PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide

Similar documents
Product Overview. Product Identification. Amps One CT Two CTs Three CTs

ibusway for Data Center

Galaxy VM. Battery Breaker Box Installation 09/

Q-Frame Main Circuit Breaker (225 A Maximum) and Adapter Kit Installation onto an NQ Panelboard Class 1640

Galaxy 300 Battery Breaker Kit G3HTBKIT1

Instruction Bulletin NF Panelboard Dual Sub-Feed Circuit Breaker Adapter Kit Installation onto an NF Panelboard Class 1670

Instruction Bulletin Dual Sub-Feed Circuit Breaker and Adapter Kit Installation onto an NQ Panelboard Class 1640

Galaxy Receiving and Unpacking 09/

Models beginning with MO, MK, 7B, 6S, 6F or 5B. Product Description. Technical Specifications. Installation Instructions.

Altivar 61/71 Adjustable Speed Drives Plastic Kits and Power Terminal Kit

H- or J-Frame Main Circuit Breaker and Adapter Kit Installation onto an NQ Panelboard Class 1640

Symmetra PX with Maintenance Bypass

Transformer Installation, Operation, and Maintenance Manual

Galaxy kva 3:3 and 3:1. Receiving and Unpacking. 380/400/415 and 208/220 V 04/2016.

SAVE THESE INSTRUCTIONS

Electrical Installation

Owner's/Installation Manual

Symmetra PX. 48 kw 400 V, 96 kw 400 V, 100 kw 208 V, 160 kw 400 V. Receiving and Unpacking 01/2016.

Galaxy VM. Classic Battery Cabinet Installation GVMCBCWUE, GVMCBC2WUE, GVMCBC2WUF, GVMCBC3WUF 07/2017.

Electrical network protection VIP30, VIP35. User s manual 12/2008

SIGNAL WORDS QUALIFIED PERSON

ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL

SAVE THESE INSTRUCTIONS

Installation Guide Smart-UPS On-Line SRT1000/1500 UXI-NCLI, SRT1000/1500 UXI-LI, Tower/Rack-Mount

Symmetra PX. 250/500 kw 400/480 V Single and Parallel Installation 07/

Installation Instructions

Temperature Control Panel Wiring Diagram Model: ISPA-120-1P-15A

Technical Manual. DLM Module. This manual should remain with the unit.

Technical Specificaions. kwh Energy Meter

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION

Enclosure for AMP1 Series Energy Meters with Swing Panel Kit

dans un panneau de distribution NQ Instruction Bulletin Boletín de instrucciones Directives d'utilisation

O & M Manual for the EATON Generator Ready Loadcenter

Safety and General Information

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR NEW YORK 18 WATT SERIES

Galaxy Installation 08/

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

Altivar 61/71 Adjustable Speed Drives Spare Parts Kits

TEMPORARY ELECTRIC WIRING FOR CARNIVALS, CONVENTIONS, EXHIBITIONS, FAIRS AND SIMILAR USES

Symmetra PX kw 208 V. Installation 01/

Installation Guide Smart-UPS On-Line SRT1000/SRT1500 XLA Tower/Rack-Mount

INSTRUCTIONS FOR THE RELIANCE CONTROLS ARM SERIES AUTOMATIC TRANSFER SWITCH

AE012 Enclosure for E5x Series Energy Meters With Swing Panel Kit Product Overview

Quik-Spec Coordination Panelboard

User Manual. Solar Charge Controller 3KW

Galaxy VM. Modular Battery Cabinets Installation GVMMODBCW, GVMMODBCN 09/

Hubbell has a policy of continuous product improvement. Please visit hubbellpowersystems.com to confirm current design specifications.

