TUNGUS. ANNEX А (obligatory) THE RESULTS OF TECHNICAL MAINTENANCE Table А.1 - Information about reloading, reexamination. Executive (company, name)

Similar documents
TUNGUS. POWDER FIRE-EXTINGUISHING MODULE MPP(N)-0.65-I-GE-U2 Passport and Manual instructions

TUNGUS. POWDER FIRE-EXTINGUISHING MODULE MPP(N)-5-I-GE-U2 Passport and Manual instructions

SAFETY FUSES PP57U SERIES Technical description and user manual

FUSES PN22 SERIES Technical description and user manual

AUTOMATIC STANDBY ACTIVATION. Operation Manual

GUBKIN E&TC (TS ) Specifications. Orenburg. The foreword

USER S MANUAL. TwinFresh R-50 SINGLE-ROOM REVERSIBLE VENTILATOR

Contents. Overview. Safety Instructions. Before Installation. Installation. Operation. Maintenance. Replacement Parts. System Specifications 8 01

UNIVERSAL SINGLE-PHASE INDUCTION ELECTRIC MOTOR PROTECTION UNIT WITH THE POSSIBILITY OF SOFT START

Ø Operating Voltage 3.8


Infiniti jx35. Nissan Pathfinder. Infiniti QX60 RUN. Ñåðòèôèêàò ñîîòâåòñòâèÿ ¹ ÒÑ RU C-RU.AE56.B Part number: 4381-Е.

Fuel level sensors Strela - Users manual. Fuel level sensors Strela. Users manual

Propane torch. Model Assembly And Operation Instructions

MATERIAL SAFETY DATA SHEET MSDS009. Ultralife Batteries, Inc Technology Parkway Newark, NY

FSG175 FENCE STAPLE GUN

315W CMH COMPLETE GROW LIGHT SYSTEM [ V] USER MANUAL

USER S MANUAL VENTS OV/ OVK/ OV1/ OV1 R/ OVK1/ VKF/ VKOM / OVP

MATERIAL SAFETY DATA SHEET

SPECIFICATIONS Horsepower: 1.5 HP Running Maximum PSI: 125 PSI Tank Capacity: 15 Gallons CFM: 6 40 PSI 5 90 PSI

HOYMILES MICRO-IVERTER MI-250

General Information. Note : The aftertreatment DOC is integrated into the inlet of the exhaust aftertreatment system. WARNING

ATM Lighting sp. z o.o

OPERATION AND MAINTENANCE

SMOKE EXTRACTION VENTILATION FOR PARKING PREMISES

Pump Manual. Model Numbers: SP240VDFS57LPM SP240VDFS80LPM. Product Names: Digital Refueling Station - 57 L/min Digital Refueling Station - 80 L/min

WALL VENTILATION GRILLES CBP

SINGLE-TURN AND MULTI-TURN ELECTRIC ACTUATORS

SERVO-OPERATED ROTOR TURNSTILE T3.РОН.XC

SPARK PLUG CLEANING KIT OPERATING MANUAL

Legat-65. Voltage Stabilizer Technical Certificate. NOVATEK-ELECTRO LTD Research-and-Manufacture Company

T1-Titanium Non-HVLP Spray Gun

EASY CHARGE Waterproof portable Battery Charger

Material Safety Data Sheet

Pocket Guide Li-Ion battery management

SAFETY DATA SHEET. The Safety Data Sheet is supplied as a service to you. For other related information, please visit:

DAKAR 2018 FUEL ORDER T3.2 / T3.0 and SxS (A.S.O. rules)

2015 Mustang Ecoboost Cold Air Intake

4. MARKING: Each cistern shall be provided with a label containing the following information or the information paper strip pasted to it.

