COOPER POWER SERIES. Electronic control battery testing, charging, and replacement instructions. Reclosers MN280074EN

Similar documents
COOPER POWER SERIES. Testing a motor capacitor on a voltage regulator procedure instructions. Voltage Regulators MN225064EN

Effective November 2016 Supersedes September 1998 (S )

COOPER POWER SERIES. Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions. Fusing Equipment MN132014EN

COOPER POWER SERIES. S.T.A.R. Hot line voltage indicator installation instructions. Fault Indicators MN320011EN. Indicator boot.

COOPER POWER SERIES. KA662R tank-lifting windlass assembly and installation instructions. Recloser Mountings MN280071EN

COOPER POWER SERIES. Dielectric grease application to recloser cable instructions. Reclosers MN280070EN

COOPER POWER SERIES. ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions. Fusing Equipment MN132017EN

COOPER POWER SERIES. KA1169R Closing Coil Transfer-Switch Accessory Operation. Reclosers MN280069EN

COOPER POWER SERIES. RTE EL-BAY-O-NET FUSE Re-Fusing Instructions. Fusing Equipment MN132024EN

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

COOPER POWER SERIES. S.T.A.R. type LVR faulted circuit indicator installation instructions. Fault Indicators MN320005EN

COOPER POWER SERIES. QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit A26 installation instructions

COOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN

COOPER POWER SERIES. Edison Modular Fuse (EMF) Installation Instructions. Fusing Equipment MN132031EN

Effective June 2016 New Issue

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN

COOPER POWER SERIES. Expulsion fuse installation instructions. Capacitors MN230005EN. Effective November 2016 Supersedes November 2001 (S )

COOPER POWER SERIES. UltraSIL polymer-insulated D-73P disconnect switches installation instructions. Switches MN008004EN

COOPER POWER SERIES. Pad-mounted Switchgear MN285019EN. Effective March 2017 Supersedes February 2007 (S )

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN

COOPER POWER SERIES. High-voltage primary bushings installation instructions. OEM Equipment MN800008EN

COOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. KA716L7001 adjustable control valve kit for Types L, E, 4E, V4E, and V4L reclosers installation and adjustment instructions

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

Effective November 2016 Supersedes February 2012 (S )

Effective May 2017 Supersedes December 2004 (S )

Effective May 2017 Supersedes January 2003 (S )

Type NR oil switch installation and operation instructions

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN

High-voltage primary bushings installation instructions

Effective March 2015 Supersedes S August 2012

COOPER POWER SERIES. Types 4H single-phase and 6H three-phase vacuum interrupter conversion kits. Reclosers MN280014EN

COOPER POWER SERIES. KA146W5 single pole-mounting hanger; KA146W2 tank lifting windlass assembly and installation instructions. Reclosers MN280039EN

COOPER POWER SERIES. Mercury switch to microswitch retrofit kit KA349WE installation instructions. Reclosers MN280022EN

COOPER POWER SERIES. Quick Connect Assembly (QCA) Retrofit Kit, General Electric Installation Instructions. Voltage Regulators MN225075EN

COOPER POWER SERIES. Surge arrester interchangeable fuse cutout combination installation instructions. Surge Arresters MN235004EN

COOPER POWER SERIES. Types D and DV recloser installation instructions. Reclosers MN280030EN

COOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions

S Voltage Regulators GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage. Standards

COOPER POWER SERIES. Fused loadbreak elbow connector installation instructions. Loadbreak Apparatus Connectors MN650014EN

S Fault Indicators. S.T.A.R. Type TPR Faulted Circuit Indicator Installation Instructions. Contents INSTALLATION PROCEDURES

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN

This Kit Is for Use with Types RE, RVE, WE, WVE, VWE, VWVE27, and VWVE38 Reclosers.

COOPER POWER SERIES. Metal-enclosed capacitor banks installation instructions. Power Capacitors MN230010EN

COOPER POWER SERIES. Metal-enclosed, pad-mounted capacitor banks installation instructions. Power Capacitors MN230009EN

Figure 1. Kearney Type HX cutout.

