TYPE TEST REPORT. OPzS CELLS AND BLOCK BATTERIES. According to IEC

Similar documents
IEC APPROVAL TESTS

OPzV Batteries. Technical Data

SVTX AGM VRLA batteries

Charging of HOPPECKE OPzV solar.power battery in Solar Applications

Features and Benefits

SPA AGM VRLA batteries

RES OPzV Premium Quality Batteries. for Renewable Energy Storage

RES OPzV Premium Quality Batteries. for Renewable Energy Storage

Reserve Power OPzV Batteries

Reserve Power OPzV Batteries

Industrial Batteries Network Power Powerfit S500 High energy density for maximum security. Specifications

OPzV Batteries. for Stationary Applications

OPzV Batteries. for Stationary Applications

2 Volt AGM Range. Haze Battery Company Ltd

Low maintenance TAB OPzS vented stationary batteries

POWER-plus. Ni-Cd XHP. Capacity: 10 Ah to 250 Ah

Industrial Batteries / Network Power. Classic OCSM.»Exceptional combination of high power, long life and excellent cycling capability«

Pure Lead-Tin Technology

Stationary Batteries OPzS Cells

Motive Power. Higher Energy. Faster Charging. Extreme Conditions. 24h

KPM type Intended for medium discharge currents from 0.5 to 2 C

PowerSafe OPzV Operation Guide for Solar Applications

Haze Battery Company Ltd

PROBLEM IN COMMISSIONING PROCESS OF 125VDC STATIONARY BATTERY IN LAM-LUK-KA SUBSTATION

Vented fibre structure Nickel Cadmium batteries for stationary systems

Powerterm L120C Single Output PSU/Battery Chargers Model C2199A-1 (12V/8A) or Model C2199A-2 (24V/6A)

EcoSafe EOPzV. Operation Guide for Solar Applications

6 & 12 Volt Monobloc. Haze Battery Company Ltd

Specification Approval Sheet

Polymer Gel Standby Battery (Front Access Design) OPERATION MANUAL

PowerSafe OPzV Operation Guide for Solar Applications

Industrial Batteries. Classic GroE.»The proven, reliable energy storage«

Industrial Batteries / Network Power. Classic Solar.»Powerful energy storage for renewable energy systems«

Industrial Batteries / Network Power. Classic Energy Bloc.»High performance, long-life energy storage«

Datasheet / Product specification Model: Solar AAA

Batteries for Renewable Energy Applications

Description Unit Specification Conditions. Nominal Capacity mah 3500 Standard Charge/Discharge. Ф=25.5±0.5 H=49.0 max. 1050(0.3C)

SPECIFICATION FOR VE 2/3A CONTENTS

Industrial Batteries / Network Power. Classic OPzS.»Proven high reliability energy storage for critical applications«

Batteries and more. Powered by (CE, UL & ISO9001 APPROVAL)

INSTRUCTION MANUAL. Maintenance-free Absorbent Glass Mat technology and valve-regulated batteries. (AGM / VRLA)

4.28±0.05V 2.4±0.1V. W :29.0mm T :11.1mm


Deep Cycle AGM Range VRLA

Industrial Batteries / Network Power. Sonnenschein A700.»The durable high energy and reliable battery system«

Industrial Batteries / Network Power. Classic Solar.»Powerful energy storage for renewable energy systems«

NorthStar Battery (NSB) Telecom Application Manual

Haze Battery Company Ltd. Sealed Lead Acid 6 & 12 Volt. AGM Range. Monobloc

6 & 12 Volt Monobloc GEL Range

NorthStar Battery Company DCN: SES DCR: 1548-S09 Date:

Specification. High temperature NiCd Rechargeable AA Cell: 1.2V 900 mah

Industrial Batteries / Network Power. Classic Solar.»Powerful energy storage for renewable energy systems«

RANGE SUMMARY OPzS Optima

FAT. FAT Battery Range FIAMM.COM

Modular Max Range BATTERY SOLUTIONS. NEBS qualified. Reliable capacities. EverExceed power your applications

FLOODED (VLA ), SEALED (VRLA), GEL, AGM TYPE, FLAT PLATE, TUBULAR PLATE: THE WHEN, WHERE, AND WHY. HOW DOES THE END USER DECIDE ON THE BEST SOLUTION?

NARADA POWER SOURCE CO., LTD.

Specification Approval Sheet

Tubular Gel Technology For Solar Applications

Guangzhou Vkan Certification and Testing Institute (CVC former GTIHEA)

MODEL NO:NI-MH 4 AA V

Applications. EMC tested

XHP. Low maintenance high performance batteries

ANNEXURE XI. (Ni Cd Battery Bank) TECHNICAL SPECIFICATIONS OF 125V STATION BATTERY BANK OF GTG I.

SPECIFICATIONS SEALED NICKEL CADMIUM RECHARGEABLE BATTERY N1700SC-HTP

Programming of different charge methods with the BaSyTec Battery Test System

AINO MICRO RANGE VRLA. Compact energy for increased security BATTERY SOLUTIONS. EverExceed power your applications

SPECIFICATION FOR VT D 70 CONTENTS

Reserve Power Systems

NARADA POWER SOURCE CO., LTD.

