SHIMADEN SINGLE-PHASE THYRISTOR POWER REGULATOR

Similar documents
PAC18 Series. Single-Phase Thyristor Power Regulator. Instruction Manual

PAC18 Series. Single-Phase Thyristor Power Regulator. Instruction Manual

PAC27 THYRISTOR TYPE SINGLE PHASE POWER REGULATOR. Instruction Manual

(with Class-1 AC resistive load) 3. G3PB-215B-2N-VD kW max. (25 A) G3PB-225B-3N-VD 2. G3PB-225B-2N-VD kw max. (35 A) G3PB-235B-3N-VD 2

THV-40SERIES. Power Controller. Single Phase Thyristor Unit (High Voltage Type) AC V. RoHS compliant

Insulation method Zero-cross function Indicators Applicable output load Model number Phototriac coupler Yes Yes (See page 6) Main Circuit

Power Controller. (see note 1) 10 sec

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW

Model Number Structure. Power Controllers G3PX. Single-phase Models. Model Number Legend

INSTRUCTION MANUAL FOR JB SERIES THYRISTOR REGULATOR

Example of Combining Different Types of Heater Control. Heater control. Temperature Controller

Series ZSE30/ISE30. High Precision, 2-color Display Digital Pressure Switch. With One-touch fittings are newly introduced. PSE

Burden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM

Three Phase Power Controller THW-A Series

TL RELAYS. TYPICAL APPLICATIONS Head lamp, Fog lamp, Fan motor, etc. ORDERING INFORMATION TYPES. High Load Relay for Smart Junction Box ACTL.

Model Number Structure

RE-PR1-F 1-Phase Din-Rail Mount 1.5, 3 & 6kW

35 35A 50 50A 1 Single phase. Solid state power controller

NRBM Series. Between main circuit terminals: 2,000V AC, 1 minute Between main circuit and auxiliary contact: 2,000V AC, 1 minute

RVS-AX Instruction Manual

EUROTHERM ONTROLS. Two phase thyristor power switches. Product data

MULTI FUNCTIONAL COUNT CHECKER MODEL Poka Patrol CNA-4mk3

Direct Coupled Damper Actuator Model MY6050A1001

SYSDrive Frequency Inverter

Power thyristor units. 460 series. Control of single-phase resistive and inductive loads. User Manual

2-Color Display High-Precision Digital Pressure Switch

Minimum 18 in-lb Torque

KEWTECH. KT56 digital multi function tester. Instruction manual

Rated load current (resistive load) SRP. Min. 0.9 (max. 25 of difference between voltage phase and current phase)

Pulsar EXtreme 2200C / 3200C

Power Switching Principles

Electronic Circuit Breaker ESS20-0..

20 amps 220 amps, 60 Hz VDC VAC G3PA-420B-VD-2 DC amps 440 amps, 60 Hz G3PA-450B-VD-2 DC12-24

INSTRUCTION MANUAL BIPOLAR POWER SUPPLY PBA SERIES OPTIONAL RACK-MOUNTING ATTACHMENT OM-21E PRINTED IN JAPAN B

A. Provide variable frequency drives to operate variable torque loads as shown on the Drawings and as specified herein.

High Frequency SineWave Guardian TM

PANcharge1k Battery Charger User's Manual

INVERTER/CHARGERS Off-Grid Power Solutions

Power consumption In operation At rest For wire sizing. Functional data Torque Motor Spring return. Rated impulse voltage Control pollution degree 3

How to Order. Nil. W Water-cooled refrigerator type. Temperature: 5 to 40 C, Humidity: 30 to 70%RH Clean water 5 to /1.

DRB-1 Series Instruction Manual

COMPACT BUT CUT OFF DC POWER CURRENT, POWER CAPSULE CONTACT RELAY

ø8 A8 Series Miniature Control Units

POWER REGULATOR LD -40PSU

Innovators in Protection Technology Moulded Case Circuit Breaker Instruction Manual

Applicable Terminal Relay Rated voltage Model G6D-F4B 12 VDC G6D-1A (see note) 24 VDC 12 VDC G6D-1A-AP (see note) 24 VDC G3DZ-F4B 12 VDC G3DZ-2R6PL

EVS RP6020. Instruction Manual

HEAVY DUTY POWER RELAYS FEATURES

FSAF24(-S) US, FSAF120(-S) US

Switching Power Supply

E-15 Uninterruptible Power Systems (UPS)

