CALEFFI. Mixing valves and actuators series 01169/17 GB. replaces dp 01169/09. Function

Similar documents
CALEFFI. Motorised ball valve for central heating systems. 638 series 01196/18 GB. replaces dp 01196/12 GB

CALEFFI. Motorised temperature regulating unit for heating and air conditioning systems WYP UPM series 01254/17 GB

CALEFFI. Hydraulic separator-manifold SEPCOLL. 559 series 01084/16 GB. replaces dp 01084/13 GB

COMPONENTS FOR SOLAR THERMAL SYSTEMS

COMPONENTS FOR SOLAR THERMAL SYSTEMS

ACCREDITED. brass EN CW617N brass EN CW614N brass EN CW614N, chrome plated PTFE PSU EPDM

CALEFFI. Modulating temperature regulating unit with distribution kit for primary circuit. 171 series 01153/15 GB. replaces 01153/07 GB

R EGI S TERED. Function

CALEFFI. Motorized ball valves with 3-wire control series ACCREDITED 01131/13 NA. Replaces 01131/07 NA

CALEFFI. Direct supply unit for heating systems. 165 series 01237/17 GB. replaces dp 01237/15 GB. Function

Connection and regulation kit for HVAC terminal units

CALEFFI. Pressure independent control valve (PICV) 145 series 01262/14 GB B 51

CALEFFI. Composite manifolds specifically designed for radiant panel systems. 670 series 01126/18 GB. replaces dp 01126/11 GB.

CALEFFI. Diverter and isolation valves for panel radiators. 3010, 3011, 3012, 3013 series 01036/12 NA. Function. Product range

CALEFFI. zone valves. Z series 01115/14 NA. Replaces 01115/11 NA. Function

CALEFFI. Differential pressure by-pass valve. 519 series 01007/14 NA. Replaces 01007/12 NA

CALEFFI. HydroMixer direct distribution unit for heating systems. 165 series 01237/13 NA. Function

G765, 3-Way, Mixing Flanged Globe Valve

CALEFFI. Pre-assembled distribution manifolds for. heating and air-conditioning systems. 663 series 01065/18 GB. replaces dp 01065/06 GB.

CALEFFI. Distribution manifold for radiant panel systems. 664 series 01260/14 GB

CALEFFI. Motorised ball zone valves with 3-contact control BY series 01131/18 GB. replaces 01131/11 GB

INSTALLATION AND COMMISSIONING MANUAL CONTENTS. Function. Important Product range Technical specifications

INSTALLATION AND COMMISSIONING MANUAL CONTENTS. Function. Product range. Technical specifications. Characteristic components

Electro Controls. Valves / Linkages WattsIndustries.co.uk

CALEFFI. Distribution manifold for radiant panel systems. 664 series 01260/18 GB. replaces 01260/14 GB

Accessories. UP timer. Timer control. Approvals. UP Series

G7100S, 3-Way, Mixing Flanged Globe Valve

EVOPLUS / EVOPLUS SAN

1 DESCRIPTION 2 WORKING PRINCIPLE 2.1 REGULATION ST

Selection Guide. Vx-7000 & Vx-9000 Series Mx4x-6xxx & Mx4x-7xxx Series. Globe Valve Assemblies. Actuator/Linkage Assemblies

DEP7 SG Iron Excess Pressure Valve

2, 3 and 4 - way valves VZL

G780, 3-Way, Mixing Flanged Globe Valve

Two port valves. pneumatically actuated

Series 870 Sleeve coupling for repairs Sizes Ø 25, Ø 32, Ø 40, Ø 50

CALEFFI. HydroMixer motorized temperature mixing unit. 167 series 01239/13 NA. Function

FLOW RATE STATIC BALANCING Valves for radiators

3-Way Linked Globe Valve Assemblies with Linear Series Actuators

CALEFFI. Pre-assembled distribution manifold for radiant panel systems S1 series 01144/11 GB. Replaces 01144/07 GB.

