Contractors Guide Central Inverter System Installation

Similar documents
For additional information, please refer to the Installation/Operation Manual

Sunwize Power Ready Express Quick Start

Illuminator System Series CM

Installation and Operation Instructions SERVICE BY QUALIFIED PERSONNEL ONLY

Sensor3 Rack (SR3 and HSR3 Series) Installation Manual

LiteMinder. LM Series Inverter Pure Sine Wave Modular Inverter Technology. Fast Transfer System 1.0 to 18.75KVA LED Compatible

LMI Watt Models

Installation Instructions

L I T H I U M B AT T E R Y

Installation Instructions and User Manual For

Sure-Lites. Installation Instructions for the Sure-Lites UX Self Powered Exit Sign with Self Diagnostics. IB505037EN Important Safeguards

Illuminator System Series CIII

TOPAZ 12 WALL PACK INSTALLATION & MAINTENANCE GUIDE (Part # LIT A)

Plasma Display Electric Pop-Up Lift (PUL)

Assembly of kick TM Utility Poles

Installation Instructions Studio Makeup Station

accqpulse Velocity Profiler Sensor Installation Guide

SMIDLEY MINI-SCALE RETROFIT INSTRUCTIONS

Installation Instructions Central Battery Units

Combo HPU Kidney Loop Motor

TOPAZ 24 DIMMER RACK INSTALLATION & MAINTENANCE GUIDE (Part # LIT A)

Installation And Operation Instructions

Installation Instructions and User Manual For. 100 Watt Inverter Power System

PEC 827E. 120 VAC AC Distribution Shelf. Critical Power Product Manual

mygrid Installation Notes

Installation Manual. For. Alumavator / Platinum Boathouse Lifts

Installing Your 220v J-POD Kit

INSTALLATION INSTRUCTIONS HIGH OUTPUT 2 SPEED RAD FAN ASSEMBLY

INSTRUCTIONS. Power Panel. Installation Instructions

INFINITY MULTA SERIES

Special Specification 6058 Battery Back-Up System for Signal Cabinets

U N I T Y / Three-Phase Uninterruptible Power Systems UT3120, UT3160, UT Hz

RECESSED TRACK (120V) SPECIFICATIONS

LIGHTPLANE 1 RECESSED - LP1R

SUT-450-I ASSEMBLY REQUIREMENTS

Installation Instructions For Part Number: Scoop and Snorkel Kit

INSTALLATION MANUAL

Hummer H up A Hummer H3T up A. 3-5 Hours INSTALLATION GUIDE INSTALLATION TIME SKILL LEVEL.

LI-ION BATTERY UPFIT KIT

ES50M-65N TROUBLESHOOTING AND REPAIR MANUAL ALL REPAIRS SHOULD BE PERFORMED BY A QUALIFIED ELECTRICIAN

INSTALLATION INSTRUCTIONS

INSPECTION REQUIREMENTS: PHOTOVOLTAIC (PV) RESIDENTIAL

Installation, Operation & Maintenance Manual DataSafe HX Front Terminal Battery Cabinets

Installation And Operation Instructions

FOG LAMPS INSTALL KIT

GRANITE ENCLOSURES MODEL NO. NPS Standard Features

BR62 Battery Rack Installation, Operation, & Maintenance Manual

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION

ENTRANCE EQUIPMENT ER D PAGE 1 OF 5

Lucent Technologies Whippany Physical Design

Adjustable Light Kits E-Z-Go TXT All Models Installation Instructions

LGT-312L E-Z-Go TXT Light Bar Bumper Kit Installation Instructions

Commercial 1000VDC String Inverter XGI Installation and Operation Guide Models: XGI XGI

