Limit Switches. Series NI700 Installation, Maintenance and Operating Instructions

Similar documents
7 NK 72 en Issue 12/99 LIMIT SWITCHES. Series NK700 INSTALLATION, MAINTENANCE AND OPERATING INSTRUCTIONS

PNEUMATIC CYLINDER UNIT. Series CP Installation, Maintenance and Operating Instructions

PNEUMATIC CYLINDER UNIT. Series CS Installation, Maintenance and Operating Instructions

MANUAL GEAR ACTUATORS

POSITIONERS Series NP

VALV-POWR SERIES VPVL MODEL C DOUBLE-ACTING AND SPRING-RETURN RACK- AND-PINION COMPACT PNEUMATIC ACTUATORS

Reduced Bore Thread-end Ball Valves Series 33R Model C. 1/2 2 (DN 15-50) AAR No. E079024

Pneumatic Cylinder Actuators Series B1C Installation, Maintenance and Operating Instructions

VALVCON Universal ADC-Series Sealed Lead Acid Back-Up Battery Upgrade Kits. Installation, Maintenance and Operating Instructions

M1/M2 POCKET FEEDER. Compact design DESIGN FEATURES. Special ball and seat design. Large ball pocket capacity. Automatic cycling

MAPAG Butterfly valve - Type BK For cryogenic applications. Installation, Maintenance and Operating Instructions

Jamesbury High-Performance Actuators. Maximizing cycle life. Lowering Costs.

3, 4 & 6 (DN 80, 100 & 150) CLASS 150 & 300 STANDARD BORE SERIES 7150, 730S & 7300 FLANGED BALL VALVES EQUIPPED WITH KEROTEST HANDLE ASSEMBLIES

NELES POSITIONERS ELECTRO-PNEUMATIC SERIES NE700 PNEUMATIC SERIES NP700

VALV-POWR SERIES VPVL MODEL D DOUBLE-ACTING AND SPRING-RETURN RACK- AND-PINION COMPACT PNEUMATIC ACTUATORS

IMO-200EN 09/2010. Trunnion mounted forged ball valves Model FF and GG. Installation, Maintenance and Operating Instructions IMO-200EN 09/2010

REACTOR DISCHARGE VALVES S & DIGESTER BLOW VALVES SB & 5300SB B FLANGED BALL VALVES

SERIES CLASS 300 FULL-BORE REACTOR DISCHARGE VALVES. Installation, Maintenance and Operating Instructions

VALV-POWR VALUE-LINE DOUBLE-OPPOSED PISTON ACTUATORS MODEL A. Installation, Maintenance and Operating Instructions

Series 7000 & 9000 Ball Valves

Cryogenic Wafer-Sphere Butterfly Valves

Standard Bore Flanged Ball Valves Series 7150, 730S & , 4 & 6 (DN 80, 100 & 150) Class 150 & 300

Series VC Pneumatic cylinder actuators

3 AND 4 CLASS 300 STANDARD BORE SERIES 730S AND 7300 REACTOR DISCHARGE VALVES. Installation, Maintenance and Operating Instructions

HAND WHEEL OPERATOR For cylinder actuators Types B1C_K/L/R and B1C_RK/RL/RR Installation, Maintenance and Operating Instructions

NELES BO SERIES BUTTERFLY VALVE FOR RECOVERY OF OXYGEN IN VACUUM PRESSURE SWING ADSORPTION (VPSA) PLANTS

NELES RE2-SERIES V-PORT SEGMENT VALVE

JAMESBURY VALVCON ESR-SERIES ELECTRONIC SPRING RETURN ELECTRIC ACTUATOR

Railroad Ball Valves Series 5REB3

JT SERIES ANGLE STEM TANK BOTTOM BALL VALVE DN25 DN150. Installation, Maintenance and Operating Instructions

SERIES 2 4 (DN ) 6300, 2 6 (DN ) 6150, 6 (DN 150) 5300 & 530S, 6 & 8 (DN 150 & 200) 5150 BALL VALVES

ICV & ICVA Flanged Injection Control Valves 2 (DN 50) Type Installation, Maintenance and Operating Instructions

JAMESBURY EASYFLOW JT SERIES ANGLE STEM TANK BOTTOM VALVES

REACTOR DISCHARGE VALVES S AND WITH MD, QA AND QC CONVERSIONS AND ESSD STEM SEAL OPTION

SERIES 835 PROCESS-RATED CLASS 150 WAFER-SPHERE HIGH-PERFORMANCE BUTTERFLY VALVES

JAMESBURY VALVCON QX-SERIES ELECTRIC ACTUATOR

Control Valves Globe 3-way, Diverting & Mixing type Series GW Installation, Maintenance and Operating Instructions

