SPECIFICATION FOR THREE-PHASE PAD MOUNT TRANSFORMERS. D. Dead Front, loop feed design shall be employed.

Similar documents
CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

SECTION PADMOUNT TRANSFORMER - OIL FILLED

MATERIAL STANDARD ELECTRIC OPERATIONS ORGANIZATION. ****Supercedes BECo Standard E and ComElectric Spec ****

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-115

MATERIAL SPECIFICATION ELECTRIC OPERATIONS ORGANIZATION. M3902 ****Supercedes BECo Standard E and ComElectric Spec ****

C. System Design and Performance Requirements

1500 kva Pad Mount Transformer GRDY/14400V Primary - 208Y/120 Wye Secondary - Oil Cooled

SPECIFICATION FOR THREE PHASE PAD-MOUNT DISTRIBUTION TRANSFORMERS

DISTRIBUTION TRANSFORMERS SPECIFICATION #

Distribution Transformers

35-kV Safefront SuperWell Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current Limiting Fuses

GENERAL INFORMATION POLE MOUNT TRANSFORMER SINGLE PHASE PAD MOUNT TRANSFORMER SINGLE PHASE POLE MOUNT TRANSFORMER THREE PHASE 17

SERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES

Distribution Transformers

TECHNICAL SPECIFICATIONS OIL FILLED PADMOUNTED THREE PHASE WYE-WYE TRANSFORMERS

15-kV Wall-Mount Switchgear Three-Phase Indoor/Outdoor 600 Amp S&C Mini-Rupter Switch

Specification Pad-Mounted Capacitor Bank with Dual Fusing Integral Load-Interrupter on Line-Side Fuse Mountings

35-kV Safefront 200 Amp SuperWell Primary Metering Station Pad-Mounted Outdoor

56-SDMS-07 REV. 01 SPECIFICATIONS FOR

Underground Distribution Switchgear

15-kV Safefront 200 Amp Primary Capacitor Station Pad-Mounted Outdoor

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Technical Specification for Pole Mounted Capacitor Rack

Solid Dielectric Load Break Switch SPECIFICATION. 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER

INSTRUCTION MANUAL #103

35-kV Safefront 200 Amp SuperWell Primary Capacitor Station Pad-Mounted Outdoor

Underground Distribution Switchgear

500 kva Pad Mount Transformer V Delta Primary - 208Y/120 Secondary - NEMA 4X - Oil Cooled

100 / 110 DRYWELL FUSE SPECIFICATION

Single-Phase Step Voltage Regulator

SECTION 27 - PAD-MOUNTED TRANSFORMERS TABLE OF CONTENTS

Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break

35-kV Safefront Mini-Switch Source Isolated Pad-Mounted Switchgear 50 Amp (Max) Clip-Mounted Current-Limiting Fuses

FIXED POWER FACTOR CORRECTION EQUIPMENT 5KV CLASS MEDIUM VOLTAGE SECTION Z

Drive Duty Transformer Specification Virginia Transformer Corp. Power Up! Selecting the Right Transformer

Technical Specification For Outdoor Substation Harmonic Filter Banks

Single Phase Padmounted Transformers kva

Figure 1. Single-phase pad-mounted voltage regulator. STANDARD FEATURES

15-kV Live Terminal 600 Amp Group Operated Pad-Mounted Metal-Enclosed Outdoor Switchgear 140 Amp (Max) Clip Mount Current-Limiting Fuses

15-kV Safefront 200 Amp Source Isolated Cable Switching Station Pad-Mounted Non-Fusible

1TSF /CD Attachment B. City and County of San Francisco Office of Contract Administration

SECTION PANELBOARDS

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008

Power IT Liquid Filled Single Phase Padmounted Transformers kva

Fixed, Medium-Voltage, Pad-Mounted, Three-Phase Power Capacitor Bank Guide Form Specification

