1ZSE EN, REV. 7. Oil SF 6. bushings type GOEK Technical guide

Similar documents
1ZSC AAA EN, REV. 7. Transformer bushings type GSBK Technical guide

1ZSE en, Rev. 7. Transformer bushings, type GOB Technical guide

Resin Impregnated Paper Bushing, Oil to SF 6. , Type GSBK

Transformer bushings, type GOH. Technical guide

1ZSC AAA en, Rev. 6. Resin impregnated paper bushing, oil to SF 6., type GSBK Technical guide

1ZSE en, Rev. 9. Transformer bushings, type GOB Technical guide

1ZSE EN, REV. 4. Wall bushings type GSA-AA Technical guide

Resin Impregnated Paper Bushing, Oil to Air, Type GSB Technical guide

1ZSE en, Rev. 3. Wall bushings, type GSA-AA Technical guide

Transformer bushings, type GOA 250. Installation and maintenance guide

Micafil transformer oil-sf 6 bushings GARIP / RTKG kv. Power and productivity for a better world TM ABB

1ZSE en, Rev. 9. Transformer bushings, type GSA-OA Technical guide

Bushings for High Voltage AC Applications

Transformer bushings, type GSA-OA Technical guide

OIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) kV to 550kV up to 5000A IEC

Transformer High Current Bushings Type CFPT & CFCT 36kV up to 40kA IEC

Fuse-links type CEF-VT Rated voltages 3/7.2 kv - 10/24 kv Rated current 0.5 A 6.3 A

HVDC bushing without oil side porcelain Type GOF, for outdoor mounting. Installation and maintenance guide

1ZSC ABJ EN, REV. 1. Gas insulated wall bushings type GGFL Technical guide

EMPAC Metal enclosed capacitor bank for wind applications

OIP Transformer Outdoor Bushings Type COT(C) 125 COT (C) kV to 550kV up to 5000A IEC

Product Brochure. Generator Circuit-Breaker HVR-EBCB For hydro or pump storage power plant

ZX-Family Gas-insulated medium voltage switchgear

Surge arrester POLIM-H..SD

Fuse-links type CEF-S Rated voltages: 6/12 kv 30/40.5 kv Rated currents: 6.3 A 63 A

MEDIUM VOLTAGE PRODUCT. TJC 4 Indoor voltage transformers

MEDIUM VOLTAGE PRODUCT. KECA 250 B1 Current Sensor Instructions for installation, use and maintenance

MEDIUM VOLTAGE PRODUCT. KECA 80 C85 Current Sensor Instructions for installation, use and maintenance

Surge arrester POLIM-H.. ND

ZX2 Gas-insulated medium voltage switchgear

MEDIUM VOLTAGE PRODUCT. KECA 80 D85 Current Sensor Instructions for installation, use and maintenance

A of 3. Edition : Date : Page : Document No. Amendments :

Product presentation CPT tech Jason Evershed, ABB Transformer Components, May 21st New RIS transformer bushings The paper-free solution

Surge arrester POLIM-C.. HD

MICAFIL RIP Transformer Bushings AirRIP / RTKF kv

en, Rev. 7. Transformer bushings, type GOM Installation and maintenance guide

INSTRUCTION MANUAL CRS Combined insulation bushing

A of 14. Edition : Date : Page : Document No. Amendments :

dfdf 34.5 kv and 69 kv, Type O Plus C II Condenser Bushings Technical Guide

en, Rev. 10. Transformer bushings, type GOH Installation and maintenance guide

PNO Condenser Bushings from 52 kv to 420 kv Oil-to-air - Oil-Impregnated Paper

Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv

Product Information. Neutral Wall Bushing GOFL

Semi-pantograph disconnector type DSSP, up to 300 kv Maximum reliability and minimal maintenance

Voltage limiting device HVL

ACCESSORIES FOR LPOF, HPPT AND XLPE HIGH VOLTAGE CABLE SYSTEMS PRODUCT CATALOGUE

Current transformers. Outdoor operation SF 6 -gas insulated. JGF ( ) kv

Voltage limiting device HVL

Low voltage bushings for pad-mounted distribution transformers Technical information guide

