HBLT-C1 Controller. Instruction Manual. For pump control of levels in industrial refrigeration systems

Similar documents
HBLT-Wire LEVEL SENSOR For analogue measurements of NH3 and HFC in refrigeration systems

WE INCREASE UPTIME AND EFFICIENCY IN THE REFRIGERATION INDUSTRY

HBSC2 CO 2 switch. Instruction manual. For detecting liquid CO 2 in refrigeration systems

HBSO1 Oil switch. Instruction manual. For detecting oil in refrigeration systems WE INCREASE UPTIME AND EFFICIENCY IN THE REFRIGERATION INDUSTRY

HBOC - OIL MANAGEMENT

Table of Contents 1. OVERVIEW OPERATION FUNCTION SPECIFICATIONS INSTRUMENT LAYOUT INSTALLATION...

ST48-WHUV.102. Wiring diagram. Product description. PID controller. Order number

ECONOMISER SERIES E2T USER MANUAL

B-RAD Select USER MANUAL TABLE OF CONTENTS

OPERATING MANUAL Digital Diesel Control Remote control panel for WhisperPower generator sets

ST Wiring diagram. Product description. Temperature controller. Order number

HGM1780. Automatic Genset Controller USER MANUAL. Smartgen Technology

DIGITAL BATTERY TORQUE WRENCH (BC-RAD SELECT) USER GUIDE

2-PHASE STEPPING MOTOR DRIVER FE Z5 DISPENSE

SI AT A22. English. Printed: Doc-Nr: PUB / / 000 / 01

SI AT A22. English. Printed: Doc-Nr: PUB / / 000 / 03

HD UNIT INSTALLATION & SERVICE BOOKLET 3-7

GRUNDFOS INSTRUCTIONS. Control HVAC. Installation and operating instructions. Other languages. net.grundfos.com/qr/i/

Signet Pressure Transmitter

USER MANUAL. Blazer Vista 1000/1400/2000. Uninterruptible Power System

Cannondale Diagnostic Tool Manual

Figure 1: WPR2 Dimensions and Hardware

SIGNET Temperature Transmitter

HERZ Motorised Actuator

βeta 20A AUTO 12V/24V SOLAR CHARGE CONTROLLER WITH REMOTE METER

Pressure chlorine changeover unit C 7520

Signet Temperature Transmitter

Fuel Level FL1. FL1 - User s manual. Rev Revision#2.0, 28/11/2014 For firmware version 1.2

MATRIX LLC LEVEL CONTROL PANEL

The Traveler Series: Wanderer

Digital Diesel Control Remote control panel for GENVERTER GV4 and GV7i

BIM-17-2 Bus Interface Module for compass and outside temperature

Uninterruptible Power System

USER MANUAL MPS 1-5KW SERIES

Operating Instructions for Pressure Transmitter with Digital Display. Model: PDA

CLA-VAL e-drive-34. User Manual. Motorised Pilots. CLA-VAL Europe LIN072UE - 04/16

PCT-3001 plus. Display LCD

CX-SERIES ADVANCED BATTERY CHARGER

Cat. No. I526-E1-1 USER S MANUAL 3G3IV-PLKEB2 /4. Braking Resistor Units 3G3IV-PCDBR2 B/4 B. Braking Units

GENERAL INFORMATION. H-1649, H-1650, H-1651 H-1653, H-1654 Easy-Count. uline.com. that may hurt accuracy:

Valor 1000W Series Instruction Manual. Serie Valor 1000W Manual de Instrucciones. Série Valor 1000W Guide de I utilisateur

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

The Traveler Series: Wanderer

User Manual. Solar Charge Controller 3KW

FieldView External Charger. User Guide

CURTIS TOLEDO. AF Series Compressors VS models with VFD WARNING

Compact Scales. Software Revision V1.25 & above

USERS MANUAL MCD REMOTE OPERATOR

HGM1770 Automatic Generator Control Module OPERATING MANUAL Smartgen Electronic

Service instructions. MAGNA Series 2000

Technical Instructions. SQV Series Electromotive Valve Actuators. Document No

PCT-3000 plus DIGITAL PRESSURE CONTROLLER FOR COOLING PLANTS

Signet Pressure Transmitter

MULTI FUNCTIONAL COUNT CHECKER MODEL Poka Patrol CNA-4mk3

HERZ Electronic room thermostat analog and digital

FLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER

HGM1780 AUTOMATIC GENERATOR MODULE CONTENT 1. SUMMARY PERFORMANCE AND CHARACTERISTICS SPECIFICATION OPERATION...