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

DISTRIBUTION TRANSFORMERS Single-Phase Pad-Mounted

25 kv Apparatus Bushings

NEW Solutions for Underground System Growth

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

SUBSTATION TYPE TRANSFORMER - MINERAL OIL FILLED THREE PHASE OISC 65 C RISE 60 HERTZ

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

A. Submit manufacturer's literature and technical data before starting work.

Automatic, Medium-Voltage, Pad-Mounted, Three-Phase Power Capacitor Bank Guide Form Specification

Effective March 2015 Supersedes S August 2012

35-kV Safefront 200 Amp Primary Metering Station Pad-Mounted Outdoor

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

35-kV 200-kV BIL Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

15-kV Safefront Mini-Switch Source Isolated Pad-Mounted Switchgear 140 Amp (Max) Clip-Mounted Current-Limiting Fuses

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS

SERIES G100 / G110 SPECIFICATION 15KV & 25KV SUBMERSIBLE & VAULT MOUNTED SF 6 -INSULATED VACUUM LOAD INTERRUPTING SWITCHES

1500 kva Padmount Transformer delta Primary Voltage 208Y/120 Secondary Voltage

Issued Revised Approved Reviewed October 31, 1984 October 22, 2002 J. Ross J. Fuller

35-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

"#$%&'(%)*#$ Installation, Operation, and Maintenance of Three-Phase Padmounted Distribution Transformers 45 kva through 10,000 kva

Outdoor Power Transmission & Distribution

Underground Distribution Switchgear

Padmount. Small Power Transformers 2500 kva Through 20,000 kva 5 kv Through 46 kv Primary Voltage 120V Through 25 kv Secondary Voltage

34-SDMS-01 SPECIFICATIONS FOR

15 kv and 25 kv Thru-Bushings

35-kV Thru-Bushings F Series (bolt-in) for Air-Insulated to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

CITY OF MARYVILLE ELECRIC DEPARTMENT Maryville, Tennessee SPECIFICATIONS FOR 15KV POWER CIRCUIT BREAKERS. September 2018

www. ElectricalPartManuals. com Substation Transformers Primary or Secondary Open

25-kV Apparatus Bushings A Series (clamp-in) for Elbow to Air-Insulated Service 200 Amp and 600 Amp

www. ElectricalPartManuals. com Westinghouse PLAZAPADTM Tamper-Resistant Transformers For Underground Power Distribution 750 Thru 2500 Kva

STANDARD SPECIFICATION FOR PAD-MOUNTED CAPACITOR BANKS FOR 15kV or 25kV APPLICATIONS

Single-phase pad-mounted step voltage regulator

Product Specifications for Phase Over Phase GOABS(r)

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

C1000 Series Automatic Cap Bank

Three-Phase Pole Mounted Recloser

Single-Phase, Liquid-Filled, Compartmental-Type, Pad-Mounted Transformers Class 7230

City of Ottawa Street Lighting. HID Shoebox Style Luminaire

PAD-MOUNTED SWITCHGEAR INSPECTION & MAINTENANCE RECOMMENDATIONS TYPE PSI/II. 15kV 25kV. Qualified Persons

15-kV Safefront 600 Amp Primary Transformer Station Pad-Mounted Outdoor

AMENDMENT ELECTRIC SERVICE MANUAL 2014

15-kV Live Terminal Primary Metering Station Pad-Mounted Outdoor

Installation, Operation, and Maintenance of Single-Phase Pad-Mounted Compartmental-Type Distribution Transformers

S&C Manual PME Pad-Mounted Gear

Northeastern Rural Electric Membership Corporation Schedule DG-2 Columbia City, Indiana Page 1 of 5

Product Specifications for Aluminum Vertical Break Switches

10 Commercial, Industrial, Agricultural Services

34-SDMS-02 SPECIFICATIONS FOR

www. ElectricalPartManuals. com WeSTinghouse Secondary Unit Substation Transformers (Power Centers) Descriptive Bulletin Page 1

