contents INSTALLATION PROCEDURES

COOPER POWER SERIES. Manually-Operated M-Force Switch Installation and Operation Instructions. Switches and Disconnects MN008003EN

COOPER POWER SERIES. Types D and DV recloser installation instructions. Reclosers MN280030EN

S Voltage Regulators GENERAL. PRODUCT INFORMATION Introduction. Contents. Acceptance and Initial Inspection. Handling and Storage.

S Voltage Regulators PRODUCT INFORMATION GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage

ELB ELB

S Voltage Regulators PRODUCT INFORMATION GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage.

Figure 1. Kearney Type HX cutout.

COOPER POWER SERIES. Instructions for oil-filled, single-phase overhead distribution transformers. Distribution Transformers MN201003EN

This Kit Is for Use with Types RE, RVE, WE, WVE, VWE, VWVE27, and VWVE38 Reclosers.

25 kv class fused loadbreak elbow connector

Two-way cable interlock kit for Magnum fixed circuit breakers

ELB ES. Product Installation Instructions

COOPER POWER SERIES. Metal-enclosed capacitor banks installation instructions. Power Capacitors MN230010EN

Installation Instructions For Motor Control Center (MCC) Units

Two-way cable interlock kit for Magnum drawout circuit breakers

Removal/installation instructions for Series NRX (IZMX) drawout levering (racking) mechanism

COOPER POWER SERIES. Metal-enclosed, pad-mounted capacitor banks installation instructions. Power Capacitors MN230009EN

200 A 25 kv and 28 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

3-way multi-family drawout cable interlock kit - type 32 - RF

Factory Authorized Mechanism Enhancement (FAME)

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal

Installation and removal instructions for Series NRX RF fixed breaker three-way Type 32 cable interlock kit

Reprogramming guide. Power Defense ICCB. Instructional Leaflet IL EN WARNING WARNING. Instructions apply to:

600 A 25 kv class BT-TAP deadbreak connector

Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version

600 A 15 and 25 kv class Cleer grounding elbow

200 A 25 and 28 kv class POSI-BREAK loadbreak elbow connector with optional integral jacket seal-canadian Edition

Instruction Booklet IB E. Contents

600 A 28 kv class Cleer loadbreak connector system

Installation Instructions for Interlocking Trip Indicator with Remote Reset for Magnum Low Voltage Circuit Breakers

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

600 A 35 kv class BT-TAP deadbreak connector

CCP2-FLR1-21_ flange-rod operating mechanism

COOPER POWER SERIES. VFI tester operating instructions. Underground Distribution Switchgear MN285001EN

600 A 15 kv class T-OP II deadbreak connector

600 A 15 kv class Cleer loadbreak connector system

Edison modular fuse, vault application products

COOPER POWER SERIES. RVAC Fluid-insulated Vacuum Switchgear; Installation, Operation, and Maintenance Instructions. Switchgear MN285005EN

Installation and Operation

Installation Instructions LINK---C

600 A 35 kv class separable splices

GWI Rev. 1 October 2007 Supersedes Rev. 0 Dated February 2004

COOPER POWER SERIES. Externally fused block banks installation instructions. Capacitors MN230004EN

Loadbreak Apparatus Connectors

COOPER POWER SERIES. Type MOST Fluid-Insulated Switchgear; Installation, Operation, and Maintenance Instructions

600 A 15 and 25 kv class deadbreak accessories, tools, and replacement parts

Replacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters

KFE10010-E. Reclosers. Contents. Type KFVE and KFVME (27kV) Bus Bar Kit KRK710-1 Installation Instructions. Cooper Power Systems

SIEMENS. XJ-L Busway Systems. Storage, Installation and Maintenance Instructions for... Piece No. 32-J Rev 3

ELF -LR current-limiting fuse

3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination

3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits

COOPER POWER SERIES. Types VWE, VWVE27, VWVE38X, WE, WVE27, and WVE38X; threephase electronically controlled; installation and operation instructions

CM52 Network Protector with Arc Flash Reduction Module

Grounding equipment COOPER POWER SERIES. Temporary Connections CA325004EN. Contents

Transcription:

Fusing Equipment MN132021EN Effective November 2016 Supersedes June 2011 (S240-97-1) COOPER POWER SERIES Installation Instructions

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation s ( Eaton ) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein. The information contained in this manual is subject to change without notice. ii

Contents DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY... ii SAFETY FOR LIFE... iv SAFETY INFORMATION... iv Safety instructions...iv PRODUCT INFORMATION.... 1 Introduction...1 Read This Manual First...1 Additional Information...1 Acceptance and Initial Inspection...1 Handling and Storage...1 Quality Standards...1 FUSE REPLACEMENT PROCEDURES... 2 Probe and Elbow Housing Disassembly...3 Fuse Disassembly...4 Replacement Fuse Installation...6 Probe Adapter Reassembly...7 Elbow Housing and Probe Reassembly...8 iii