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

Installing Power Components

Galaxy VX. 380 V, 400 V, 415, and 440 V UPS System Technical Specifications 12/

Symmetra PX 20 kw. InfrastruXure 208 V. Installation 01/

VD0C06N908C July 1998 Raleigh, NC, USA. Instruction Bulletin ALTIVAR 66, ALTIVAR 58, ALTIVAR 18. Dynamic Braking Resistor Kit User s Manual

CTRC Series Flexible Rogowski Current Transformer - Installation Guide

SAVE THESE INSTRUCTIONS

Jefferson Public Works Shop Building 2011

INSTRUCTIONS FOR THE RELIANCE Fast/Tran TM ARL0909 & ARL0909R

Quick Start Guide TS 910 & TS 920

SINAMICS G130. Motor reactors. Operating Instructions 05/2010 SINAMICS

Pneumatic Isolation Module

GE Grid Solutions. Multilin Meter Enclosure. Instruction Manual. Manual P/N: A4 Manual Order Code: GEK C LISTED * A4*

Electronically Commutated Motor Wiring Manual

DC POWER SUPPLY ALIMENTATION C.C.

RT Series Step Down Transformer for RT Series UPS 6-10kVA UL Input Vac Output Vac User Guide

PF Guard Power Factor Capacitor Bank Installation, Operation, and Maintenance Manual

www. ElectricalPartManuals. com Instruction Bulletin ALTIVAR FLEX58 TRX Adjustable Speed Chassis Drive Controllers Installation Guide

Clark Public Utilities Commercial Electric Service Handbook. This page left blank intentionally.

ENTRANCE EQUIPMENT ER D PAGE 1 OF 5

Installation Guide Smart-UPS 1200/1500 VA 100/120/230 Vac Rack-Mount 1U

INSTRUCTIONS. Power Panel. Installation Instructions

Freedom egen System End-of- Line Functional Checklist

Dry Contact Closure Interface

SynergEX Panelboards for Hazardous Locations

Start UP Guide. Symmetra LX Tower Rack-Mount. UPS Models 200 V, 4-8 kva 208/240 V, 4-8 kva 220/230/240 V, 4-8 kva

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2

Installation Instructions

Asymmetrical Installation Instructions. Components: i2cove Asymmetrical LED Light Fixtures. 12 [305mm] [918mm] 48.

Smart-UPS VT kva 208/220 V Single and Parallel Installation. With Batteries 11/2016.

North America Phase Converters & Electrical Supply

Quick Start Guide TS 910

Power-Zone 4 Low Voltage, Metal-Enclosed Drawout Switchgear with Masterpact Low Voltage Power Circuit Breakers Class 6037

SDM320D / SDM320A. Single phase din rail meter SDM320D / SDM320A user manual

Sunny Boy Accessories SUNNY BOY COMBINER BOX TLUS SBCBTL6

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE

9200 Revenue Meter. Model Certification Current Inputs. Complies with the accuracy requirements of the ANSI C Revenue Metering Standard

Installation Instructions for Load Management Kit A051C329

Altivar 58 TRX Adjustable Speed Drive Controllers in Motor Control Centers hp, 480 V or 1 50 hp, 208/240 V Class 8998

ALWAYS SAVE THIS BOOK FOR FURE REFERENCE.

Installation Instructions For Motor Control Center (MCC) Units

Company Switch Installation Instructions and User Manual

High Frequency SineWave Guardian TM

INSTALLATION MANUAL ELECTRIC DOUBLE OVEN RANGE

AMENDMENT ELECTRIC SERVICE MANUAL 2014

Galaxy VX. 480 V UPS System Technical Specifications 07/

Installation Instructions

Dead Tank Outdoor Vacuum Circuit Breaker, Type VOX

CABINET - CURRENT TRANSFORMER Indoor - Outdoor 240 Volts Amperes Maximum

SE-125 MANUAL GROUND-FAULT GROUND-CHECK MONITOR

Installation Instructions

PowerWorx Power Distribution Products Select Series Circuit Breaker for ±24 or ±48 Vdc User Manual

SM-1700 Secondary Shunt Trip Coil Assembly. Powered by Safety

Transcription:

PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide 7002-0289-00 Instruction Bulletin