NELES SOFT SEATED BALL VALVES, SEAT SUPPORTED, FULL AND REDUCED BORE, SERIES X

Ceramic Ball Valves. Series E2 and E6. Installation, Maintenance and Operating Instructions

Wafer-Sphere 14" 20" Butterfly Valve. Installation, Maintenance and Operating Instructions

3-Way Flanged Ball Valves Series AM150FD & AM150FB Model A 3 & 4 (DN80 & 100) Class 150. Installation, Maintenance and Operating Instructions

CAPPING VALVE. Series PZ Installation, Maintenance and Operating Instructions

Double Acting Cylinder Actuator Series VC Installation, Maintenance and Operating Instructions

3-Way Flanged Ball Valves 6, 8 & 10 (DN150, 200 & 250) Model D Series DM150FD 6 & 8 (DN150 & 200) Series DM150FB Model D

4" 9RET/REL FULL-PORT BOTTOM- OUTLET VALVES (AAR NO. E079011)

Valv-Powr VPVL Mod C Value-Line Double-Opposed Piston Actuators. Installation, Maintenance and Operating Instructions

PNEUMATIC CYLINDER ACTUATORS, SERIES B1

IMO - 528EN Issue Date: 1/11

ADVANCED AUTOMATION SYSTEM

Control Valves Globe 3-way, Diverting & Mixing type Series GW Installation, Maintenance and Operating Instructions

3-Way Flanged Ball Valves 12 (DN300) Series DM150FD Model A

1/4" 2" (DN 8 50) ELIMINATOR 2000 CWP AND ANSI CLASS 600 THREADED END BALL VALVE

ICV & ICVA Injection Control Valves Series 4000 Model C. Installation, Maintenance and Operating Instructions

3-Piece Ball Valves Series 4000 Model A

Polymerization High cycle valves

3-Way Flanged Ball Valves Series AM150FD & AM150FB Model A

PNEUMATIC CYLINDER ACTUATORS, SERIES B

Tank Car Fire-Tite Top-Loading and Unloading Valves

Delayed Coker Switch Ball Valve

VALUE-LINE 3-Piece Ball Valves Series 3A & 3C 1/2 2 (DN15-50) Installation, Maintenance and Operating Instructions

7 ND 70 en Rev Issue 1/99 VALVE CONTROLLER. Series ND800 INSTALLATION, MAINTENANCE AND OPERATING INSTRUCTIONS

NELES RA SERIES V-PORT SEGMENT VALVE

6D15 DIGESTER CAPPING VALVES

NELES R-SERIES SEGMENT VALVE Flanged RE and Wafer RE1

NELES TRUNNION MOUNTED BALL VALVE, FULL BORE Series XH Installation, Maintenance and Operating Instructions

CLINCHER 2-Piece Thread-end Ball Valves Series 2000

NELES RE-SERIES V-PORT SEGMENT VALVE

VALVCON V-Series ELECTRIC ACTUATORS 115 VAC AND 230 VAC. Installation, Maintenance and Operating Instructions

NELES HIGH CAPACITY TRIPLE ECCENTRIC DISC VALVE, METAL SEATED NELDISC SERIES L6

Wafer-Sphere Butterfly Valves

ADVANCED AUTOMATION SYSTEM. Installation, Maintenance and Operating Instructions

NELES METAL SEATED BALL VALVES, SEAT SUPPORTED, FULL AND REDUCED BORE, SERIES X

VALVCON V-Series. ELECTRIC ACTUATORS With Speed Control/Timer Board (Option J ) Installation, Maintenance and Operating Instructions

JAMESBURY ELECTRIC ACTUATORS VALVCON ADC-SERIES WITH OPTIONAL BATTERY BACK-UP POWER

V-port segment valves Series R1L Titanium Series R21L Titanium Series R2_S High consistency. Installation, Maintenance and Operating Instructions

Control Valves Globe-Omega, Multistage trim Series GM Installation, Maintenance and Operating Instructions

Limit Switch Type 4747

Spring Diaphragm Actuator Series VD Installation, Maintenance and Operating Instructions

Control Valves Globe-Unbalanced Single Seated, Series GU Installation, Maintenance and Operating Instructions

EMERGENCY SHUTOFF AND FIRESAFE VALVES FIGURE 1075

NELDISC Metal seated high performance triple eccentric disc valve Series L1 and L2 Installation, Maintenance and Operating Instructions