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING

The Circuit and Control Technology in the Power Conditioner and Converter for Wind Turbine Systems

Digital Engine Tachometer

SYMBOL LEGEND DANGER WARNING NOTE THIS INDICATES DANGER TO THE LIFE AND HEALTH OF THE USER IS APPROPRIATE PRECAUTIONS ARE NOT TAKEN

AC Motor Systems. Speed Control Systems B-137. Speed Control Systems Introduction. BHF Series FE200 ES01/ US Series

Thyristor power controller TE10A. Burst-firing Single-cycle Advanced Single-cycle

FALL-OF-POTENTIAL GROUND RESISTANCE TESTER

SECTION MOTOR CONTROL

HYBRID HYDRAULIC O OIL COOLING EQUIPMENT O-1

Input terminals Isolation method Zero cross function Operation indicator Alarm output Applicable load (See note.) Model

POLARISED, MONOSTABLE SAFETY RELAY with (mechanical linked) forced contacts operation

Portable Instruments. Bulletin 2000-E

RP Instruction Manual

Circuit Breakers. Switching & Controls. Selection Guide NC1V Series Dimensions Accessories

Electronic Circuit Breaker ESS20

Micro-differential Pressure High-precision Digital Pressure Sensor For Gas DP-M SERIES

EPS/ELA-Series User Manual EPS/ELA 250W

WARNING WARNING. ECM3000 Control Motor User's Manual CAUTION NOTICE SAFETY PRECAUTIONS

ZWD100PAF Series Instruction Manual

0.5 s to 30 h (30 s, 3 min, 30 min, 3 h, 30 h)

2 to 25 A, 100 to 240 VAC G3PF-225B-STB Compact slotted

ZWD225PAF Series Instruction Manual

Power System Solutions (PSS)

RVS-DN Digital Reduced Voltage Motor Starter

ILLUMINATOR LV. Emergency Lighting Inverter System 175VA through 750VA. Illuminator Series LV Single Phase

Technical Data Sheets

SCR Power Controllers

Circuit Breakers. Switching & Controls. Selection Guide NC1V Series Dimensions...

INSTALLATION INSTRUCTIONS FOR SYMCOM'S MODEL 777-HVR-SP ELECTRONIC OVERLOAD RELAY

MPPT Solar Integrated Inverters (500VA~2500VA) User Manual THE SOLAR TECH CO.,LTD. Solar Integrated Inverter Series 500VA~2500VA 13.

TOWA SEIDEN INDUSTRIAL CO., LTD.

CD3000S-1PH Thyristor Unit Heater Break version

Bulletin 825 SMM Smart Motor Manager

1. Electronic Stabilizer and Technical Development. 2. Electronic Stabilizer General

High Accuracy Eddy Current Type Displacement Sensor GP-A SERIES. Resolution 0.04 % F.S., Linearity ±0.5 % F.S., IP67G environment resistance

MIDDLE LOAD RELAY FOR SMART J/B

Power consumption Wire/transformer sizing. Motor. Spring return. Motor. Spring return. EMC Low voltage directive

PD-Series Ground Fault Circuit Protection

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS

G3PE-Single-phase. Solid State Relays for Heaters

MB A 12V/24V DC PROGRAMMABLE DUAL BATTERY ISOLATOR

Thermal-cutoff, Fuse and Fuseholder Incorporated into a Simple Compact Device

MODEL: PSN3. Final Control Elements. STROKE 6: 0 to 60 mm (0 to 2.36 )

LINE CONDITIONERS USER'S GUIDE

LV Capacitor Bank APC

BLH. 24 VDC Input 15W / 30W / 50W / 100W BLH

韩国 Autonics 进口固态继电器型号模拟固态继电器 SRPH1 SRPH1 Series SSR 比例控制继电器选型说明书 pdf Single phase, Analog input type SSR Features Power control/ Cycle control/phase c

TC abc. Three phase thyristor for resistive, inductive and temperature dependent (complex) loads CONTROLS DATA MANAGEMENT PROCESS AUTOMATION

1 Form A 5A small size power relay for interface

Transcription:

Shimaden, Temperature and Humidity Control Specialists C %RH SHIMADEN SINGLE-PHASE THYRISTOR POWER REGULATOR approved BASIC FEATURES Easy Front Key Setting compliance A 7-segment LED displays input and output values and various parameters. Slow-Up, Slow-Down Function Output Current Detection Function (Optional) Parameter Setting Function (Optional) Universal Power Supply (100 240 V AC) Automatic Frequency Discerning Function (50/60 Hz)