HAZARD CATEGORIES AND SPECIAL SYMBOLS Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service, or maintain it. The following special messages may appear throughout this bulletin or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure. The addition of either symbol to a Danger or Warning safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed. This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death. DANGER DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING WARNING indicates a potentially hazardous situation which, if not avoided, can result in death or serious injury. CAUTION CAUTION indicates a potentially hazardous situation which, if not avoided, can result in minor or moderate injury. CAUTION CAUTION, used without the safety alert symbol, indicates a potentially hazardous situation which, if not avoided, can result in property damage. Provides additional information to clarify or simplify a procedure. PLEASE NOTE Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

70002-0289-00 PowerLogic High Density Metering System 12/2007 Table of Contents 4-METER ENCLOSURE Introduction... 1 Box Contents... 1 Parts and Accessories... 1 Safety Precautions... 2 Specifications... 2 Installation... 4 Mounting the Enclosure... 6 Mounting Dimensions... 8 Wiring Connections... 10 Shorting Block Use... 11 Current Transformers... 12 Wiring Diagrams... 13 Control Power... 15 Replacing CPT Secondary-Side Fuse... 16 Communications... 17 Initializing the Meters... 17 Removing a Meters... 18 Cover Plates... 19 METER WIRING PATTERNS Safety Precautions... 21 Wire Colors... 21 2007 Schneider Electric All Rights Reserved i

PowerLogic High Density Metering System 70002-0289-00 Table of Contents 12/2007 ii 2007 Schneider Electric All Rights Reserved

70002-0289-00 PowerLogic High Density Metering System 12/2007 4-Meter Enclosure SECTION 1 4-METER ENCLOSURE INTRODUCTION The PowerLogic High Density Metering System is used to monitor the amount of electricity used in individual units of multi-unit residential or commercial buildings. The system consists of one or more power meters housed in a wall-mounted metal cabinet or enclosure. Multiple enclosures may be installed at a single location. Meters are assigned to a tenant who occupies an individual unit within a complex. The meter monitors and records the energy consumed inside the unit. At pre-determined times, tenant billing software polls the meter through a communications link to gather usage information. This information can be used as a means of monitoring overall electrical usage or to generate an electric bill for the tenant. Some states do not permit sub-billing. Before billing tenants, check your state and local regulations. BOX CONTENTS PARTS AND ACCESSORIES The following components are shipped with the 4-Meter Enclosure: Enclosure containing pre-installed meters (if any), shorting blocks, ground bar, wiring harness, and disconnect MCT2W terminating resistor Cover plate assembly kit Installation bulletin for meter This installation guide The following PowerLogic meters can be mounted in the enclosure: PM210 PM750 ION6200 The enclosure is typically shipped with the meters factory-installed and wired. The 4-Meter Enclosure can contain from 0-4 meters. Table 1 lists part numbers and accessories for the High Density Metering System 4-Meter Enclosure. Table 1: Parts and Accessories Description PowerLogic Power Meter Cover Plate Assembly Kit Part Number See Power Meter installation document (PM210, PM750, ION6200). 96DINCVRPLT For more information on your particular meter, see the meter installation bulletin (also available in the technical library at www.powerlogic.com). PowerLogic Tenant Metering Software is purchased separately and includes installation and use instructions. 2007 Schneider Electric All Rights Reserved 1

PowerLogic High Density Metering System 70002-0289-00 4-Meter Enclosure 12/2007 SAFETY PRECAUTIONS This section contains important safety precautions that must be followed before attempting to install, service, or maintain electrical equipment. Carefully read and follow the safety precautions outlined below. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E. This equipment must be installed and serviced only by qualified electrical personnel. Turn off all power supplying this equipment before working on or inside equipment. Always use a properly rated voltage sensing device to confirm that power is off. All unused conductors not terminating in an insulated connector or plug at the enclosure bracket(s) must be protected using enclosed heat shrink sleeves or electrical tape. Replace all devices, doors, and covers before turning on power to this equipment. Failure to follow this instruction will result in death or serious injury. WARNING BONDING BETWEEN METALLIC PARTS IS NOT AUTOMATIC. SUPPLIED SCREW MUST BE INSTALLED TO MAINTAIN BONDING. Failure to follow this instruction can result in electrical shock. SPECIFICATIONS Table 2: Technical Specifications PHYSICAL CHARACTERISTICS Dimensions Without hood W 7.42 inches, H 30.8 inches, D 7.37 inches [W 189 mm, H 288 mm, D 188 mm] W 7.88 inches, H 31.5 inches, D 7.50 inches With hood [200.03 mm, H 303 mm, D 191 mm] Mounting Wall mount Weight (maximum including meter, hood, and Control Power 46 lbs./22.2 kg. Transformer (CPT)) COMMUNICATIONS RS485 port POWER 2-wire, up to 19200 baud, Modbus RTU Power specifications vary according to equipment configuration. See separate power specifications in Table 3. 2 2007 Schneider Electric All Rights Reserved