Technical Manual. An Invensys company

Stationary batteries with modified tubular electrodes

NorthStar Battery Company DOC Code: SES DCR-721-S05 Date:

Sealed Rechargeable Nickel Cadmium N800AA/BTNP

Product Guide. An Invensys company

NorthStar Battery Company DCN: SES DCR: 1413-S08 Date:

STANDARDIZATION ORGANIZATION FOR G.C.C (GSO) GSO 34/2007

SEC. MICROLYTE +Plus. Industrial Battery Co. Supplied Worldwide by: Visit our website on Features. Application

Haze Battery Company Ltd. Sealed Lead Acid 6 & 12 Volt. AGM Range. Monobloc

SPECIFICATION FOR VH F CONTENTS

INSTRUCTIONS FOR ACID FILLING AND FIRST CHARGING OF DRY, UNCHARGED EXIDE India TRACTION BATTERIES

CHARGE METHODS FOR NI-CD BATTERIES

BAE SECURA Product Programme Stationary Batteries ENERGY FROM BATTERIES BAE

PAKISTAN STANDARD LEAD ACID STARTER BATTERIES - Part-1: General Requirements and Methods of Test. (All Rights Reserved) PS: 206-1/2012 (2 nd Rev.

ENGLISH. RS Stock number Description:

BOOST POWER 1212 Product Description

Industrial Batteries / Network Power. Marathon M-FT.»AGM modular power«

SPB. Technical manual

Industrial Batteries - Standby Power Marathon L Reliable and safe energy in long-term storage. Specifications

Reserve Power Systems

FIAMM Industrial Batteries December 2012 FIAMM AGM Valve Regulated Recombination Batteries: FLX Series- Engineering Manual TABLE OF CONTENTS

Industrial Batteries - Classic GroE The proven, reliable energy storage

Industrial Batteries Network Power Classic OGi Suitable universal energy storage.

Specification Approval Sheet

Industrial Batteries / Network Power. Marathon L / XL.»More energy for safer storage«

Nickel Zinc Battery Evaluation at Crane

Haze Battery Company Ltd. Sealed Lead Acid 2 Volt Bloc. Gelled Electrolyte Range

POWER FOR TOMORROW. Motive Power. Network Power. Chargers. Bloc Batteries. Accessories. Service

CELLYTE 12 PLF & 12PLT Range

Industrial Batteries / Network Power. Classic OGi.»Superior performance for

Transcription:

TYPE TEST REPORT OPzS CELLS AND BLOCK BATTERIES According to IEC 60896-11 Systems Sunlight SA, 2 Ermou & Nikis Str, Syntagma Square 105 63 Athens, Attica, Greece Report Type Type Test acc. to IEC 60896-11, DIN 40736 & DIN 40737 Product Type OPzS cells and block batteries Date Iss. by Appr. by Lang. Doc. Nr. 09/04/2013 dfour kmit EN 15.167.0021.00 Report: Issue date: 09/04/2013 Page 1 by 40

INDEX... 3 1 Discharge Capacity.... 4 1.1 2V - OPzS 50Ah Plate... 5 1.2 6V - OPzS 50Ah Plate... 10 1.3 12V - OPzS 50Ah Plate... 15 1.4 70Ah Plate... 20 1.5 100Ah Plate... 25 1.6 125Ah Plate.... 30 2 Short Circuit Current & DC Internal Resistance... 35 3 Charge Retention during Storage... 36 4 Cycle life test (Endurance in Discharge Charge Cycles)... 37 5 Suitability for Floating Operations... 38 6 Service Life Test (at 60 C)... 40 Report: Issue date: 09/04/2013 Page 2 by 40

This test report applies to all Sunlight s OPzS cells and monobloc batteries of the vented type for float charge applications, (i.e. permanently connected to a load and to a d.c. power supply), in a static location (i.e. not generally intended to be moved from place to place) and incorporated into stationary equipment or installed in battery rooms for use in telecom, uninterruptible power supply (UPS), utility switching, emergency power or similar applications and also solar applications. Table 1 shows the relation between the test type and the number of cells acc. to IEC60896-11. The selection of the cell type Vs the test type was made in order to be able to extrapolate the results to the whole OPzS range. In most cases, the selection was made by the possible worst case scenario. Test Clause According to IEC60896-11 Samples per Test 14. Capacity (240 h, 120h, 48h, 10 h, 8 h, 3 h, 1 h, 0,5 h) 6 15. Suitability for floating battery operation 6 16. Endurance in cycles 6 17. Endurance in overcharge 6 18. Charge retention 3 19. Short-circuit current and internal resistance 3 Table 1 Test type Vs Cell Type acc. to IEC 60896-11 Some extra tests have been added by Sunlight and are presented below: Extra Tests Impact of stress temperature of 55 o C or 60 o C (as per IEC 60896-21, clause 6.16) Samples per Test 3 Table 2 Supplementary type tests Report: Issue date: 09/04/2013 Page 3 by 40

1 Discharge Capacity. The purpose of this test is to confirm the capacity of the cells/batteries to a specific end-voltage at the selected discharge rate. One cell type per 50Ah, 70Ah, 100Ah and 125Ah plate has been selected. Regarding the 50Ah plate, the tests have been separated into two categories: 2V cells Monoblock batteries The reason for this categorization is the difference of the separator for these two types (the plate remains the same but the monoblock batteries are using thinner separator comparing to the 2V cells). Each cell type was tested at the following rates: Rate C0,25 C1 C3 C8 C10 C20 C48 C120 Temperature ( o C) 20 20 20 20 20 20 20 20 Final Voltage (V/cell) 1,6 1,6 1,7 1,8 1,8 1,8 Table 3 Discharge rates and end voltages The most common applications for the Sunlight OPzS batteries are: Table 4 Sunlight OPzS batteries applications Deviation according to IEC: cells have been submitted initially to two C10 discharges (IEC mentions that the cells shall not have been previously submitted to any discharges). In any case, the results from the two initial discharges were successful with the actual capacity to be 95% of the rated capacity. Report: Issue date: 09/04/2013 Page 4 by 40

