SBS-Control. Table of contents. Operating Instructions BKS24-9A. Operating Instructions

Similar documents
D6.. Butterfly valves. For controlled operation.

Shut-off and butterfly valves for open-close applications and control mode

Butterfly valves for open-close applications and control mode

Imports of seed for sowing by country Calendar year 2011 Source: ISF compilation based on official statistics and international seed trade reports

AUSTRIA. Table 1. FDI flows in the host economy, by geographical origin. (Millions of US dollars)

Lifting Instructions for 1336 PLUS and FORCE D Frame Drives

Global Dialysis - Cost per Dialysis Session

Infographics on Electromobility (January 2019)

67 th edition. Renewable energy. Appendices. 44 Other renewables consumption 45 Biofuels production

Packing Data Installation Instructions

BP Statistical Review of World Energy June 2017

JURISDICTIONS PARTICIPATING IN THE CONVENTION ON MUTUAL ADMINISTRATIVE ASSISTANCE IN TAX MATTERS

JURISDICTIONS PARTICIPATING IN THE CONVENTION ON MUTUAL ADMINISTRATIVE ASSISTANCE IN TAX MATTERS

JURISDICTIONS PARTICIPATING IN THE CONVENTION ON MUTUAL ADMINISTRATIVE ASSISTANCE IN TAX MATTERS

Global Competitiveness Index Rankings

9.01 ICT use for business-to-business transactions

19,000 38,500. Mean Crop. 5, ,827 Max , ,869 Last Year 6, ,

Universal Charging and Testing Unit FPU-1 for Bladder, Piston and Diaphragm Accumulators

Summary of debt securities outstanding

Allen-Bradley 1397 Pulse Encoder Interface Card

Charging and testing unit FPU for Bladder, Piston and Diaphragm Accumulators

Primary energy. 8 Consumption 9 Consumption by fuel. 67 th edition

Universal Charging and Testing Unit FPU-1 for Bladder, Piston and Diaphragm Accumulators

Production of heat by type Terajoules

Table 5 Production, trade and supply of hard coal Thousand metric tons and kilograms per capita

Table 5 Production, trade and supply of hard coal Thousand metric tons and kilograms per capita

The new STx chain hoist NEW. Sophisticated technology prepared for the future

Table 23 Production of minor oil products from refineries - by type Thousand metric tons

UAE draft regulation for Electric Vehicle

Total credit to the non-financial sector (core debt), % of GDP Table F1.1

35,000 52,000 87,000 1,600 8, ,400 76,600. Mean Crop. Monthly YTD Min ,671 8,211 Max. 2017

Production of minor oil products from refineries - by type Thousand metric tons

1. INTERNATIONAL OVERVIEW. 1.0 Area and population. population (1,000) area

1204 Terminator. Instructions 1204 T F B2. (Catalog Number 1204-TFA1, 1204-TFB2) Where this Option is Used. What this Option Contains

5.01 Secondary education enrollment rate

CSM-K. high capacity clean steam generator

Spain s exports by oil product group and country of destination

Climate control for the future Holistic process protection

2.01 Availability of latest technologies

FEDERAL RESERVE statistical release

KINGDOM OF CAMBODIA NATION RELIGION KING 3

Section III Macroeconomic environment

control & instrumentation solutions The AEL6 series smart electric actuator

Microsoft Social Engagement Translation Guide Last Updated: October 2017

FLUID REPLACEM Brake fluid and engine coolant (antifreeze and water solution) must be completely replaced at specific intervals. See table below. Your

KINGDOM OF CAMBODIA NATION RELIGION KING 3

KINGDOM OF CAMBODIA NATION RELIGION KING 3

Rectangular photoelectric proximity switches

Production of heat by type Terajoules

KINGDOM OF CAMBODIA NATION RELIGION KING 3

LPI ranking and scores, 2014

KINGDOM OF CAMBODIA NATION RELIGION KING 3

KINGDOM OF CAMBODIA NATION RELIGION KING 3

KINGDOM OF CAMBODIA NATION RELIGION KING 3

KINGDOM OF CAMBODIA NATION RELIGION KING 3

KINGDOM OF CAMBODIA NATION RELIGION KING 3

CrimpTest-1 kn. Calibration Bracket

Portable Compressors MOBILAIR M 122 With the world-renowned SIGMA PROFILE Free air delivery 11.1 m³/min