STRA-24 for chilled beams

Flowmeter Ultrasonic Flow Metering / Dosing Device. Operating Manual

Installation Guide Smart-UPS On-Line SRT1000/1500 UXI-NCLI, SRT1000/1500 UXI-LI, Tower/Rack-Mount

Installation Guide Smart-UPS On-Line SRT1000/SRT1500 XLA Tower/Rack-Mount

Operating Instructions. Pneumatic Control Valve Low Temperature. Type Series GS3

Eclipse Solar Suitcase

User Manual Solar Charge Controller 3KW

TYPE 5867 PORTABLE Q METER

Users Manual. Defender 1 8.0KW to 14.0KW Online Emergency Lighting Inverter. Technical Manual # Revision B

Smart 110 with built-in flashlight for 6 240Ah lead-acid batteries

Operating instructions Flow monitor SI / / 2014

USER S MANUAL G SERIES USER S MANUAL. Ref.49-MG000EN08

Operating instructions Flow monitors SI6600 SI6700 SI /02 01/2011

AS4V DC ALARM BEFORE USE... CAUTION WARNING INSTRUCTION MANUAL AS4V MODEL. (dual or quad alarm trip; field-configurable)

Operating instructions Flow monitors SI5000 SI / / 2007

8000mAh Jump Starter User Manual

27.6 Vdc 1 Amp Switch Mode Power Supply for Fire EN54-4:1997 +A1 +A2

SWA-2441/2451 PID TEMPERATURE CONTROLLER INSTRUCTION MANUAL

PRESSURE GOVERNOR, ENGINE MONITORING, AND MASTER PRESSURE DISPLAY MODEL DDA100

Operation Manual. Temperature Controller ST49. Revision 1.1, dated on

User Manual Digital Energy Uninterruptible Power Supply ML Series UPS VA GE Digital Energy Power Quality

Digital Pressure Regulator Sentronic PLUS Series 614

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

MB A 12V/24V DC PROGRAMMABLE DUAL BATTERY ISOLATOR

Operating instructions Platform/floor scales

Operating Instructions. Angle Seat Control Valve. Type 7020

User manual Temperature Calibrator JOFRA CTC-140/320/650 A/B JOFRA CTC-1200 A Copyright 2005 AMETEK DENMARK A/S ( UK)

SERVICE MANUAL (DOMESTIC & INTERNATIONAL)

OCS-T High Resolution Digital Crane Scale

Users Manual. Cobra Plus Stand-By Emergency Lighting Inverter. Technical Manual # Revision B

Advanced Hybrid Wind / Solar Charge Controller. User Manual

PowerView PV380-R2 Mechanical Configuration

Combined Ventilation Controller RVWS-T-224HA

WATERFLUX 3070 Quick Start

PANcharge1k Battery Charger User's Manual

KCR1. Kiln Controller Handbook. Kilncare Ltd. The Kiln Works 907 Leek New Road Baddeley Green Stoke-on-Trent Staffordshire, ST2 7HQ United Kingdom

MAGPOWR Spyder-Plus-S1 Tension Control

BM kv Digital Insulation Tester USER MANUAL

BSPDDRIVE ITT. Goulds Pumps. Aquavar SPD (Single Pump Drive) Simplex Variable Speed Pump Controller

SWA-24X2C PID Temperature Controller with Timer (SWA-2442C/2452C)