70002-0289-00 PowerLogic High Density Metering System 12/2007 4-Meter Enclosure Table 2: Technical Specifications (continued) ENVIRONMENTAL CHARACTERISTICS Meter operating temperature PM210, PM750-10 C to +55 C ION6200-20 C to +70 C Storage temperature -40 C to +85 C Humidity rating 5 to 95% RH at 50 C (non-condensing) Pollution degree 2 Altitude 9842 ft./3000 m STANDARDS US and Canada Enclosure UL 508A Meter Accuracy Rating PM210 ANSI C12.16 Accuracy Class 1 PM750 ANSI C12.20 Accuracy Class 0.5 ION6200 ANSI C12.20 Accuracy Class 0.5 Table 3: Power Specifications Meter Specification Without Control Power Transformer (CPT) PM210 PM750 ION6200 With CPT PM210 PM750 ION6200 CT inputs CT inputs Voltage Inputs PM210/PM750 ION6200 115 to 415 ± 10% Vac, 5 VA x 4 = 20 VA; 50 to 60 Hz or 125 to 250 ± 20% Vdc, 3W 115 to 415 ± 10% Vac, 5 VA x 4 = 20 VA; 50 to 60 Hz or 125 to 250 ± 20% Vdc, 3-wire 100 to 240 Vac, 13 VA x 4 = 52 VA; 50 to 60 Hz or 110 to 300 Vdc, 8W 480 ± 10% Vac, 30 VA; 60 Hz 480 ± 10% Vac, 30 VA; 60 Hz 480-600 ± 10% Vac, 65 VA; 60 Hz 5 A nominal, 6 A maximum 10 to 480 Vac (L-L) 10 to 277 Vac (L-N) 10 to 1.6 MVac with external VT 100 to 600 Vac (L-L) 60 to 347 Vac (L-N) 2007 Schneider Electric All Rights Reserved 3

PowerLogic High Density Metering System 70002-0289-00 4-Meter Enclosure 12/2007 INSTALLATION The 4-Meter Enclosure is available in two configurations (see Figure 1). The Type 1 configuration has clear viewing windows in the door and is intended for indoor applications. The Type 3R configuration has a rain hood and a solid door (no viewing windows) and is intended for outdoor applications. The door is equipped with a hasp for a lock or seal to prevent tampering. Figure 1: 4-Meter Enclosure Type 1 Type 3R Rain hood Hasp 4 2007 Schneider Electric All Rights Reserved

70002-0289-00 PowerLogic High Density Metering System 12/2007 4-Meter Enclosure The meters, interior components, and wiring connections are covered by a protective, removable, exterior case enclosure. To access the interior, remove the case from the supporting base/backplate (see Figure 2). The meters are positioned on a supporting bracket attached to the base/backplate that swivels outward to allow access to the back of the meter and terminals for field wiring. To remove the case, complete these steps: 1. Push the locking bar up to open the door. 2. Remove the front bonding screw. 3. Lift the case up and out to slide off the base/backplate. Figure 2: Case Removal 3 1 2 2007 Schneider Electric All Rights Reserved 5

