Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

Similar documents
Factory Authorized Mechanism Enhancement (FAME)

Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version

Instruction Booklet IB E. Contents

Removal/installation instructions for Series NRX (IZMX) drawout levering (racking) mechanism

O & M Manual for the EATON Generator Ready Loadcenter

Installation Instructions for Interlocking Trip Indicator with Remote Reset for Magnum Low Voltage Circuit Breakers

Installation Instructions for KPS and KPH Circuit Breakers and Molded Case Switches

Simple Electrically Operated Ground & Test Device For use in Type VCP-W Switchgear rated up to 15kV, 25 and 40kA UPPER TERMINAL SET VERSION

Two-way cable interlock kit for Magnum drawout circuit breakers

www. ElectricalPartManuals. com Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers

Installation Instructions for R-Frame G-Series (RG) 310+ Trip Unit

Magnum Breaker Remote Racking Device (MRR1000)

Reprogramming guide. Power Defense ICCB. Instructional Leaflet IL EN WARNING WARNING. Instructions apply to:

Instructions for installation, operation, and maintenance of medium voltage VC-W MR2 (integral racking)

Advanced Test Equipment Rentals ATEC (2832)

Installation and removal instructions for Series NRX RF fixed breaker three-way Type 32 cable interlock kit

3-way multi-family drawout cable interlock kit - type 32 - RF

Two-way cable interlock kit for Magnum fixed circuit breakers

38 kv Type VCPW-HD Simple Electrical Ground & Test Device (SEG&TD) lower terminal instruction booklet

CM52 Network Protector with Arc Flash Reduction Module

TVSS Installation for RLCM/CHGENLC, RLCU, and CHGEN ATSs

CCP2-FLR1-21_ flange-rod operating mechanism

Digitrip Retrofit System for General Electric AKR/AKRU-6D/7D-30S Series Breakers

Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

Flush Mount AIN ALPHA Meters. General. Hardware Kit

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

High-voltage primary bushings installation instructions

Magnum breaker remote racking device (MRR1000)

Digitrip Retrofit System for the Federal Pioneer 25-H(L)-2, 30-H(L)-2, 30-H(L)-3, and 30-3 Breakers

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN

IL131029EN. Instructions for the 15kV VCP-W 25-63kA Simple Manual Ground and Test Device

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN

COOPER POWER SERIES. ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions. Fusing Equipment MN132017EN

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN

DANGER. See Wiring Diagrams on page 7 for illustrations of both internal and connection wiring diagrams. WARNING

COOPER POWER SERIES. Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions. Fusing Equipment MN132014EN

COOPER POWER SERIES. High-voltage primary bushings installation instructions. OEM Equipment MN800008EN

COOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN

50 / 75 / 150 DHP [Cable or Hard Bus Application] Ground and Test Device

COOPER POWER SERIES. S.T.A.R. type LVR faulted circuit indicator installation instructions. Fault Indicators MN320005EN

Installation Power Management Unit Battery Cables and Battery Harness

Type NR oil switch installation and operation instructions

Digitrip Retrofit System for Allis-Chalmers LA-600 F Electrically Operated Fused Breakers

COOPER POWER SERIES. Testing a motor capacitor on a voltage regulator procedure instructions. Voltage Regulators MN225064EN

5/15/27 kv, 25/31.5/50/63 ka Manual Ground & Test Devices Installation, Operations and Maintenance Manual

Vacuum Circuit Breaker (Vehicle)

SPX9000 FR10 FR12 Adjustable Frequency Drives

Digitrip Retrofit System for Siemens-Allis RLX-1600 Breakers

General information on handling and maintenance of SDC TM Solid Dielectric Capacitor Bushings

Digitrip Retrofit System for BBC LKD 8 Breakers

T- VACR Fixed (up to 40kA) T-VAC Draw out (up to 40kA)

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

www. ElectricalPartManuals. com Digitrip Retrofit System for BBC LKD 8 Breakers IL 33-LK8-2

Effective June 2016 New Issue

COOPER POWER SERIES. S.T.A.R. Hot line voltage indicator installation instructions. Fault Indicators MN320011EN. Indicator boot.