Grounding Systems. Equipment Grounding & Grounded Conductors

INSTALLATION INSTRUCTIONS

Installing and Removing Power Supplies

XENON POWER SUPPLY 4000 Watt Gladiator IV

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

Installation And Operation Instructions

GMC Mesh Grille

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS DRAWERS #240

! "! User Manual Myers Power Products CTEP/G Manual 6/2009

Cold Air Intake System, LS6-Z06

10 Commercial, Industrial, Agricultural Services

In-ceiling mount NDA-FMT-DOME. en Installation manual

HP BladeSystem c7000 Carrier-Grade Options Installation Guide

Model Numbers SAVI-NOTE75, SAVI-NOTE150

Installation and Service Manual

INSTALLATION PROCEDURE Step 1. Unpack and verify shipment. Double-check site specifics. Step 2. - Page 3 -

Universal Tall HoneyBadger Chase Rack Installation Instructions

Approved Contractor Construction e-guide Residential Commercial

650 Series Cargo Van Lift Mounting Instructions Fullsize Ford 1992-Present

Installation Guide TB499 Conveyor/Dryer/Stacker Part #: M-3250 Revision Date:

NOTE: The orientation of the mounting brackets are critical. (See Figure 4)

IMPORTANT SAFEGUARDS

INSTRUCTION SHEET PRL-97X04 AC AND DC VOLTAGES

Installation Instructions and User Manual For

MOUNTING SYSTEMS SPECIFICATIONS

READ THIS BEFORE INSTALLING SWITCHGEAR

Dynamic Braking Kit for FlexPak 3000 and WebPak 3000 Digital DC Drives 1.5 HP to VAC, 3 HP to VAC without NEMA1 Enclosures

DayStar Quick Start Guide

INSTALLATION INSTRUCTIONS

ELECTRIC SERVICE RULES DISTRIBUTED GENERATION Issued Jan 2016

Installation and Operating Procedures For C&D Technologies TRUE Front Access TEL Series Batteries

Important: Please read these instructions carefully and completely before starting the installation. TITAN Fuel Tanks INSTALLATION GUIDE

MIRRORLITE RECESSED EMERGENCY LIGHTING

Apollo Solar Inverter Switchgear Module Installation Manual Rev 1.2 Page 1

** DO NOT EXCEED THE RECOMMENDED VEHICLE TOWING WEIGHT RATING ** DODGE RAM 1500

Power Back Up Product Announcement

= Experienced

ANZI Transfer Switch and Generator Wiring Installation Addendum

INSTALLATION INSTRUCTIONS WINCH MOUNTING KIT Part Number: Application: Honda Rancher TRX420

TOYOTA TUNDRA BUMPER STEP ASSIST Preparation

Master/Slave Actuators Spring Return Rotary 24 Vac - Modulating Control

Installation Manual TWM Performance Short Shift Kit Stage 1 and Stage 2 MazdaSpeed 6

LPE C5 Battery Relocation Kit

STACK-ON UNIT WARNING. Illustration 1

RoadRelay 4. Installation Guide

Important: Please read these instructions carefully and completely before starting the installation. TITAN Fuel Tanks INSTALLATION GUIDE

Transcription:

Contractors Guide Central Inverter System Installation Step By Step Procedures 3,000 Watt/VA Vertical (Stacked) and Horizontal (Side by Side) 5 Step Installation 1. Mounting the Cabinet 2. Install / Connect Batteries 3. Install Conduit 4. Install AC Wiring 5. Energize System Inverter shown is 3KW using a Stacked (Vertical) configuration. (Factory prefered configuration) Note - Remove Floor Mounting Brackets from Inverter Cabinet for Vertical Mounting configuration For additional information, please refer to the Installation/Operation Manual Page 1

