7-0000.B Mounting Installation Instructions NKQ, GK General Information Preliminary steps. Belimo actuators with NEMA ratings should be mounted indoors in a dry, relatively clean environment free from corrosive fumes. If the actuator is mounted outdoors, a protective enclosure must be used to shield the actuator.. For new construction work, order dampers with extended shafts. Instruct the installing contractor to allow space for mounting the Belimo actuator on the shaft. For replacement of existing gear train actuators, there are two options: A. From a performance standpoint, it is best to mount the actuator directly onto the damper shaft. B. If the damper shaft is not accessible, mount the non-spring return actuator with a ZG-GMA crankarm kit, and a mounting bracket (ZG-00, ZG-0, ZG-0, ZG-0). Direction of Rotation Switch Please refer to the appropriate product literature for detailed installation information. Reference Mounting Methods Guide Wiring Guide Damper Application Guide Electronic fail-safe actuators have a reversing switch on the cover. Switch position indicates start point. For the non-spring return, with the switch in position, the actuator rotates clockwise with a decrease in voltage or current. With the switch in position 0, the actuator rotates counterclockwise with a decrease in voltage or current. The electronic fail-safe rotates clockwise when the switch is in the position and power is applied to wire #. When power is applied to wire # and # for the - version, the actuator rotates counter clockwise. Rotating the switch to 0 reverses the control logic. 0 VDC VDC VDC 0 VDC During checkout, the switch position can be temporarily reversed and the actuator will reverse its direction. This allows the technician a fast and easy way to check the actuator operation without having to switch wires or change settings on the thermostat. When the check-out is complete, make sure the switch is placed back to its original position.
Installation Instructions Quick-Mount Visual Instruction for Mechanical Installation C A B D 0 See next page for standard mounting instructions. A* B C** D NKQB / to.0 <.0" to 7 ft-lb GKB / to.0 <.0" 0.8 to 7 ft-lb *NKQB clamps have an insert that self-centers on the following diameter shafts: / (default), / and.0. GKB clamps have an insert that self-centers on / diameter. Without the insert, the clamp centers on.0" **Shorter with reversible clamp for the GKB Note: If an auxiliary switch or potentiometer is used while the clamp is reversed, part number (P/N) 8-0000 is needed to connect the clamp to the auxiliary device.
Mounting Installation Reversible Clamp Quick Mount (GK) Center the anti-rotational bracket in the slot. Standard Mounting. Turn the damper shaft until the blades are fully closed.. Slip the actuator s universal clamp over the damper shaft. Make sure that the duct and the controls on the cover are accessible. Place the actuator in the desired mounting position. ➁ Hand tighten the two nuts on the actuators universal clamp.. Disengage the actuator gear train by pressing the manual override button and rotate the clamp until centered. ➁ Slide the anti-rotation strap up under the actuator so it engages the actuator at the center of the cutout. Bend the bracket as needed to support the rear of the actuator. Secure to ductwork with self-tapping screws (No. 8 recommended).. Loosen the nuts on the universal clamp. Press the manual override button and rotate the clamp to about from the closed position (/ to /8 between stop and clamp). ➁ Tighten the two nuts on the universal clamp with a 8, 0 or mm wrench (see table, column D on page for required torque).. Snap on the reflective position indicator. ➁ Adjust end-stops, if required. Mount actuators indoors. If mounted outdoors, use approved protective enclosure. The damper is now fully closed but the actuator is from fully closed. This is called pre-loading the actuator. When the actuator is powered and sent to the closed position: it will put its full torque on the shaft compressing the edge and blade seals. This ensures that the damper will meet its leakage rating. The actuator is electronically protected from overload and will not be damaged. Testing the installation without power. Disengage the gear train with the manual override button and move the shaft from closed to open to closed. Ensure that there is no binding and that the damper goes fully open and closes with of actuator stroke left.. Correct any problems and retest.
Wiring On/Off, Floating Point Torque (based on in-lb per sq. ft) Supply Consumption Fail-Safe 0 in-lb [0 Nm], Apprx. sq. ft. in-lb [ Nm], Apprx. sq. ft. Motor Drive (Default) VDC +0%/-0% VA rating Wattage running (holding) Airside Products GKB(X)- 0 () NKQB(X)- () Seconds Wiring NKQ GK VAC Transformer Blk () Common Red () + W_B W99_0 a open a closed a Wht () + The indication of direction is valid for switch position. 0 On/Off Floating Point or On/Off control 8 Provide overload protection and disconnect as required. Actuators may also be powered by VDC for a V power supply. Meets culus requirements without the need of an electrical ground connection. Contact closures A & B also can be triacs. A & B should both be closed for triac source and open for triac sink. Note: Floating Point not available on NKQ series
Wiring to 0 VDC Torque (based on in-lb per sq. ft) Supply Consumption Feedback Fail-Safe Airside Products GKB-SR, GKX-SR NKQB-SR, NKQX-SR in-lb [ Nm], Apprx. sq. ft. 0 in-lb [0 Nm], Apprx. 90 sq. ft. Motor Drive (Default) VDC +0%/-0% VA rating Wattage running (holding) 0 () () TO 0 VDC Seconds Wiring VAC Transformer W to 0 ma Control Signal ( ) (+) Ω 00Ω Blk () Common Red () Hot + Wht () Y Input, to 0V Org () U Output, to 0V To other actuators 0 Provide overload protection and disconnect as required. Actuators may be connected in parallel. consumption and input impedance must be observed. Actuators may also be powered by VDC. The ZG-R0 00Ω resistor converts the to 0 VDC control signal to to 0 ma, up to actuators may be connected in parallel. Only connect common to neg. ( ) leg of control circuits.