Air-Operated Waste Oil Drainer

UNIVERSAL SINGLE PHASE INDUCTION ELECTRIC MOTOR PROTECTION UNIT

Operating Instructions. PowerMax. CORDLESS CAULKING GUN Modell: HPS-4C2-10.8V Li-Ion 380ml to 410ml (5:1)Coaxial Cartridges

37 LITRE MOBILE SANDBLASTING UNIT

HYDRODYNAMIC FUEL EMULSIFER TRGA-3G INSTALLATION, OPERATION, MAINTENANCE MANUAL

Hydraulic PTO Flow Device

Hot runner thermocouple Model TC46

Classification NEZ 4X4 CHAMPIONSHIP. Technical regulations for cars prepared for off-road (Group TR2) year

Bi-Directional Progressive Safety Gear

ULTRASONIC FLOW SENSOR QALCOSONIC FLOW 2

Hybrid & Electric Cars Guidance for organisers of Speed events

SPARKSCAN1 HIGH VOLTAGE CLAMP OPERATING MANUAL

SB20G. Large Pressurized Abrasive Blaster Assembly & Operating Instructions

CO 3-WAY PNEUMATIC VALVE INSTRUCTION MANUAL 2080

with Instruction Manual

Explanatory sheet about safety of product for transportation (Safety Data Sheet for transportation) 1. Basic item 2. Product information

E/ECE/324/Rev.2/Add.106/Rev.6/Amend.5 E/ECE/TRANS/505/Rev.2/Add.106/Rev.6/Amend.5

OWNER S MANUAL TOLL-FREE HELPLINE: (Monday - Friday / 8am - 4:30pm CST)

Engine, Generators Maintenance & Safety. UAE, Dubai, Cityseason Suites Hotel. Training Course : One Weeks Training Course In. As Under Details :

Auto-Reamer. 2100E2 Nozzle Cleaning Station. Operating Manual and Parts List. January 2018 v18.1

900 PEAK AMP PORTABLE JUMP STARTER

Operating Instructions

Technical Notice. Lithium Battery Information Sheet

10A / 15A / 20A Solar Charge Controller. PU1024 / PU1524 / PU2024 series INSTRUCTION MANUAL

Operating instructions Accu Jet

INSTALLATION and OPERATING INSTRUCTIONS

LITHIUM MANGANESE DIOXIDE

Breath Alcohol Tester

Users Manual Direct Drive Roof Fans

Bellows. GT Exhaust Accessories Installation and Operation Manual. Rev. B. (c) Copyright 2012, GT Exhaust, Inc. All Rights Reserved

2018 Mustang Ecoboost Cold Air Intake P/N: ( ) Application: 2018 Ford Mustang 2.3L Manual or Automatic Transmission

NOVATEK-ELECTRO LTD Research-and-Manufacture Company Voltage Stabilizer Legat-35

Power supply unit PS-303

Mustang V-6 Cold Air Intake P/N: ( A600) Application: Ford Mustang 3.7L Manual or Automatic Transmission

Operating instructions

ENGLISH: Original instructions INSTRUCTION MANUAL. Cordless Cleaner CL106FD. Read before use.

RULES FOR THE CONSTRUCTION AND CLASSIFICATION OF SHIPS IDENTIFIED BY THEIR MISSIONS CHAPTERS APPROACH

SAFETY AND OPERATING MANUAL. Lithium-Ion cordless hammer drill WX372 WX372.1 WX372.9

Water Broom. Instruction manual ESPAÑOL: PÁGINA 7 FRANÇAIS : PAGE 13 MODEL PCA270

Contrail Rockets 98mm Hybrid Rocket Motor Reload Instruction Manual

Open Frame Reciprocating Gas/Diesel Engine Driven Compressor. Installation Guide

ATM Lighting sp. z o.o

AUTOMATED SELECTION OF THE MATERIAL A FAN BLADE PS-90A

SINGLE-ROOM ENERGY RECOVERY VENTILATION UNIT

MASCARELLO CARROCERIAS E ÔNIBUS LTDA

Gavita HortiStar 1000 DE EU/US

OD 8382 OPTICAL DISSOLVED OXYGEN AUTOCLEAN

Classification Baltic Cup. Technical regulations for cars prepared for off-road (Group TR3) year

Dry installed pump type LANDY BTP.

Tension Meter. Edition FT 03.E. FT Series. Instruction Manual. Valid as of: Please keep the manual for future reference!