1/4" 2" (DN 8 50) A-STYLE MODEL D THREADED END 2000 CWP BALL VALVE

1/4 2 (DN 8 50) ELIMINATOR 2000 CWP AND ASME CLASS 600 THREADED END BALL VALVE

Wafer-Sphere Butterfly Valve Series 835W & 835L (DN )

1/4 2 (DN 8 50) CLINCHER SERIES 2000 THREADED-END BALL

METSO NELES HIGH PERFORMANCE TRIPLE ECCENTRIC DISC VALVE, METAL SEATED SERIES BW

K815W, K815L, K830W, K830L, K860W, & K860L Wafer-Sphere Butterfly Valve. Installation, Maintenance and Operating Instructions

VALVE CONTROLLER. SERIES ND800 Rev Installation, Maintenance and Operating Instructions 7 ND 70 en Issue 5/01

Series 7000 Railroad, Standard Bore Flanged Ball Valves

Accord DS/DM Series UltraSwitch Switch box

Versions. Version with K VS Version with K VS 2.0. Fig. 1: Type 3967 Solenoid Valve

7 ND 70 en Issue 12/99 VALVE CONTROLLER. Series ND800 Rev. 5.0 INSTALLATION, MAINTENANCE AND OPERATING INSTRUCTIONS

1/4" 2" (DN 8 50) ELIMINATOR 2000 CWP AND ANSI CLASS 600 THREADED END BALL VALVE

Solenoid Valves Type 3963

VALVCON V-Series ELECTRIC ACTUATORS 115 VAC AND 230 VAC With Iso/Readback Board Installed (Option U )

Installation, Maintenance and Operating Instructions

Wafer-Sphere Butterfly Valve Series K815W, K815L, K830W & K830L Model A Cryogenic

INTELLIGENT VALVE CONTROLLER ND7000H ND9000H, ND9000F, ND9000P Rev. 4.0 Installation, Maintenance and Operating Instructions

ECON Limit Switch Box Fig

Valve Position Monitors

Transcription:

Limit Switches Series NI700 Installation, Maintenance and Operating Instructions 7 NI 72 en 12/2008

2 7 NI 72 en Table of Contents 1 INTRODUCTION... 3 1.1 General description... 3 1.2 Markings... 3 1.3 Specifications... 3 1.4 Recycling and disposal... 3 1.5 Safety precautions... 4 2 INSTALLATION ON A METSO ACTUATOR.. 4 2.1 Installing limit switch NI700/S1 on Metso Automation actuators with VDI/VDE 3845 mounting face... 4 2.2 Installing the limit switch NI700/S2 on Metso Automation series B actuator... 5 2.3 Installing the limit switch (S2) and positioner NP700/NE700/S2... 5 2.4 Installation on other actuators... 6 2.5 Installing the limit switch N_I700/700 on the positioner... 6 3 ELECTRICAL CONNECTIONS... 6 4 ADJUSTMENT... 6 5 CIRCUITRY... 6 6 MAINTENANCE... 6 7 ORDERING SPARE PARTS... 6 8 DRAWINGS AND PARTS LISTS... 7 8.1 NI700, exploded view and parts list... 7 8.2 Mounting parts for B1C6-502 and B1J8-322 actuators (S1)... 8 8.3 Mounting parts for Quadra-Powr actuators (S1)... 9 8.4 Mounting parts for SP actuators (S1).. 10 8.5 Mounting parts for B1C6-20 and B1J8-20 actuators (S2)... 11 8.6 Mounting parts for B1C25-502 and B1J25-322 actuators (S2)... 12 9 CONNECTION DIAGRAMS... 13 9.1 Limit switch NI700/X, NPI700/700/X... 13 9.2 Limit switches NI7211, N_I700/7211 and NI7221, N_I700/7221... 14 9.3 Limit switch NI7254, N_I700/7254... 15 9.4 Limit switch NI7256, N_I700/7256... 16 10 TYPE CODE... 17 READ THESE INSTRUCTIONS FIRST! These instructions provide information about safe handling and operation of the limit switch. If you require additional assistance, please contact the manufacturer or manufacture s representative. Addresses and phone numbers are printed on the back cover. SAVE THESE INSTRUCTIONS! All brand or product names are trademarks or registered trademarks of their respective owners. Subject to change without notice.