24 24 AC Breaker Panel 3 feet minimum clearance in front of all units 13 38 Man Machine Interface Panel Master Inverter Cabinet Battery Cabinet 4.0 Inter-cabinet Battery Cable Ports for Vertical Mounting Horizontal Mounting Mounting Slot See Detail Bracket, Floor Mounting 9.97 21.00 1.5 1.5 Master Inverter Cabinet Floor Mounting Bolt Pattern 72 64.3.75 x 2.13 Slot for Floor Mounting 1.38.31 Dia. holes for 1/4 hardware Floor Mounting Brackets and Cabinet to Cabinet Vertical Mounting 38 55.6 Mounting Slot Detail Battery Cabinet Horizontal (Side by Side) Battery Cabinet mounted to the right side of Electronics Cabinet for proper battery cable routing from cabinet to cabinet Vertical Mounting Vertical (Stacked) Battery Cabinet mounted underneath Electronics Cabinet for proper battery cable routing from cabinet to cabinet Overall Mechanical Dimensions Page 2

Step 1 Mounting the Cabinet Mounting can be either Vertical (Stacked) or Horizontal (Side by Side). Each cabinet is shipped with Floor Mounting Brackets to accommodate both configurations. Preferred method is Vertical mounting such that the Front Panel Display is at user's eye level. For Vertical configuration, the Floor Mounting Bracket must be removed from the Inverter Cabinet. Lay Inverter Cabinet on its back or side and remove the underside mounted (8x) ¼-20 flange bolts. Prepare floor so that it is level and smooth and secure Battery Cabinet into floor using Concrete Wedge Anchors or other suitable method (hardware provided by others). If using Horizontal mounting, secure the Inverter cabinet to the left of the battery cabinet for proper battery cable routing from Battery Cabinet to Electronics Cabinet. Note - Uneven surfaces may cause difficult front cover removal/installation Install Grommet (8x) 1/4-20 hardware ( 2x) Floor Mounting Bracket Floor Anchor Hardware (Supplied by contractor) Page 3

*Install Grommet in Battery Cabinet for wire protection before stacking the cabinets. Secure Inverter cabinet on top of Battery Cabinet with 6 x ¼-20 bolts (factory provided). Bolts are mounted from the underside of the Battery Cabinet and screw up into PEM fasteners in the bottom of the Inverter Cabinet. Master Inverter Cabinet Grommets in center knockout View shows bolts from the bottom Battery Cabinet securing up into the Inverter Cabinet 6x 1/4-20 hardware Battery Cabinet Page 4

Step 2 Installing and Wiring the Batteries Note Always ensure that all 3 of the DC Fuses in the battery cabinet are removed before starting installation. Battery cable lengths are sufficient for Vertical or Side by Side mounting. Positive and Negative battery cables should be trimmed to length when using Vertical (Stacked) configuration before installing into the battery cabinets terminal blocks.this system has a Series/Parallel battery arrangement. Four batteries are wired in series on each shelf to produce 48VDC. Each 48VDC battery shelf is wired together so that there are 3 battery shelves (strings) in parallel. Please see wiring schematic in the manual and on the battery cabinet door for further explanation. 1. Route Red and Black wires from Inverter Cabinet to Battery Cabinet. Connect Red and Black wires to the top side of the Positive and Negative Terminal Blocks respectively. Positive +48VDC Red cable is the front Terminal Block, Negative DC Black cable is the Rear Terminal Block.When using the Vertical Stacked configuration, the DC wires have to be run between the two inverter modules on the bottom shelf of the Inverter Cabinet. 2. Load all 12 batteries onto the battery shelves. Ensure proper spacing between batteries so that Battery-Battery Buss Bar Jumpers can be installed properly in Step 4 below. 3. Connect all Positive battery cables on each shelf to the right battery on each shelf. 4. Connect all Battery Buss Bars between adjacent batteries on each shelf. 5. Connect all Negative battery cables on each shelf to the left battery on each shelf. 6. Measure and ensure correct DC string voltage (48VDC) and ensure all connections are made. 7. Install all 3 Fuses. Horiz. Cabinets Neg. Battery Cable Pos. Battery Cable To Terminal Blocks Neg (BLK) Pos (RED) Fuses Route Battery Cables through wire ports M6 Bolt, 10mm socket Torque to 40 in lbs Insulating Cover Connecting Cable Lug -- + Flat Washer on all battery connections Lockwasher on all battery connections -- + Install Grommets for Horiz. Cabinet installation Nominal DC Voltage 48VDC (12 Batteries) See Detailed Diagram on Cabinet Door Battery Buss Bar Page 5