! SAFETY FOR LIFE Safety for life! SAFETY FOR LIFE Eaton meets or exceeds all applicable industry standards relating to product safety in its Cooper Power series products. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Eaton employees involved in product design, manufacture, marketing, and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high voltage lines and equipment, and support our Safety For Life mission. Safety information The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians who are familiar with this equipment should install, operate, and service it. A competent technician has these qualifications: Is thoroughly familiar with these instructions. Is trained in industry-accepted high and low-voltage safe operating practices and procedures. Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment. Is trained in the care and use of protective equipment such as arc flash clothing, safety glasses, face shield, hard hat, rubber gloves, clampstick, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. Hazard Statement Definitions This manual may contain four types of hazard statements: DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in equipment damage only. Safety instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. DANGER Hazardous voltage. Contact with hazardous voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around highand low-voltage lines and equipment. G103.3 WARNING Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. G101.0 WARNING This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury and equipment damage. G102.1 WARNING Power distribution and transmission equipment must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install or maintain power distribution and transmission equipment can result in death, severe personal injury, and equipment damage. G122.2 iv

WARNING Capacitive Test Point Operating Instructions: Use only voltage indicating instruments specifically designed for test points. Use of conventional voltage sensing devices may provide false No Voltage indications. The test point must be dry and free of contaminants when checking for voltage. After indication is taken: clean, dry, and lubricate the test point cap with silicone grease and assemble to the test point. Always consider the termination to be energized until the test point No Voltage indication is confirmed by other means. Failure to comply could result in death or severe personal injury. WARNING All associated apparatus must be de-energized during any hands-on installation or maintenance. Failure to comply could result in death, severe personal injury and equipment damage. Pulling Eye Semi-Conducting Shield Loadbreak Probe Arc Follower Product Information Introduction The 200 A, 15 and 25 kv Class Fused Loadbreak Elbow Connectors from Eaton combines a fully-shielded and insulated plug-in termination with fullrange current-limiting fuse protection. The Fused Loadbreak Elbow Connector provides a convenient and cost effective means to adding fused protection to underground distribution systems, for connecting underground cables to transformers, switching cabinets and junctions equipped with loadbreak bushings. Read This Manual First Read and understand the contents of this manual and follow all locally approved procedures and safety practices before installing or operating this equipment. Additional Information These instructions cannot cover all details or variations in the equipment, procedures, or process described nor provide directions for meeting every possible contingency during installation, operation, or maintenance. When additional information is desired to satisfy a problem not covered sufficiently for the user s purpose, please contact your Eaton representative. EPDM Insulation Test Point Semi-Conductive Insert Drain Wire Tab Probe Adapter Current-Limiting Fuse Loadbreak Band Acceptance and Initial Inspection Each current-limiting replacement fuse is completely inspected and tested at the factory. It is in good condition when accepted by the carrier for shipment. Upon receipt of the current-limiting replacement fuse, inspect the connector thoroughly for damage and loss of parts incurred during shipment. If damage or loss is discovered, file a claim with the carrier immediately. Handling and Storage If the current-limiting replacement fuse is to be stored for an appreciable time before installation, provide a clean, dry storage area. Locate the replacement fuse so as to minimize the possibility of physical damage. Quality Standards ISO 9001 Certified Quality Management System. Coppertop Connector Drain Wire Tab Figure 1. Line illustration of 200 A 25 kv Fused Elbow. 1