CALEFFI. Manifolds in composite specifically designed for radiant panel systems. 670 series 01126/05 GB. Function

G6125C, 2-Way, Pressure Compensated Flanged Globe Valve

VE-x Plug & Seat Valve Assemblies

F6125HD, 5, 2-Way Butterfly Valve Resilient Seat, 304 Stainless Steel Disc

RS Series. Three way rotary valves for temperature control systems

G765, 3-Way, Mixing Flanged Globe Valve

F6100HD, 4, 2-Way Butterfly Valve Resilient Seat, 304 Stainless Steel Disc

Flow controller with integrated control valve (PN 16) AHQM return and flow mounting

2-Way & 3-Way Non Spring Return Characterized Ball Valves

SPIRA-TROL. ½" to 4" ASME (ANSI) Two-port KEA, KFA and KLA Control Valves

Electronic Temperature Control & Bulb Well Assembly (AC)

MTD Silent Series MIXED FLOW IN-LINE DUCT FAN

Seated valves VF 2, VL 2-2-way VF 3, VL 3-3-way

2-Port and 3-Port Zone Valves, PN 16 / 20

DRV4 and DRV4G Cast Steel Pressure Reducing Valves

Filled System Thermometers

2-Port and 3-Port Zone Valves & Actuators, PN16

SPARE PARTS EXPLODED VIEW GAS WALL BOILERS

MINIMATIC COMPACT - COMPETITIVE - FLOW CONTROL NORTHVALE KORTING LTD

548 hydraulic separator

Valves & Flow Control Components Valves & Flow Control Components

2-Port and 3-Port Zone Valves, PN16

CALEFFI. Ball shut-off valve fitted for integrated flow rate measuring sensor. 111 series 01234/13 GB. (kpa) (mm w.g.) G (m 3 /h)

F6100HD, 2-Way Butterfly Valve Resilient Seat, 304 Stainless Steel Disc

Seated valves (PN 6) VL 2 2-way valve, flange VL 3 3-way valve, flange

LK Manifold Shunt VS2

Superstatic 440. Static Heat- and Cooling Meter. Application

2-way and 3-way globe valves

VALVES WITH SA03 ELECTRIC ACTUATOR

3-port seat valves PN6 with flanged connection

STAF-SG. ANSI flanges. Balancing valves DN

MOTORISED BALL VALVE. Uni/Bi-directional. patented. 3 points 2 points Price list root SR... SS... SY... Connection with ball valve.

STAF, STAF-SG. Balancing valves PN 16 and PN 25 DN

Your Global Source for Today s Most Popular Solenoid Valves

Valve Series V2001 Three-way Valve Type 3323

DRV7 and DRV7G SG Iron Pressure Reducing Valves

STAF-SG. ANSI flanges. Balancing valves Size 3/4-16

Flow controller with integrated control valve (PN 16) AHQM - return and flow mounting

TECHNICAL FEATURES MOTORIZED VALVES USE. Data sheet

VG2000 Series Cast Iron Flanged Globe Valves

F6100HD, 4, 2-Way Butterfly Valve Resilient Seat, 304 Stainless Steel Disc

Table of Contents Introduction 3 Chapter 2: Operation 4 Chapter 3: Components 5 Chapter 4: Specifications 8

Superstatic 440. Static Heat Meter, Static Cooling Meter. Application

TWA S/K/P. Incorporating. R410A Air cooled water chillers with axial fans and scroll compressors from 189 kw to 1007 kw

Electromotoric actuators

HYDRAULIC SEPARATOR PRODUCTION RANGE. Code Size Max. flow rate (l/h) " "1/ "1/ " 8.

AVQMT. AVQT controller can be combined with AVT or STM thermostatic actuators.

Spring Return and Double Acting Pneumatic Quarter- Turn Actuators For Output Torques to 13,444 lb.in.

3-port valves. pneumatically actuated

Spiraflo Steam flowmeters

Heat Exchanger Accessories

CALEFFI. Pre-assembled distribution manifolds for radiant panel systems. series 663 & /05 NA. Function

TRF.. series spring return rotary actuators for CCV

V5422L / V5422E ACTUATED BUTTERFLY VALVES. FEATURES With factory-mounted electric actuator

Technote. Frese OPTIMIZER - pressure independent 4-pipe coil control unit. Application. Benefits. Features.

Gas Pressure Governors

Pressure Independent Control Valve

G7150D, 3-Way, Diverting Flanged Globe Valve

Pre-assembled distribution manifolds for radiant panel systems

CONTROL VALVES CONTROL VALVES BALL VALVES VBN2, VBN3 SERIES DESCRIPTION FEATURES SPECIFICATIONS

Seated valves (PN 16) VF 2-2-way valve, flange VF 3-3-way valve, flange

Transcription:

Mixing valves and actuators 610-611 - 612-63 series RIT ISO 01 M 214 LI 01169/17 replaces dp 01169/09 unction The mixing valves allow the centralisation heating system to be regulated by mixing the boiler outlet water with the return water from the system, in order to obtain the desired flow temperature to the user. They can be motorized and combined with climatic regulators to send the hot water to the user according to the actual thermal load required, thus respecting the recent energy saving provisions. Reference documentation - Instruction sheet 11211921 igital regulator with functional synoptic for heating and cooling. - Instruction sheet 18057 Optimiser digital climate regulator for heating 1520 series. - Instruction sheet 180 Optimiser digital climate regulator for heating and heating/cooling 1520 series. Product range Three-way butterfly threaded mixing valve with manual control sizes N 20 (3/4 ) N (2 1/2 ) Three-way flanged butterfly mixing valve with manual control sizes N 50 N 125 our-way butterfly threaded mixing valve with manual control sizes N 20 (3/4 ) N (2 1/2 ) our-way flanged butterfly mixing valve with manual control sizes N 50 N 125 Three-way sector threaded mixing valve with manual control sizes N 20 (3/4 ) N (2 1/2 ) Three-way flanged sector mixing valve with manual control sizes N 50 N 125 61202 series Three-way motorized sector threaded mixing valve, RH version sizes N 20 (3/4) N (2 1/2 ) 61201 series Three-way motorized sector threaded mixing valve, LH version sizes N 20 (3/4) N (2 1/2 ) ode 6302/04 ctuator for mixing valves from 3/4 to with auxiliary microswitch, RH version ode 6302/04 ctuator for mixing valves from 3/4 to with auxiliary microswitch, LH version ode 6301/03 ctuator for mixing valves from 2 to 5 with auxiliary microswitch electric supply V (ac) or 24 V (ac) electric supply V (ac) or 24 V (ac) electric supply V (ac) or 24 V (ac) Technical specifications Materials ody: Rotor: over: ushing: Lever: Seals: cast iron N 1561/98 N-JL- cast iron N 1561/98 N-JL- aluminium aluminium P6630 PM Performance Medium: water, glycol solutions Max. percentage of glycol: 30% Max. working pressure: 6 bar Working temperature range: 2 110 Rotor rotation angle: Threaded connections: langed connections: 3/4 2 1/2 N 50 N 125, PN 6 can be coupled with counterflange N 1092-1 ctuators Type with 3 contacts, electric supply: - codes 6302, 6312, 6301: V - 50 Hz - codes 6304, 6314, 6303: 24 V - 50 Hz Power consumption: - codes 6302, 6304, 6301, 6303: 3 V - codes 6312, 6314: 4,5 V uxiliary microswitch contact rating: - codes 6302, 6304, 6301, 6303: 10 (2) - 250 V (ac) - codes 6312, 6314: 16 (4) - 250 V (ac) Protection class: IP 42 Operating time: - codes 6302, 6304, 6301, 6303: 60 s - codes 6312, 6314: 180 s Torque: - codes 6302, 6304, 6301, 6303: 15 N m - codes 6312, 6314: 35 N m Maximum ambient temperature: 55 With adapter

3/4 1" 1 1/4" 1 1/2" 2" 2 1/2" 156 150 52 52 52 52 52 66 56 2,8 2,8 3,1 3,6 4,6 8,8 N 50 N N 80 N N 125 180 160 1 2 1 2 7,1 9,8 13,1 20,2 32 3/4 1" 1 1/4" 1 1/2" 2" 2 1/2" 156 150 56 158 2,9 3 3,3 4 5,1 9,7 N 50 N N 80 N N 125 180 160 1 2 1 2 8,3 11,6 16,4 21 28 3/4 1" 1 1/4" 1 1/2" 2" 2 1/2" 156 150 56 158 2,8 2,8 3,1 3,6 4,6 8,8 N 50 N N 80 N N 125 180 160 1 2 1 2 8 9,6 13,2 20,3 26 ode 605 606 607 608 609 620 ode 611050 611060 611080 611 611120 ode 650 660 680 610 610120 ode 615 616 617 618 619 611020 ode 612050 612060 612080 612 612120 ode 615 616 617 618 619 612020 630. 25 125 112 61 ode 0,72 631. 79 44 83 162 ode 1,3 imensions