PRESSURE GOVERNOR, ENGINE MONITORING, AND MASTER PRESSURE DISPLAY MODEL: TCA100

Positive displacement batch controller

User Manual. Digital Energy Uninterruptible Power Supply ML Series UPS VA. GE Digital Energy Power Quality. GE imagination at work

Transcription:

Instruction Manual HBLT-C1 Controller For pump control of levels in industrial refrigeration systems Instruction manual HBLT-C1 Controller (006-UK) 1 / 14

Table of Contents Safety Instructions... 3 Introduction... 4 Design... 4 Software... 4 Technical Data... 5 Design and Functions... 6 Installation Instructions... 7 Electrical Connection... 7 Fitting Instructions... 8 LED Indication... 8 CON Mode:... 11 Alarm Mode:... 11 Calibration:... 12 Error Detection... 13 Repairing the Controller:... 13 Further Information... 14 Instruction manual HBLT-C1 Controller (006-UK) 2 / 14

Safety Instructions CAUTION! Always read the instruction manual before commencing work! Heed all warnings. Installation and use of the controller may only be carried out by adequately qualified individuals. The operator must be aware of the consequences of setting up the controller incorrectly. Factory settings do not guarantee safe operation, since the configuration parameters depend on the type of system. If changes are made to type-approved equipment, this type approval becomes void. The equipment s inputs and outputs as well as its accessories may only be connected as shown in this guide. HB Products assumes no responsibility for damages that result from failing to abide by the above. Explanation of symbols: In this instruction manual, the following symbol is used to indicate important safety instructions to the user. The symbol will always appear when the information is necessary. The safety instructions, and particularly the warnings, must always be read and adhered to. CAUTION! Refers to threats to system components or a possible limitation of functionality. NOTE! Contains important further information about the product, and provides additional tips. It is found in instructional documents describing the correct execution of a certain action. In this context, the head of operations is urged to abide by all the mandatory regulations, so as to avoid accidents and do everything possible to prevent damage to people and materials in the situation in question. Intended use and terms of use: HBLT-C1 level controller is designed to continuously measure and regulate refrigerants in industrial refrigeration systems. If you want to use HBLT-C1 for a different purpose, and if you evaluate that it will not be able to function without problems in this capacity, then prior permission must be obtained from the manufacturer. Prevention of collateral damage: Make sure that faults are assessed and relevant precautions are formulated by qualified personnel. In this way, you will prevent collateral damage from the HBLT-C1, which would result in damages to persons and materials. Environmentally-correct behaviour and disposal instructions: HBLT-C1 is also built according to environmentally-correct behaviour. The modules can easily be disassembled to allow sorting, and are sent for recycling after sorting. Instruction manual HBLT-C1 Controller (006-UK) 3 / 14

Introduction HBLT-C1 is designed for level control in vessels in industrial refrigeration systems. It can be used in connection with the HBLT-A1 analogue level sensor or other similar sensors with a 4-20 ma output signal. Design The controller can be configured for the variations in application that occur in industrial refrigeration systems. Set-up is carried out using a simple menu system with buttons on the front. The measured value can also be read from a 3-figure display on the front of the component. LED lamps indicate low, high, and pump status. Valve feedback will be visualised with 5 led and 3-digit display. Software The controller is supplied with a microprocessor-based design. It is always delivered with the newest software. We continuously develop our products and so there may be changes in the software. The controller cannot be updated after delivery. The controller is designed with a simple menu structure that does not allow for resetting to factory settings. The actual software version can be viewed in the display by pushing on [UP] and [DOWN] at same time. The HBLT-C1 controller connected to sensor type HBLT-A1 as well as a modulating motor valve (Ill. MVS661). Instruction manual HBLT-C1 Controller (006-UK) 4 / 14