Orifice Flow Meters POP-S (E5720 rev /03/2013)

Check Valves DN PN 80, 100, 160

RECEIVER MOUNT KIT LP-8 Tailgate Spreaders

with Instruction Manual

Installation and operating instructions. Solar charge controller MPPT 10 A / 20 A Z Z

DIGI-CUT 40PFC MV. Part No. 9030H OPERATOR S MANUAL

WELDING INVERTER. PEGAS 160 E Smart PEGAS 200 E Smart OPERATING MANUAL. ALFA IN a.s. PEGAS E Smart Manual EN 04

User s Manual Roof Radial Fans

Modern Automotive Technology Chapter 5. The Auto Shop and Safety

Contrail Rockets 54mm Hybrid Rocket Motor Reload Instruction Manual

CAST RESIN TRANSFORMERS

Transcription:

ANNEX А (obligatory) THE RESULTS OF TECHNICAL MAINTENANCE Table А.1 - Information about reloading, reexamination TUNGUS Date Work to do Executive (company, name) Executive s signature and stamp Istochnik Plus, closed joint stock company 659322, 1, Socialisticheskaya St., Biysk, Altay region, Russia, Tel.: (3854) 30-19-32, 30-58-59 www.antifire.org antifire@inbox.ru POWDER FIRE-EXTINGUISHING MODULE MPP(N)-2.7-I-GE-U2 Passport and Manual instructions The alterations not given in the present passport and not affecting the principal technical characteristics, dimension and connecting sizes can be introduced into the module design.

2 11 1 PURPOSE 1.1 Powder fire-extinguishing module MPP(N)-2.7-I-GE-U2 made in two versions: ceiling-mounted (c) and wall-mounted (w) (hereinafter referred to as the MPP) is intended for automatic smothering fires class A (solids), B (liquids), C (gases) and E (electrical equipment under tension without taking into account the value of firefighting powder discharge voltage). The MPP models differ with bracket design intended to fasten the module to the bearing construction. MPP can be equipped with electronic activation device during the usage of which a module obtains a function of self-activation and can be used as an autonomous powder fire-extinguishing mean. 1.2 The MPP is not designed to extinguish the ignition of substances that can burn without air access. 1.3 The MPP is intended to extinguish both the local seats of fire and fires on square and in volume in the room. 1.4 The MPP can be performed in normal version with operating temperatures of minus 50 o С to plus 50 o С, in special version at operating temperatures of minus 60 o С to plus 90 o С, or in wide temperature operation range of minus 60 o С to plus 125 o С. MPP operation is allowed under relative humidity not more than 95% when temperature is 25 o С. 1.5 The fire extinguishing powder is ejected by the gas generated with a cold gas source CGS-3(М) SIAV 066614.025.000 TU. 1.6 The MPP is a reused-product. 1.7 Examples of the MPP marking (model) records when ordered: MPP(N)-2.7(c)-I-GE-U2 ТU 4854-020-54572789-10 (ceiling-mounted) in normal version at temperatures of minus 50 o С to plus 50 o С; MPP(N)-2.7(w)-I-GE-U2 ТU 4854-020-54572789-10 (wall-mounted) in normal version at temperatures of minus 50 o С to plus 50 o С; MPP(N-T)-2.7(c)-I-GE-U2 ТU 4854-020-54572789-10 (ceiling-mounted) in special version at temperatures of minus 60 o С to plus 90 o С; MPP(N-T)-2.7(w)-I-GE-U2 ТU 4854-020-54572789-10 (wall-mounted) in special version at temperatures of minus 60 o С to plus 90 o С; MPP(N-T1)-2.7(c)-I-GE-U2 ТU 4854-020-54572789-10 (ceilingmounted) in wide temperature operation range of minus 60 o С to plus 125 o С; MPP(N-T1)-2.7(w)-I-GE-U2 ТU 4854-020-54572789-10 (wall-mounted) in wide temperature operation range of minus 60 o С to plus 125 o С. 11 CERTIFICATE OF ACCEPTANCE AND SALE The fire extinguishing module МPP(N)-2.7(c)-I-GE-U2 МPP(N-Т)-2.7(c)-I-GE-U2 МPP(N-Т1)-2.7(c)-I-GE-U2 (tick off the necessary) MPP(N)-2.7(w)-I-GE-U2 MPP(N-T)-2.7(w)-I-GE-U2 MPP(N-T1)-2.7(w)-I-GE-U2 corresponds to the requirements of ТU 4854-007-54572789-03 and is considered to be fit for use. Batch No Manufacturing date (month, year) Inspector signature and stamp Sold (name of the Seller) Sale date Shop stamp