COOPER POWER SERIES. Instructions for oil-filled, single-phase overhead distribution transformers. Distribution Transformers MN201003EN

COOPER POWER SERIES. Manually-Operated M-Force Switch Installation and Operation Instructions. Switches and Disconnects MN008003EN

Factory Authorized Mechanism Enhancement (FAME)

Installation Instructions for Interlocking Trip Indicator with Remote Reset for Magnum Low Voltage Circuit Breakers

S Voltage Regulators PRODUCT INFORMATION GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage

Reprogramming guide. Power Defense ICCB. Instructional Leaflet IL EN WARNING WARNING. Instructions apply to:

S Voltage Regulators PRODUCT INFORMATION GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage.

Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version

COOPER POWER SERIES. VFI tester operating instructions. Underground Distribution Switchgear MN285001EN

Instructions for using Functional Test Kit on Digitrip 520 and 1150 family of Power Circuit Breaker Trip Units and Series G and FD MCCB Trip Units

Removal/installation instructions for Series NRX (IZMX) drawout levering (racking) mechanism

S Voltage Regulators GENERAL. PRODUCT INFORMATION Introduction. Contents. Acceptance and Initial Inspection. Handling and Storage.

COOPER POWER SERIES. Types VWE, VWVE27, VWVE38X, WE, WVE27, and WVE38X; threephase electronically controlled; installation and operation instructions

CCP2-FLR1-21_ flange-rod operating mechanism

Two-way cable interlock kit for Magnum drawout circuit breakers

3-way multi-family drawout cable interlock kit - type 32 - RF

Advanced Test Equipment Rentals ATEC (2832)

Two-way cable interlock kit for Magnum fixed circuit breakers

Installation and removal instructions for Series NRX RF fixed breaker three-way Type 32 cable interlock kit

O & M Manual for the EATON Generator Ready Loadcenter

COOPER POWER SERIES. Externally fused block banks installation instructions. Capacitors MN230004EN

CM52 Network Protector with Arc Flash Reduction Module

Effective October 2016 Supersedes January 2014 (S )

Installation Instructions for KPS and KPH Circuit Breakers and Molded Case Switches

Instruction Booklet IB E. Contents

Installation Guide Smart-UPS On-Line External Battery Pack XBP48RM1U-LI

Magnum Breaker Remote Racking Device (MRR1000)

Battery Charger Retrofit Kit Q-DCCHG1 for DC Cabinet Retrofit Manual

II DISTRIBUTION & SUBSTATION TYPE C

Installation Power Management Unit Battery Cables and Battery Harness

GWI Rev. 1 October 2007 Supersedes Rev. 0 Dated February 2004

Edison modular fuse, vault application products

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION

COOPER POWER SERIES. Type VSA12, VSA12B, VSA16, VSA20, and VSA20A operation and installation instructions. Reclosers MN280063EN

www. ElectricalPartManuals. com Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers

COOPER POWER SERIES. Type MOST Fluid-Insulated Switchgear; Installation, Operation, and Maintenance Instructions

Models DP10 & DP20 Series Low Voltage Disconnects User s Manual Rev. 1.1 October 31, 2007

Installation Instructions for R-Frame G-Series (RG) 310+ Trip Unit

COOPER POWER SERIES. RVAC Fluid-insulated Vacuum Switchgear; Installation, Operation, and Maintenance Instructions. Switchgear MN285005EN

Types VSA12, VSA12B, VSA16, VSA20, and VSA20A; three-phase; air-insulated; electronically controlled recloser

AC/DC Powered Peak Detection Fast Charger for 4- to 8-Cell Ni-Cd & Ni-MH Batteries

OPERATING INSTRUCTIONS PLEASE READ CAREFULLY

Item No. : Power Dome LT. User s Manual

DUSTTRAK AEROSOL MONITOR SOLAR POWER KIT MODEL

Generator Start Control Module

BlinkerBeam Solar Controller

PUMP SPY INSTALLATION AND OPERATING INSTRUCTIONS

TABLE OF CONTENTS. Page 1

Installation Instructions for Eaton Surge Protective

Manufacturing & Service: Bierer & Associates Inc. Patent No. 6,885,180. ST Series Service Tester Phase Identifier Operating Instructions ST500PGN