Transformer Bushings Type COT COT kv to 245 kv up to 3150 A IEC 137

DM Condenser bushings, kV DURESCA

Contact us. Catalog Low voltage generators for diesel and gas engines Industrial Marine applications - series Standard series

Medium voltage products. KEVCD A combined current and voltage sensor Instructions for installation, use and maintenance

LV Capacitors QCap-L series Capacitors for power factor correction

Surge arrester POLIM-H..N

Mini contactors B6, BC6 with 3 pole

PABS. AIR-TO-SF 6 - Gas-insulated bushing IEC STANDARDS ANSI STANDARDS AN ALSTOM COMPANY

Electronic overload relays EF205 and EF370

Product brochure Generator circuit-breaker HVS-63S System type GCB with innovative built-in monitoring

Protection and Connection Motorized and automatic transfer switches IEC Technical guide

System pro M compact Supplementary protector S 200 PR for ring-tongue applications acc. to UL1077

INTRODUCTION. The plug-in connection on the cables and lightning arrestors, allows for easy installation and replacement.

High Voltage Surge Arresters Buyer s Guide Section PEXLIM R

NXPLUS C Single busbar. Maintenance-free for lifetime

Electronic overload relay EF65, EF96 and EF146

Overview Overvoltage protection

Thermal overload relay TF65 and TF96

Transformer Bushing Type EKTG

Bus bar Bushings up to 1.1kV and from 1.6kA to 4kA for Liquid Filled Transformers:

SACE Emax 2/ML Low-voltage air circuit breakers for naval applications

Low voltage capacitors CLMD Improving power factor and enhancing power quality of your network

IEC Separable Connectors 36 kv and 42 kv, 630A and 1250A Front T-Body / Coupling (Rear) T-Body Connector

Data Sheet DS/NGB-EN Rev. B. Multi barriers. Measurement made easy. Fieldbus barrier for PROFIBUS PA for FOUNDATION Fieldbus-H1

Contact us. ABB France Electrification Products Division Low Voltage Products and Systems 3, rue Jean Perrin F Chassieu cedex / France

Current accuracy class. Sensor principles

B kv Gas-insulated Substations

Motor-drive mechanism, type BUL. Technical guide

Inductive voltage transformers

Inductive voltage transformers

A manufacturer s view of bushing reliability, testing and analysis. Lars Jonsson Håkan Rudegard

Transformer Bushing Type EKTO

Combined instrument transformers

en, Transformer bushing, type GSA-OA Installation and maintenance guide...

ABB MEASUREMENT & ANALYTICS DATA SHEET. Series and Katharometer power supply units

SF 6 Gas Insulated Switchgear Type SDH714 for 72.5 to 145 kv

SR1 multipurpose enclosures Enclosures for automation and distribution applications

IEC Separable Connectors 17.5 kv/24 kv, 630A

SF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS)

Zinc Oxide Surge Arrester EXLIM R

AF / AF09Z pole Contactors AC / DC Operated - with Screw Terminals

AF / AF09Z pole Contactors AC / DC Operated - with Screw Terminals

3 TM Cold Applied Barrier Boot System

Thermal overload relay TF140DU and TF140DU-V1000

KECA 80 C85 Current Sensor Instructions for installation, use and maintenance

MEDIUM VOLTAGE PRODUCTS. Fault Current Limiters I S. -limiter and FC-Protector The worldʼs fastest switching devices

ABB PTTR SPAIN. Zaragoza. The product: Cast coil transformers

Field Experience & Reliability Tests for the New EasyDry Condenser Bushing LUKAS MUGGLI

Model WEP Electro-pneumatic positioner. WEP positioner A valve control without compromise

SF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv

Transcription:

1ZSE 2750-106 EN, REV. 7 Oil SF 6 bushings type GOEK Technical guide

Original instruction The information provided in this document is intended to be general and does not cover all possible applications. Any specific application not covered should be referred directly to ABB, or its authorized representative. We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB.