STANDARD SPECIFICATION FOR TYPE PLD LIVE-FRONT/DEAD-FRONT PAD-MOUNTED SWITCHGEAR 15kV 25kV A. General

Transcription:

City of Cartersville Electric System P.O. Box 1390 320 S. Erwin St. Cartersville, GA 30120 770-387-5631 March 2006 SPECIFICATION FOR THREE-PHASE PAD MOUNT TRANSFORMERS This specification provides standardization of physical and electrical requirements for three-phase, self-cooled, oil-immersed, pad-mounted transformers designed for underground distribution systems. The word utility describes the buyer which is the City of Cartersville Electric System; the word vendor describes the seller, vendor, supplier, or manufacturer. I. General Information A. Provisions and terminology of current revisions of ANSI Standards C57.12.00, 12.10, 12.20, 12.22, 12.25, 12.26, 12.28, 12.70, 12.80, 12.90, latest revisions apply. B. Winding temperature rise above ambient shall not exceed 65 C at rated capacity. Hot spot rise shall be limited to 80 C. Excessive tank heating due to imbalanced loading or loss of a primary phase shall not occur. C. A five-legged core shall be provided. D. Dead Front, loop feed design shall be employed. II. Construction Features A. The pad-mounted, compartmental-type transformers shall consist of the transformer tank with high-voltage and low-voltage cable terminating compartment. The transformer tank and compartment shall be assembled as an integral unit for mounting on a pad. B. Transformer tank shall be sealed-tank construction with either a welded main cover or a bolted main cover and capable of withstanding a pressure of 7 psig without permanent distortion. If a welded main cover is used, a bolted temper-resistant hand-hole shall be provided. C. There shall be no exposed screws, bolts, or other fastening devices which are externally removable. There shall be no openings through which foreign objects such as sticks, rods, or wires might contact energized parts. The construction shall limit the entry of water (other than flood water) into the compartment so as not to impair the operation of the unit. Transformer shall meet tamper resistance requirements set forth in ANSI C57.12.28. D. Full-height, air-filled incoming and outgoing terminal compartments with hinged doors shall be located side-by-side separated by a steel barrier, with the incoming compartment on the left. The high-voltage (incoming) compartment will be accessible only after the door to the low-voltage (outgoing) compartment has been opened. To facilitate making connections and permit cable pulling, the doors and compartment hood shall be removable. Removable door sill on compartments shall be provided to permit rolling or skidding of unit into place over conduit studs or cable. E. Both compartment doors must be capable of being secured with a single padlock having a 1/2 diameter shackle and a recessed, captive pentahead bolt. The compartments will have 1

hinged doors equipped for latching in the open position. The high-voltage compartment door will have a pentahead bolt fastening device which is accessible only through the low-voltage compartment. F. The hinge assemblies shall be made of corrosions-resistant material. Stainless-steel hinge pins of 3/8 minimum diameter will be provided. G. All exterior nuts and bolts shall be stainless steel or chemically treated to prevent corrosion. H. Lifting provisions in accordance with ANSI Standards shall be provided; jacking and rolling provisions shall be provided. I. The nameplate is to be located in the low-voltage portion of the compartment. Information on the instruction nameplate shall comply with ANSI Standard C57.12.07 and shall include the kva rating, high voltage, low voltage, weight, manufacture date, serial number, impedance, type oil utilized, and state non-pcb. J. Provisions for tank grounding shall be supplied in both the high-voltage and low-voltage compartments. These provisions shall consist of: 1. 500kVA and below: 1/2-13 UNC tapped hole 7/16 deep 2. 750kVA and above: (2) 1/2-13 UNC tapped holes 1/2 deep K. The following accessories are to be provided on all units: 1. One-inch filling provision 2. One-inch drain valve with sampler 3. Liquid level indication 4. Pressure relief device 5. Grounding lugs L. Transformers shall be painted inside and outside; color shall be Munsell 7GY, Outdoor Green. Paint shall be of such quality as to resist rust, fading, etc., for a minimum 15-year (exposed to elements) period and comply with ANSI C57.12.28. M. NEMA Standard 260, Figure 2 safety labels shall be provided inside the compartment. No labels shall be placed on the exterior surface of transformer (utility will provide exterior safety label). III. Electrical Requirements A. Transformers shall be provided for wye-wye connection to 60 hertz alternating current for the following voltages as specified in the order: High Voltages Low Voltages 12,470 GRDY/7200 208 GRDY/120 12,470 GRDY/7200 480 GRDY/277 B. High voltage insulation level shall be 15kV class, 95kV BIL. Low voltage insulation level shall be 1.2kV class, 30kV BIL. Should future requirements specify a high voltage in excess of 15,000 GRDY, insulation class shall be 18kV, 125 BIL. Higher secondary voltages shall be provided with an insulation level based on latest standards for the required voltage. Dual voltage transformers shall meet insulation level requirements for the higher voltage. 2