Transcription:

Reclosers MN280074EN Effective May 2017 Supersedes September 2009 (S280-90-6) Electronic control battery testing, charging, and replacement instructions COOPER POWER SERIES

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation s ( Eaton ) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or other-wise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein. The information contained in this manual is subject to change without notice. replacement instructions MN280074EN May 2017 i

Contents DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY... i Safety for life... iii Safety INFORMATION... iii Safety instructions... iii Introduction.... 1 Read this manual first...1 Additional information...1 Control battery storage... 1 Battery testing procedure.... 1 Battery test in the control...2 Battery test on the bench...4 Battery test INFORMATION.... 5 Battery charging information.... 6 Battery replacement.... 7 Battery disposal.... 7 ii replacement instructions MN280074EN May 2017

! SAFETY FOR LIFE Safety for life Eaton s Cooper Power series products meet or exceed all applicable industry standards relating to product safety. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Eaton employees involved in product design, manufacture, marketing, and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high voltage lines and equipment and support our Safety For Life mission.! SAFETY FOR LIFE Safety information The instructions in this manual are not intended as a sub stitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians, who are familiar with this equipment should install, operate and service it. A competent technician has these qualifications: Is thoroughly familiar with these instructions. Is trained in industry-accepted high- and low-voltage safe operating practices and procedures. Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment. Is trained in the care and use of protective equipment such as flash clothing, safety glasses, face shield, hard hat, rubber gloves, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and under stand all cautions and warnings. Hazard Statement Definitions This manual may contain four types of hazard statements: DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in equipment damage only. Safety instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. DANGER Hazardous voltage. Contact with hazardous voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around high- and low-voltage lines and equipment. G103.3 WARNING Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling, or maintenance can result in death, severe personal injury, and equipment damage. G101.0 WARNING This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply may result in death, severe personal injury, and equipment damage. G102.1 WARNING Power distribution and transmission equipment must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install, or maintain power distribution and transmission equipment can result in death, severe personal injury, and equipment damage. G122.3 replacement instructions MN280074EN May 2017 iii

Introduction Service information MN280074EN provides battery testing and charging information for the following electronic recloser controls: FXA, FXB, Form 3, Form 3A, Form 4C, Form 5, Form 5 LS/UDP, Form 5/Triple-Single, and Form 6 Pole Mount (standard, triple-single, loop scheme). Read this manual first Read and understand the contents of this manual, the specific control s service information manual, and follow all locally approved procedures and safety practices before installing or operating this equipment. For battery testing and charging refer to the appropriate instruction manual: Service Information S280-75-1, Installation, Setting, Testing Form 3A Type ME Control Service Information S280-78-1, Installation and Operation of Types FXA and FXB Control Service Information S280-78-3, Type FXB Control Front Panel Programming Guide Service Information S280-77-1, Installation and Operating Instructions Form 4C Control Service Information S280-79-1, Installation of the Form 5 Control Service Information S280-79-10, Installation and Operation of Form 5, Form 5 UDP, Form 5 DC NOVA Recloser Controls Service Information S280-79-12, Form 5 LS/UDP Recloser Controls Installation and Operation Instructions Service Information S280-42-3, Installation of Form 5/ Triple-Single Recloser Control Service Information MN280077EN, Form 6 Pole Mount Recloser Control Instructions Service Information MN280080EN, Form 6 Triple-Single Pole Mount Recloser Control Instructions Service Information MN280082EN, Form 6-LS Pole Mount Recloser Control Instructions Additional information These instructions cannot cover all details or vari ations in the equipment, procedures, or process described, nor to provide directions for meeting every possible contin gency during installation, operation, or maintenance. For additional information, contact your Eaton representative. Control battery storage Sealed lead acid batteries should only be stored in a fully charged state. Permanent irreversible damage will result if a battery is stored in a deeply discharged state. After three months of storage, check the open circuit voltage. The battery will require recharging if it is at or below 24 volts at 25 c (77 f). Never store batteries at temperatures exceeding 47 c (117 f), as permanent damage can result in one month. Storage at or below room temperature is recommended to prolong storage time and maintain maximum capacity over time. Important To maintain sufficient charge to operate the control and prevent battery cell damage, the sealed lead-acid batteries should be charged after no more than three months of storage. Important The battery must be disconnected prior to shipping or storing the control. The control battery is fully charged prior to shipment and is ready for use. Refer to the battery charging information section. Important Connect the control battery when ac power is connected to the control s ac supply input terminal block. When shipped from the factory, the battery source is disconnected and its output plug is taped to the cabinet. Connect the battery plug into the mating connector to complete the battery circuit. Battery testing procedure A control battery can be tested in the control or on the bench. When performing a manual battery test, while the battery is in the control, follow the battery testing procedure as specified in the control s service information manual. In general, battery testing is accomplished on the front panel of the FXA / FXB, Form 4C, Form 5, Form 5 LS/UDP, Form 5/Triple-Single, and Form 6 Pole Mount controls. 1 replacement instructions MN280074EN May 2017