7 NI 72 en 3 1 INTRODUCTION 1.1 General description The NI700 limit switch provided with inductive proximity switches is used for indication of the electrical position of valves and other devices. The cam discs activating the proximity switches are mounted on the shaft. The switching points of the proximity switches (1 or 2 pcs.) can be chosen freely. 1 or 2 proximity switches earth connection Fig. 1 PG 13,5 Position transmitter layout 1.2 Markings 1 or 2 cam discs knock-out for nut-mounted PG 9 collar The limit switch is provided with an identification plate sticker, see Fig. 2. Identification plate markings from top to bottom are: Complete type designation Type of switch Electrical values Enclosure class Temperature range Conduit entry (-L, -I or -NJ) Serial number A separate plate in older versions shows the conduit entry (-L, -I or -NJ). The type designation is described in Section 11. 1.3 Specifications Proximity switch: Inductive, diameter 8-14 mm / 0.31-0.55 in Sensing range 2 mm / 0.08 in Protection class IP67 P+F NJ2-12GK-N 01 P+F NJ2-12GM40-E2 11 P+F NJ2-12GM40-E 21 OMRON E2E-X3D1-N 54 ifm IFC2002-ARKG/UP 56 Other switch types on special order Electrical values: According to switch type Switch accuracy: < 1 Number of switches: 1 or 2 Approvals NI72../X ATEX II 2 G EEx ia IIC T6 Protection class of housing: IP65 (DIN 40050, IEC 529) / NEMA 4 and 4X Conduit entry: PG 13.5 and knockout for additional entry PG9 NPT 1/2 = CE1 (L) ISO M20x1.5 = CE2 (I) R 1/2 = CE3 (NJ) Ambient temperature: According to switch type or -25 - +51 C/-13 - +123 F for NI7201/X Weight: Approx. 0.6 kg / 1.1 lbs Materials: Body: aluminium alloy, epoxy coated Cover: polycarbonate Internal parts: stainless steel and plastic Sealing: nitrile and neopren rubber 1.4 Recycling and disposal Most limit switch parts can be recycled if sorted according to material. Most parts have material marking. A material list is supplied with the limit switch. In addition, separate recycling and disposal instructions are available from the manufacturer. A limit switch can also be returned to the manufacturer for recycling and disposal against a fee. Fig. 2 Identification plate (NI7211)

4 7 NI 72 en 1.5 Safety precautions CAUTION: Do not exceed the performance limitations! Exceeding the limitations marked on the position transmitter may cause damage to the transmitter and associated devices. Damage or personal injury may result. WARNING: Observe caution with the live parts of the position transmitter! The position transmitter and limit switches are fed with a voltage that, depending on the system, can be lethal. Do not touch any uncovered parts of the wires. Always detach the wires before dismantling the position transmitter. Ex i WARNING: Make sure that the complete installation and wiring is intrinsically safe before operating the device! Ex i WARNING: Electrostatic charge hazard! The pointer window is non-conductive. Clean with damp cloth only. Ex i WARNING: Spark hazard! Protect the aluminium housing from impacts. Ex i NOTE: The mounting must be in accordance with the installation guidelines IEC-EN 60079-10. 2 INSTALLATION ON A METSO ACTUATOR When the limit switch is ordered together with the valve, installation and adjustment are performed at the factory according to circuit diagrams in Chapter 10 or the customer's specifications. When the limit switch is ordered separately, the installation parts belonging to the particular entity must also be ordered. Ordering example: (B1CU)-Z-NI7211/S1 or (B1J12)-Z- NI7211/S2 or (B1J12-NP724/S2)-Z-NI7211/S2 The limit switch is equipped with both VDI/VDE 3845 (S1) mounting face and Metso (S2) mounting face. Both mounting faces require different shafts. S1: H coupling; S2: C coupling. The limit switch can be mounted on the actuator. If also the positioner is needed, use positioner/limit switch combination (e.g. NPI724/S1/7211). If limit switch NI700/S1 is mounted on an excisting actuator B_6-20 with bracket 4216200, make sure that the shaft and draught piece can rotate freely. Remove material from the bracket according to Fig. 3, if needed. Fig. 3 Installing NI700/S1 position transmitter on B series actuator (older version). 2.1 Installing limit switch NI700/S1 on Metso actuators with VDI/VDE 3845 mounting face 2.1.1 Installation steps 1. The actuator piston must be in the up position (in spring-return actuators as determined by the spring). 2. Install the pointer (only B_U) parallel with the valve closure member and fasten the draught piece (2) with a screw (29) to the pointer cover (B_U) or to the coupling (QP), as shown in Fig. 4. Secure the draught piece fastening screw with thread-locking compound (e.g. Loctite) and tighten it properly. 3. Fasten the mounting bracket (1) to the position transmitter. 4. Fasten the mounting bracket (1) to the actuator. The mechanical coupling (223) of the position transmitter must be positioned in the draught piece (2) as shown in Fig. 4. Fig. 4 draught piece (2) limit switch NI700/S1 screw (29) 225 bracket(1) Installing, S1 bracket 4216200 shaft/h-coupling screw draught piece pointer cover B1C/B1J/B1J actuator