C. Taps are not required unless specified for units under 500 kva rating. For 500 kva transformers and larger, provide two 2 1/2% taps above and two 2 1/2% taps below rated primary voltage. The tap changer handle shall be located in the primary compartment. D. Allowable percent impedance for transformers under 750 kva rating shall be within the range of 1.2% to 5.7%. For transformers 750 kva rating and larger, percent impedance shall be within the range of 1.5% to 5.75%. IV. Bushings and Terminals A. Electrical characteristics of transformer bushings and terminals shall be as listed below: Basic Impulse 60 Cycle Insulation Insulation Level Dry One-Minute Class (kv) Dry Withstand (kv) Withstand (kv) 1.2 30 10 15.0 95 35 18.0 125 40 B. Bushings and terminals shall be located on the tank wall that is common to the high-voltage and low-voltage compartments. The location and sequence shall be as shown in Figure 1. C. Unless otherwise specified, the incoming high-voltage section shall be equipped with six (6) 200-ampere bushing wells in accordance with ANSI Standard C119.2. Six (6) screw-out loadbreak inserts shall be provided. Inserts shall be designed to mate with RTE SBT IV, G.E. Sure-Make, or equivalent elbows. Bushings shall be located as shown in Figure 1. A minimum of five accessory brackets (parking stands) shall be provided at the same height and in the same plane as the high-voltage bushings. D. Low-voltage line and neutral bushings shall be externally clamped with spades. Low-voltage line and neutral terminals shall be arranged for vertical take-off and mounted in a staggered configuration on the tank wall. Minimum horizontal and vertical spacing between terminals shall be as shown in Figure 1. Terminals shall be one piece NEMA standard tinned terminal spades. Terminals used on 112 ½ kva rated units and larger shall be braced from above. A minimum of six inches (6 ) shall be maintained between the tank wall and the center of hole nearest the tank on the spade. (NOTE: CHANGE FROM 6 TO ADEQUATE SPACING) Minimum Qty. of kva Rating Holes for Spades Under 112 ½ 8 112 ½ and larger 12 E. The low-voltage neutral bushing shall be an insulated bushing with high-voltage and lowvoltage neutrals tied together internally by a removable link and brought out through the lowvoltage X0H0 bushing with a removable external ground connection. The ground strap shall be adequate to carry the fault current based on the rating of the transformer. F. Terminal designations shall be as defined by ANSI Standard C57.12.70, Terminal Markings for Electrical Apparatus, with each terminal clearly marked with oil resistant yellow paint. The identification of terminal connections shall be shown on the instruction nameplate. G. The angular displacement between the high-voltage and low-voltage terminal shall be zero degrees. H. All terminals shall have adequate and safe clearance from compartment doors when closed. 3