PowerLogic High Density Metering System 70002-0289-00 4-Meter Enclosure 12/2007 MOUNTING THE ENCLOSURE Mount the metering enclosure next to the distribution panelboard that serves the load to be monitored. The recommended clearances for the installed enclosure are shown in Figure 3 below: Figure 3: Recommended Enclosure Clearances 1. Top View A 2. Top View B 3. Front View A 1 69 2.7 2 147 5.8 4. Front View B MIN. CLEARANCE TO THE LEFT MIN. CLEARANCE TO THE RIGHT 3 4 19.8 MIN. CLEARANCE ABOVE 6 2007 Schneider Electric All Rights Reserved

70002-0289-00 PowerLogic High Density Metering System 12/2007 4-Meter Enclosure EQUIPMENT DAMAGE HAZARD CAUTION Do not drill into the enclosure. Drilling will produce metal shavings that may fall into vents, reduce spacings, and possibly create electrical short circuits. Failure to follow this instruction can result in equipment damage. Six (6) pre-drilled 3/8-inch holes are provided on the backplane of the enclosure for mounting. Use #10 or up to 5/16 inch screws, with washers, to attach the enclosure to the wall. Always mount with a minimum of six (6) screws. Figure 4 shows the pre-drilled mounting holes and knockout points for the electrical conduit. Figure 4: Mounting Holes and Conduit Knockouts Mounting Holes Electrical Conduit Knockouts 2007 Schneider Electric All Rights Reserved 7

PowerLogic High Density Metering System 70002-0289-00 4-Meter Enclosure 12/2007 Mounting Dimensions Figure 5 shows dimensions for the enclosure without the hood. Figure 6 shows dimensions for the enclosure with a hood. Measurements shown are in [millimeters] and inches. Figure 5: Dimensions for Type 1 Enclosure (without Hood) A. Front view B. Back view C. Side view D. Top view 192 7.5 349 13.8 A 783 30.8 B 349 13.8 FRONT 121 4.8 BACK C D 187 7.4 TOP LEFT 8 2007 Schneider Electric All Rights Reserved

70002-0289-00 PowerLogic High Density Metering System 12/2007 4-Meter Enclosure Figure 6: Dimensions for Type 3R Enclosure (with Hood) A. Front view B. Back view C. Side view D. Top view 200 7.9 A B 349 13.8 798 31.4 349 13.8 FRONT 121 4.8 7.5 [190] BACK C D 190 7.5 TOP LEFT 2007 Schneider Electric All Rights Reserved 9

PowerLogic High Density Metering System 70002-0289-00 4-Meter Enclosure 12/2007 WIRING CONNECTIONS Conduit knockouts are provided on the enclosure (see Figure 4 on page 7). To comply with national and local standards, Class 1 (voltage input) wiring must be kept separate from Class 2 (current transformer and communications) wiring. Refer to NEC code and local codes before installing. For all field wiring, use copper conductors with 600V rated insulation only. Control power and voltage inputs require overcurrent protection external to the enclosure. Voltage inputs must be connected to the load side of a Class CC, G, J, RK1, RK5, L or T 15A branch circuit fuse or inversetime/instantaneous-trip circuit breaker. Use copper conductors only. Conduit hubs must be rated to the same weather rating as the enclosure and must comply with the standard for Conduit, Tubing and Cable Fittings, UL 514B. The wiring configuration is designed specifically for the High Density Metering System application. Do not change the wiring configuration. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E. This equipment must be installed and serviced only by qualified electrical personnel. Turn off all power supplying this equipment before working on or inside equipment. Always use a properly rated voltage sensing device to confirm that power is off. All unused conductors not terminating in an insulated connector or plug at the enclosure bracket(s) must be protected using enclosed heat shrink sleeves or electrical tape. Replace all devices, doors, and covers before turning on power to this equipment. Failure to follow this instruction will result in death or serious injury. 10 2007 Schneider Electric All Rights Reserved