9.4 Firefighting powder utilization is made according to paragraph 5.7 requirements. 9.5 CGS utilization should be made according to the following instructions. 9.5.1 Actuate CGS in premises equipped with supply-and-exhaust ventilation. For this purpose CGS is placed in a clamp, connected to a direct current power source, which is correspondent to p. 12 or p. 13 of Table 1. The launch is made distantly without any people inside. 9.5.2 After launching make sure that the premises are ventilated till safe concentration or enter using isolating protective breath means, draw CGS from the clamp using thermo protective gloves, and then utilize according to the requirements of p. 5.8. 10 WARRANTY 10 10.1 The factory-manufacturer guarantees the correspondence of the MPP to the requirements of technical conditions if the Customer observes operation, transportation and storage conditions stated in the present Passport. 10.2 Service life is stated to be: - not more than 10 years for MPP(N)-2.7-I-GE-U2; - not more than 5 years for MPP(N-T)-2.7-I-GE-U2, MPP(N-T1)-2.7-I-GE-U2, and is estimated from the date of accepting the MPP by Quality Department of the factory-manufacturer. 10.3 The factory-manufacturer is not responsible for: - misoperation if the owner does not observe operation rules; - negligent storage and transportation of the MPP; - passport loss; - after performing certification, reloading the MPP under item 7.2 if they were not carried out at the factory-manufacturer; - expiration of the service life stated from the date of accepting the MPP by Quality Department of the factory-manufacturer. TECHNICAL CHARACTERISTICS 2.1 Technical characteristics of the MPP are given in Table 1. Table 1 Name Value 1 Case capacity, lit 2.7+0.2 2 Dimension, mm, not more than: - diameter 155 - height (with installation bracket) 215 3 Total weight of the MPP, kg, not more than 4.8 4 Fire extinguishing powder ISTO-1 weight, TU 2149-001-54572789-00, kg 2.6+0.2 5 MPP fast action (time from the moment of sending impulse to a triggering element of the MPP to the moment of ejecting extinguishing powder out of the module), sec. of 3 to 10 6 Operating time (time of ejecting extinguishing powder), sec., not more than not more than 1 7 Pressure of membrane rupture, MPa 2.5 2.7 8 Firefighting ability of ceiling-mounted MPP, nozzle-spay is set vertically downwards 8.1 Protected square (S, m 2 ) and volume (V, m 3 ) in the room for fires class A in case of fire-extinguishing from the height (Н, m) 8.2 Protected square (S, m 2 ) and volume (V, m 3 ) in the room for fires class B in case of fire-extinguishing from Н S V 2 32.5 65 2.6 25 65 4 25 65 Н S V 2 14 18 the height (Н, m) 4 14 18 9 Firefighting ability of wall-mounted MPP from the height of 1 to 4 m, nozzle-spay is set vertically downwards 9.1 Protected square (S, m 2 ) and volume (V, m 3 ) in the Cl. S V room for fires class A, B А 25 65 В 14 18 10 Fire extinguishing ability of MPP for fires, Class А, in the volume of the horizontal channel 1.2 m wide, 2.8 m height, 9 m length: 30.2 11 Maximum rank of the model fire site, Class B, when extinguishing at an open area from the 4 m height (Н) 3 89В *)