Battery test in the control Caution Recloser misoperation. The control must be removed from service before disconnecting the control battery. Disconnecting the control battery from an in-service control may cause recloser misoperation (unintentional operation). Failure to comply can result in equipment damage and personal injury. T213.4 Follow the appropriate procedure below to perform a battery test in the control. The values in the test procedures are based on testing at 25 c (77 f). Caution Equipment damage. Shorting battery positive to battery negative at the battery test terminals on the control panel will cause damage to the control. The control will be inoperative and possible misoperation (unintentional operation of the recloser) can result. T214.1 Form 3/3A battery test procedure Follow the procedure to perform a battery test on the nickel-cadmium battery in the Form 3 / 3A control. This procedure requires a separate battery tester (kmet tester). 1. Remove the control from service. Refer to the To Remove Control From Service Section in Service Information S280-75-1. 2. Disable the control battery charger by opening the fused switch or removing ac power from the control. Wait 3 to 5 minutes to allow the battery voltage to stabilize prior to testing open circuit battery voltage. 3. Three battery test terminals in the lower right corner of the front panel are used to check the battery voltage, quiescent drain, and charging rate. The left hand pair of terminals (v) are connected directly across the battery to check battery voltage. The red terminal (far left) is battery positive (+). 4. The battery in the Form 3/3A control will see a steady drain of approximately 1.5 2.5 Milliamperes (may be as high as 4.5 Milliamperes with certain accessories). 5. From the battery test terminals on the control front panel measure the battery voltage. If battery voltage is below 24 volts, the battery is either low on charge or failing. The battery should be removed for recharging and re-tested before returning to service. 6. If battery voltage is above 24 volts, perform the following load test. While measuring battery voltage connect a 10Ω, 10 watt resistor across the battery test terminals, for approximately 2 3 seconds. For ambient temperatures above -6 c (20 f), battery voltage should drop by no more than 3 volts from the open circuit voltage. Either a ka638me voltmeter accessory or a kmet tester can be used for the load test. Both devices have a built in 10Ω load resistor. 7. If the temperature is below -6 c (20 f), the battery voltage / temperature should follow the lower curve in Service Information S280-75-2 Figure 53. If the voltage falls below the lower curve, the battery should be removed for bench testing. FXA/FXB battery test procedure Follow the procedure to perform a battery test in the FXA/FXB control. Control connected to ac power Initial condition: ac power is connected to the control and battery circuit is connected. 1. For the FXA, connect a voltmeter to the battery test terminals located on the lower half of the front panel. Battery voltage should read 26 28 vdc. For the FXB, monitor the lcd display. 2. For the FXA, press and hold the battery load test switch for 5 seconds, this places a 15Ω load on the battery. Voltage drop should not exceed 2 vdc. For the FXB, press the battery test button. The FXB will provide the unloaded and loaded battery voltage and a BATTERY OK! Or BATTERY NOT OK! Indication. Control disconnected from ac power Initial condition: ac power is disconnected and battery circuit is connected. 1. For the FXA, connect a voltmeter to the battery test terminals located on the lower half of the front panel. Battery voltage should read 23 27 vdc. If the battery voltage is less than 23 vdc, recharge the battery prior to performing step 2. 2. For FXA, press the battery load test switch for 5 seconds; this places a 15Ω load on the battery. Voltage drop should not exceed 2 vdc. For FXB, press battery test button. The FXB will provide the unloaded and loaded battery voltage and a BATTERY OK! Or BATTERY NOT OK! Indication. Disconnect the battery when the control is removed from service. replacement instructions MN280074EN May 2017 2