70002-0289-00 PowerLogic High Density Metering System 12/2007 4-Meter Enclosure Shorting Block Use See Figure 7 and follow the instructions below for using the shorting blocks. Figure 7: Shorting Block Use Internal wiring to meter current inputs GND I123 - I1+ I2+ I3+ NOTE: Short block is shown in shorted position. WARNING HAZARD OF ELECTRICAL SHOCK Do not loosen slider screws or attempt to move sliders. These screws are locked in place at the factory. Failure to follow these instructions can result in death or serious injury. Shorting Bar Screws DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Before loosening the screws: Remove all power from the circuit. Use a properly rated voltage sensing device to confirm that all power is off. Failure to follow these instructions can result in death or serious injury. I123 - GND I1+ I2+ I3+ Sliding Shorting Bar Shorting the Current Inputs By default, the current inputs are shorted when you receive the enclosure. To short the current inputs, complete these steps: 1. Turn off all power supplying this equipment before working on or inside this equipment. Use a properly rated voltage sensing device to confirm that all power is off. 2. Loosen the four (4) shorting bar screws. 3. Slide shorting bar toward field connection screws or bottom of the enclosure. 4. Tighten all four (4) shorting bar screws (6 ± 1 in. lbs.). 2007 Schneider Electric All Rights Reserved 11

PowerLogic High Density Metering System 70002-0289-00 4-Meter Enclosure 12/2007 Removing Short from Current Inputs Current Transformers To measure the energy from the circuit, you must remove the default short from the current inputs. To remove short from the current inputs, complete these steps: 1. Turn off all power supplying this equipment before working on or inside this equipment. Use a properly rated voltage sensing device to confirm that all power is off. 2. Ensure field wiring leads from current transformers are securely connected to the shorting block. 3. Ensure wiring within the enclosure is securely connected to a metering device. 4. Loosen the four (4) shorting bar screws. 5. Slide shorting bar away from field connection screws or toward the top of the enclosure. 6. Tighten the left-most (GND) shorting bar screw. Field-installed current transformer (CT) leads require stripped wire terminal connections. The CT shorting block is shipped in the shorted position by default from the factory. Recommend metering class current transformers with 5A secondary. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Never open circuit a CT; use the shorting block to short circuit the leads of the CT before attaching or removing any meter. Failure to follow this instruction will result in death or serious injury. 12 2007 Schneider Electric All Rights Reserved

70002-0289-00 PowerLogic High Density Metering System 12/2007 4-Meter Enclosure Wiring Diagrams The wiring diagrams in this manual use the symbols shown in Table 4. Table 4: Wiring Diagram Symbols Symbol Description Voltage disconnect switch Fuse Earth Ground Protective conductor terminal symbol S1 Current transformer S2 Shorting block Potential transformer US equivalent: NOTE: The disconnect circuit breaker must be placed within reach of the power meter and labeled: Disconnect Circuit Breaker for Power Meter. 2007 Schneider Electric All Rights Reserved 13

PowerLogic High Density Metering System 70002-0289-00 4-Meter Enclosure 12/2007 Figure 8: 1-Phase 2-Wire System Line-to-Neutral 1CT Figure 9: 1-Phase 2-Wire System Line-to-Line 1CT N L1 L1 L2 V N V 1 V 2 V 3 V N V 1 V 2 V 3 S2 S1 I 123 I 1+ I 2+ I 3+ S2 S1 I 123 I 1+ I 2+ I 3+ For PM210 and PM750, use System Type 10. For ION6200, use Volts Mode 2W. To avoid distortion, use parallel wires for control power and voltage inputs. Keep the fuse close to the power source. For PM210 and PM750, use System Type 11. For ION6200, use Volts Mode 2W. To avoid distortion, use parallel wires for control power and voltage inputs. Keep the fuse close to the power source. Use with 120/240 V systems. Figure 10: 1-Phase Direct Voltage Connection 2 CT Figure 11: 3-Phase 3-Wire 2 CT no PT N L1 L2 L1 L2 L3 V N V 1 V 2 V 3 V N V 1 V 2 V 3 S2 S1 S2 I 123 I 1+ I 2+ I 3+ S2 S1 S2 I 123 I 1+ I 2+ I 3+ S1 S1 For PM210 and PM750, use System Type 12. For ION6200, use Volts Mode 2W. To avoid distortion, use parallel wires for control power and voltage inputs. Keep the fuse close to the power source. For PM210 and PM750, use System Type 30. For ION6200, use Volts Mode Delta Direct. Figure 12: 3-Phase 3-Wire 3 CT no PT Figure 13: 3-Phase 4-Wire Wye Direct Voltage Input Connection 3 CT L1 L2 L3 N L1 L2 L3 V N V 1 V 2 V 3 V N V 1 V 2 V 3 S2 S1 S2 S1 S2 I 123 I 1+ I 2+ I 3+ S2 S1 S2 S1 S2 I 123 I 1+ I 2+ I 3+ S1 For PM210 and PM750, use System Type 31. For ION6200, use Volts Mode Delta Direct. S1 For PM210 and PM750, use System Type 40. For ION6200, use Volts Mode 4W-Wye. Use with 208Y/120 V, 480Y/277 V, and 600Y/347 V (ION6200 only) systems. 14 2007 Schneider Electric All Rights Reserved