COOPER POWER SERIES. Expulsion fuse installation instructions. Capacitors MN230005EN. Effective November 2016 Supersedes November 2001 (S )

Digitrip Retrofit System for Allis-Chalmers G-25 Breakers

COOPER POWER SERIES. UltraSIL polymer-insulated D-73P disconnect switches installation instructions. Switches MN008004EN

AMVAC TM and ADVAC TM Breaker commissioning procedures

Effective November 2016 Supersedes September 1998 (S )

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

Power Break Circuit Breakers

PAD-MOUNTED SWITCHGEAR INSPECTION & MAINTENANCE RECOMMENDATIONS TYPE PSI/II. 15kV 25kV. Qualified Persons

Cutler-Hammer I.B. ATS-RT03. Instructions for Cutler-Hammer Residential Automatic Transfer Switch

Vacuum Circuit Breakers (Vehicle)

Instructions for using Functional Test Kit on Digitrip 520 and 1150 family of Power Circuit Breaker Trip Units and Series G and FD MCCB Trip Units

Effective March 2015 Supersedes S August 2012

www. ElectricalPartManuals. com Digitrip Retrofit System for the Westinghouse DA-50 IL 33-DAC-2 WARNING

dfdf 34.5 kv and 69 kv, Type O Plus C II Condenser Bushings Technical Guide

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

Manual Transfer Switch

Instructions for the Use, Operation and Maintenance of Types VCP-TL and VCP-TRL Linear Magnetic Vacuum Circuit Breakers

User manual W-VACi. W-VACi 12 / 17.5 / 24 kv IEC Vacuum Circuit Breakers

Instructions for installation, operation, and maintenance of 38 kv type VacClad-W arc resistant metal-clad switchgear

Smart-UPS RT External Battery Pack Stack/Rack-Mount 6U

Digitrip Retrofit System for the General Electric AKR 6D/7D-30/50 and AKRT 6D/7D-50 Series Breakers

Instructions for Installation, Operation and Maintenance of Type VCP-W Vacuum Circuit Breakers IB131006EN

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN

COOPER POWER SERIES. Edison Modular Fuse (EMF) Installation Instructions. Fusing Equipment MN132031EN

SM-1700 Secondary Shunt Trip Coil Assembly. Powered by Safety

COOPER POWER SERIES. Pad-mounted Switchgear MN285019EN. Effective March 2017 Supersedes February 2007 (S )

COOPER POWER SERIES. KA1169R Closing Coil Transfer-Switch Accessory Operation. Reclosers MN280069EN

2000-LB. ENGINE STAND

SecoVac * Ground & Test Device

1000-LB. MOTORCYCLE LIFT TABLE OWNER S MANUAL

Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9928C

IB PowlVac ITE-HK Remote Racking Device

COOPER POWER SERIES. RTE EL-BAY-O-NET FUSE Re-Fusing Instructions. Fusing Equipment MN132024EN

1000-LB. ENGINE STAND

Instructions for installation, operation, and maintenance of 5/15 kv type VacClad-W arc resistant metal-clad switchgear Contents

Vacuum Circuit Breakers (Vehicle)

COOPER POWER SERIES. Surge arrester interchangeable fuse cutout combination installation instructions. Surge Arresters MN235004EN

1000-lb Hydraulic Truck Crane

PATENT PENDING. Phone: (877) Operation and Service Manual

Effective November 2016 Supersedes February 2012 (S )

TXJ0500/RR500 1,000-lbs. Truck Bed Roller Dolly

Transcription:

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod Eaton Corporation Moon Twp, PA. U.S.A. 15108 1

INTRODUCTION READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE ATTEMPTING TO USE THIS DEVICE. IMPROPER USE CAN RESULT IN DEATH, BODILY INJURY AND/OR PROPERTY DAMAGE. SAFETY PRECAUTIONS: All safety codes, safety standards and/or regulations must be strictly observed in the installation, operation and maintenance of this device. WARNING THE WARNINGS AND CAUTIONS INCLUDED AS PART OF THE PROCEDURAL STEPS IN THIS DOCUMENT ARE FOR PERSONNEL SAFETY AND PROTECTION OF EQUIPMENT FROM DAMAGE. AN EXAMPLE OF A TYPICAL WARNING LABEL HEAD- ING IS SHOWN ABOVE IN REVERSE TYPE TO FAMILIARIZE PERSONNEL WITH THE STYLE OF PRESENTATION. THIS WILL HELP TO INSURETHAT PERSONNEL ARE ALERT TO WARNINGS, WHICH MAY APPEAR THROUGHOUT THE DOCUMENT. IN ADDITION, CAUTIONS ARE ALL UPPER CASE AND BOLDFACE AS SHOWN BELOW. CAUTION COMPLETELY READ AND UNDERSTAND THE MATERIAL PRESENTED IN THIS DOCUMENT BEFORE ATTEMPTING INSTALLATION, OPERATION OR APPLICATION OF THE EQUIPMENT. IN ADDITION, ONLY QUALIFIED PERSONS SHOULD BE PERMIT-TED TO PERFORM ANY WORK ASSOCIATED WITH THE EQUIPMENT. ANY WIRING INSTRUCTIONS PRESENTED IN THIS DOCUMENT MUST BE FOLLOWED PRECISELY. FAILURE TO DO SO COULD CAUSE PERMANENT EQUIPMENT DAMAGE. WARNING SATISFACTORY PERFORMANCE OF THESE MINIMOD AND OR BREAKERS IS CONTINGENT UPON PROPER APPLICATION, CORRECT INSTALLATION AND ADEQUATE MAINTENANCE. THIS INSTRUCTION BOOK MUST BE CAREFULLY READ AND FOLLOWED IN ORDER TO OBTAIN OPTIMUM PERFORMANCE FOR LONG USEFUL LIFE OF THE MINIMOD AND OR CIRCUIT BREAKER ELEMENTS. 2