Table of contents Design 5 Testing 7 Test tap 7 Test tap adapter 7 Dimensions 8 Electrical data 9 Connection details 10 Draw rod system with standard bottom contacts 10 Tight bottom contact 10 SF 6 side terminal 10 Data for end-shields 11 Conductor loading 13 Short-time current 13 Overload capacity of bushings 13 Ordering particulars 14 Recommendations for positioning 15

OIL SF 6 BUSHINGS TYPE GOEK TECHNICAL GUIDE 5 Design 1. Top housing 2. Porcelain insulator 3. Valve for connection to pressure sensor 4. Mounting flange (Test tap on opposite side, see Fig. 02) 5. M12 for earthing device 6. Porcelain insulator 7. Bottom contact 8. SF6 side terminal 9. Flexible connection 10. Pre-stressed tubes 11. Expansion tank with rubber bellows 12. Extension for current transformers 13. Condenser core 14. Transformer oil 15. Bottom end nut Bushing type GOEK is intended for immersed oil-sf 6 service and can be mounted in any direction from vertical to horizontal. It can also be used for oil-oil applications. The bushing is built up around a centre tube on which the condenser core is wound. The condenser core is wound from full width insulating paper. The foils are located so that the best possible combination of external flashover withstand and internal puncture strength is achieved. The insulators and the mounting flange are held by the centre tube and sealing is accomplished by oil-resistant rubber gaskets in grooves. 1 2 3 8 9 10 11 A set of concentric tubes is prestressed and serves as a spring which holds the main bushing components together and provides adequate pressure on the gaskets at all expected temperatures, load conditions and mounting directions. The annular space formed between the tubes makes an efficient cooling duct for heat dissipation, thus improving the current-carrying capacity and thermal stability of the bushing. The bushing is equipped with an expansion tank in which a nitrogen-filled rubber bellows is mounted. This is an advantage since it permits mounting at any angle from vertical to horizontal, and also facilitates mounting on the transformer without further connection to separate expansion tanks. Variations in the length of the centre tube and the housing are compensated by a flexible connection inside the top housing. The mounting flange is an aluminium alloy casting, which is protected by a two-component primer and twocomponent grey-blue paint. The surface roughness of the gasket area is Ra 6.3 on the oil side and Ra 1.6 on the SF 6 side. On the mounting flange there is a test tap. This tap is automatically earthed by a protective cap when the tap is not connected to external test or measuring circuits. 4 5 6 12 13 14 To detect possible gas leakage, the bushing can be equipped with an oil pressure monitoring equipment. The connection of the bushing to the transformer can be made with the draw-rod or tight bottom contact. 7 15 01 Oil - SF 6 bushing type GOEK.

6 OIL SF 6 BUSHINGS TYPE GOEK TECHNICAL GUIDE The bushing tube between the SF 6 side and the transformer is sealed in two ways. One seal is made by the SF 6 terminal and the other by a plug in the centre tube or by a tight bottom contact. The mounting flange is equipped with an extension on the oil side to provide space for current transformers. Extension lengths 300 and 600 mm are available. GOEK 1675 can also be supplied without flange extension. The bushing requires a shield at the oil side. The purpose of this shield is to avoid excess voltages in the oil at the bottom end nut and at the connection between the insulated lead from the transformer winding and the bottom contact in the bushing. The maximum voltage in the oil at the surface of the shield insulation must be limited to values that are normal for insulated conductors and similar components in the same transformer. ABB manufactures shields of this type - these are quoted for and supplied separately. The shields are made of aluminium and are insulated with epoxy or pressboard. The shield may be mounted on the bottom end nut of the bushing, or on the bottom contact of the draw rod. Table 1. General specifications Application: Classification: Transformers Oil impregnated paper, capacitance graded, completely immersed bushing Ambient temperature: +40 to -40 C, minimum value as per temperature class 2 of IEC 60137. Immersion medium on switchgear side: SF 6 gas. Max daily mean temperature +75 C Max pressure of medium on switchgear side: Altitude of site: Immersion medium on transformer side: Oil level below bushing flange: Markings: 750 kpa overpressure < 1 000 m Transformer oil. Maximum daily mean oil temperature 90 C. Maximum temporary oil temperature 115 C Maximum 30 mm Conforming to IEC/ IEEE