Operating principle The aleffi 610 and valves are three-way, respectively butterfly and sector types, while the aleffi is a four-way butterfly valve. The 610 and valves can be used both as mixing valve or as a diverter, the only as a mixing valve. Legend oiler flow System flow oiler return System return oiler inlet (with valve in mixing function) Mixing valve function iverter function The three-way mixing valve allows simultaneous control of the primary circuit medium and of the system return medium. In particular the two mediums are mixed directly inside the valve. lso the four-way mixing valve allows simultaneous control of the primary circuit medium and of the system return medium. The two mediums are mixed directly inside the valve body, so as to enable double circulation on both the primary and secondary circuit. The mixing valve, in this application, also performs the hydraulic separation of the primary circuit from the secondary circuit. Mixing valve function Mixing valve function iverter function Installation example of 3-way butterfly valve with mixing valve function

hanging the inlet position: customized installation The series 610, 611 and can be used customizing the ports use: 1) for the 610 and it is possible to exchange the hot water inlet port from the boiler (marked with the label ) with the cold water inlet port returning from the system, placed on line. The mixed water outlet port remains the same in both configurations, i.e. the one positioned at below the graduated plate. 2) for the it is possible to exchange the hot water inlet port from the boiler (marked with the label ) with the mixed water inlet port flowing to the system, placed on line. The cold water inlet port returning from the system remains the same in both configurations, i.e. the one positioned at on the opposite of the graduated plate. In this case it is necessary to access inside the valve body unscrewing the four hexagonal screws (fig.1), and rotating of 180 only the rotor shaped bushing (fig.2). When customizing the ports use, we recommend removing the label and marking them according to the new diagram in order to facilitate the components maintenance. Legend oiler flow System flow oiler return System return oiler inlet (with valve in mixing function) standard ustomized 1 2 3 Installation example of 3-way sector valve with mixing valve function

4 6 7 8 9 Hydraulic characteristics Δp (mm w.g.) Δp (kpa) onstruction details Use at high temperature The body material, internal devices and PM seals make it possible to use the aleffi 610, 611 and mixing valves in heating systems with temperatures up to 110. nti-friction system Inside the valves, between the mixing device and the body, there is a bushing made of anti-friction material that absorbs the volume variations, if any, caused by the thermal expansion of the parts that make up the valve and ensures ease of rotation throughout the temperature range of use. (m 3 /h) linear characteristic Thanks to the profile of the flow passage sizes obtained on the bushing, the regulation feature resulting in the system is of linear type, which is the optimal condition to guarantee the best management of the variable thermal loads on the system. OILR INLT 5000 0 1800 1600 0 1 0 0 800 0 600 500 450 0 350 300 250 180 160 120 50 4500 00 3500 3000 2500 80 60 0,3 0,35 0, 0,45 Δp (mm w.g.) 0,5 0,6 Δp (mm w.g.) 0,7 0,8 0,9 1 3/4 7,5 N 50 45 1,2 1,4 1,6 1,8 2,5 3/4 7,8 N 50 53 11,9 N 72 3/4" 3,5 2 3 4,5 5 12,3 N 80 16,8 N 80 10 12 18,5 N 80 30 N 183 14 16 18 25 20 30 2 - N 50 2 1/2 - N 35 45 30 N 2 45 N 125 3 50 N 80 60 2 53 N 125 410 2 1/2 72 N Δp (kpa) N 125 80 120 180 160 (m 3 /h) 2 1/2 80 45 35 30 25 18 16 14 12 9 8 7 6 4,5 4 3,5 3 2,5 1,8 1,6 1,4 1,2 50 20 10 5 2 1 0, 0,80 0, 0,60 0,5 Δp (kpa) Possibility of motorization The aleffi 610, 611 and mixing valves are supplied with manual control but they can be motorized using the aleffi 63 series actuators. Sizing method To select the most appropriate size of the aleffi 610, 611 and mixing valves it is necessary to know two sizes: - the medium flow rate passing through the mixing valve - the head loss to be attributed to the valve. enerally a loss value of 5 15% of the head loss of the circuit used is assigned to the mixing valves. xample low rate requirement: = 5 m 3 /h System pipes: 2 Head loss of the circuit used: Δp = 3000 mm w.g. = 30 kpa Mixing valve selection: The mixing valve head loss Δp V must be between 5% (Δp V, point ) and 15% (Δp V, point ) of the head loss of the circuit used: Δp V = Δp 0,05 = 150 mm w.g. = 1,5 kpa (point ) Δp V = Δp 0,15 = 450 mm w.g. = 4,5 kpa (point ) Using the valve load loss diagram, the x-axis value identified is 5 m 3 /h and moving up vertically the and points are identified, which obtained at the intersection with the respective load loss values. The line joining points and intersects the head loss elbow of the 4-way valve, which will therefore be installed on the system. In most cases, a proper sizing leads to the choice of a valve with smaller diameter than that of the pipe to which it is installed. Installation Valve installation The 610, 611 and mixing valves, installed with horizontal rotor axis, can be turned in any position, avoiding to position the actuator cable glands upwards. If instead they are installed with vertical rotor axis, the actuator must necessarily be above the valve. 3/4" 7,2 N 50 42 11,9 N 62 16,5 N 80 123 30 N 172 2 42 N 125 3 (m 3 /h) 2 1/2 62 Valve motorization or installing the 63 series actuators to the valve, refer to the instruction sheet with the detailed information.