Technical Data HBLT-C1 HBLT-C1-ENC Supply: Voltage 24 V AC/DC ± 10 % 100..240 V AC Frquency 50/60 Hz 50/60 Hz Current draw Max 40 ma Max 1.5 A Connection Screw terminal Screw terminal Wire size < 2,5 mm² < 2,5 mm² Installation conditions : Surrounding temperature -20 +70 C -20 +70 C Protection class IP45 IP65 Relative humidity 20 80 % 20 80 % Approvals: EMC Emission EN61000-3-2 EN61000-3-2 EMC Immunity EN6100-4-2 EN6100-4-2 GOST R No 0903044 Mechanical specifications: Mounting In front of panel On wall External measurement 96x96x94 mm (BxHxD) 298x198x182 mm (BxHxD) Cut-out measurement 92,8x92,8 mm N.A. Material Plastic Plastic Weight 0.2 kg 1.4 kg Display: Digit s display 3 digits, red 3 digits, red Alarm indication LED (green og red) LED (green og red) Programming From front From front Updatting 1 time each second 1 time each second Valve position indication 5 x LED 5 x LED Input: Analogue input - sensor 4-20 ma 4-20 ma Analogue input valve feedback 4-20 ma 4-20 ma Alarm max level Relay 5 25 V DC Relay 5 25 V DC Output: Analogue output 4-20 ma 4-20 ma Load 3A/24 VDC 3A/24 VDC Relay output @24VAC/VDC: 3 x 3A @24VAC/VDC: 3 x 3A @110 VAC: 3 x 5A @110 VAC: 3 x 5A @220 VAC: 3 x 5A @220 VAC: 3 x 5A Solid state output NC/NO-1A-24VAC/VDC NC/NO-1A-24VAC/VDC NOTE! All terminals are protected against wrong termination up to a supply voltage of 40V. If the supply voltage is greater than 40V, the electronics will be damaged. NOTE! Avoid direct sunlight, heavy dust, or heat. Do not expose the instrument to rain or strong humidity from ammonia vapour or other corrosive refrigerants. Instruction manual HBLT-C1 Controller (006-DK) 5 / 14

Design and Functions HBLT-C1 is designed for measuring/regulating refrigerant levels in: Pump vessels Separators Inter coolers Economisers Condensators Receivers Pump separator installed with an HBLT- A1 analogue sensor for continuous level control of the vessel. The sensor is connected to the HBLT-C1 controller, which on the basis of current levels controls the modulating valve so that a constant level is maintained. The tank's/container's level is displayed based on the measured analogue value. Based on PI regulation, the controller can control the pump or the valve, and hence the rate at which the system is filled. HBLT-C1 supports all pumps and valves indicated in the technical data. The controller has the following functions: Level control Alarm indication P-regulation High or low pressure regulation Pump start/stop Valve feedback Instruction manual HBLT-C1 Controller (006-UK) 6 / 14

Installation Instructions The following applies to the design of the panel: 1) It must be installed on the front of the panel. The front is designed with protection class IP54. Rear facing electronics are designed in protection class IP45. 2) The instrument is placed at eye-level to make set-up and reading as easy as possible. Be careful with sunlight from windows as it can affect the reading on the display. 3) It is installed with a standard cable without insulation. If EMC from other sources of noise is greater than described in EN 6100-6-2, an insulated cable must be used. Electrical Connection Terminal Power IN 24 V AC/DC Sensor input Alarm IN PC GND/INT ma feedb. Low level alarm out High level alarm out Pump Control out Solid state relay Power IN 100 240 VAC Description Supply voltage to the controller Input from the sensor, e.g. HBLT-A1 Alarm in (5..24 VDC) can be used for extra high level alarm (GND from Power IN). PC (no function) ma feedback (positioning of valve. GND is connected to Control out ) Low level alarm in the vessel High level alarm in the vessel Signal to start the pump 4-20 ma analogue signal to the modulating valve or pump Solid state relay AKVA valve (AC/DC) Supply voltage with power supply built in Instruction manual HBLT-C1 Controller (006-UK) 7 / 14