7 NI 72 en 5 2.2 Installing the limit switch NI700/S2 on Metso series B actuator 2.2.1 Installation steps 1. Operate the actuator to place the piston in the up position (spring-return actuator as determined by the spring). 2. Install the pointer parallel with the valve closure member and fasten the draught piece (2) to the pointer cover with the coupling strap positioned as shown in Fig. 5. Secure the draught piece mounting screw with thread-locking compound (e.g. Loctite) and tighten it properly. 3. Fasten the mounting bracket (1) to the position transmitter. Note the washers (3)! 4. Fasten the mounting bracket (1) to the actuator. The mechanical coupling (223) of the position transmitter must be positioned in the draught piece (2) as shown in Fig. 5. Observe the difference in installing the transmitter on the B1C and B1J actuators as compared with the case of the B1JA actuator. Fig. 5 B1C or B1J actuator washers (3) hex screws (4) pointer cover Installing, S2 mounting bracket (1) limit switch coupling (223) draught piece (2) B1JA actuator 2.3 Installing the limit switch (S2) and positioner NP700/NE700/S2 Installation of a separate limit switch with a positioner is possible if both the limit switch and the positioner have S2 shaft. E.g. NP724/S2-Z-NI7211/S2. 2.3.1 Actuators B1C/B1J/B1JA6-20 1. The actuator piston must be in the up position (in springreturn actuators as determined by the spring). 2. Install the pointer parallel with the valve closure member and fasten the spline driver (2) to the pointer cover with the coupling strap positioned as shown in Fig. 5. Secure the spline driver fastening screw with a sealant (e.g. Loctite) and tighten it properly. 3. Fasten the bracket (5) to positioner NP700/NE700 with screw (7) and washer (6), see Section 9.5. 4. Fasten limit switch NI700 to the bracket (5), see Section 9.2. Fig. 6 Installing the rod (10) 5. Fasten the rod (10) with screws and bushings (12+11). Turn the bushing (11) onto the screw (12) so that the spacing inside the bushing is placed against the head of the screw, see Fig. 6. Apply the outer sphere of the bushing with Molykote BR2 vaseline (or the equivalent). 6. Tighten the lock nuts (26). 7. Fasten the assembly to the actuator. The mechanical coupling of the positioner must be placed into the spline driver (2) as shown in Fig. 5. 8. Complete the piping of the positioner according to its installation, operating and maintenance instructions. For installation instructions of the positioner/limit switch combinations see positioners' manuals (7 NP 72 / 7 NE 72). 2.3.2 Actuators B1C/B1J/B1JA25-502 1. The actuator piston must be in the up position (in spring-return actuators as determined by the spring). 2. Install the pointer parallel with the valve closure member and fasten the spline driver (2) to the pointer cover with the coupling strap positioned as shown in Fig. 5. Secure the spline driver mounting screw with a sealant (e.g. Loctite) and tighten it properly. 3. Fasten positioner NP700/NE700 and limit switch NI700 to the mounting bracket (1), see Section 9.6. 4. Fasten the rod (10) with screws and bushings (12+11). Turn the bushing (11) onto the screw (12) so that the spacing inside the bushing is placed against the head of the screw, see Fig. 4. Apply the outer sphere of the bushing with Molykote BR2 vaseline (or the equivalent). 5. Tighten the lock nuts (26). 6. Fasten the assembly to the actuator. The mechanical coupling of the positioner must be placed into the spline driver (2) as shown in Fig. 3. 7. Complete the piping of the positioner according to its installation, operating and maintenance instructions.