Wiring diagrams ctuator code 6302-6304 (SM50) M ctuator code 6312-6314 (SM) M ctuator 1-counter clockwise rotation (W) 2-clockwise rotation (W) 3-common uxiliary microswitch (graphical representation at the end of the rotation indicated) 4-common 5-normally closed N 6-normally open NO W L N 1 2 3 4 5 6 W ctuator 1-clockwise rotation (W) 2-counter clockwise rotation (W) 3- common uxiliary microswitch (graphical representation at the W end of the rotation indicated) W W 4-normally open NO 5-normally closed N 6-common L N 1 2 3 4 5 6 W oupling with digital regulators ctuator code 6302 (SM50) with modulating digital regulator for heating and cooling code 161010 ctuator code 6312 (SM) with modulating digital regulator for heating and cooling code 161010 lectric connections R2 W counter clockwise rotation R3 W clockwise rotation N Neutral lectric connections R2 W clockwise rotation R3 W counter clockwise rotation N Neutral NOT: heck the actuator rotation direction. If necessary exchange the terminals 1 and 2 of the actuator ctuator code 6302 (SM50) with Optimiser digital climate regulator code 151 lectric connections L Phase L Phase 1 W counter clockwise rotation 2 W clockwise rotation N Neutral ctuator code 6312 (SM) with Optimiser digital climate regulator code 151 lectric connections L Phase L Phase 1 W clockwise rotation 2 W counter clockwise rotation N Neutral NOT: heck the actuator rotation direction. If necessary exchange the terminals 1 and 2 of the actuator

161 igital regulator with functional synoptic for heating and cooling complete with immersion flow probe with pocket and return probe Pt0 6 mm. Optional climatic probe. djustment temperature range: 5 95. lectric supply: V - 50/60 Hz. Protection class: IP 20 / N 60529. Probe cable length: 1,5 m. 6120 Three-way motorized sector mixing valve, threaded connections. Max. working pressure: 6 bar. Working temperature range: 2 110. oiler inlet, RH side ode Voltage V ode 161010 612025 612026 612027 612028 3/4 17,2 11,9 16,5 30,0 1520 igital temperature controller complete with flow contact probes and outside probe. djustment range: 20. lectric supply: V - 50/60 Hz. Protection class: IP. 6120 Three-way motorized sector mixing valve, threaded connections. Max. working pressure: 6 bar. Working temperature range: 2 110. oiler inlet, LH side ode Voltage V ode 151 152 153 with 1 channel with 2 channels with 3 channels 612015 612016 612017 612018 3/4 17,2 11,9 16,5 30,0 1520 igital temperature controller for heating and cooling. omplete with flow probe, outside probe and relative humidity limit probe. lectric supply: V - 50/60 Hz. Power consumption: 5,5 V. Protection class: IP. 63 tech. broch. 01169 ctuator for mixing valves from 3/4 to. With auxiliary microswitch. lectric supply: V or 24 V - 50 Hz. Power consumption: 3 V. Microswitch contacts rating: 10 (2) - 250 V (ac). Protection class: IP 42. Operating time: 60 s. With adapter. ode 152021 1 channel ode 6302 6304 Voltage V 224 Motor torque (N m) 15 15 63 ctuator for mixing valves from 3/4 to 1 1/2. With auxiliary microswitch. lectric supply: V or 24 V - 50 Hz. Power consumption: 3 V. Microswitch contacts rating: 10 (2) - 250 V (ac). Protection class: IP 42. Operating time: 60 s. With adapter. 63 tech. broch. 01169 ctuator for mixing valves from 2 to 5. With auxiliary microswitch. lectric supply: V or 24 V - 50 Hz. Power consumption: 4,5 V. Microswitch contacts rating: 16 (4) - 250 V (ac). Protection class: IP 42. Operating time: 180 s. With adapter. oiler inlet, LH side ode Voltage V Motor torque (N m) ode Voltage V Motor torque (N m) 6301 6303 224 15 15 6312 6314 224 35 35

pplication diagrams Shut-off valve Pump Temperature probe Pressure gauge Thermometer