OIL SF 6 BUSHINGS TYPE GOEK TECHNICAL GUIDE 7 Testing A tightness test is carried out on the assembled bushing after the final drying and impregnation. The test is carried out according to IEC 60137. Each bushing is subjected to a final electrical routine test. The test is made at room temperature with the bushing submerged in transformer oil (valid for GOEK 1050 and GOEK 1425). Capacitance and tan d are measured in steps up to the power frequency withstand voltage, which is held for one minute. Capacitance and tan d are also measured with decreasing voltage at the same voltage levels as before the one minute test. Measurements for detection of internal partial discharge (PDmeasurements) are also made. These measurements are carried out at the same time, and at the same levels, as the tan d test. It is always demonstrated that the PD-value is maximum 5 pc at a test voltage level equal to the rated system voltage. During testing of the transformer, a bushing type GOEK 1050 can be replaced by a bushing type GOE 900-650; a bushing type GOEK 1425 can be replaced by a bushing type GOE 1300-1150; and a bushing type GOEK 1675 can be replaced by a bushing type GOE 1675-1175. Test tap The GOEK bushings are equipped with a test tap connected to the outer layer of the condenser core. The test voltage of the tap is 20 kv, 50 Hz for one minute. Maximum service voltage is 6 kv. In connection with an external capacitance, the test tap can be used as a voltage tap. The test tap has dimensions according to IEEE, Potential tap type A. Test tap adapter For permanent connection of the test tap to measuring circuits, a test tap adapter is required. Catalog number 2769 522-C. Electrical type testing is carried out according to IEC 60137 and IEC 62271-211, i.e. the gas side is placed in a metal cylinder filled with insulating gas at the pressure of 0.35 MPa (absolute) and with the diameter 450/540/650 for GOEK 1050/1425/1675 respectively. Note: Dimensions of the bushings do not meet requirements shown in IEC 61639, Table 3. Pr 22.5 (Pg 16 acc. to DIN 40430) Turnable in optional direction 02 Test tap. 03 Test tap adapter.

8 OIL SF 6 BUSHINGS TYPE GOEK TECHNICAL GUIDE Dimensions Flange SF 6 side L2 Position of test tap Ra 1.6 D1 L1 L7 Position of pressure sensor D2 D3 L6 D5 L8 L5 1) L4 L3 Earthed layer Ra 6.3 D1 Flange oil side 1) For bushings with tight bottom contact, see Fig. 06 for definition of L5. M12 For earthing device D2 D3 04 Dimensions. Table 1. Dimensions. Type GOEK 1050 1425 1675 Extension for current transformers mm Type bottom contact Dimensions Catalog number L1 L2 L3 L4 L5 L6 L7 L8 300 Standard LF 124 001-B 450 885 305 325 835 230 395 740 300 Tight LF 124 011-B 305 325 905 600 Standard LF 124 001-C 605 625 1135 600 Tight LF 124 011-C 605 625 1205 300 Standard LF 124 002-B 650 1090 305 315 1035 350 545 520 300 Tight LF 124 012-B 305 315 1105 600 Standard LF 124 002-C 605 615 1335 600 Tight LF 124 012-C 605 615 1405 0 Standard LF 124 003-A 880 1395 5 150 985 350 695 915 0 Tight LF 124 013-A 5 150 1055 300 Standard LF 124 003-B 305 360 1285 300 Tight LF 124 013-B 305 360 1355 600 Standard LF 124 003-C 605 640 1585 600 Tight LF 124 013-C 605 640 1655

OIL SF 6 BUSHINGS TYPE GOEK TECHNICAL GUIDE 9 Electrical data Table 2. Electrical data. The electrical data are valid in accordance with criteria in IEC 61639. 1) 5000 A available on request. Type GOEK Rated voltage U m kv, RMS Rated phase-toearth voltage U Y kv, RMS Dry lightning impulse LI kv, peak Dry switching impulse SI kv, peak Routine test 1 min dry 50 Hz kv, RMS Rated current 1) at mounting angle 0-75 Ir A Reduced current for horizontal mounting and up to 15 from horizontal A Nominal capacitances between conductor and test tap C 1 ±10 % pf Flange extension, mm 0 300 600 1050 245 170 1050 850 460 2500 1600-274 364 1425 420 245 1425 1175 630 2500 1600-263 335 1675 550 318 1675 1300 750 2500 1600 231 253 308 05 Nameplate with marking example. ABB GOEK 1050 Ludvika, Sweden 2011 LF 124 001-C No. 888999 Um/Uy 245/170 kv Ir (vert./horiz.) 2500/1600 A 50/60 Hz LI 1050 kv SI 850 kv AC 460 kv M 200 kg L 1135 mm 0-90 C1 350 pf Tan δ 0.39 % C2 900 pf Tan δ 0.17 % D1 D2 D3 D4 D5 t Mass kg Cantilever load, N In operation, at mounting angle 0-30 >30 20 (8x) 350 400 244 264 23 180 2500 1500 5000 180 200 2500 1500 5000 20(8x) 430 480 244 330 23 285 2500 1500 5000 200 285 320 2500 1500 5000 24 (12x) 660 720 344 428 30 495 2500 1500 5000 320 495 540 2500 1500 5000 540 575 2500 1500 5000 575 Test for 60 s