Fitting Instructions HBLT-C1 is fitted on the front of the panel. A 92.8 x 92.8 mm hole must be cut. The module is fitted in a panel cut-out on the front of the panel. Mounting brackets (2 units) are placed on the side of the module, and the module is secured with the 2 screws. LED Indication The buttons have the following functions: [CON] : Provides access to the control parameters: Setpoint, P-band, ramp function, LP/HP mode, AKVA periodic time as well as valve position [ALARM] : Provides access to alarm level: low level, high level, as well as pump level and hysteresis [CAL] : Provides access to minimum and maximum calibration [TEST] : Starts the test mode, where all parameters are tested [ROTATE] : Used to switch between the alarm parameters. : Confirms/saves data and also functions as return/forward to the next function. [ ] : Changes the parameters in a positive direction with +1 for each click, or through its scroll function by holding the button down. [ ] : Changes parameters in a negative direction with -1 with each click, or through its scroll function by holding the button down. [Mode] : Change from operational mode to displaying of valve position in 3-digit display [Mode] : Possibility to set up manual operation of analogue output 4 20 ma (0 100%) Push the button in 10 sec. Led is flashing with a frequency of 2 Hz when the manual operation is activated. [Valve] : Displaying the valve position with 20% intervals. The LED lamps have the following functions: RUN [green LED]: Indicates when the controller is in operation ALARM LOW [red LED]: Indicates a low level ALARM HIGH [red LED]: Indicates a high level PUMP [green LED]: Indicates pump function VALVE [5 x yellow ]: Indicates valve position Instruction manual HBLT-C1 Controller (006-UK) 8 / 14

Menu flow chart: IDLE 040 [CON] [ALARM] [CAL] Press in 5 sec [MODE] Press in 10 sec [TEST] SET 040 LOW L10 LOW L10 MIN 000 MAX 000 [Rotate] + MANUEL 000 P-band P30 HYS L05 LP/HP LP Ramp 005 HIGH H85 HYS H05 HIGH H85 Valve 005 PUMP P30 PUMP P30 AKVA 006 HYS P05 IDLE 040 Instruction manual HBLT-C1 Controller (006-UK) 9 / 14

Test procedure: 100 High level hysterese Setpoint + Pband/2 Setpoint Setpoint - Pump setpoint Pband/2 setpointsterese Pump hysterese High level setpoint Low level hysterese Low level setpoint 0 The frequency speed is 1 % each sec in test mode 3-digit display: Displays setpoint, programming parameters, as well as information to help navigate the display. Display Parameter Units Min Max Factory settings Operational parameters Current liquid level in the 3 figure display % 0 100 0 The valve s position with 5 LEDs LEDs 0 5 0 Control parameters Setpoint % 0 100 040 P-band % 0 200 P30 LP/HP mode LP HP LP Ramp function start up %/sec 0 100 005 Valve reaction damping opening/close %/sec 0.1 100 005 Period time pulse valve sec 3 10 6 Alarm parameters Low level Lxx % 0 100 10 High level Hxx % 0 100 85 Pump level Pxx % 0 100 15 Instruction manual HBLT-C1 Controller (006-UK) 10 / 14

CON Mode: The desired Setpoint and P-band can be set in CON-mode. Both are set as a percentage (0-100%). The sum of the Setpoint and the P-band may not exceed 100%. If the Setpoint and P-band is set so it causing that the valve e.g. close at 120% (Setpoint = 80 % & P-band at 100 %), the valve will close at 100 % of security reasons. Ramp function: Since there can be great fluctuations in the process parameters during process start-up, it is possible to establish a ramp function (at start-up only). When it is set to 0, the function is inactive. Valve damping: Depending which valve is installed, it may be necessary to dampen the speed at which the valve opens. This is used especially when the valve reacts too quickly/strongly. When it is set to 0, the function is inactive. If using an oversized valve for the system, a stable control is achieved by increasing the proportional band. It should be noted, however, that by having a large proportional band will have a level offset from the setpoint in controllen. Most often this will offset level does not mean anything in a plant, but if you want to achieve a lower set point with an oversized valve, you can set the desired setpoint in the controller slightly lower than the actual desired setpoint. Alarm Mode: By pushing ALARM mode one gains access to setting up the following alarms, with corresponding hysteresis: LOW = low level (Lxx) Hysteresis LOW HIGH = high level (Hxx) Instruction manual HBLT-C1 Controller (006-UK) 11 / 14