70002-0289-00 PowerLogic High Density Metering System 12/2007 4-Meter Enclosure Control Power Control power wiring depends on the installed meter. For the PM210 and PM750, see Figure 14 and Figure 15. For the ION6200, see Figure 16 and Figure 17. Using jumpers, control power can be derived from the phase conductors. Control power can also be supplied by a separate feed. Power Meters PM210 and PM750 Figure 14: Direct Connect Control Power (Phase to Phase) < 415 + 10% Vac Figure 15: Direct Connect Control Power (Phase to Neutral) < 300 + 10% Vac L1 L2 V+ V- NL1 V+ V- Control power source > 415 Vac (L-L) or > 300 Vac (L-N) require a control power transformer. A control power transformer is available in this enclosure by specifying an input voltage range of 4T, which allows control power connections of 480-600 ± 10% Vac (PM210, PM750, ION6200). ION6200 Meter Figure 16: Direct Connect Control Power (Phase to Phase) < 240 + 10% Vac Figure 17: Direct Connect Control Power (Phase to Neutral) < 240 + 10% Vac L1 L2 V+ V- NL1 V+ V- Control power source > 240 Vac requires a control power transformer. A control power transformer is available in this enclosure by specifying an input voltage range of 4T, which allows control power connections of 480-600 ± 10% Vac. 2007 Schneider Electric All Rights Reserved 15

PowerLogic High Density Metering System 70002-0289-00 4-Meter Enclosure 12/2007 Replacing CPT Secondary-Side Fuse You must remove the finger guards to replace the fuse. The fuse should be a 5A, 260V, 5AG standard fuse (Bussman #FNQ-5 or equivalent). See Figure 18 below. Figure 18: Remove Finger Guards Fuse Finger Guard 16 2007 Schneider Electric All Rights Reserved

70002-0289-00 PowerLogic High Density Metering System 12/2007 4-Meter Enclosure Communications Figure 19: RS485 Serial Modbus Connection The last panel on daisy chain must be terminated. Use the MCT2W terminating resistor, included with enclosure. Torque all screws to 10± 1 in.-lbs (1.13 n-m ± 0.1) Multiple enclosures can be daisy-chained together. The maximum number of meters on a daisy-chain is 32. See the separate meter instruction bulletin for more information on communications connections. The terminator should be removed when connecting additional enclosures. The meters use common daisy-chain wiring and communicate using Modbus protocol over RS485. The last meter in the chain must be terminated. Figure 19 shows the communications connections. + - SHD white/blue blue/white + - shield Belden 9841 Terminator for last meter in daisy chain only. INITIALIZING THE METERS The meter must be initialized before placing into service. For instructions on initializing the meters, see the meter instruction bulletin shipped with the enclosure (also available at www.powerlogic.com). 2007 Schneider Electric All Rights Reserved 17