1.1 2V - OPzS 50Ah Plate Instruction: IEC 60896-11, clause 14 Test items: 6pcs, 2V - 5 OPzS 250 Specification: Test Result: Actual Capacity Vs Rated Capacity Ca 95 % Crt at 1 st cycle and Ca 100 % Crt at 5 th cycle Successful 5 OPzS 250 Rate C0,25 C1 C3 C8 C10 C20 C48 C120 Current (A) 330,2 148,6 68,8 32,9 27 15,6 7,47 3,15 Final Voltage (V) 1,6 1,6 1,7 1,8 1,8 1,8 Test Temperature ( o C) 20 20 20 20 20 20 20 20 Nominal Capacity (Ah) 82,6 148,6 206,4 263,2 270,0 312,0 358,6 378,0 Measured Capacity (Ah) 97,29 168,46 229,52 282,14 288,80 333,86 379,47 396,74 Nominal Capacity (50 Ah Plate) 16,5 29,7 41,3 52,6 54,0 62,4 71,7 75,6 Measured Capacity (50 Ah Plate) 19,46 33,69 45,90 56,43 57,76 66,77 75,89 79,35 Result (%) 117,9% 113,4% 111,2% 107,2% 107,0% 107,0% 105,8% 105,0% Table 5 Summary of test results for the 2V 5 OPzS 250 Summary of test results: Tests were successful. In all the rates the following was applied Ca 100 % Crt The measurement curves are shown below: 2V 5 OPzS 250 \ C0,25 discharge curve 1,70 117,9% 1,65 1,60 1,55 0 5 10 15 20 Figure 1. C0.25 Capacity Test Report: Issue date: 09/04/2013 Page 5 by 40

Voltage (V/cell) 2V 5 OPzS 250 \ C1 discharge curve 1,70 113,4% 1,65 1,60 1,55 0 10 20 30 40 50 60 70 Figure 2. C1 Capacity Test 2V 5 OPzS 250 \ C3 discharge curve 111,2% 1,70 1,65 0 15 30 45 60 75 90 105 120 135 150 165 180 195 210 Figure 3. C3 Capacity Test Report: Issue date: 09/04/2013 Page 6 by 40

Voltage (V/cell) 2,10 2V 5 OPzS 250 \ C8 discharge curve 107,2% 1,70 0 60 120 180 240 300 360 420 480 540 Figure 4. C8 Capacity Test 2,10 2V 5 OPzS 250 \ C10 discharge curve 107% 0 60 120 180 240 300 360 420 480 540 600 660 Figure 5. C10 Capacity Test Report: Issue date: 09/04/2013 Page 7 by 40

Voltage (V/cell) 2,10 2V 5 OPzS 250 \ C20 discharge curve 107% 0 120 240 360 480 600 720 840 960 1080 1200 1320 Figure 6. C20 Capacity Test 2,10 2V 5 OPzS 250 \ C48 discharge curve 105,8% 0 240 480 720 960 1200 1440 1680 1920 2160 2400 2640 2880 3120 Figure 7. C48 Capacity Test Report: Issue date: 09/04/2013 Page 8 by 40

2,10 2V 5 OPzS 250 \ C120 discharge curve 105% 0 720 1440 2160 2880 3600 4320 5040 5760 6480 7200 7920 Figure 8. C120 Capacity Test Report: Issue date: 09/04/2013 Page 9 by 40

1.2 6V - OPzS 50Ah Plate Instruction: IEC 60896-11, clause 14 Test items: 6pcs, 6V - 6 OPzS 300 Specification: Test Result: Actual Capacity Vs Rated Capacity Ca 95 % Crt at 1 st cycle and Ca 100 % Crt at 5 th cycle Successful 6V - 6 OPzS 300 Rate C0,25 C1 C3 C8 C10 C20 C48 C120 Current (A) 373,7 181,6 82,6 38,5 31,2 17,69 8,28 3,40 Final Voltage (V) 4,8 4,8 5,1 5,25 5,4 5,4 5,4 5,55 Test Temperature ( o C) 20 20 20 20 20 20 20 20 Nominal Capacity (Ah) 93,4 181,6 247,8 308,0 312,0 353,8 397,4 408,0 Measured Capacity (Ah) 108,03 190,78 262,57 320,11 318,82 363,69 408,97 419,89 Nominal Capacity (50 Ah Plate) 15,6 30,3 41,3 51,3 52,0 59,0 66,2 68,0 Measured Capacity (50 Ah Plate) 18,00 3 43,76 53,35 53,14 60,61 68,16 69,98 Result (%) 115,6% 105,1% 106,0% 103,9% 102,2% 102,8% 102,9% 102,9% Table 6 Summary of test results for the 6V 6 OPzS 300 Summary of test results: Tests were successful. In all the rates the following was applied Ca 100 % Crt The measurement curves are shown below: 5,55 6V 6 OPzS 300 \ C0,25 discharge curve 5,40 5,25 5,10 115,6% 4,95 4,80 4,65 0 5 10 15 20 Figure 9. C0.25 Capacity Test Report: Issue date: 09/04/2013 Page 10 by 40