I. World trade in Overview

Spain s exports by oil product group and country of destination. Year Corporación de Reservas Estratégicas de Productos Petrolíferos

THE WITTUR ANSWER TO THE MACHINE ROOMLESS MARKET REQUIREMENTS. MRL W Line. EMOTION IN MOTION

Table 16 Refinery distillation capacity, throughput and output Thousand metric tons

YOUR PARTNER IN MIXING

Spain s imports by oil product group and country of origin

Table 13 Production, trade and supply of conventional crude oil Thousand metric tons; kilograms per capita; reserves production ratio (R/P) in years

Instruments and accessories

Table 13 Production, trade and supply of conventional crude oil Thousand metric tons; kilograms per capita; reserves production ratio (R/P) in years

Mechatronic brake system INTORQ Control

Table 16 Refinery distillation capacity, throughput and output Thousand metric tons

EVOline Socket Modules

Table 13 Production, trade and supply of conventional crude oil Thousand metric tons; kilograms per capita; reserves production ratio (R/P) in years

Production (bbl/day)

MODERNISATION SOLUTIONS. MRM W Line. TIME FOR A FACE-LIFT!

Product Overview INCH

Flying production. with travelling HF welding machines TDW & TDW-Mega. Built for you. Built to last. machines equipment expertise service

Appendix E. Average Percent Correct in the Mathematics Content and Cognitive Domains TIMSS 2011 INTERNATIONAL RESULTS IN MATHEMATICS APPENDIX E 459

Kernel Wt. 533,229,317 1,005,999,479 1,539,228, ,964, ,947, ,911, Crop Year

MODERNISATION SOLUTIONS. MRM W Line. T I M E T O M A X I M I Z E YO U R S P A C E!

World Air Conditioner Demand by Region

Fork through-beam sensors

WORLD MOTOR VEHICLE PRODUCTION BY COUNTRY AND TYPE QUARTERS June 14, 2018

Parents Perceptions of School Performance Scale, Fourth Grade

Fork through-beam sensors

Summary of Contributions to UN Peacekeeping by Country and Post.

Thermal Coal Market Presentation to UNECE Ad Hoc Group of Experts on Coal in Sustainable Development December 7, 2004

AlixPartners Automotive Electrification Index. Second Quarter 2017

Spain s imports by oil product group and country of origin

PLASTIC WELDING. New! TRIAC AT. Intelligent and robust.

STATISTICAL ANNEX NOTE ON QUARTERLY PROJECTIONS

Civil Dialogue Group on WINE Thursday April 19th, 2018

PLASTIC WELDING. New! TRIAC AT. Intelligent and robust.

Spain s imports by oil product group and country of origin

Coal. 36 Reserves and prices 38 Production and consumption. 67 th edition

Table F3.1 TIMSS 4th grade scores by GDP per capita (PPP), GDP per capita (USD) Math score

Emissions per capita and GDP

Citrus Fruit - Fresh and Processed Statistical Bulletin 2016

Selection Guide for P Series Pump Accessories & Options

Made UNDER high pressure

ACEA Report. Vehicles in use Europe 2017

Performance Derby: MSCI Regions/Countries Earnings & Revenues Growth 2019E / 2018E / 2017A

Transcription:

Operating Instructions BKS24-9A Operating Instructions BKS24-9A Table of contents Operating Instructions 1 Operating controls and indicators 2 2 Preparations for faultless commissioning and operating 3 3 Programming the number of dampers per BKS24-9A 4 4 Adding / removing of dampers 5 5 System testing 6 6 Function testing 7 7 Fault alarms 8 Technical data 9 wwwbelimocom M3-A12-BKS24-9A en v21 112009 Subject to changes 1 / 12