10 OIL SF 6 BUSHINGS TYPE GOEK TECHNICAL GUIDE Connection details Draw rod system with standard bottom contacts The centre tube of the bushing is used as current conductor. The transformer leads are fitted with cable lugs, which are bolted to a bottom contact. This contact is drawn against the bottom end nut by a steel draw rod. See Fig. 5. SF 6 side terminal Ø 150 At the level of the flange the draw rod is split into two parts. If required to meet the transport conditions, we can position a joint at any desired level below the flange. This must be stated in the order. The lower part with contact and shield can then be secured to the cover during transport and storage of the transformer. This system has the following additional advantages compared to other methods used for high currents: No hand holes required in the transformer tank. The centre tube is used as conductor. No special supports required in the transformer as the case with plug contacts. Perfect guiding of the bushing into the transformer. The end shield may be fixed to the bottom contact and will thus be correctly positioned with respect to the bottom end nut (for contact with N1=6). No mechanical forces exerted on the leads from the transformer winding at any time. Tight bottom contact A system with tight bottom contact is also available. This system consists of a bottom contact with 4 threaded holes. The bottom contact is soldered together with the bottom end nut. See Fig. 6. L5 58 39 M 16 Threaded hole M8 for pulling wire M12 Flange oil side 25 Additional joint 65 51 N1=4 N1=6 05 Draw rod system with standard bottom contacts. 60 H1 L5 M12 SF 6 side terminal The terminal stud assembly consists of a stud, a tightening ring, a gasket, bolts and washers. The electrical contact function and the sealing function are completely separated. The stud is first fastened to the bushing top with M10 bolts, which provide proper electrical contact. The contact surface is located inside the gasket and is thereby well protected from corrosion. Finally the tightening ring with the gasket is pressed against the stud by means of M8 bolts.

OIL SF 6 BUSHINGS TYPE GOEK TECHNICAL GUIDE 11 19 L5 M12 06 Tight bottom contact. Ø 150 Ø 60 Ø 150 125 170 20 Ø 96 78 45 LF 170 050-AA (Aluminium) or LF 170 050-AL (Copper, silver-plated) M12 (x4) Ø 50 LF 170 050-AH (Copper, silver-plated) 07 Terminal stud, SF 6 side.

12 OIL SF 6 BUSHINGS TYPE GOEK TECHNICAL GUIDE Data for end-shields The maximum voltages in the oil at the surface of the shield insulation and the parts surrounding the bushing must be limited to those values normal for insulated conductors and other similar components in the same transformer. The withstand voltages in a specific case depend upon many factors beyond the control of the bushing manufacturer. Therefore the configurations and distances given below are only intended as guide lines. R min 5 Edges within this area should be rounded to R min = 5 mm 45 60 Earthed layer H6 A R1 A = Distance to flat surface, e.g. tank or core clamp. D4 H5 R3 D5 D4 R2 Ø125 Ø102 20 60 60 18 13 08 Shield, oil side. Table 3. Insulated shield, oil side. All dimensions refer to the epoxy insulated shield, which is used as a base. The thickness of the pressboard is 3 mm for -UP and -VP. Shield To be used with GOEK Dimensions according to Fig. 8 (mm) D4 D5 H4 H5 H5 (tight bottom contact) H6 R1 R2 R3 Mass kg Cat. No. Epoxy insulated U 1050-1425 262 174 265 170 100 90 492 30 8 2.1 LF 170 046 -U -UP V 1675 352 200 365 240 170 120 351 24 14 2.5 LF 170 046 -V -VP Pressboard insulated 1)