DESCRIPTION The Eaton 4000A Mini-Mod is an integrated assembly for drawout vacuum circuit breakers, bus and control devices coordinated electrically and mechanically for medium voltage circuit protection and control. The metal-clad integrity provides maximum circuit separation and safety. All circuit breakers are equipped with self-aligning and self-coupling primary and secondary disconnecting devices, and arranged with a mechanism for moving it physically between connected and disconnected positions. All major primary components, such as circuit breaker, voltage transformer, control power transformer and buses are completely enclosed and grounded by metal barriers. A metal barrier in front of the circuit breaker and auxiliary drawer ensures that, when in the connected position, no live parts are exposed by opening the compartment door. Automatic shutters cover primary circuit elements when the removable element is in the disconnected, test or removed position. All primary bus conductors and connections are insulated with track-resistant fluidized bed epoxy coating for rated maximum voltage of the assembly. Mechanical interlocks are provided to maintain a proper and safe operating sequence. Instruments, meters, relays, secondary control devices and their wiring are isolated, where necessary, by grounded metal barriers from all primary circuit elements. Corona emissions within the Mini-mod assemblies have been eliminated or reduced to very low levels by special fabrication and assembly techniques. By making switchgear assemblies corona free, Eaton Corporation has made its switchgear more reliable. Circuit Breaker Compartment The mechanism for levering the breaker is a unique cell mounted design. It incorporates all the safety interlocks to render the breaker mechanically and electrically trip free during the levering procedure. A silver plated copper ground bus provided on the levering pan assembly is engaged by a spring loaded ground contact on the circuit breaker to ensure that the circuit breaker remains grounded throughout its travel. 3

Figure #1: View of the 4000A MiniMod with part descriptions. 4

Figure #2: Outline drawing with reference dimensions. 5

Figure #3 and #4: View of the breaker in the text and connected positions. 6

Figure #5: View of the breaker on the rails getting ready to be racked in the MiniMod. Figure #6: View of the breaker racked in the MiniMod. 7

Figure #7: View inside the MiniMod. 8

MiniMod Un-Packing and Incoming Inspection: If the MiniMod is to be placed in storage, maximum protection can be obtained by keeping it packed as shipped. Before placing it in storage, checks should be made to make sure that the unit is free from shipping damage and is in satisfactory operating condition. The MiniMod is shipped within a wood crate. When it arrives and needs to be unpacked then the top of the crate should be removed first. Then the sides should be removed. The unit should be kept on the bottom pallet temporarily. Inspect the unit for shipping damage and or missing parts. Make sure the red brick colored spouts in the back of the units do not have any significant cracks. If any problems are found then please contact your local Eaton Salesman or EESS for repair / replacement parts. The unit can now be moved around via a pallet jack and or fork lift truck. Eaton suggests moving the unit around attached to the pallet. This is due to the large size of the unit and the unbalanced weight of the unit. Eaton suggests the wood crate be saved in storage as long as possible in case it is needed. The MiniMod is supplied with lifting hooks and or lifting metal strips located on the top of the unit. A large overhead crane can be used to life the unit. These lifting hooks or lifting metal straps can be removed during the installation process. MiniMod Operational Inspection: It is best to perform this testing with the MiniMod on the pallet outside of the switchgear. We do not suggest you mount the MiniMod in the switchgear and then perform these tests. Testing with just the breaker and MiniMod allows for the user to see the operation from all sides and avoid any damage to the breaker and or MiniMod. Test the operation of the left hand and right hand shutter drivers by pushing them by hand forward and backwards. If binding is found then try to remove the foreign item causing the binding. If required grease the parts to improve the operation. Frequency of Inspection and Maintenance: Periodic inspections and associated maintenance are essential to the safe and reliable operation of the MiniMod and VCP-WG Vacuum Circuit Breaker Elements. The inspection frequency and associated maintenance recommended are intended to insure the best possible ongoing service. It is imperative that an established schedule be followed. To establish an exact schedule for a specific installation, use the following guidelines: 1. Customers such as Utilities having extensive experience with Power Distribution components should schedule their inspection and maintenance intervals using well established best practices in their industry. 2. All other customers should use the following guidelines as good conservative practice: a. In a clean, non-corrosive environment, inspect and maintain each MiniMod annually or after every 100 levering in operations, whichever comes first. 9