FEATURES As a succession device for the PAC15 Series which achieved a record of long-term durability and reliance, the PAC18 Series thyristor power regulator pursues an even higher level of functionality and safety. Corresponding compliance mark Safety standards: Safety IEC61010-1 : EMC EN61326 (The specified noise filter must be used.) FUNCTIONS Automatic detection of power frequency 50/60 Hz Control circuit power supply is 100 V 240 V common: this corresponds to a wide power/voltage range. Output current detection function (optional) available, adaptable to overcurrent protection, current limit function and alarm output function (power failure, overcurrent, heater break detection and hardware error) CONTROL TYPE Display Control type Phase control/phase angle proportional output Phase control/voltage proportional output Phase control/voltage square current proportional output Cycle calculation zero voltage switching control Complex control CONTROL TYPE AND OUTPUT WAVEFORM Item Control type Phase control Harmonic disturbance Possibility of occurrence Flickering occurrence None Applicable load Constant resistive load Inductive load (transformer primary control) Output waveform 10% output 50% output 90% output Cycle calculation zero voltage switching control None Possibility of occurrence Constant resistive load Complex control: Short time phase control is executed only when output rises from zero percent, after which operation switches to cycle control. SAFETY MEASURES Thanks to the power supply instantaneous stop handling function and the power failure handling function, overcurrent trouble during transformer load has been eliminated and power supply variation, distortion, and noise, in comparison with the former series, have been improved. Detects shorting of thyristor device, gate set to off and alarm output (optional). Load current is detected by CT (optional), gate set to off when overcurrent occurs and alarm is output.

SETTINGS Setting panel included as standard equipment Ramp setting, variation limit setting, current limit setting and manual output setting are easily conducted by use of the front key and digital display. Manual output setting, current limit setting, ramp upper limit setting and ramp lower limit setting are conducted with an external adjuster. CONTROL TYPE (1) Phase control/phase angle proportional output (same as PAC15P) Phase angle output proportional to control input can be obtained. Phase angle Output voltage 0% Control input 0% Control input (2) Phase control/voltage proportional output Output voltage proportional to control input signal can be obtained. (3) Phase control/voltage square (current) proportional output The characteristics of this function are to output power in proportion to control input. This also has constant voltage characteristics and therefore is applicable to nichrome heaters and allows controllability to be improved. In cases of manual adjustment, etc., power adjustment which is proportional to the scale of a regulator is available. Output voltage Output Voltage characteristics 0% Control input (4) Cycle calculation zero voltage switching control (same as PAC15C) Output proportional to control input signal can be obtained. 0% Power characteristics Control input Output (5) Complex control Short time phase control is executed only when output rises from zero percent, after which operation switches to cycle control. Used for transformer primary control by cycle control. 0% Control input

PANEL PART NAMES AND EXTERNAL CONNECTION DIAGRAM Panel Part Names Parameter display Alarm display Data display Error dot Data change/manual dot Switches and their names Parameter key: Primarily used for switching screen displays. Down key: Primarily used for switching parameters. Decreases numerical values. Up key: Primarily used for switching parameters. Increases numerical values. Enter key: Primarily used to enter parameter settings. External Connection Diagram Temperature controller Contact input Auto/manual switching input VR3 VR2 VR1 Control input External adjuster Function Manual adjuster Current limit adjuster Ramp upper limit adjuster Ramp lower limit adjuster VR used VR3 VR1, VR2 VR1, VR2 VR1, VR2 Alarm contact output Control power supply input Rapid fuse 100 240 V Main power supply Load Note: Main power supply and control power supply should be used in the same phase.