6 7 NI 72 en 2.4 Installation on other actuators 1. Operate the actuator so that the valve closes. Also turn the limit switch shaft to activate the closed limit proximity switch (the lower one). 2. Fasten the coupling (2) between the limit switch and the actuator to the actuator (or to limit switch shaft). 3. Fasten the mounting bracket (1) to the limit switch. 4. Fasten the mounting bracket (1) with the limit switch to the actuator so that the mechanical coupling (223) of the limit switch (or the shaft end) is inserted in the slot of the coupling (2). Observe what was said about the position of the limit switch shaft in step 1 above! 2.5 Installing the limit switch N_I700/700 on the positioner The bottom of the limit switch acts also as the cover for the positioner. See drawings in chapter 9. It is possible to mount a limit switch on an existing positioner, however, the shaft and locking wheel of the positioner must be changed. It is recommended to order a pre-assembled combination. The positioner should be adjusted before the mounting of the limit switch. 1. Operate the actuator until the valve is in the closed or open position. 2. Note the position of the actuator and valve when mounting the limit switch on the actuator. Make sure that the shaft (215) is in the right position: the lower switch is activated at the closed limit and the upper switch at the open limit. 3. Place the limit switch on the positioner so that the shafts are correctly engaged. 4. Fasten the screws (258). 5. Check the adjustant of the limit switch. See chapter 4 for details. Remove the limit switch before the adjustment of the positioner. Loosen the screws (258). Note the position of the shaft relative to the positioner when removing the limit switch. Check the adjustment of the limit switch always after remounting. cam disc to adjust the point where the switch is activated 5-6 before limit. Use the LED indicator or a separate measuring instrument as on aid. After re-installation of the actuator, first adjust its mechanical limits according to the valve, then the possible positioner according to separate instructions, and finally the limit switch. Adjustment completed, turn the pointer (210) to make the yellow line parallel with the valve closure member. 5 CIRCUITRY The internal circuitry of the limit switch is shown in the circuit diagrams of Chapter 10. The connection diagrams are also supplied with the limit switch 6 MAINTENANCE Regular maintenance of the limit switch is not necessary. 7 ORDERING SPARE PARTS NOTE: Always use original spare parts to make sure that the position transmitter functions as intended. When ordering spare parts, always include the following information: type code, sales order number, serial number number of the parts list, part number, name of the part and quantity required This information can be found from the identification plate or documents. 3 ELECTRICAL CONNECTIONS Before connecting the power, make sure that the electric specification and the wiring meet the installation conditions. Also observe the function of the proximity switch (make or break when the active face is covered. See also the information on the identification plate. 4 ADJUSTMENT The pointer (210) need not be removed for adjustment. When the limit switch is ordered together with the valve and the actuator, the proximity switches are adjusted at the factory. The limits are adjusted by changing the position of the cam discs (221) on the shaft. Depending on the type, the proximity switch is activated when the active face is either covered or free. With the actuator in the open or closed position, turn the

7 NI 72 en 7 8 DRAWINGS AND PARTS LISTS 8.1 NI700, exploded view and parts list Item Qty Description Recommended spare 201 1 Housing 202 1 Earth connection 203 1 Cover, assy 205 1 Equi potential bonding 206 2 Screw 209 8 Terminal 210 1 Pointer 211 2 (1) Screw 212 1 O-ring X 213 2 Washer 214 1 (2) Lock ring X 215 1 Shaft, assy 216 2 (1) Inductive proximity sensor 217 1 Washer 218 1 Screw 219 2 Screw 220 1 Fastening plate 221 2 (1) Cam disc 223 1 Coupling 225 1 Adapter Item Qty Description Recommended spare 226 1 Seal 227 1 Grub screw 229 2 End stop 241 1 Appliance connector 242 1 Gasket 243 1 Appliance socket 247 1 Wire 248 1 Wire 249 1 Wire 250 1 Wire 251 1 Wire 252 2 (1) Bushing 254 1 ID plate 256 1 Additional plate 257 1 Screw 258 3 Screw 265 4 (3) Screw 266 1 Seal X 268 1 Support (with one switch only) 226 1 Seal

8 7 NI 72 en 8.2 Mounting parts for B1C6-502 and B1J8-322 actuators (S1) Item Qty Description 1 1 Mounting bracket 2 1 Draught piece 3 4 Washer 4 4 Screw 28 1 Screw 29 2 Screw 36 1 Coupling jacket

7 NI 72 en 9 8.3 Mounting parts for Quadra-Powr actuators (S1) Drive: male Item Qty Description 1 1 Mounting bracket 2 2 Coupling half 3 1 Adapter 4 4 Screw 5 4 Hex nut 6 1 Screw 7 4 Screw 8 4 Washer 9 4 Screw 10 4 Washer Drive: female spline Item Qty Description 1 1 Mounting bracket 2 1 Ear 4 4 Screw 28 4 Screw 29 1 Screw 30 (4) Screw 35 1 Coupling 36 1 Coupling jacket

10 7 NI 72 en 8.4 Mounting parts for SP actuators (S1) Item Qty Description 1 1 Mounting bracket 2 2 Coupling half 3 1 Adapter 4 4 Screw 5 4 Hex nut 6 1 Screw 7 4 Screw 8 4 Washer 9 4 Screw 10 4 Washer