b. For special conditions such as frequent levering in operations, contaminated environments, and high temperature/humidity conditions, the inspection frequency should be a minimum of twice per year. 3. Fault interruptions have the greatest impact on the MiniMod. MiniMod that have been subjected to 15 full rated fault interruptions should be immediately inspected and the schedule for inspection and maintenance should be re-evaluated based upon the inspection results. Additionally, because of the variability of system fault characteristics, if there are any customer uncertainties in the records of the magnitude, duration, or other fault details, increased inspection frequency should be considered. 4. The unit should be visually examined to make sure there is no cracking of the insulation parts and damage done to the internal components. 5. Create and maintain a dated permanent record of all inspections, maintenance performed, actions taken, observations made, and measurements taken. Not only will this provide valuable historical information, it can help to establish whether or not the present schedule needs to be adjusted. 6. Perform ongoing visual inspections, when possible, of all equipment on a regular basis. Be alert for an accumulation of dirt in and around the primary contacts, loose hardware and or discolored insulation. For assistance in establishing or updating a detailed Inspection and Maintenance schedule for a specific application, please contact your local Eaton representative. General Torque Guidelines: Bolts and screws must be properly torqued. This is especially true if part and/or accessories are added or replaced. The table below provides guidelines on torque levels. The table is intended as a general guideline and should be applied in conjunction with the experience and good judgment of the individual performing the work. Bolt Size Torque (LB-IN) 8-32 24 10-32 36 1/4-20 72 5/16-18 144 (12 lb-ft) 3/8-16 300 (25 lb-ft) 1/2-13 540 (45 lb-ft) 10

Troubleshooting: a) Insulation: Visually inspect the insulators, barriers, spouts, boots, for dirt, dust, and cracking. If problems are identified then clean and or replace the components are required. b) Corona: Visually inspect the insulators, barriers, spouts, boots, for signs of corona discharge. This can normally be identified by holes in the insulation, white powder like substance on the insulation, burn marks, If problems are identified then clean and or replace the components are required. Adjust the design to improve the corona performance by contacting your local Eaton Salesman and or use switchgear common best practices. c) Insulation Integrity: Insulation integrity should be checked on a yearly basis via performing a standard industry HiPot test via a HiPot test machine. d) Control Circuit Wiring: Visually inspect all secondary control voltage wiring. Make sure the components work correctly and operate smoothly. Replace any worn or defective wiring. e) Shutter operating mechanism: Visually inspect the proper operation of the shutter drivers. If binding is found then remove the foreign elements causing the binding. If parts are found bent or damaged then replace the damaged parts. If required grease the moving components. f) Levering In operating mechanism: Visually inspect the proper operation of the levering in system. If binding is found then remove the foreign elements causing the binding. If parts are found bent or damaged then replace the damaged parts. If required grease the moving components. Quality Test: In order to perform a quality test of the MiniMod a standard 31 frame VCP-WG breaker should be racked in and out of the MiniMod. Perform this test five times. After the end of the fifth operation the testing is complete. The unit can then be mounted into the switchgear. Check to make sure the breaker can successfully be racked in and out of the MiniMod without any of the components binding, rubbing, and or breaking. If problems are identified then contact your local Eaton Salesman or EESS for repair / replacement parts. 11

This instruction booklet is published solely for information purposes and should not be considered all inclusive. If further information is required, you should consult Eaton. Sale of product shown in this literature is subject to terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between the parties. This literature is not intended to and does not enlarge or add to any such contract. The sole source governing the rights and remedies of any purchaser of this equipment is the contract between the purchaser and Eaton. NO WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE OF TRADE, ARE MADE REGARDING THE INFORMATION, RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, addition-al expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and description contained herein. 12