I 24V 50Hz I Titore 220-2 V 50 Hz Outside probe Shut-off valve Pump Temperature probe Pressure gauge Thermometer /I ST Summer/Winter Mode Selector Safety thermostat optional S/W /I

SPIITION SUMMRY Three-way butterfly mixing valve with manual control. Heavy series. Threaded 3/4 connections (3/4 2 1/2 ). langed N 50 (N 50 N 125) connections. oupling with counterflange N 1092-1. ast iron body and rotor. luminium cover. Lever in P6630. PM seals. Medium: water, glycol solutions. Maximum percentage of glycol 30%. Temperature range 2. Maximum working pressure 6 bar. an be motorized. our-way butterfly mixing valve with manual control. Heavy series. Threaded 3/4 connections (3/4 2 1/2 ). langed N 50 (N 50 N 125) connections. oupling with counterflange N 1092-1. ast iron body and rotor. luminium cover. Lever in P6630. PM seals. Medium: water, glycol solutions. Maximum percentage of glycol 30%. Temperature range 2. Maximum working pressure 6 bar. an be motorized. Three-way sector mixing valve with manual control. Heavy series. Threaded 3/4 connections (3/4 2 1/2 ). langed N 50 (N 50 N 125) connections. oupling with counterflange N 1092-1. ast iron body and rotor. luminium cover. Lever in P6630. PM seals. Medium: water, glycol solutions. Maximum percentage of glycol 30%. Temperature range 2. Maximum working pressure 6 bar. an be motorized. 63 series ctuator for 3/4 (3/4 5 ) mixing valves. Three point type regulation. lectric supply V (ac) or 24 V (ac). Power consumption 3 V (3/4 ), 4,5 V (2 5 ). ynamic torque 15 N m (3/4 ) 35 N m (2 5 ). Operating time 60 seconds (3/4 ) 180 s (2 5 ). Protection class IP 42. Maximum ambient temperature 55. quipped with auxiliary microswitch, contact rating 10 (2) - 250 V (ac) (3/4 ), 16 (4) - 250 V (ac) (2 5 ). ode 161010 igital regulator with functional synoptic for heating and cooling. lectric supply V - 50/60 Hz. Three-point type. Power consumption 3 V. djustment working temperature range 5 95. Protection class IP 20/N 60529. omplete with flow/return Pt 0 probes and contact probe holder. Probes flow/return working range -50 180. Two-wire cable with pocket connection 1/8 M connection, length 1,5 m. 1520 series OPTIMISR digital climate regulator. lectric supply V (ac), ±10%; 50/60 Hz. Power consumption 5,5 V. Output signals for 3 relay contacts for code 151, 6 relay contacts for code 152, 10 relay contacts for code 153. ontact rating 250 V (ac), 8 (2) (max 9 in total). Protection class II. Protection class IP. mbient temperature range 0. Storage temperature range -20. Maximum permissible humidity lass according to IN 0. Settable mixing valve rotation time from 10 to 0 s. ata storage with no power supply one year. RS 232 remote reading. lock operating life with no power supply 4 hours. Minimum SP function changeover time 10 min. Sizes: 180 x x 60 mm. ode 152021 OPTIMISR digital climate controller for heating and heating/cooling. lectric supply V (ac), ±10%; 50/60 Hz. Power consumption 5,5 V. Output signals: 3 heating relay contacts 6 heating/cooling relay contacts. ontact rating 50 V (ac), 8 (2) (max 9 in total). Protection class II. Protection class IP. mbient temperature range 0. Storage temperature range -20. Maximum permissible humidity class according to IN 0. Settable mixing valve rotation time from 10 to 0 s. ata storage with no power supply one year. Remote reading via minidin RS 232 connection. lock operating life with no power supply 4 hours. Minimum SP function changeover time 10 min. Sizes: 180 x x 60 mm. ode 162 Outside compensated temperature probe. ode 164 ew point detector. Working temperature range: 30 RH%. We reserve the right to make changes and improvements to the products and related data in this publication, at any time and without prior notice. aleffi S.p.. S.R. 229 no. 25 28010 ontaneto d gogna (NO) Italy Tel. +39 0322 8491 ax +39 0322 863723 info@caleffi.com www.caleffi.com opyright 2017 aleffi