Form 4C battery test procedure Caution Equipment damage. Shorting battery positive to battery negative at the battery test terminals on the control panel will cause damage to the control. The control will be inoperative and possible misoperation (unintentional operation of the recloser) can result. T214.1 Caution Equipment damage. Do not short battery positive to mechanical ground. Failure to comply will cause damage to the control. T256.1 Follow the procedure to perform a battery test in the Form 4C control. Control connected to ac power Initial condition: ac power is connected to the control and battery circuit is connected. 1. Set meter range switch to lo. 2. Place the battery meter toggle switch in volts position. Battery voltage should read 27 29 vdc. 3. With the battery meter toggle switch in volts position, press the battery load test button for 5 seconds (places 5ω load on battery). Voltage drop should not exceed 3 vdc. 4. Set meter range switch to hi. 5. Place the battery meter toggle switch in current position. Press the battery load test button for 5 seconds. Battery charger should show charge rate of 250 to 500 ma. Control disconnected from ac power Initial condition: ac power is disconnected, battery circuit connected, and meter range switch set to lo. 1. Place battery meter toggle switch in the volts position. Battery voltage should read 25 27 vdc. If the battery voltage is less than 23 vdc, recharge the battery prior to performing step 2. 2. With the battery meter toggle switch in the volts position, press the battery load test button for 5 seconds, this places a 5Ω load on the battery. Voltage drop should not exceed 3 vdc. Form 5 battery test procedure The battery test key on the operator panel is used to test the condition of the Form 5 control battery. No external current/voltage meter is necessary for testing. The control performs a self test every 12 hours or when initiated by an external command. When a battery test is initiated, the spurious charge is first drained to allow the battery voltage to equalize. A 5Ω, 55 watt resistor is then placed across the battery terminals and a voltage drop is calculated. If the drop from the equalized voltage to the test voltage exceeds 2 volts, then the check battery led is illuminated. Follow the procedure to perform a battery test in the form 5 control. 1. Using the next and back keys, scroll through the lcd display to the battery monitor screen, either screen 29 or 31 depending on firmware version. 2. Note the normal volts and normal current readings from the screen. Charging: normal voltage should be between 25 31 volts with the higher voltage at colder temperatures. Under normal conditions, with ac connected and the battery trickle charging the current should read between 12 20 ma. With ac connected and in bulk charging mode, current will range from 12 600 ma. Discharging: with ac disconnected and the battery supplying the load, the current will read -180 to -350 ma depending on the accessories connected. 3. Momentarily, press the change/lamp test key, then the battery test key. Ac power can be either connected or disconnected for step 3. 4. Note the test volts reading from the lcd and the status of the check battery led. Service the battery if the check battery led is illuminated. Form 6 battery test procedure This procedure applies to Form 6 pole mount control only. The condition of the Form 6 control battery can be determined by using the battery test function in the battery menu. No external current/voltage meter is necessary for testing. Alarm conditions During a manual battery test a 5Ω, 55 watt resistor is placed across the battery terminals for approximately 5 seconds. The Form 6 control measures the battery voltage, if the voltage drops below 22.8 Vdc for one full second, the alarm led (battery alarm) is illuminated. When the Form 6 control is disconnected from ac power and the control battery drops below 23.5 Vdc for 60 seconds, the alarm led will illuminate. If the battery voltage continues to decay and drops below 22 vdc, the Form 6 control will shut down. Follow the procedure to perform a battery test in the Form 6 pole mount control. The battery test is blocked for 30 seconds upon power up of the control. 3 replacement instructions MN280074EN May 2017