Table 1 to be continued 12 Circuit characteristics of electric triggering unit for MPP(N)-2.7, MPP(N-T)-2.7 modifications: - safe current of testing circuit, А, not more than - operating current, А, not less than: а) for MPP(N)-2.7 b) for MPP(N-T)-2.7 - electric resistance, Оhm 13 Circuit characteristics of electric triggering unit for MPP(N-T1)-2.7 modification: - safe current of testing circuit, А, not more than - operating current, А, not less than: 4 9 0.03 0.15 0.2 8 16 0.2 0.6 2 5 - electric resistance, Оhm 14 Irregularity coefficient of spraying powder К 1 (SP 5.13130.2009) 1.0 NOTE: *) Firefighting ability of ceiling-mounted MPP for fires class A when extinguishing from a height H is determined by the following formulae: - within a height range of 2 to 2.6 m: S=32.5-12.5 (H-2); **) - according to GOST R 53286-2009 model site, rank 89В, is the surface of burning petrol (benzine) as a circle 1.89 m in diameter having the surface area (S) 2.8 m 2. 7.1 Special technical maintenance is not required. Examine the integrity of the disk (membrane) closing the MPP nozzle-sprayer and the MPP grounding available once a quarter. If the disk (membrane) is not intact (damage, holes of puncture, cracks), replace the module. 7.2 Reloading after operating the MPP should be carried out by the MPP factory-manufacturer or MPP factory-manufacturer or in organizations having a license for this kind of activity. 7.3 The delivery set for MPP reloading: - CGS-3(М)-01 SIAV 066614.025.000 TU for MPP of normal version; CGS-3(М)-02 SIAV 066614.025.000 TU for MPP of special version, or CGS- 3(М)-06 SIAV 066614.025.000 TU for MPP of wide temperature operation range (see item 3 on Figure 1) 1 item; - rubber ring 020-026-36 GOST 9833-73 (see item 10 on Figure 1) 1 item; - fire-extinguishing powder ISTO-1 TU 2149-001-54572789-00 (see item 2 on Figure 1) 2.6 kg; - membrane of SIAV 634233.006.003 drawing (see item 6 on Figure 1) 1 item. 7.4 After MPP checking and reloading notes are made on MPP case (with a label or ticket fastening) and in MPP manual (See Annex А). 8 STORAGE AND TRANSPORTATION 3 COMPLETENESS OF SET 3.1 The MPP set to be supplied consists of: a) The module MPP TU 4854-020-54572789-10 1 item; b) Passport and Manual instructions - 1 copy; c) MPP package 1 item. 4 DESIGN AND OPERATION PRINCIPLE 4.1 The MPP design 4.1.1 The MPP (See Figure 1 and 2) consists of a case 1 where fire extinguishing powder (OP) 2 and cold gas source (CGS) 3 with electric triggering element 4 are placed. In the bottom of the case there is a nozzlesprayer 5, the output hole of it is closed by membrane 6. Module has a grounding clamp 7. In the upper part the MPP is fitted with bracket 8 to fasten to the ceiling (Figure 1) or bracket 9 to fasten to the wall (Figure 2). 8.1 The MPP transportation and storage conditions should meet the requirements of OG-4 GOST 15150-69. 8.2 The MPP transportation in the factory packing at temperatures of minus 50 o C to plus 50 o С is allowed by all kinds of transport according to the rules of transporting the goods by this kind of transport and taking into account transport conditions harsh environment (G), GOST 23170-78. 8.3 When stored and transported the MPP, conditions preventing them from mechanical damage, direct sunlight, rainfalls and aggressive media should be provided. 9 MPP UTILIZATION AFTER FIXED SERVICE LIFE EXPIRATION 9.1 Utilization works should be made by MPP factory-manufacturer or in organizations having a license for this kind of activity. 9.2 Disassemble MPP. 9.3 MPP frame utilization is made by means of taking to scrap metal.