OIL SF 6 BUSHINGS TYPE GOEK TECHNICAL GUIDE 13 A (mm) 1000 500 Shield-V Shield-U 0 0 0 500 1000 (kv) U 500 1000 1500 2000 2500 (kv) Li 09 Recommended minimum distance A for different shields and test voltages. (U = Power frequency, LI = Lightning impulse) Ø172 Shield mounted on the bushing 102 Bottom contact N1=6 Shield mounted on the draw rod bottom contact. (Not possible for draw rod bottom contact with N1=4.) 10 Mounting alternatives, oil side. LF 170 046-F 11 Shield, SF 6 side.

14 OIL SF 6 BUSHINGS TYPE GOEK TECHNICAL GUIDE Conductor loading The rated currents specified in this catalog are based on thermal tests and are in accordance with IEC 60137 and apply to the built-in conductors of the bushings. The GOEK bushings conform to the requirements of IEC 60137 and IEEE for currents given in Table 4. Short-time current The rated thermal short-time current (I th ), as defined in IEC 60137 clause 2, is listed in Table 4 for draw rod system and for tight bottom contact. Overload capacity of bushings If the conductor for the bushing is selected with 120 % of the rated current of the transformer, the bushing is considered to be able to withstand overload conditions according to IEC 60354 without further clarification or tests. This recommendation complies with IEC 60137. Table 4. Rated current, short-time current and dynamic current as defined in IEC 60137. Rated current IEC A Current IEEE A Short-time current I th 1 s ka I th 2 s ka Dynamic current I d peak ka 2500 2100 100 100 250

OIL SF 6 BUSHINGS TYPE GOEK TECHNICAL GUIDE 15 Ordering particulars When ordering, please state: Type and catalog number for bushing. Catalog number for draw rod, if standard bottom contact is chosen. Catalog number for SF 6 side terminal. Catalog number for shield on oil side. Shield on SF 6 side must also be specified. Catalog number for pressure monitoring equipment. Additional accessories or modifications. Test required in addition to the normal routine tests. Table 6. Pressure monitoring equipment. (For details, see product information 5693 827-6.) Supply voltage Catalog number 230 V AC LF 410 024-K 115 V AC LF 410 024-L Table 5. Catalog numbers. Type GOEK 1050 1425 1675 Extension for current transf. mm Type bottom contact Catalog number for bushing LF 124... Catalog number for draw rod LF 124... Catalog number for SF 6 side terminal LF 170... Number of threaded holes in the bottom contact Material Oil side 4 6 Aluminium Copper, silver plated Catalog number for shields LF 170... Epoxy insulated Pressboard insulated 300 Standard 001-B 101-B 101-E 050-AA 050-AL or -AH 046-U 046-UP 046-F 300 Tight 011-B - - 600 Standard 001-C 101-C 101-F 600 Tight 011-C - - 300 Standard 002-B 102-B 102-E 050-AA 050-AL or -AH 046-U 046-UP 046-F 300 Tight 012-B - - 600 Standard 002-C 102-C 102-F 600 Tight 012-C - - 0 Standard 003-A 103-A 103-D 050-AA 050-AL or -AH 046-V 046-VP 046-F 0 Tight 013-A - - 300 Standard 003-B 103-B 103-E 300 Tight 013-B - - 600 Standard 003-C 103-C 103-F 600 Tight 013-C - - SF 6 side

16 OIL SF 6 BUSHINGS TYPE GOEK TECHNICAL GUIDE Recommendations for positioning The expansion tank must be in its uppermost position. See Fig. 12. For further information see Testing (for SF 6 side spacing) and Data for end-shields (for oil side spacing). 90 12 Recommendations for positioning.

ABB AB, Components SE-771 80 Ludvika Sweden E-mail: sales@se.abb.com www.abb.com/transformercomponents Copyright 2019 ABB. All rights reserved. Specifications subject to change without notice. 1ZSE 2750-106 en, Rev. 7, 2019-02-15