Voltage (V/cell) 5,85 6V 6 OPzS 300 \ C1 discharge curve 5,70 5,55 5,40 5,25 5,10 105,1% 4,95 4,80 4,65 0 10 20 30 40 50 60 70 Figure 10. C1 Capacity Test 6,00 6V 6 OPzS 300 \ C3 discharge curve 5,85 5,70 5,55 5,40 106% 5,25 5,10 4,95 0 15 30 45 60 75 90 105 120 135 150 165 180 195 Figure 11. C3 Capacity Test Report: Issue date: 09/04/2013 Page 11 by 40

Voltage (V/cell) 6,15 6V 6 OPzS 300 \ C8 discharge curve 6,00 5,85 5,70 5,55 103,9% 5,40 5,25 5,10 0 60 120 180 240 300 360 420 480 540 Figure 12. C8 Capacity Test 6,15 6V 6 OPzS 300 \ C10 discharge curve 6,00 5,85 5,70 102,2% 5,55 5,40 5,25 0 60 120 180 240 300 360 420 480 540 600 660 Figure 13. C10 Capacity Test Report: Issue date: 09/04/2013 Page 12 by 40

Voltage (V/cell) 6,30 6V 6 OPzS 300 \ C20 discharge curve 6,15 6,00 5,85 5,70 102,8% 5,55 5,40 5,25 0 120 240 360 480 600 720 840 960 1080 1200 1320 Figure 14. C20 Capacity Test 6,30 6V 6 OPzS 300 \ C48 discharge curve 6,15 6,00 5,85 5,70 102,9% 5,55 5,40 5,25 0 240 480 720 960 1200 1440 1680 1920 2160 2400 2640 2880 3120 Figure 15. C48 Capacity Test Report: Issue date: 09/04/2013 Page 13 by 40

6,30 6V 6 OPzS 300 \ C120 discharge curve 6,15 6,00 5,85 102,9% 5,70 5,55 5,40 0 720 1440 2160 2880 3600 4320 5040 5760 6480 7200 7920 Figure 16. C120 Capacity Test Report: Issue date: 09/04/2013 Page 14 by 40

1.3 12V - OPzS 50Ah Plate Instruction: IEC 60896-11, clause 14 Test items: 6pcs, 12V - 2 OPzS 100 Specification: Test Result: Actual Capacity Vs Rated Capacity Ca 95 % Crt at 1 st cycle and Ca 100 % Crt at 5 th cycle Successful 12V - 2 OPzS 100 Rate C0,25 C1 C3 C8 C10 C20 C48 C120 Current (A) 139,3 64,2 28,3 12,75 10,3 5,74 2,66 1,10 Final Voltage (V) 9,6 9,6 10,2 10,5 10,8 10,8 10,8 11,1 Test Temperature ( o C) 20 20 20 20 20 20 20 20 Nominal Capacity (Ah) 34,8 64,2 84,9 102,0 103,0 114,8 127,7 132,0 Measured Capacity (Ah) 36,29 65,71 85,53 103,19 104,82 119,17 133,75 133,61 Nominal Capacity (50 Ah Plate) 17,4 32,1 42,5 51,0 51,5 57,4 63,8 66,0 Measured Capacity (50 Ah Plate) 18,15 32,85 42,77 51,60 52,41 59,59 66,87 66,81 Result (%) 104,2% 102,3% 100,7% 101,2% 101,8% 103,8% 104,8% 101,2% Table 7 Summary of test results for the 12V 2 OPzS 100 Summary of test results: Tests were successful. In all the rates the following was applied Ca 100 % Crt The measurement curves are shown below: 11,10 12V 2 OPzS 100 \ C0,25 discharge curve 10,80 10,50 10,20 104,2% 9,90 9,60 9,30 0 5 10 15 20 Figure 17. C0.25 Capacity Test Report: Issue date: 09/04/2013 Page 15 by 40

Voltage (V/cell) 11,70 12V 2 OPzS 100 \ C1 discharge curve 11,40 11,10 10,80 10,50 10,20 102,3% 9,90 9,60 9,30 0 10 20 30 40 50 60 70 Figure 18. C1 Capacity Test 1 12V 2 OPzS 100 \ C3 discharge curve 11,70 11,40 11,10 10,80 100,7% 10,50 10,20 9,90 0 15 30 45 60 75 90 105 120 135 150 165 180 195 Figure 19. C3 Capacity Test Report: Issue date: 09/04/2013 Page 16 by 40

Voltage (V/cell) 12,30 12V 2 OPzS 100 \ C8 discharge curve 1 11,70 11,40 11,10 101,2% 10,80 10,50 10,20 0 60 120 180 240 300 360 420 480 540 Figure 20. C8 Capacity Test 12,60 12V 2 OPzS 100 \ C10 discharge curve 12,30 1 11,70 11,40 101,8% 11,10 10,80 10,50 0 60 120 180 240 300 360 420 480 540 600 660 Figure 21. C10 Capacity Test Report: Issue date: 09/04/2013 Page 17 by 40