OUTPUT ADJUSTMENT FUNCTION (1) Ramp upper limit (high power) adjustment The output value for ramp upper limit can be adjusted from 0.1 to 100.0% when the control input is. Because maximum output is turned down, output rampof the device relative to the control input signal is changed. (2) Ramp lower limit (low power) adjustment The output value for ramp lower limit can be adjusted from 0.0 to 99.9% when the control input is 0%. It is used when you want to output even when control input is 0%. Because minimum output is adjusted, output ramp of the device relative to the control input signal is changed. Adjustment/output of ramp upper limit Adjustment/output of ramp lower limit Output Adjustment range Output Adjustment range 0% Control input 0% Control input (3) Variation limit (slow-up time/slow-down time) adjustment Input variation can be limited by the variation limit setting, and therefore the output variation of the device can be delayed. Configurations (4) Current limit: only for phase control (optional) Function for limiting the current to the set current value (within 0 120% of the rated current). Selected when controlling heaters which generate primary inrush current such as platinum, molybdenum and tungsten or SiC heater. Note: The more load rate exceeds the rating, the more output power drops. Slow-up time Output Slow-down time Current limit adjustment range: 0 120% Control input Current (5) Heater break alarm (optional) Generally, there are cases where quick detection and consequent alarm output are required such as when even one heater is broken within a heat source which consists of several heaters. Also, power down due to deterioration, such as that involving a SiC heat generator, can be detected. This can also be used as a signal for the replacement period of taps and heat generators. 0% 200% 300% Load factor ON Heater break OFF Steady current Alarm setting point Current

ALARM DETECTION Hardware error (thyristor shorted) PAC18 Rapid fuse CT R U Overcurrent (insulation failure of load side, abnormal current flow due to earth fault, etc.) Heater break (heater break, heater deterioration) Load Power failure (frequency exceeded the range of 40 70 Hz, unstable) Alarm types Power failure Overcurrent (optional) Hardware error (optional) Heater break (optional) Alarm display Conditions Power supply frequency is outside the 40 70 Hz range. Power supply frequency is unstable. Output current has exceeded 130% of rating. Output current fl ows when output is 0%. Heater break has been detected. Input error Control input is below -10% or over 110%. Alarm output Available Not available Corresponding action Stops output. Output is automatically reset if alarm conditions are eliminated. Stops output. Turn off the power, remove the cause, and then turn the power back on. Stops output. If a hardware error alarm occurs even if a load is connected, repair is required. Control continues. SPECIFICATIONS Control element configuration : Thyristor x 2 inverse-parallel connection Main/control power supply : 100 ~ 240 V AC, 5 VA (main/control power supply used in the same phase) Voltage fluctuation tolerance : Max. ±10% of rated voltage Rated frequency : 50/60 Hz Rated current : Any one of 6 types (20, 30, 45, 60, 80, 100 A) Control output range : 0 ~ 97% or more Applicable load : Resistance load or inductive load (transformer primary control: phase control or complex control) Control type : Phase control, cycle calculation zero voltage switching control, complex control (specify when ordering) (No output feedback function) P: Phase control (specify when ordering); phase angle proportional output, voltage proportional output or voltage square proportional output C1: Cycle calculation zero voltage switching control X1: Complex control (phase control when output increases from 0%, followed by cycle calculation zero voltage switching control) Cooling : Self cooling Protection : 1) Electronic overcurrent gate cutoff circuit (optional); alarm output when operating, detection by current transformer (CT) 2) External rapid fuse (sold separately) 3) Hardware error detection (optional); detects short circuit or thyristor shorting when output is 0%. Control input : Current: 4 ~ 20 ma DC [receiving impedance 100Ω] common with contact Voltage: 1 ~ 5 V, 0 ~ 10 V DC [input resistance approx. 200kΩ] common with contact Standard functions External adjustment function : External adjusters such as ramp lower limit, ramp upper limit, current limiter and manual can be connected. Up to 3 external adjusters can be used. B characteristics 10kΩ 3 lines External adjusters sold separately Variation limit : 0.0 ~ 99.9 sec. variable setting (set by front surface key switch) (slow-up, slow-down) Time required to reach 0 ~ output