NNote: Ac power can be either connected or disconnected for battery test. 1. Press the menu button on the front panel. 2. Using the down arrow key, navigate to the battery menu and press enter. 3. Using the down arrow key, navigate to the test battery menu and press enter. 4. Press the F4 button to test the battery. The message testing will appear on the LCD while the load is being applied to the battery. The battery test results will display in the battery metering menu. Voltage should be between 25 31 vdc with the higher voltage at colder temperatures. Under normal conditions, with ac connected and a fully charged battery, the charging current should be less than 20 ma. With ac connected and a discharged battery the current range should be between 20 and less than 450 ma. Current of 450 ma or greater indicates a problem with the charging circuit on the pole mount power supply. With ac disconnected and the battery supplying the load, current will read -400 to -600 ma depending on connected accessories. (On the LCD it will display as -0.40 To -0.60.) This battery test procedure should be conducted in a clean environment, such as a repair shop. Follow the procedure to perform a bench test on a control battery in a service shop: 1. Remove the control from service. Refer to the control s service information for the Remove the control from service procedure. 2. Remove the battery from the control and carefully transport it to a suitable service facility. 3. Measure battery voltage. 4. Apply test load and measure battery voltage after 5 seconds of load to determine voltage drop. Refer to Table 1 for bench test load condition. 5. Remove test load. Refer to Table 1 for battery test information. If the battery fails the test or is four years or older refer to Table 1 in the Battery replacement section for battery replacement information. For additional detail regarding battery testing, including charge and discharge rates, refer to the control s service information manual. Battery test on the bench Caution Recloser misoperation. The control must be removed from service before disconnecting the control battery. Disconnecting the control battery from an in-service control may cause recloser misoperation (unintentional operation). Failure to comply can result in equipment damage and personal injury. T213.4 replacement instructions MN280074EN May 2017 4

Battery test information Table 1. Control battery bench testing and replacement information Control type Battery Battery catalog part # Voltage Type Amp/Hour Bench test load condition for 5 sec. Acceptable voltage drop at end of test load Battery tester **Battery replacement kit Form 3/ Gould or KA450ME2S 24V Nickel- 1.5 10Ω, 3V KA638ME not Form 3A Gates or Cadmium 55 watt or less voltmeter required General or Electric *MET Tester FXA/FXB Hawker KFX-105-1 24V Lead 2.5 15Ω, 2V voltmeter or not Cyclon Acid 55 watt or less BATTERY required TEST button on control panel Form 4C Hawker KME4-215 24V Lead 8 5Ω, 3V Battery test not Cyclon Acid 55 watt or less panel required Form 5 Hawker KME4-215 24V Lead 8 5Ω, 3V BATTERY not Swing Cyclon Acid 55 watt or less TEST required Panel hot key on standard control panel capacity Form 5 Hawker KME5-134-1 24V Lead 13 5Ω, 2V BATTERY KME5-709-11 Swing Genesis (two Acid 55 watt or less TEST Panel or 12V hot key on or high Yuasa KME5-134-3 batteries) control panel KME5-709-14 capacity Form 5 Hawker KME4-215 24V Lead 8 5Ω, 3V BATTERY not Fixed Cyclon Acid 55 watt or less TEST required Panel hot key on standard control panel capacity Form 5 Hawker KME5-134-1 24V Lead 13 5Ω, 2V BATTERY KME5-709-17 Fixed Genesis or (two Acid 55 watt or less TEST or Panel Sonnenschein KME5-134-2 12V 18 hot key on KME5-709-12 high or batteries) control panel or capacity Yuasa KME5-134-3 12 KME5-709-13 Form 5/ Hawker KME5-134-1 24V Lead 13 5Ω, 2V BATTERY KME5-709-17 Triple- Genesis or (two Acid 55 watt or less TEST or Single Sonnenschein KME5-134-2 12V 18 hot key on KME5-709-12 high or batteries) control panel or capacity Yuasa KME5-134-3 12 KME5-709-13 Form 6 Hawker KME4-215 24V Lead 8 5Ω, 3V MENU not Pole Cyclon Acid 55 watt or less button on required Mount operator standard panel capacity Form 6 Hawker KME5-134-1 24V Lead 13 5Ω, 2V MENU not Pole Genesis (two Acid 55 watt or less button on required Mount 12V operator high batteries) panel capacity * Form 3 controls below serial number 10649 require a special battery-testing cable and adapter (ka1114me1) with the met tester. ** The form 5 control batteries have different dimensions; therefore, if the replacement battery ordered is a different brand than the original battery, a kit with mounting hardware may be required to accommodate the replacement battery size. 5 replacement instructions MN280074EN May 2017