8 Table 2 Ceiling-mounted MPP fire-extinguishing parameters in the room 5 Parameters Fires class А Fires class В Н, m 2.0 2.6 4 2.0; 4.0 2.0 4.0 S, m 2 32.5 25 25 14 - - V, m 3 65 65 65-18 18 а, m 5.7 5.0 5.0 3.74 3.0 2.12 b, m 5.7 5.0 5.0 3.74 3.0 2.12 һ, m 2.0 2.6 2.6-2.0 4.0 Table 3 Ceiling-mounted MPP fire-extinguishing parameters into the open area Parameters Fires class А Fires class В S, m 2 25 14 - - V, m 3 65-18 а, m 5.0 3.33 3.0 2.12 b, m 5.0 4.2 3.0 2.12 һ, m 2.6-2.0 4.0 MPP in case in horizontal position Figure 1 Figure 2 4.1.2 The MPP actuates by means of current impulse that can be generated by: - receiving/control, fire alarm, and safeguard devices; - manual start button; - self-contained signaling-and-triggering devices (for example, signaling-and-triggering self-contained automatic device for fire extinguishing setups USPAA-1 ТU 4371-032-00226827-99, signaling-and-triggering device USP-101 ТU 4371-004-21326303-96). 4.2 Operation 4.2.1 After sending electric pulse to the outputs of the electric triggering unit 4, the CGS 3 generates gas which makes OP 2 loose and creates pressure inside the MPP case to rupture membrane 6 and eject through nozzle-sprayer 5 the jet of OP into the zone of burning. 5 SAFETY MEASURES Figure 6 5.1 The staff who was allowed to operate the MPP should study this Passport and observe its requirements. 5.2 It is not allowed: - keeping and installing the MPP near heat sources; - effecting rainfalls, direct sunlight, aggressive media, and moisture on the MPP; - shocking the case and the CGS;

6 7 - dropping from the height more than 2 m; - dismantling the MPP, except for maintenance work according to Section 7 of the present Passport; - using the MPP with damaged case (dents, cracks, through holes); - performing of any fire tests without experimental works program concordance or in case of absence of company-manufacturer representative. 5.3 Before connecting the module to the mains, the output ends of the triggering unit should be closed by twisting not less than twice and sealed. Connect the MPP only after its grounding. Electric safety while assembling the MPP should be provided by meeting the requirements PUE, PTE, PTB and PZSE 5.4 Loading, reloading, certification and technical maintenance should be carried out in the rooms specially equipped and designed for it at the MPP factory-manufacturer or in organizations having a license for such kind of activity. 5.5 After detecting the module defects (dents, cracks, through holes) during the operation or after its service life, the module should be sent to the factory-manufacturer or utilized according to p. 9. 5.6 While operating the module is fire- and explosion-proof. 5.7 Fire extinguishing powder has no harmful effect on the body and clothes of people, does not cause damage to property and is easy-to-remove. After MPP actuation to remove the combustion products and fire extinguishing powder in the air it is necessary to use general ventilation. It is allowed to apply mobile ventilations sets for this purpose. The powder fell is removed by vacuum cleaner, dry rag followed by wet cleaning. Extinguishing powder waste utilization should be made according to the instruction: Utilization and Regeneration of Fire Extinguishing Powders, Мoscow: VNIIPO, 1988. 5.8 CGS utilization after actuation should be made by means of device taking to scrap metal. 5.9 The bearing construction, the MPP is fastened to, should sustain the impulse load from the module kickback at the moment of OP ejecting. 6 PREPARATION OF THE MPP TO OPERATION, LAYOUT AND MOUNTING 6.3 Connect the MPP with the bracket, fasten the connection with nuts. 6.4 The number of modules in the rooms protected should be defined in accordance with section 9 SP 5.13130.2009. 6.5 While protecting separate surface parts, i.e. at local protection in rooms or under shelter at the height of installation (Н) to 4 m, the local surface area (S) equals 2.8 m 2 and is a circle. 6.6 The configuration of powder spraying and the area image, where fire extinguishing is achieved, are given in Figure 5 and in Tables 2 for the ceilingmounted MPP; in Figure 4 and Table 3 for the wall-mounted MPP. 6.1 Unpack the MPP, and examine the integrity of case and membrane. 6.2 Fasten the bracket 8 (See Figure 1) on the ceiling or bracket 9 (See Figure 2) on the wall. Positions of holes in the bracket intended to fasten the MPP on the ceiling are given in Figure 3a, to fasten MPP on the wall in Figure 3b. Figure 4 Figure 5