1 Operating controls and indicators a b c d e f g h i a Retaining-Clip Lift clip with Screwdriver for mounting-/removing b Label For zone identification c Label 1 9 For damper identification d LEDs (red) FAULT dampers 1 9 Off Flashing On = No alarm = Alarm present = Alarm stored e Pushbutton PRG (This pushbutton is recessed, use a proper tool to operate) Programming the number of dampers Check the number of dampers f LED (green) NORMAL Position Flashing On g LED (yellow) SAFE Position Flashing On = Dampers run to NORMAL Position (OPEN) = Dampers have reached NORMAL Position = Dampers run to SAFE Position (CLOSE) = Dampers have reached SAFE Position h Pushbutton TEST System Test Functional Test (Dampers/Actuators/Control Unit) (for checking the system manually) i Electrical connection 9-Pin Terminal Connectors 2 / 12 M3-A12-BKS24-9A en v21 112009 Subject to changes wwwbelimocom

2 Preparations for faultless commissioning and operating 21 Fire dampers are installed and mechanically tested OPEN and CLOSED end positions attainable 22 Fire damper actuators (AC 24 V) connected (both cables) to the BKN230-24 or BKN230-24-C-MP units 23 Terminals 1 to 7 of the BKN230-24 or BKN230-24-C-MP unit correctly wired according to the wiring diagram and technical documentation Ensure correct polarity when connecting the 2-wire conductors (terminals 6 and 7) 24 AC 230 V All BKN230-24 and BKN230-24-C-MP units connected to the AC 230 V power supply (by mains connector or terminal box) 25 Number and sequence of connected dampers labelled BSK 34 Zone 1a BSK 37 and programmed (eg1 5) on the front of the BKS24-9A unit BSK 35 BSK 36 BSK 38 Programming see Para 3 26 AC 24 V OPEN Command is present at the BKS24-9A unit BKS24-9A 11 causing the dampers to be moved to the operating position T ~ 12 13 Control ON (OPEN) T ~ 14 Programming input 27 All other inputs correctly wired according to the wiring diagram and thetechnical documentation 1 9 10 18 wwwbelimocom M3-A12-BKS24-9A en v21 112009 Subject to changes 3 / 12

3 Programming the number of dampers per BKS24-9A Targets Factory programmig: The BKS24-9A unit is factory programmed for 9 dampers 1 9 The programming must be modified accordingly when connecting 1 to 8 dampers 1 8 31 35 Procedure 31 Note preparatory work in Para 2 32 Press and hold PRG key (until 35 included) 33 The fault LEDs for the number of dampers programmed light up for 4 seconds (eg 1 to 9) Zone 1a BSK 34 BSK 35 BSK 37 BSK 38 BSK 36 34 The fault LEDs for the number of dampers programmed Zone 1a and acknowledged by the BKS24-9A unit start flashing (eg 1 to 5) BSK 34 BSK 35 BSK 36 BSK 37 BSK 38 The number of dampers acknowleged must correspond to the number of dampers labelled 35 Press the TEST key at the same time as the PRG key The numer of dampers acknowledged is now programmed in the BKS24-9A unit Note A System test is initiated automatically (see Para 5) 4 / 12 M3-A12-BKS24-9A en v21 112009 Subject to changes wwwbelimocom

4 Adding / removing of dampers Example A fire damper is to be added to an existing system, resp or is beeing removed The dampers 1 to 5 are in operation and damper 6 is the new one, or but, damper 5 is being removed The comment in (bold italics) refers to the removal of a damper 41 45 Procedure 41 Note preparatory work in Para 2 An automatic system test is performed when the power supply (AC 24 V) is energised (see Para 5) Start flashing: The status LED for OPEN and the fault LED of the new damper 6, or The status LED for OPEN and the fault LED of the removed damper 5 42 Label adapting on the front of the BKS24-9A unit Dampers 1 4 or Dampers 1 6 Press and hold the PRG key 43 The fault LED for the five dampers programmed (see example) light up for 4 Seconds Zone 1a BSK 34 BSK 35 BSK 36 BSK 37 BSK 38 BSK 39 44 The fault LEDs for the number of dampers programmed Zone 1a and acknowledged by the BKS24-9A unit start flashing after adding a damper actuator the fault LED 1 to 6 start BSK 34 BSK 37 BSK 35 BSK 38 flashing after removing a damper actuator the fault LED 1 to 4 BSK 36 BSK 39 start flashing The number of dampers acknowledged must correspond to the number of dampers labelled 45 Press the TEST key at the same time as the PRG key The number of dampers acknowledged is now programmed in the BKS24-9A unit Note A System test is initiated automatically (see Para 5) wwwbelimocom M3-A12-BKS24-9A en v21 112009 Subject to changes 5 / 12