7 NI 72 en 11 8.5 Mounting parts for B1C6-20 and B1J8-20 actuators (S2) Item Qty Description 1 1 Mounting bracket 2 1 Draught piece 3 2 Washer 4 2 Screw 5 1 Bracket 6 1 Washer 7 1 Screw 8 2 Washer 10 1 Rod 11 2 Bushing 12 2 Screw 13 2 Stud (B1C6 only) 14 2 Hexagon nut (B1C6 only) 26 2 Locking nut 27 2 Washer 28 2 Screw

12 7 NI 72 en 8.6 Mounting parts for B1C25-502 and B1J25-322 actuators (S2) Item Qty Description 1 1 Mounting bracket 2 1 Draught piece 3 2 (4) Washer 4 2 (4) Screw 8 2 Washer 9 2 Screw 10 1 Rod 11 2 Bushing 12 2 Screw 26 2 Locking nut 27 2 Washer 28 2 Screw

7 NI 72 en 13 9 CONNECTION DIAGRAMS 9.1 Limit switch NI700/X, NPI700/700/X OPEN A - + BLUE BROWN 1 3 TERMINAL Phoenix MBK BU CLOSED K - BLUE + BROWN 4 6 FACTORY ADJUSTMENT: Active faces of proximity switches are covered when actuator is in intermediate position. Active face A (upper switch) becomes free at open limit of travel and face K (lower switch) at closed limit. Function can be inverted on site by re-adjusting the cam discs. Sensing distance 2...4 mm, depending on type of switch Supply voltage 8 V DC (Ri 1 kω) Current consumption active face free, > 3 ma active face covered, < 1 ma PROXIMITY SWITCH Intrinsically safe II 2 G EEx ia IIC T6. According to CENELEC EN50014 and EN50020. Voltage (Ui), current (Ii), power (Pi), inductance (Li) and capacitance (Ci) according to certificate of switch, table 1. Table 1. Type of proximity switch Electrical values Ui Ii Pi Li Ci (V) (ma) (mw) (µh) (nf) Ambient temperature Certificate of proximity switch 01 P+F NJ2-12GK-N 16 52 169 50 45-25 C... +51 C PTB 00 ATEX 2048 X 02 P+F NJ2-12GK-SN 16 52 169 150 50-40 C... +51 C PTB 00 ATEX 2049 X 03 P+F NJ2-11-N-G 16 52 169 50 30-25 C... +62 C PTB 00 ATEX 2048 X 04 P+F NJ2-11-SN-G 16 52 169 150 50-40 C... +62 C PTB 00 ATEX 2049 X 07 P+F NJ2-12GM-N 16 52 169 50 30-25 C... +62 C PTB 00 ATEX 2048 X 09 P+F NCB2-12GM35-N0 16 52 169 100 90-25 C... +62 C PTB 00 ATEX 2048 X

14 7 NI 72 en 9.2 Limit switches NI7211, N_I700/7211 and NI7221, N_I700/7221 A = OPEN K = CLOSED A BLUE BROWN 1 2 3 A BLUE BROWN 1 2 3 K BLUE BROWN 4 5 6 K BLUE BROWN 4 5 6 NI7211 NI7221 FACTORY ADJUSTMENT: Active faces of proximity switches are free when actuator is in intermediate position. Active face A (upper switch) becomes covered at open limit of travel and face K (lower switch) at closed limit. Function can be inverted on site by re-adjusting the cam discs. PROXIMITY SWITCH Pepperl+Fuchs NJ2-12GM40-E2, PNP (11) Pepperl+Fuchs NJ2-12GM40-E, NPN (21) Sensing range 2 mm / 0.08 in Rated voltage U = 10-60 V DC Output current 200 ma active face covered, LED on Quiescent current 15 ma active face free Ambient temperature -25 - +70 C / -13 - +158 F

7 NI 72 en 15 9.3 Limit switch NI7254, N_I700/7254 A = OPEN K = CLOSED BK (BU) 1 BK (BU) 1 A WH (BN) 3 A WH (BN) 3 1 BK (BU) 4 3 K WH (BN) NI7254 6 K BK (BU) WH (BN) 4 6 2 NI7254/P FACTORY ADJUSTMENT: Active faces of proximity switches are free when actuator is in intermediate position. Active face A (upper switch) becomes covered at open limit of travel and face K (lower switch) at closed limit. Function can be inverted on site by re-adjusting the cam discs. PROXIMITY SWITCH OMRON E2E-X3D1-N (E2E-X3D1-G) Sensing range 3 mm / 0.12 in Rated voltage U = 12-24 V DC Output current 3-100 ma active face covered, LED on Quiescent current 0.8 ma active face free Ambient temperature -25 - +70 C / -13 - +158 F