Fuse Replacement Procedures Complete current-limiting replacement fuse includes: Current-Limiting Fuse Two (2) Spare Set Screws Bleeder Strap Two (2) Probe Installation Tools One (1) 1/8" Hex Wrench Two (2) 3/16" Hex Wrenches Silicone Lubricant Installation Instruction Sheet DANGER Hazardous Voltage. Both sides of the fused loadbreak elbow must be disconnected and grounded prior to any hands-on installation or maintenance. Failure to comply will result in death or severe personal injury and equipment damage. WARNING The operator should always use personal protective equipment (insulated gloves, clampstick and eye protection) whenever operating the fused loadbreak elbow. The operator should always be in the best possible operating position, providing firm footing and enabling a secure grasp of the clampstick, while maintaining positive control of the elbow before, during and immediately after operation. If there is any question regarding the operator s operating position, de-energize the elbow before operation. The operator should not be looking directly at the connector during the moment of circuit interruption or connection. Failure to comply could result in death or serious injury. Step 1 Voltage Test Operation The Fused Loadbreak Elbow Connector is equipped with two integral capacitive test points that can be used to establish whether or not the fuse has interrupted the tap circuit. The test point on the source side of an open fuse will indicate a voltage while the test point on the tap side of the fuse will indicate no voltage. Both test points will indicate a voltage if the fuse has not operated. Step 2 Establish visible break and visible ground Using a clampstick, isolate fuse by disconnecting the Fused Loadbreak Elbow Connector from the apparatus bushing and parking the Fused Loadbreak Elbow Connector on an appropriate feedthru device. Install an insulated protective cap on the apparatus bushing. Isolate the Fused Loadbreak Elbow Connector on the tap-end of the fuse by disconnecting and placing the tap-end cable termination on an appropriate feedthru device. Install an insulated protective cap on the tap-end apparatus bushing. Then create a visibly traceable ground on both sides of the fuse. WARNING Capacitive Test Point Operating Instructions: Use only voltage indicating instruments specifically designed for test points. Use of conventional voltage sensing devices may provide false No Voltage indications. The test point must be dry and free of contaminants when checking for voltage. After indication is taken: clean, dry, and lubricate the test point cap with silicone grease and assemble to the test point. Always consider the termination to be energized until the test point No Voltage indication is confirmed by other means. Failure to comply could result in death or severe personal injury. 2

Probe and Elbow Housing Disassembly Step 3 After a visible ground is achieved on both sides of the fuse, remove the Fused Loadbreak Elbow Connector from feedthru device. Step 4 Install supplied wire probe wrench into wrench hole of loadbreak probe. Turning counterclockwise, unthread and remove loadbreak probe from fused loadbreak elbow. Step 5 Detach drain-wire lead from the drain-wire eye of the elbow housing. At the overlap of elbow housing and cable housing, insert supplied bleeder strap approx. 1/2" (13 mm) under lip of elbow housing. Slide strap around the entire circumference of fused loadbreak elbow to vent the interfaces. Leave the bleeder strap inserted between housings. Remove Loadbreak Probe Wire Probe Wrench Probe Removed Turn Counterclockwise to loosen Elbow Housing Elbow and Cable Housing Overlap Bleeder Strap Cable Housing Drain Wires 3

Fuse Disassembly Step 6 Gripping the square portion of the cable housing, and keeping the cable housing stationary, apply a twist-and-pull motion to the elbow housing to separate it from the cable housing. Note: A screwdriver through the pulling eye on top of the elbow will aid in twisting and pulling to separate. Discard bleeder strap after housings are separated. Upper Pulling Eye Elbow Housing Step 7 Using the supplied 1/8" hex wrench, unthread the two set screws from the probe adapter. 1/8" Hex Wrench Facing Outward Separate Cable Housing Grip While Separating 4

Step 8 Remove probe adapter from fuse end cap stud on top of fuse. Step 9 Gripping the square portion of the cable housing, use the supplied 3/16" hex wrench to loosen and unthread fuse from cable housing. Probe Adapter Fuse End Cap Stud 3/16" Hex Wrench 5

Replacement Fuse Installation Step 10 Remove old fuse from cable housing. Step 11 Thread fuse clockwise by hand and start threads into the connector in bottom of the cable housing until hand-tight. Remove Old Fuse Insert Replacement Fuse Threaded End Threaded End 6

Probe Adapter Reassembly Step 12 Holding the square portion of the cable housing, complete fuse assembly using the supplied 3/16" hex wrench. Tighten until fuse bottoms and the hex wrench twists. Confirm check dimension shown in illustration above. Position the long end of the hex wrench on the cable housing nosepiece, verify that the top of the fuse end cap is equal to or below indicator notch on the hex wrench. Step 13 Install probe adapter on unthreaded stud. Probe adapter should rest flush on top of fuse end cap. Fuse End Cap Probe Adapter Probe Adapter Seated Flush On Top of Fuse End Cap Indicator Notch Check Dimension Use the Hex Wrench notch to measure proper depth. Indicator Notch 7

Elbow Housing and Probe Reassembly Step 14 IMPORTANT Align the flats of the probe adapter parallel to the nosepiece of the bushing. Step 15 Using supplied lubricant, clean and lubricate elbow and cable interfaces. Assemble elbow housing onto the cable housing. Make sure the test point is facing outward away from the front plate of the apparatus. Assemble set screws into the probe adapter. Using supplied 1/8" (3 mm) hex wrench, thread the two set screws until they bottom out on the end post of the fuse, then tighten each set screw an additional 1/8-1/4 turn until tight. Loadbreak Bushing Insert Probe Adapter Seated Flush On Top of Fuse End Cap Facing Outward Insert Elbow 1/8" (3mm) Hex Wrench Clean and Lubricate Interfaces with Supplied Lubricant Align the Flats of the Probe Adapter Parallel to the Nosepiece of the Bushing 8