Additional functions (optional) Output control detection function (built-in current transformer [CT]) Overcurrent : Electronic overcurrent gate cutoff circuit, outputs alarm when it detects that output current value is in excess of 130% of the rating. Current limit function : Phase control only supported Using pure metal load, etc., inrush current limitation, response time 0.1 sec. or less (initial value of rated current) 0 ~ of rated current set by external adjuster (current limiter) or 0 ~ 120% of rated current set by front panel key operation Hardware error alarm : Alarm is output when thyristor error (thyristor device is shorted and current flows even though output is 0%) is detected. Heater break alarm : Heater break is detected and alarm is output. Heater break judgment 0 ~ setting Alarm output : 1 point, 1a contact, 240 V AC, 1A Power failure, overcurrent (optional), hardware error (optional), heater break (optional) selection; alarm contact output; redundant selection possible External adjuster : Up to 3 external adjusters can be used. B characteristics 10kΩ 3 lines Parameter setting function : Data communication adapter (sold separately) can be connected. By connection with a PC, various settings, control input values, output values and various setting values can be displayed. External rapid fuse : Protect thyristor and power equipment from load short, etc. General specifications Operating ambient temperature range : -10 ~ 55 C (current must be reduced for 50 C or higher.) Operating ambient humidity range : 90% RH or lower (no dew condensation) Operating ambient elevation range : altitude 2000 m or below Storage temperature : -20 ~ 65 C Safety standards : Safety IEC61010-1 : EMC EN61326 The specified noise filter however must be used. 20/30A HF2030A-XB 45A HF2050A-XB 60A HF2060A-XB 80A HF2080A-XB 100A HF2100A-XB Insulation resistance : Between control power supply terminals and control input terminals: Min. 500 V DC, 20MΩ Between main power supply terminals and chassis: Min. 500 V DC, 20MΩ Dielectric strength : Between control power supply terminal and control input terminal: 2300 V AC, 1 minute Between main power terminal and chassis: 2000 V AC, 1 minute Plastic case material : Polycarbonate External dimensions and weight : 20/30A: 48 (W) x 117 (D) x 170 (H), approx. 0.8 kg 45A/60A: 68 (W) x 151 (D) x 188 (H), approx. 1.8 kg 80A/100A: 113 (W) x 151 (D) x 204 (H), approx. 3.0 kg Terminal cover : Standard attached CURRENT CAPACITY AND HEAT VALUE Voltage (0.9 1.3 V) is produced between terminals by current flowing to the thyristor. Voltage between terminals and accumulation of current (W) turn into Joule heat, resulting in a rise in temperature of the thyristor device. Takeradiation and ventilation into account. Ambient temperature/ load current characteristics PAC18 Internal heat value Rated current 20A 30A 45A 60A 80A 100A Heat value 22W 36W 47W 65W 77W 96W 100 90 Load current (%) 10 0 Ambient 50 55 temperature ( C)

CODE SELECTION TABLE ITEMS CODE SERIES PAC18 Single-Phase Thyristor Power Regulator CONTROL TYPE CONTROL INPUT RATED CURRENT OUTPUT CURRENT DETECTION FUNCTION (OPTIONAL) P0 P1 P3 C1 X1 PARAMETER SETTING FUNCTION (OPTIONAL) REMARKS Phase control/phase angle proportional output Phase control/voltage proportional output Phase control/voltage square (current) proportional output Cycle calculation zero voltage switching control Complex control (Phase control only when output rises from zero percent, then switches to cycle control) 3 Voltage 1 5 V DC Input resistance: 200k/contact, common 4 Current 4 20 ma DC Receiving impedance: 100 built-in/contact, common 6 Voltage 0 10 V DC Input resistance: 200k/contact, common 020 20A 030 30A 045 45A 060 60A 080 80A 100 100A 0 Without 1 With: Overcurrent protection, current limit function, alarm output 1 point 1a contact 240 V AC 1A (Power failure alarm, overcurrent alarm, heater break detection alarm, hardware error alarm) 0 Without 1 With (data communication adapter (sold separately) can be connected.) 0 Without 9 With Note: If the CE designation is required on the product, please specify this when ordering. On the condition that the product is used with a noise filter as specified by SHIMADEN, the CE safety standard (EMC Directive) shall be satisfied. Rapid fuse and fuse holder External adjuster Name Rated current Fuse type Type Rapid fuse Fuse holder Rapid fuse with fuse holder 20A/30A 350GH-50UL QSF006 45A/60A 350GH-100UL QSF007 80A/100A CF5R06-150 QSF008 20A 60A HT4017 QSH002 80A/100A CMS-5 QSH003 20A/30A 350GH-50UL + HT4017 set QSF01F 45A/60A 350GH-100UL + HT4017 set QSF01G 80A/100A CF5R06150 + CMS-5 set QSF01H Type QSV003 Noise filter Type HF2030A-XB HF2050A-XB HF2060A-XB HF2080A-XB HF2100A-XB B10k Rated current 20A30A 45A 60A 80A 100A Mounting dimentions 20 mm or more 20 mm or more 100 mm or more PAC18 PAC18 PAC18 100 mm or more