Step 3 Installing the AC Conduit Use Provided Knock-Outs located on Tops and Sides of Inverter Cabinet Note Drilling into cabinets may VOID warrant - metal shavings can short circuit electronic components. Input and Output Wires should be run in separate conduit per NEC. Knock-Outs are a dual size for 7/8" and 1-1/8. Follow all Local and National Electrical Codes (NEC) 24 17.25 2.50 4x 2.50 2x 1.75 Top 16x dual knockout 1-1/8 and 7/8 dia. 13 6x 2.0 Left Side Right Side 24.5 38 4x 1.75 Master Inverter Cabinet 2.5 6.5 Knockout pattern identical to right side Page 6

Step 4 Installing the AC Wiring Ensure the AC Input Breaker CB1 is in the OFF (Down) position before starting. See Installation/Operating manual (section 7) for AC Input and Output AC ratings. Remove Plastic AC Circuit Breaker Cover (secured with 2 x ¼-20 bolts). Wire AC input directly to top side of Input Breaker - AC Input Circuit Breaker on Left side. Wire Input Neutral and Ground connections to appropriate Neutral and Ground Bars. Do not share Neutrals with Emergency and Non-Emergency loads. Connect AC output wires to the top side of Normally-On terminal block or output circuit breakers if provided. Standard equipment always has a Normally-On output terminal block for output wire connections. AC Output Breakers are Optional. Follow all Local and National Electrical Codes (NEC) AC Breaker Cover Remove 2x 1/4-20 bolts Ground Terminal Block AC Input/Output Neutrals AC Input Normally On Terminal Block Wire terminal screws Standard Output Terminal Block Illustration CB1 Neutral Terminal Block AC output wires AC Input/Output Neutrals Optional Output Circuit Breaker Illustration Ground Terminal Block Normally On Terminal Blocks Switched Command Terminal Block AC Input Wire terminal screws Neutral Terminal Block CB1 CB2 CB3 Page 7

Step 5 Starting Up/Energizing the Unit Ensure batteries are installed, the wiring is checked per Step 2. Ensure AC Power is present and lighting loads are connected per Step 4. Flip on Input Circuit Breaker CB1. Flip on System's On/Off Switch located to the right of the Interface Panel. System will go through start up diagnostics and go into charge mode if there are no errors. Press the system test button or momentarily drop AC power to energize emergency power and ensure that the inverter can support the lighting loads without going into a fault condition. Replace and secure AC Breaker Cover and its clear access window with locking screw. Install front cover to Cabinets. Contents of shipment 1KW to 3KW Models include: Cabinets 1KW model uses single cabinet. 2.2KW, 2.8KW and 3KW models use two cabinets. Floor Mounting Brackets Attached to Battery Cabinet or 1KW Inverter Cabinet. Batteries 4 pcs for 1KW, 8 pcs for 2.2KW, 10 pcs for 2.8KW and 12 pieces for 3KW Battery Cable Kit All Models Cabinet Hardware Kit All Models except 1KW Installation/Operation Manual All Models Contractors Guide All Models Tools Required for Installation (typical all models) 3/8" Nut Driver and/or 3/8" Socket and Ratchet Straight Blade Screwdriver(s) Square Head (Robertson) Screwdriver Phillips Head Screwdriver - #2 10MM Socket and Ratchet or 10MM Wrench (Torque set to 30 in-lbs.) 3/16 Allen Head (Only for Side By Side mounting Battery Cable Replacement) Hardware for securing cabinet to floor i.e. Hilti Kwik Bolt or equivalent Multi-Meter capable of DC and AC Measurements Page 8