Voltage (V/cell) 12,60 12V 2 OPzS 100 \ C20 discharge curve 12,30 1 11,70 11,40 103,8% 11,10 10,80 10,50 0 120 240 360 480 600 720 840 960 1080 1200 1320 Figure 22. C20 Capacity Test 12,60 12V 2 OPzS 100 \ C48 discharge curve 12,30 1 11,70 11,40 104,8% 11,10 10,80 10,50 0 240 480 720 960 1200 1440 1680 1920 2160 2400 2640 2880 3120 Figure 23. C48 Capacity Test Report: Issue date: 09/04/2013 Page 18 by 40

12,60 12V 2 OPzS 100 \ C120 discharge curve 12,30 1 11,70 101,2% 11,40 11,10 10,80 0 720 1440 2160 2880 3600 4320 5040 5760 6480 7200 7920 Figure 24. C120 Capacity Test Report: Issue date: 09/04/2013 Page 19 by 40

1.4 70Ah Plate Instruction: IEC 60896-11, clause 14 Test items: 6pcs 2V - 6 OPzS 420 Specification: Test Result: Actual Capacity Vs Rated Capacity Ca 95 % Crt at 1 st cycle and Ca 100 % Crt at 5 th cycle Successful 2V - 6 OPzS 420 Rate C0,25 C1 C3 C8 C10 C20 C48 C120 Current (A) 516,5 265,9 122,8 58,5 47,4 27,4 13,13 5,51 Final Voltage (V) 1,6 1,6 1,7 1,8 1,8 1,8 Test Temperature ( o C) 20 20 20 20 20 20 20 20 Nominal Capacity (Ah) 129,1 265,9 368,4 468,0 474,0 548,0 630,2 661,2 Measured Capacity (Ah) 153,47 292,09 383,65 481,01 502,29 573,52 649,37 675,07 Nominal Capacity (70 Ah Plate) 21,5 44,3 61,4 78,0 79,0 91,3 105,0 110,2 Measured Capacity (70 Ah Plate) 25,58 48,68 63,94 80,17 83,72 95,59 108,23 112,51 Result (%) 118,9% 109,9% 104,1% 102,8% 106,0% 104,7% 103,0% 102,1% Table 8 Summary of test results for the 2V 6 OPzS 420 Summary of test results: Tests were successful. In all the rates the following was applied Ca 100 % Crt The measurement curves are shown below: 2V 6 OPzS 420 \ C0,25 discharge curve 1,70 118,9% 1,65 1,60 1,55 0 5 10 15 20 Figure 25. C0.25 Capacity Test Report: Issue date: 09/04/2013 Page 20 by 40

Voltage (V/cell) 2V 6 OPzS 420 \ C1 discharge curve 1,70 109,9% 1,65 1,60 1,55 0 10 20 30 40 50 60 70 Figure 26. C1 Capacity Test 2V 6 OPzS 420 \ C3 discharge curve 104,1% 1,70 1,65 0 15 30 45 60 75 90 105 120 135 150 165 180 195 Figure 27. C3 Capacity Test Report: Issue date: 09/04/2013 Page 21 by 40

Voltage (V/cell) 2V 6 OPzS 420 \ C8 discharge curve 102,8% 1,70 0 60 120 180 240 300 360 420 480 540 Figure 28. C8 Capacity Test 2V 6 OPzS 420 \ C10 discharge curve 106% 0 60 120 180 240 300 360 420 480 540 600 660 Figure 29. C10 Capacity Test Report: Issue date: 09/04/2013 Page 22 by 40

Voltage (V/cell) 2,10 2V 6 OPzS 420 \ C20 discharge curve 104,7% 0 120 240 360 480 600 720 840 960 1080 1200 1320 Figure 30. C20 Capacity Test 2,10 2V 6 OPzS 420 \ C48 discharge curve 103% 0 240 480 720 960 1200 1440 1680 1920 2160 2400 2640 2880 3120 Figure 31. C48 Capacity Test Report: Issue date: 09/04/2013 Page 23 by 40

2,10 2V 6 OPzS 420 \ C120 discharge curve 102,1% 0 720 1440 2160 2880 3600 4320 5040 5760 6480 7200 7920 Figure 32. C120 Capacity Test Report: Issue date: 09/04/2013 Page 24 by 40

1.5 100Ah Plate Instruction: IEC 60896-11, clause 14 Test items: Specification: Test Result: 6pcs 2V - 6OPzS600 Actual Capacity Vs Rated Capacity Ca 95 % Crt at 1 st cycle and Ca 100 % Crt at 5 th cycle Successful 2V - 6 OPzS 600 Rate C0,25 C1 C3 C8 C10 C20 C48 C120 Current (A) 656,6 378,1 175 83,6 67,2 39,4 19,07 8,05 Final Voltage (V) 1,6 1,6 1,7 1,8 1,8 1,8 Test Temperature ( o C) 20 20 20 20 20 20 20 20 Nominal Capacity (Ah) 164,2 378,1 525,0 668,8 672,0 788,0 915,4 966,0 Measured Capacity (Ah) 231,9 400,5 563,8 688,6 700,0 814,9 925,0 979,8 Nominal Capacity (100 Ah Plate) 27,4 63,0 87,5 111,5 112,0 131,3 152,6 161,0 Measured Capacity (100 Ah Plate) 38,66 66,75 93,97 114,76 116,67 135,81 154,17 163,30 Result (%) 141,3% 105,9% 107,4% 103,0% 104,2% 103,4% 101,1% 101,4% Table 9 Summary of test results for the 2V 6OPzS600 Summary of test results: Tests were successful. In all the rates the following was applied Ca 100 % Crt The measurement curves are shown below: 2V 6 OPzS 600 \ C0,25 discharge curve 1,70 141,3% 1,65 1,60 1,55 0 5 10 15 20 25 Figure 33. C0.25 Capacity Test Report: Issue date: 09/04/2013 Page 25 by 40