EXTERNAL DIMENTIONS/WEIGHT 20/30A: 48x170x117 mm/approx. 0.8 kg 5.5 48 117 Unit: mm 14.5 160 170 5 5 5.5 Notch 12.5 2-M4 49 45/60A: 68x188x151 mm/approx. 1.8 kg 5.5 68 151 Unit: mm 188 5 178 5 19 5.5 Notch 6.5 R U 9.5 11 166 11 188 2-M5 84 80/100A: 113x204x151 mm/approx. 3.0 kg Unit: mm 2-5.5 113 80 151 22.5 204 194 5 11.5 181 204 R 5 U 5.5 Notch 27 2-M8 11.5 82

NOISE COUNTERMEASURES CONDITION FOR CE MARKING 1. For dealing with EMC command Use in combination with a noise filter designated by Shimaden. Install the noise filter on the same metal plate as the PAC18. Concerning the noise filter, please ensure that it is properly grounded. The length of wiring between the noise filter and the PAC18 should be 0.5 m or less. 2. For dealing with low-voltage command When power line is wired, as a precaution against accidental shorting, make sure to install one molded case circuit breaker for each PAC18. The rated current of a molded case circuit breaker should be less than 1.3 times as high as that of the PAC18. With phase control, part of the power supply sine wave is dropped. This produces distortion in the sine wave if the power supply impedance is high. Also, because the power supply is switched each half cycle, a switching noise is produced. The power supply distortion and noise may affect other equipment. In the case of cycle calculation zero voltage switching, an extremely small amount of noise is produced in comparison with phase control due to switching near the zero cross point of the power supply. However, because some noise is produced by switching to a large current, you should use a noise filter if necessary. Also, if power supply impedance is high, the power supply may flicker in synch with the ON/OFF status of the thyristor. Power supply 100240 V Noise filter PAC18 Make sure that the wiring between noise fi lter and PAC 18 is as short as possible. R U Load (heater) Noise filter The frequency of noise produced by the thyristor is distributed in a place below several megahertz, and the noise dampening effect of commonly available commercial noise fi lters is insuffi cient. Using noise fi lters specifi ed by Shimaden can dampen this noise. This noise fi lter is specially designed for Shimaden thyristor power regulators. External configuration/dimentions Dimentions (unit: mm) Type Rated current A B C D E F G M N Weight (kg) HF2030A-XB 20A, 30A 248 240 220 200 90 70 80 M5 M4 Approx. 1.8 HF2050A-XB 45A 268 250 235 220 90 70 80 M6 M4 Approx. 2.5 HF2060A-XB 60A 268 250 235 220 90 70 80 M6 M4 Approx. 2.5 HF2080A-XB 80A 304 280 265 250 130 110 95 M8 M6 Approx. 4.5 HF2100A-XB 100A 304 280 265 250 130 110 95 M8 M6 Approx. 5.0 2-R3.25 length 8 2-M 2-M N 2 6.5 No. Name Input terminal Metal case Name plate Output terminal Grounding terminal F E D C B A G

EXTERNAL DIAGRAM OF SEPARATELY SOLD PRODUCTS External adjuster Type: QSV003 External diagram of external adjuster 2 M9P0.75 55 31 6 1.6 20 30 40 50 60 9.5 70 80 Resistance value: B10k 2.7 10 16 20 36 10 0 100 90 Lead wire length: 1 m With crimping terminal for M3 3 9.5 12 Unit: mm Fuse holder Type: QSH002 Hinode Electric Co., Ltd. HT4017 65 65 26 18.2 41 22 26 132 116 102 16 48 3.4 8 17.8 16 17.8 35 1.5 4.3 1 Unit: mm Type: QSH003 Fuji Electric Co., Ltd. CMS-5 70 Insulation cover 44 11 6 6 13 35 21 72 13 35 21 72 Unit: mm

Warning The PAC18 series is designed for the control of temperature, humidity and other physical values of general industrial equipment. (It is not to be used for any purpose which regulates the prevention of serious effects on human life or safety.) Caution If the possibility of loss or damage to your system or property as a result of failure of any part of the process exists, proper safety measures must be made before the instrument is put into use so as to prevent the occurrence of trouble. Temperature and Humidity Control Specialists (The contents of this brochure are subject to change without notice.) Head Office: 2-30-10 Kitamachi, Nerima-Ku, Tokyo 179-0081 Japan Phone: +81-3-3931-7891 Fax: +81-3-3931-3089 E-MAIL: exp-dept@shimaden.co.jp URL: http://www.shimaden.co.jp 09CPAC18130ILC