Battery charging information Battery charging To maintain the battery charge, energize the control s built-in charger with ac power applied to the input terminal block. If it is not possible to charge the battery with the control s built-in charger, a portable bench type charger is available. Refer to Table 2 for the appropriate portable charger and charging procedures for each specific control. Do not attempt to charge a lead acid battery below 2 vdc with the ka43me7001 charger. The charger will not operate if it does not detect a battery above 2vdc. If the lead acid battery is below 19 vdc for more than two days, replace the battery. The expired battery should be disposed of in an environmentally responsible manner. Consult local regulations for proper battery disposal. Figure 1. KA43ME7001 battery charger replacement instructions MN280074EN May 2017 6

Table 2. Portable battery charging information Control type Portable charger Portable battery charging information* Form 3 /3A KA1142ME3 (120 VAC) or Charge discharged battery at 50 ma for 48 hrs KA1142ME4 (240 VAC) (CHARGE switch position), then adjust to 15 ma (MAINTAIN switch position) to maintain a full charge. Form 4C KME4-711 (240 VAC) charger kit Refer to instruction manual S280-77-7. FXA/FXB Form 5 swing panel std capacity Form 5 fixed panel std capacity or KA43ME7001 (120 VAC) Form 6 pole mount std capacity Form 5 swing panel high capacity Form 5 fixed panel high capacity Form 5 triple-single high capacity Form 6 pole mount high capacity KA43ME7001 (120 VAC) IMPORTANT Use adapter KME5-325-1 battery assembly to connect the two 12 Volt batteries to the KA43ME7001 charger. Never connect a single 12 Volt battery to the KA43ME7001 charger. * For more detailed charging instructions refer to the following instruction manuals: for chargers KA1142ME3 and KA1142ME4 refer to manual S280-75-61 for charger KME4-711 refer to manual S280-77-7 for charger KA43ME7001 refer to manual S280-79-14 Connect the battery directly to KA43ME7001 charger. The charger continuously monitors the battery voltage. A red LED indicator on the body of the charger illuminates when charging. The red LED blinks to indicate when the battery has reached a full charge. This process can take up to 24 hours. Use adapter KME5-325-1 battery assembly to connect the two 12 volt batteries to the KA43ME7001 charger. The charger continuously monitors the battery voltage. A red LED indicator on the body of the charger illuminates when charging. The red LED blinks to indicate when the battery has reached a full charge. This process can take up to 24 hours. Battery replacement In a typical application, the life expectancy of a lead acid battery is three to five years. To determine the state of the battery, perform a bench battery test. If a nickel-cadmium battery fails the bench battery test, recharge and retest. If it fails a second test replace the battery. Battery replacement is recommended after four years for lead acid batteries and five years for nickel-cadmium batteries, or if the battery fails the bench battery test procedure. Refer to table 1 to identify the appropriate replacement battery and whether a battery replacement kit is necessary. The form 5 control batteries have different dimensions; therefore, if the replacement battery ordered is a different brand than the original battery, a kit with mounting hardware may be required. Battery disposal Expired batteries should be disposed of in an environmentally responsible manner. Consult local regulations for proper battery disposal. 7 replacement instructions MN280074EN May 2017

! SAFETY FOR LIFE Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton s Power Systems Division 2300 Badger Drive Waukesha, WI 53188 United States Eaton.com/cooperpowerseries 2017 Eaton All Rights Reserved Printed in USA Publication No. MN280074EN KA2048-598 Rev: 05 May 2017 Eaton is a registered trademark. All trademarks are property of their respective owners. For Eaton s Cooper Power series product information call 1-877-277-4636 or visit: www.eaton.com/cooperpowerseries.