5 System testing The system test deals with the connected dampers, the actuators, the installation and the control unit Note preparatory work in Para 2 The dampers are moved to the OPEN and CLOSED position during the test 51 Initiation criteria a) Automatic After programming of connecting After powering up (AC 24 V) 52 57 Procedure b) After a fault alarm By pressing the TEST key 52 All 11 LEDs light up for 4 Seconds (lamptest) 53 The OPEN/CLOSED status LEDs flash alternately for the duration of the system test 54 The dampers are moved in the CLOSED direction and must attain the safe postion 55 The dampers are moved in the OPEN direction and must attain the operating position (as described in Para 26) 56 The status LED for OPEN starts flashing when the damper departs from the safe position The status LED for OPEN gives a steady light when the damper reaches the operating position 57 The system is now ready to use ok 6 / 12 M3-A12-BKS24-9A en v21 112009 Subject to changes wwwbelimocom

6 Function testing The purpose of the function test is for checking the system manually Note preparatory work in Para 2 The connected fire dampers are moved to the CLOSED and OPEN positions 61 Initiation criteria Press and hold the TEST key 62 66 Procedure 62 The status LED for OPEN lights up All fire dampers are in the operating position (OPEN) The fault LEDs 1 to 9 are off 63 Press and hold the TEST key The staus LED for CLOSED will start flashing 64 When the status LED for CLOSED gives a steady light it means that the dampers have reached the safe position Release the TEST key 65 The dampers move to the operating position When the status LED for OPEN gives a steady light it means that the function test has been completed successfully 66 The system is ready for use ok wwwbelimocom M3-A12-BKS24-9A en v21 112009 Subject to changes 7 / 12

7 Fault alarms Note Possible causes see Para 73 71 Existing fault Fault in the system Fault LED flashing (eg damper 4) Status LED for OPEN or CLOSED flashing (depending on control signal) Existing fault Contact K1 open 72 Stored fault Temporary fault in the system Fault LED bright (eg damper 4) Stored fault Contact K1 closed A stored fault can be acknowledged in two ways: 1 Manually with the TEST key (see Para 4) 2 Automatically when the dampers have run properly to two successive end positions OPEN / CLOSED 73 Initiation criteria When a fire damper does not reach the operating position or safe position within the specified running time Para 21 Open-circuit or wrong polarity on 2-wire conductor Para 24 to 27 Open-circuit or fault in the Tripping Device BAE72-S Para 24 No power supply or fault in the BKN230-24 or BKN230-24-C-MP unit Para 23 Open-circuit or fault at the plug connections from damper actuator to the BKN230-24 or BKN230-24-C-MP unit Para 22 After adding a damper actuator to or removing one from an existing system Para 4 74 Unit fault Fault in the BKS24-9A unit All 11 LEDs on the BKS24-9A unit flash in unison It means that the BKS24-9A unit is defective and must be replaced 8 / 12 M3-A12-BKS24-9A en v21 112009 Subject to changes wwwbelimocom