V. Fusing. A. Transformers rated 1500 kva and below shall be equipped with fuse holders for three bay-onet type (RTE, G.E., Kerney DEWL ) oil-immersed expulsion fuses accessible through the primary compartment. The fuses shall be removable using a hot-stick for external replacement of fuse cartridges. Fuse holders shall be located in the upper portion of the compartment, above the loadbreak bushings. A drip shield shall be provided to keep oil from dripping onto the bushings. B. Three bay-o-net type fuses shall be provided according to the following table. kva rating Fuse Size/Type Preference 45 5A DEWL Kearney 124080-5 or equivalent 75 5A DEWL Kearney 124080-5 or equivalent 112½ 8A DEWL Kearney 124080-8 or equivalent 150 12A DEWL Kearney 124080-12 or equivalent 225 15A DEWL Kearney 124080-15 or equivalent 300 25A DEWL Kearney 124080-25 or equivalent 500 30A DEWL Kearney 124080-30 or equivalent 750 35A DEWL Kearney 124080-35 or equivalent 1000 50A RTE Cooper 4000358C12 or equivalent 1500 65A RTE Cooper 4000358C14 or equivalent 2000 N/A N/A 2500 N/A N/A C. Internal current limiting fuses ( CLF ) shall not be provided unless specified in the order. In those cases where they are so specified, the statement CURRENT LIMITING FUSE INSIDE TANK shall be stenciled in yellow characters of at least 1 height immediately below the bayonet fuse holders. VI. Dielectric Fluid VII. Testing A. The liquid supplied in these transformers shall be a non-pcb type, as defined by Federal Regulation No. 40CFR 761, dated May 31, 1979, and subsequent revisions. Should any other oil be identified as a hazardous substance, it shall not be used B. The liquid contained in these transformers shall be identified as a non-pcb type with a separate label, no larger than three inches (3 ) by five inches (5 ), affixed to the transformer tank in the immediate vicinity of the nameplate. A. Routine tests on all transformers shall be as specified in the latest revision of Section 8 of ANSI C57.12.00. ANSI Test Code C57.12.90 shall be followed for all testing procedures. B. Loss evaluation tests including Full Load Loss (LL) in Watts at 85 C and No Load Loss (NL) in Watts at 85 C shall be provided with bid submittal so that cost of ownership can be determined by utility. Method of determining cost of ownership is determined by utility and is subject to change at any time without notice to vendor. As of this specification revision, owner s Total Ownership Cost (TOC) formula is as follows: TOC = Initial Cost + 4.5 * NL + 1 * LL C. Dielectric test shall be in accordance with ANSI Standard C57.12.26. 4

VIII. Shipping IX. Warranty D. Doors shall be opened and closed several times before vendor delivers unit, checking for misalignment, warping, improper hinging, etc. A. Transformers shall be shipped with a single transformer per pallet and delivered on a flat-bed truck situated for side unloading. B. For transformers 1000 kva and above, 36 hours notice shall be given before delivery to allow utility to arrange unloading. C. Certified test reports for each transformer, identified by serial number and rated kva, must be submitted to utility within 30 days of delivery of transformer to utility. A. Each transformer shall be guaranteed by vendor against failure due to any cause, except misapplication, abuse, or acts of God, for a minimum of one (1) year after delivery of transformer to utility or after delivery of certified test report to utility, whichever is later. B. Acceptance tests will be performed by owner to verify compliance with specifications stated herein and with quoted losses. Any transformers found not meeting these specifications or exceeding quoted losses may be refused by utility within thirty (30) days of delivery or transformer or delivery of certified test report, whichever is later. Transformers may be returned to vendor for full credit, vendor is to pay all original delivery and return transportation costs. X. Deviations to Specifications Vendors quoting transformers to this specification shall indicate any areas where deviations are required by their design and shall include sufficient information to permit full evaluation of same. This data shall accompany bid submittal from bidder. Approval drawings from manufacturer may be required on any specification changes. XI.IFD IFD(internal fault detection )shall be added to all transformers at factory and repair shops. 5