Wiring MFT Torque (based on in-lb per sq. ft) Supply Consumption Feedback Fail-Safe in-lb [ Nm], Apprx. sq. ft. 0 in-lb [0 Nm], Apprx. 90 sq. ft. Motor Drive (Default) VDC +0%/-0% VA rating Wattage running (holding) -0 VDC (default) VDC Variable (0 to 0 VDC) Airside Products GKX-MFT 0 () NKQX-MFT () - Seconds Wiring VDC/-0 ma VAC Transformer Control Signal to 0 ma or to 0 VDC ( ) (+) Ω 00Ω / watt 7 Blk () Common Red () + Hot Wht () Y Input, to 0V Org () U Output, to 0V MFT Floating Point (GK only) VAC Transformer to 0 VDC Feedback Signal A B 8 Blk () Common Wht () Hot + Wht () Y Input 9 Pnk () Y Input Org () U Output to 0V MFT W99_B PWM On/Off VAC Transformer (AC only) Position Feedback VDC VAC/DC Transformer Position ( ) ( ) (+) a Blk () Common Red () + Hot Wht () Y Input Org () U Output MFT Blk () Common Red () Hot Wht () Y Input Pnk () Y Input MFT Provide overload protection and disconnect as required. Actuators may be connected in parallel if not mechanically mounted to the same shaft. consumption and input impedance must be observed. Actuators may also be powered by VDC Provide Position overload feedback protection cannot and be disconnect used with a as Triac required. sink controller. The actuator internal common reference is not compatiable. Actuators may be connected in parallel if not mechanically mounted to the same shaft. consumption and input impedance must be Control observed. signal may be pulsed from either the Hot (Source) Actuators or Common may also (Sink) be powered VAC line. by VDC. 7 Position feedback cannot be used with a Triac sink controller. ZG-R0 may be used. The actuator internal common reference is not compatiable. 8 Control Contact signal closures may be A pulsed & B also from can either be triacs. the Hot A (Source) & B should both or Common be closed (Sink) for triac VAC source line. and open for triac sink. 7 ZG-R0 may be used. 9 For triac sink the common connection from the actuator Contact closures A & B also can be triacs. A & B should 8 both must be closed be connected for triac to source the hot and connection open for triac of the sink. controller. For triac sink the common connection from the actuator Note: 9 Floating Point not available on NKQ series must be connected to the hot connection of the controller.
Operations Mechanical Features Manual Override The Belimo non-spring return actuators have a black, manual override button located on the top of the housing. Press this button and the gear train is disengaged so the damper shaft can be moved manually. Release the button and the gear train is re-engaged. Use the manual override to test the installation without power. For tight shut-off the damper should close with of actuator stroke left. Manual override button Mechanical Angle of Rotation Limiting The adjustable stops are needed when there is no damper stop or if you want the damper to stop rotating before it reaches its stops. The non-spring return actuators can be indefinitely stalled in any position without harm.. Loosen the two end stops with a No. Phillips head screwdriver being careful not to unscrew the captive nut under the slot.. Move the stops (in. steps) to the desired position and re-tighten the screws. Setting the Fail-Safe Position Belimo's new Electronic Fail-Safe Actuators allows the user to set the fail position (0-00% in 0% increments). To set the position of the fail-safe, rotate the cover away from the fail-safe switch. Turn the switch to the desired positon. To set with PC Tool, turn the switch to PROG FAIL-SAFE. When done, rotate the cover back into position. Note: If switch is left in PROG FAIL-SAFE, the PC Tool software setting is active and can set the fail-safe position. It is recommended that the switch be set on the front of the actuator. This gives a simple visual as to what the fail-safe positon is set as. If the fail-safe is programmed using the PC Tool, and the switch is then moved off the PROG FAIL-SAFE position, the new position will override the PC Tool setting. The direction switch does not affect the fail-safe position switch. 7
Belimo worldwide: www.belimo.com BELIMO Americas USA Locations, Old Ridgebury Road, Danbury, CT 080 Tel. 800--908, Fax 800-8-88, marketing@us.belimo.com 09 Fortunado Loop, Sparks, NV 89 Tel. 800 987-90, Fax 800-987-887, marketing@us.belimo.com Canada Locations, / 7 Coopers Avenue, Mississauga, Ontario LZ E8 Tel. 8-80-7089, Fax 90-7-, marketing@us.belimo.com Latin America and The Carribean Customer Service, Tel. 0-79-89, Fax 0-79-99, marketing@us.belimo.com 8/0 Subject to change. Belimo Aircontrols (USA), Inc.