Hysteresis HIGH PUMP= pump level (Pxx) Hysteresis PUMP is used to move forward in the menu from LOW to Hysteresis PUMP. [ROTATE] is used to switch between alarm setpoints. You can leave alarm mode by pressing in the hysteresis pump mode. High level setpoint = 90% High level hysteresis = 7% Pump level setpoint = 50% Pump level hysteresis = 5% Low level setpoint = 10% Low level hysteresis = 15% High level equipment cutout High level equipment restart 90% 83% High level setpoint High level hysteresis Pump restart Pump cutout 50% 45% Pump level setpoint Pump level hysteresis Low level equipment restart 25% Low level hysteresis Low level equipment cutout 10% Low level setpoint NOTE! If [ ], [ ] or the button is not pressed within 10 seconds, automatic calibration mode is exited automatically. Calibration: [CAL] provides access to 2-point calibration. A 2-point calibration can be carried out on two randomly selected points from 0-100%. Based on these two values, the controller itself calculates the sensor s full scale and 0-point. You can access calibration by pressing [CAL] for 5 seconds. The RUN lamp is shut off and the red LED button in CAL is turned on when you have gained access to the calibration function. The min/max calibration values are set with the up and down arrow function, and then confirmed with: A) Min. calibration is confirmed by pressing the button once = B) Max. calibration is confirmed by pressing the button twice = Instruction manual HBLT-C1 Controller (006-UK) 12 / 14

After calibration and activation with, ten seconds will pass before it automatically reverts back to normal operation. This is repeated for min. and max. respectively. Error Detection Error Cause Error diagnostics No light in the display and no LED lamps activated There is no change in display The valve or the pump do not react to the signal from the controller. No power to the unit or the wrong voltage 1) Defective cable from sensor 2) Defective sensor 3) Valve shut 4) Wrong min./max. calibration. Measure the power on 24 V input terminals. 1-2) Check the sensor. See error detection in the sensor s instruction manual. 3) Look at the valve s position on the 5LED on the front of the instrument. Defective cable or lack of a connection Check the connection to the sensor or to the pump of the valve. the valve The display shows too low/high level in relation to the actual level in the vessel. High/low alarm occurs frequently The display flickers or is unstable 1) The cable is defective or there is no connection to the sensor 2) Calibration is not correct 3) Calibration is not carried out at the operating temperature 4) Sensor not calibrated to the correct refrigerant 1) Turbulence in the liquid 2) Alarm set too close to the desired setpoint 1) Loose connection in the power supply or the sensor 2) EMC interference from mobile telephones, frequency converters, or other equipment that does not meet the legal requirements for EMC. 1) Measure the signal from the sensor 2) Calibrate the controller 3) Calibrate at operational temperature 4) Calibrate the sensor. Look at the sensor s instruction manual. 1) Check the system s operational state 2) Set the high alarm at a greater difference in value to the desired setpoint. 1) Check for loose connections 2) Check the equipment that is causing flickering 3) Install insulated wire from the sensor to the operator. Repairing the Controller: If repairs are required, the following procedure must be followed: Go to www.hbproducts.dk and access the menu called servicering af produkter (servicing products). Input all the information into the RMA form and receive an RMA-number. Print out the form and send it in together with the sensor. Following this procedure ensures quick processing. Instruction manual HBLT-C1 Controller (006-UK) 13 / 14

Please fill out one form per product type. Return the product to the nearest agent. The addresses of our agents can be found on our website. Further Information For further information please visit our website www.hbproducts.dk or send an email to support@hbproducts.dk HB Products A/S Bøgekildevej 21 DK8361 Hasselager support@hbproducts.dk www.hbproducts.dk Instruction manual HBLT-C1 Controller (006-UK) 14 / 14