16 7 NI 72 en 9.4 Limit switch NI7256, N_I700/7256 A = OPEN K = CLOSED 1 - A 3 DC + 4 - K 6 DC NI7256 + 1 A 3 1 3 K 4 6 2 NI7256/P FACTORY ADJUSTMENT: Active faces of proximity switches are free when actuator is in intermediate position. Active face A (upper switch) becomes covered at open limit of travel and face K (lower switch) at closed limit. Function can be inverted on site by re-adjusting the cam discs. Connection: load can be connected to + or -. PROXIMITY SWITCH Ifm electronic IFC2002-ARKG/UP Sensing range 2 mm / 0.08 in Rated voltage U = 10-36 V DC Output current 150 ma active face covered, LED on Quiescent current 0.6 ma active face free Ambient temperature -25 - +80 C / -13 - +176 F

7 NI 72 en 17 10 TYPE CODE LIMIT SWITCH, Series NI700 1. 2. 3. 4. 5. 6. NI 7 1 11 A / S1 CE04 1. PRODUCT GROUP NI Limit switch with inductive proximity switches 2. SERIES CODE 3. QTY OF SWITCHES 1 1 pc. 2 2 pcs. 4. SWITCH TYPE P+F; NJ2-12GK-N DC; >3 ma; <1 ma; Intrinsically safe 01 acc. to EEx ia IIC T6, 2-wire type. Temperature range -25 - +51 C / -13 F to +123 F. P+F; NJ2-12GM40-E2 DC; 200 ma; quiescent current <15 ma; PNP, 11 3-wire type. Temperature range -25 C to +70 C / -13 F to +158 F. P+F; NJ2-12GM40-E DC; 200 ma; quiescent current <15 ma; NPN, 21 3-wire type. Temperature range -25 C to +70 C / -13 F to +158 F. OMRON E2E-X3D1-N DC; 100 ma; quiescent current <0,8 ma, 54 2-wire type.temperature range -25 C to +70 C / -13 F to +158 F. IFM ELECTRONIC IFC2002-ARKG/UP DC; 150 ma; quiescent current <0.6 ma; 2-wire type. 56 Temperature range -25 C to +80 C / -13 F to +176 F. 5. ACTION (with 1 switch only) A Switch for open limit K Switch for closed limit 8. OPTIONS Standard, IP 65 enclosure, PG 13.5 conduit entry, without sign. Temperature range according to switch type. Intrinsically safe construction, VTT ATEX II 2 G EEx ia IIC T6 certification X (EN 50014, EN 50020). Temperature range -25 C to +51 C / -13 F to +123 F. Limit switch with attachment face according to S1 standard VDI/VDE 3845. Not applicable to globe valve actuators. Limit switch with attachment face according to S2 Metso Connection plug acc. to DIN 43650A and ISO 4400, P with 2-wire types only. Y Special CE04 CE05 CE06 CONDUIT ENTRY NIPPLES 1/2 NPT conduit entry nipples PG13.5 / 1/2 NPT M20x1.5 conduit entry nipples PG13.5 / M20x1.5 R1/2 (PF1/2) conduit entry nipples PG13.5 / R1/2

18 7 NI 72 en

7 NI 72 en 19

20 7 NI 72 en Metso Automation Inc. Europe, Levytie 6, P.O. Box 310, 00811 Helsinki, Finland. Tel. +358 20 483 150. Fax +358 20 483 151 North America, 44 Bowditch Drive, P.O. Box 8044, Shrewsbury, MA 01545, USA. Tel. +1 508 852 0200. Fax +1 508 852 8172 Latin America, Av. Independéncia, 2500-Iporanga, 18087-101, Sorocaba-São Paulo, Brazil. Tel. +55 15 3235 9700. Fax +55 15 3235 9748/49 Asia Pacific, 238A Thomson Road, #25-09 Novena Square Tower A, 307684 Singapore. Tel. +65 6511 1011. Fax +65 6250 0830 China, 19/F, the Exchange Beijing, No. 118, Jianguo Lu Yi, Chaoyang Dist, 100022 Beijing, China. Tel. +86-10-6566-6600. Fax +86-10-6566-2575 Middle East, Roundabout 8, Unit AB-07, P.O. Box 17175, Jebel Ali Freezone, Dubai, United Arab Emirates. Tel. +971 4 883 6974. Fax +971 4 883 6836 www.metso.com/automation