PowerLogic High Density Metering System 70002-0289-00 4-Meter Enclosure 12/2007 REMOVING A METERS If you need to remove a meter from the enclosure, a cover plate must be attached unless another meter is inserted into the slot. See Cover Plates on page 19. DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E. This equipment must be installed and serviced only by qualified electrical personnel. Turn off all power supplying this equipment before working on or inside equipment. Always use a properly rated voltage sensing device to confirm that power is off. All unused conductors not terminating in an insulated connector or plug at the enclosure bracket(s) must be protected using enclosed heat shrink sleeves or electrical tape. Replace all devices, doors, and covers before turning on power to this equipment. Failure to follow this instruction will result in death or serious injury. WARNING BONDING BETWEEN METALLIC PARTS IS NOT AUTOMATIC. SUPPLIED SCREW MUST BE INSTALLED TO MAINTAIN BONDING. Failure to follow this instruction can result in electrical shock. To remove a meter, complete these steps: 1. Turn off all power supplying this equipment before working on or inside this equipment. Use a properly rated voltage sensing device to confirm that all power is off. 2. Turn off the disconnect switch, located below the bottom meter. (See Figure A 1 on page 22.) 3. Short CT shorting block. 4. Remove the meter. 5. Insulate any loose wires, especially from the ION6200 meter. 6. Turn on the disconnect switch. 7. Restore power. Do not remove the short on the current transformer shorting block while the meter is removed from the enclosure. 18 2007 Schneider Electric All Rights Reserved

70002-0289-00 PowerLogic High Density Metering System 12/2007 4-Meter Enclosure COVER PLATES Figure 20: Cover Plate Cover plates are used to cover openings when no meter is present. Any time a meter is removed from the enclosure, a cover plate must be attached unless another meter is inserted into the slot. Figure 20 shows the cover plate assembly. To Install: 1. Align the cover plate with the cut-out on the enclosure bracket door as shown. 2. Hook either the left or right locking tab into cut-out engaging the edge of the opening. 3. Rotate opposite tab until it contacts the edge of cut-out. 4. Press on cover plate surface to fully seat cover plate in opening. 5. Install the two thread- forming screws into opposite corners as shown. 6. Using an IP30 TORX Plus driver, torque the screws to 40 45 in.-lbs. (4.52-5.08 n-m) Mounting Screws Torque to 40 45 in.-lbs. Mounting Holes 2007 Schneider Electric All Rights Reserved 19

PowerLogic High Density Metering System 70002-0289-00 4-Meter Enclosure 12/2007 20 2007 Schneider Electric All Rights Reserved

70002-0289-00 PowerLogic High Density Metering System 12/2007 Meter Wiring Patterns APPENDIX A METER WIRING PATTERNS SAFETY PRECAUTIONS DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Turn off all power supplying this equipment before working on or inside equipment. Use a properly rated voltage sensing device to confirm that all power is off. Replace all devices, covers, and close all doors before turning on power to this equipment. Before energizing enclosure, all unused spaces must be filled with blank covers. Use only established wiring configuration designed for the High Density Metering System. Failure to follow this instruction will result in death or serious injury. Figure A 1 on page 22 shows a partial diagram of the typical field connections inside the enclosure. Meters are all wired in the same manner. Table A 1 lists the wire colors. Wire Colors Table A 1: Control Power Voltage Current Comm Wire Colors V+ Yellow V- White V1 Black V2 Red V3 Blue VN White I1- White I2- White I3- White I1+ Black I2+ Red I3+ Blue - Black + Red SH Bare GND Green/Yellow 2007 Schneider Electric All Rights Reserved 21

PowerLogic High Density Metering System 70002-0289-00 Meter Wiring Patterns 12/2007 Figure A 1: Typical field connections Current Inputs for Meter 2 Disconnect Switch RS485 Communication Connections Phase Voltage Inputs Current Inputs for Meter 1 Control Power Input 22 2007 Schneider Electric All Rights Reserved

Schneider Electric USA Power Monitoring and Control 295 Tech Park Drive Ste 100 LaVergne, TN 37086 USA www.powerlogic.com Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. 70002-0289-00 2007 Schneider Electric All Rights Reserved 12/2007