Technical data BKS24-9A Communication and control unit for control and monitoring of up to nine motorized fire dampers in combination with the communication and power supply units BKN230-24 or BKN230-24-C-MP Signals the operating positions and any faults from the fire dampers to which it is connected Reduced wiring costs due to 2-wire communication Propagation of group alarm and damper position to an overhead system via auxiliary contacts Panel mounting (DIN rail) Technical data Electrical data Nominal voltage AC 24 V, 50/60 Hz Power supply range AC 21,6 28,8 V Power consumption In operation For wire sizing 35 W 55 VA (I max 64 A at 25 ms) Connection Terminals for 2 x 15 mm 2 Lenghts of conductors 2-wire conductors a/b control input 13 max 600 m (wire 075 mm 2 ) max 600 m (wire 075 mm 2 ) Auxiliary contacts AC 24 V at 05 A Safety Protection class III safety extra-low voltage / UL Class 2 Supply Degree of protection IP20 EMC CE according to 2004/108/EG Mode of operation Type 1 (EN 60730-1) Rated impulse voltage 05 kv (EN 60730-1) Control pollution degree 2 (EN 60730-1) Ambient temperature 0 +50 C Non-operating temperature 30 +50 C Maintenance Maintenance-free Dimensions / Weight Dimensions See «Dimensions» on page 2 Weight Approx 160 g Safety notes Product features Mode of operation Fault Auxiliary contact K2 The device is not allowed to be used outside the specified field of application, especially in aircraft or in any other airborne means of transport It may only be installed by suitably trained personnel Any legal regulations or regulations issued by authorities must be observed during assembly The device may only be opened at the manufacturer s site It does not contain any parts that can be replaced or repaired by the user The device contains electrical and electronic components and is not allowed to be disposed of as household refuse All locally valid regulations and requirements must be observed The BKS24-9A unit receives position signals from the BKN230-24 or the BKN230-24-C-MP units and transmits control commands to them over the 2-wire conductors Correct operation of the dampers is indicated by the 2 LEDs: Control ON = NORMAL Position Control OFF = SAFE Position If the damper does not reach the required position within the preset time, the appropriate on-board FAULT LED flashes and, at the same time, the FAULT contact K1 is activated This contact is overridden as soon the defective damper reaches the requried position The on-board FAULT LED remains on, until the fault is reset An auxiliary contact is provided for signaling the positions of dampers to a higher-level system The function of the auxiliary contact can be programmed via terminal 14 according to the instructions beside wwwbelimocom M3-A12-BKS24-9A en v21 112009 Subject to changes 9 / 12

Product features Installation and connections Functional testing Fire zoning (Continued) The BKS24-9A unit can be clipped directly onto a 35 mm DIN mounting rail and external wiring is connected by two 9-pin terminal connectors Functional testing can be performed by pressing the TEST pushbutton While this button is held depressed, the dampers run to the SAFE position Any malfunctions are indicated by the internal FAULT LEDs The required fire zones must be taken into account when making the groupings and when wiring the BKS24-9A unit Electrical installation Wiring diagram Notes Connect via safety isolation transformer Relay contacts K1 and K2 are shown without power applied BKN230-24 a1 a9 BKN230-24-C-MP BKN230-24 b1 b9 BKN230-24-C-MP Common input 1 2 3 4 5 6 7 8 9 10 T ~ 11 12 13 14 16 15 17 18 Control ON (Normal) / OFF (Safe) T ~ Programming input for auxiliary contact K2 Fault K1 Group alarm fire dampers 1 9 Auxiliary contact K2 Function to be programmed by appropriate wiring of terminal 14 Contact K1 and auxiliary contact K2 Dimensions [mm] Dimensional drawings Function contact K1 Situation Status Alarm 15 16 No alarm 15 16 Programming auxiliary contact K2 Function Wiring Status Contact K2 closed, when all Dampers OPEN Contact K2 closed, when Damper No 1 OPEN Contact K2 closed, when all Dampers CLOSED 14 11 T ~ 14 12 17 18 14 left open 95 45 62 90 105 20 41 10 58 10 / 12 M3-A12-BKS24-9A en v21 112009 Subject to changes wwwbelimocom

All inclusive 5 years Guarantee Worldwide present Complete assortment from a single source Examined Quality Short delivery time Comprehensive support Headquarters Subsidiaries, Representatives and Agencies BELIMO Holding AG Brunnenbachstrasse 1 CH-8340 Hinwil Tel +41 (0)43 843 61 11 Fax +41 (0)43 843 62 68 info@belimoch wwwbelimocom Agentina Australia Bahrain Belgium Bosnia-Herzegovina Brazil Bulgaria Canada Chile Croatia Cyprus Czech Republic Denmark Egypt Estonia Finland France Great Britain Germany Greece Hong Kong Hungary Iceland India Indonesia Ireland Israel Italy Japan Jordan Kuwait Latvia Lebanon Liechtenstein Lithuania Luxembourg Malaysia Mexico Morocco Netherlands New Zealand Norway Oman Pakistan People s Republic of China Philippines Poland Portugal Qatar Republic of Korea (South Korea) Rumania Russia Saudi Arabia Singapore Slovakia Slovenia South Africa Spain Sweden Switzerland Taiwan Turkey Ukraine United Arab Emirates United States of America Belimo worldwide: wwwbelimocom