Voltage (V/cell) 2V 6 OPzS 600 \ C1 discharge curve 1,70 105,9% 1,65 1,60 1,55 0 10 20 30 40 50 60 70 Figure 34. C1 Capacity Test 2V 6 OPzS 600 \ C3 discharge curve 107,4% 1,70 1,65 0 15 30 45 60 75 90 105 120 135 150 165 180 195 Figure 35. C3 Capacity Test Report: Issue date: 09/04/2013 Page 26 by 40

Voltage (V/cell) 2V 6 OPzS 600 \ C8 discharge curve 103% 1,70 0 60 120 180 240 300 360 420 480 540 Figure 36. C8 Capacity Test 2V 6 OPzS 600 \ C10 discharge curve 104,2% 0 60 120 180 240 300 360 420 480 540 600 660 Figure 37. C10 Capacity Test Report: Issue date: 09/04/2013 Page 27 by 40

Voltage (V/cell) 2V 6 OPzS 600 \ C20 discharge curve 103,4% 0 120 240 360 480 600 720 840 960 1080 1200 1320 Figure 38. C20 Capacity Test 2,10 2V 6 OPzS 600 \ C48 discharge curve 101,1% 0 240 480 720 960 1200 1440 1680 1920 2160 2400 2640 2880 3120 Figure 39. C48 Capacity Test Report: Issue date: 09/04/2013 Page 28 by 40

2,10 2V 6 OPzS 600 \ C120 discharge curve 101,4% 0 720 1440 2160 2880 3600 4320 5040 5760 6480 7200 7920 Figure 40. C120 Capacity Test Report: Issue date: 09/04/2013 Page 29 by 40

1.6 125Ah Plate. Instruction: IEC 60896-11, clause 14 Test items: 6pcs 2V - 24 OPzS 3000 Specification: Test Result: Actual Capacity Vs Rated Capacity Ca 95 % Crt at 1 st cycle and Ca 100 % Crt at 5 th cycle Successful 2V - 24 OPzS 3000 Rate C0,25 C1 C3 C8 C10 C20 C48 C120 Current (A) 2966 1861 877,7 418 336,1 194,5 92,3 38,50 Final Voltage (V) 1,6 1,6 1,7 1,8 1,8 1,8 Test Temperature ( o C) 20 20 20 20 20 20 20 20 Nominal Capacity (Ah) 741,5 1861,0 2633,1 3344,0 3361,0 3890,0 4430,4 4620,0 Measured Capacity (Ah) 849,1 1928,6 2786,0 3453,9 3480,7 3979,5 4544,9 4789,2 Nominal Capacity (125 Ah Plate) 30,9 77,5 109,7 139,3 140,0 162,1 184,6 192,5 Measured Capacity (125 Ah Plate) 35,38 80,36 116,08 143,91 145,03 165,81 189,37 199,55 Result (%) 114,5% 103,6% 105,8% 103,3% 103,6% 102,3% 102,6% 103,7% Table 10 Summary of test results for the 2V 6 OPzS 420 Summary of test results: Tests were successful. In all the rates the following was applied Ca 95 % Crt The measurement curves are shown below: 2V 24 OPzS 3000 \ C0,25 discharge curve 1,70 114,5% 1,65 1,60 1,55 0 5 10 15 20 Figure 41. C0.25 Capacity Test Report: Issue date: 09/04/2013 Page 30 by 40

Voltage (V/cell) 2V 24 OPzS 3000 \ C1 discharge curve 1,70 103,6% 1,65 1,60 1,55 0 10 20 30 40 50 60 70 Figure 42. C1 Capacity Test 2V 24 OPzS 3000 \ C3 discharge curve 105,8% 1,70 1,65 0 15 30 45 60 75 90 105 120 135 150 165 180 195 Figure 43. C3 Capacity Test Report: Issue date: 09/04/2013 Page 31 by 40

Voltage (V/cell) 2V 24 OPzS 3000 \ C8 discharge curve 103,3% 1,70 0 60 120 180 240 300 360 420 480 540 Figure 44. C8 Capacity Test 2V 24 OPzS 3000 \ C10 discharge curve 103,6% 0 60 120 180 240 300 360 420 480 540 600 660 Figure 45. C10 Capacity Test Report: Issue date: 09/04/2013 Page 32 by 40

Voltage (V/cell) 2V 24 OPzS 3000 \ C20 discharge curve 102,3% 0 120 240 360 480 600 720 840 960 1080 1200 1320 Figure 46. C20 Capacity Test 2,10 2V 24 OPzS 3000 \ C48 discharge curve 102,6% 0 240 480 720 960 1200 1440 1680 1920 2160 2400 2640 2880 3120 Figure 47. C48 Capacity Test Report: Issue date: 09/04/2013 Page 33 by 40

2,10 2V 24 OPzS 3000 \ C120 discharge curve 103,7% 0 720 1440 2160 2880 3600 4320 5040 5760 6480 7200 7920 Figure 48. C120 Capacity Test Report: Issue date: 09/04/2013 Page 34 by 40