Step 16 Push down and twist elbow housing to align the probe adapter. The threaded hole in the probe adapter should be centered with respect to the hole in the elbow housing and perpendicular to the probe axis. By hand, insert loadbreak probe into the elbow housing along the center axis of the interface and thread the probe into the probe adapter. A thin layer of silicone lubricant applied to the last 1/4" (6 mm) of the probe body (not on the threads) can aid in installation. After at least three turns or when the probe is seated (5-1/2 turns) onto the probe adapter, use provided installation tool to properly torque the loadbreak probe. Proper torque is applied when the tool twists at least 180 (1/2 turn). Note: If a different installation tool is used it must apply a torque of 100 to 120 lbf-in (11.0 13.5 N-m). Re-attach drain wire lead to the drain wire eye of the elbow housing. Clean and lubricate bushing and elbow housing interfaces areas with a thin, uniform coating of the silicone provided. Do not connect two different phases of a multiple-phase system. Before closing a single-phase loop, make certain both ends of the loop are the same phase. Clean and Lubricate Interface Assemble Loadbreak Probe Step 17 After the fuse has been replaced, using a clampstick, install the Fused Loadbreak Elbow Connector back onto the grounded feedthru device. Step 18 Using a clampstick, remove the insulated protective cap from the tap end apparatus bushing. Install the tap end cable termination onto the tap end bushing using the appropriate procedure for the tap end cable termination. Step 19 Using a clampstick, remove the insulated protective cap from the apparatus bushing and the Fused Loadbreak Elbow Connector from the feedthru device. Install the Fused Loadbreak Elbow Connector onto the apparatus bushing using the standard loadmake operating procedures described in Step 20. Note: Before installing the Fused Loadbreak Elbow Connector back onto the apparatus bushing, the cause for the fuse operation should be remedied. Drain Wires 9

Step 20 Operating Procedures Loadmake Operation Area must be clear of obstructions or contaminants that would interfere with the operation of the fused loadbreak elbow. Securely fasten a clampstick to the pulling eye of the fused loadbreak elbow. Place the fused loadbreak elbow over the bushing, inserting the white arc follower of the probe into the bushing approximately 2 1/2" (65 mm) until a slight resistance is felt. This will align and stabilize the fused loadbreak elbow. Turn your back to the bushing and grasp the clampstick securely and obtain good footing. Slam the fused loadbreak elbow onto the bushing with one quick and continuous motion. Turn around and apply a force to the clampstick to push the fused loadbreak elbow onto the bushing. A popping or snapping sound is often heard when this operation is performed. To check that the fused loadbreak elbow is properly latched apply a gentle pull force to the clampstick. When latched properly the fused loadbreak elbow will not slide back off of the bushing. Loadbreak Operation Area must be clear of obstructions or contaminants that would interfere with this operation. Use clampstick to secure standoff insulator or portable feedthru in bracket. Ground devices to system ground per appropriate Installation Instructions. All associated apparatus must also be grounded. Secure fused loadbreak elbow eye firmly onto clampstick and lock. Twist clampstick clockwise until the fused loadbreak elbow rotates slightly on bushing about 1/4" (6 mm). This action will break any surface friction between outer surface of bushing and inner surface of fused loadbreak elbow. Withdraw fused loadbreak elbow from bushing with a fast, firm, straight motion. Minimum amount of travel of fused loadbreak elbow to break load is 9" (230 mm). Use clampstick to place fused loadbreak elbow on lubricated standoff insulator or portable feedthru. (Follow loadmake instructions.) Place an insulated protective cap with ground wire attached to system ground on any exposed energized bushing using clampstick. Follow the same operating procedures as for the fused loadbreak elbow as outlined above under Loadmake Operation. As a last operation, push on the clampstick to seat the fused loadbreak elbow all the way onto the bushing again. This insures that the fused loadbreak elbow is latched and was not dislodged during the latching check in previous step above. Fault Close 1. It is not recommended that operations be made on known faults. 2. If a fault is experienced, the fused loadbreak elbow connector, probe, and the bushing must be replaced. 10

T his page is intentionally left blank. 11

! SAFETY FOR LIFE Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton s Power Systems Division 2300 Badger Drive Waukesha, WI 53188 United States Eaton.com/cooperpowerseries 2016 Eaton All Rights Reserved Printed in USA Publication No. MN132021EN November 2016 Eaton is a registered trademark. All trademarks are property of their respective owners. For Eaton s Cooper Power series product information call 1-877-277-4636 or visit: www.eaton.com/cooperpowerseries.