2 Short Circuit Current & DC Internal Resistance The purpose of this test is to define prospective short-circuit value Isc and internal resistance Ri of the specific OPzS units. The short circuit current is defined by determining two data pairs in the following way: a. First data pair (Ua, Ia) After 20 s of discharge at the current Ia = 4 x I10, the voltage and current shall be recorded to give the first data pair. The current shall be interrupted after 25 s maximum and, without recharge and after an open circuit stand of 5 min, the second data pair shall be determined. b. Second data pairs (Ub, Ib) After 5 s of discharge at the current Ib = 20 I10, the voltage and current shall be recorded to give the second data pair. Instruction: IEC 60896-11, clause 6.3 Test items: Specification: Temperature: Test Result: 3pcs 2V - 5 OPzS 250, 3pcs 12V - 2 OPzS 100, 3pcs 6V - 6 OPzS 300, 3pcs 2V - 6 OPzS 420, 3pcs 2V - 6OPzS600 & 3pcs 2V - 24 OPzS 3000 values must be ±10 % of the specification values 20 o C Successful The results are shown on the table below: Cell type Cnom (Αh) DIN values I1 (Α) I2 (Α) U1 at 20sec (V) U2 at 5sec (V) Ri-test (mω) Isc-test (A) Ri-spec ±10% (mω) Isc-spec ±10% (Α) Ri-test Vs. spec Isc-test Vs. spec 2V 5 OPzS 250 250 100 500 7 1,710 0,618 3269 0,671 3000 92,0% 109,0% 2V 6 OPzS 420 420 168 840 1,943 1,620 0,481 4210 0,518 3900 92,9% 108,0% 2V 6 OPzS 600 600 240 1200 1,911 1,501 0,427 4715 0,447 4500 95,7% 104,8% 2V 24 OPzS 3000 3000 1200 6000 1,882 1,385 0,104 19376 0,108 18800 96,3% 103,1% 12V 2 OPzS 100 100 40 200 11,67 10,23 9,03 1332 9,679 1260 93,3% 105,7% 6V 6 OPzS 300 300 120 600 5,775 4,865 3166 0 3040 94,8% 104,1% Table 11 Rint & Isc Results Report: Issue date: 09/04/2013 Page 35 by 40

discharge voltage (volts per cell) 3 Charge Retention during Storage The purpose of this requirement is to show the residual dischargeable capacity Cr after storage on open circuit under defined conditions of temperature and time. Instruction: IEC 60896-11, clause 18 Test items: 6pcs 2V - 6 OPzS 420 Result: Successful. Capacity reduction is less than 2,5% per month Test procedure: After having undergone the initial capacity test (Ca1), the battery is fully recharged, thoroughly cleaned and then is being stored on open circuit at an average cell temperature of 20 C ± 2 C for a period of 90 days. During that time, the maximum cell temperature does not exceed +25 C and the minimum temperature is not less than +15 C. At the end of the open circuit storage the residual capacity is determined. Results: initial residual Cell type 2V 6 OPzS 420 Test initial temper. (To) 19 oc 20 oc Test samples 6 cells Average test current (I) 42 A 42 A Discharge rate C10 Discharge time (t) 705 min 665 min Rated capacity (Cr) 420 Ah Test capacity (C) 494 Ah 466 Ah Rated current (Ir) 42 A Capacity at 20 o C 496 Ah 466 Ah Cut off voltage (Uf) Vpc Capacity at 20 o C % 118,2% 110,8% Capacity reduction in 3 months % Capacity reduction per month % 7,38% 2,46% 2,10 1,70 1,65 1,60 Initial capacity test:\\6 cells 2V 6 OPzS 420, Rate:10h, Temp:19oC, Result:118,2% Residual capacity test:\\6 cells 2V 6 OPzS 420, Rate:10h, Temp:20oC, Result:110,8% 0 60 120 180 240 300 360 420 480 540 600 660 720 discharge time (minutes) Figure 49. Capacity test before and after the storage period Report: Issue date: 09/04/2013 Page 36 by 40

4 Cycle life test (Endurance in Discharge Charge Cycles) The purpose of the test is to measure the endurance in discharge-charge cycles for applications where frequent discharges of the battery are to be encountered due either to a deliberate choice of operational or to frequent power-line outages. Instruction: IEC 60896-11, clause 16 Test items: 6pcs, 2V 6 OPzS 420 Test Result: 1520 cycles to reach 80% C10 Test procedure: The test was performed under the following profile: a. Capacity test settings: 10h rate at 1.80V/c according DIN capacity and current values (C10=420Ah, I10=42A). Capacity is implemented after an equalizing charge b. Discharge cycling settings: Discharge with 2.0 x I10 for 3 hours. This current corresponds to ~4h discharge DIN rate. The 3h discharge out of 4h nominal yields 75% DoD for each cycle. c. Recharge the battery for 21h at 2.40 ± 0.01 V/cell d. Nominal electrolyte density is 1.240 ± 0.010 gr/ml at 20 C e. Nominal single cell voltage deviation is -50 to +100mV from the average battery voltage f. During test, the electrolyte temperature is 25± 5 C Figure 50. Capacity Vs Cycles Report: Issue date: 09/04/2013 Page 37 by 40

5 Suitability for Floating Operations The purpose of the test is to check the suitability of the cells or batteries in this operation. A battery in floating operation has a constant voltage, permanently applied to its terminal which is sufficient to maintain it in a state close to full charge and is intended to supply a circuit whose normal power supply may fail. Test items: 6pcs, 2V 6 OPzS 420 Test Result: Successful. The cells retained their capacity, voltage and density values within nominal range without water loss Test procedure: The cells are kept at an ambient temperature close to 20 C. The upper surface of the cells (lids) was kept clean and dry throughout the test. The cells were submitted to a permanent floating charge at a voltage 2.23Vpc. After intervals of three months, the voltage and the electrolyte density of each cell and the level of the electrolyte were measured and noted. After six months of battery floating operation, the cells were subjected to a capacity test at 10h DIN rate. The following rules and settings have been observed: Nominal floating voltage for the battery is 2.23 ± 1% V/cell Nominal electrolyte density is 1.240 ± 0.010 gr/ml at 20 C Nominal single cell voltage deviation is -50 to +100 mv from the average battery voltage During test, the electrolyte temperature is 20± 5 C Results: Densities (gr/ml at 20 o C) Variation from average cell 1 2 3 4 5 6 Average Minimum Maximum to Minimum to Maximum initial 1,240 1,239 1,240 1,240 1,239 1,239 1,240 1,239 1,24 0,000 0,000 at 3 months 1,242 1,24 1,242 1,243 1,241 1,241 1,242 1,24 1,243-0,002 0,002 at 6 months 1,243 1,241 1,242 1,244 1,242 1,244 1,242 1,241 1,244-0,001 0,002 Conclusion: Densities remain within nominal values Float voltage (Volts) Variation from average cell 1 2 3 4 5 6 Average Minimum Maximum to Minimum to Maximum initial 2,205 2,251 2,265 2,258 2,21 2,201 2,232 2,201 2,265-0,031 0,033 at 3 months 2,212 2,236 2,262 2,251 2,212 2,205 2,230 2,205 2,262-0,025 0,032 at 6 months 2,221 2,235 2,254 2,246 2,222 2,221 2,233 2,221 2,254-0,012 0,021 Conclusion: Float voltages remain within nominal values Water consumption (mm from MAX level) Variation from average cell 1 2 3 4 5 6 Average Minimum Maximum to Minimum to Maximum initial MAX MAX MAX MAX MAX MAX MAX MAX MAX not detected not detected at 3 months MAX MAX MAX MAX MAX MAX MAX MAX MAX not detected not detected at 6 months MAX MAX MAX MAX MAX MAX MAX MAX MAX not detected not detected Conclusion: No water loss was detected within 6 months Report: Issue date: 09/04/2013 Page 38 by 40

discharge voltage (volts per cell) initial after 6 months Cell type 2V 2 OPzS 250 Test initial temper. (T) 21 oc 19 oc Test samples 6 cells Average test current (I) 42 A 42 A Discharge rate C10 Discharge time (t) 658 min 667 min Rated capacity (Cr) 250 Ah Test capacity (C) 274 Ah 278 Ah Rated current (Ir) 25 A Capacity at 20 o C 273 Ah 280 Ah Cut off voltage (Uf) Vpc Capacity at 20 o C % 109,0% 111,8% Capacity difference % 2,8% 2,10 1,70 1,65 1,60 Initial capacity test:\\6 cells 2V 2 OPzS 250, Rate:10h, Temp:21oC, Result:109% Capacity test after 6 months:\\6 cells 2V 2 OPzS 250, Rate:10h, Temp:19oC, Result:111,8% 0 60 120 180 240 300 360 420 480 540 600 660 720 discharge time (minutes) Figure 51. Capacity test before and after the floating period Report: Issue date: 09/04/2013 Page 39 by 40

Capacity (% to the nominal) 6 Service Life Test (at 60 C) The purpose of the test is to define the expected lifetime of the battery under normal service conditions (floating voltage of 2.23 V/c and temperature 20 o C). The parameter that is used to accelerate the test is the temperature. The batteries are subjected to the normal floating voltage but at a much higher temperature (60 o C). The acceleration factor to extrapolate the service life at 20 o C from the achieved duration at 60 o C is the value that corresponds to the halving of the lifetime for every 9 o K temperature rise. F (60vs20) = 2 [(60-20)/9] = 21.77 times LifeTime at 20 o C = LifeTime at 60 o C x 21.77 Test items: 6pcs, 2V 6 OPzS 420 Test Result: Days at 60 o C: 472.8 Test procedure: Equivalent Service Life at 20 o C: 28.2 years The batteries are subjected to the test conditions for periods of 30 days each. After the end of each period a discharge test was applied in order to measure the available capacity under the following conditions: a. 10h capacity test at 1.80V/cell at 20 o C (DIN values) b. Full charge before and after a capacity test c. The end-of-test criteria is the capacity drop below 80% of the DIN nominal value Results - 6 cells 6 OPzS 420 Days at 60 o C achieved: 472.8 days Equivalent service life at 20 o C: 28.2 years 140% Life time test on 6 cells 2V 6 OPzS 420 - Capacity evolution 120% 80% 472,8 60% 40% 20% 0% 0 30 60 90 120 150 180 210 240 270 300 330 360 390 420 450 480 Days at 60 o C Figure 52. Days vs Capacity Report: Issue date: 09/04/2013 Page 40 by 40