COOPER POWER SERIES. Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions. Fusing Equipment MN132014EN

Similar documents
Effective November 2016 Supersedes September 1998 (S )

COOPER POWER SERIES. Testing a motor capacitor on a voltage regulator procedure instructions. Voltage Regulators MN225064EN

COOPER POWER SERIES. QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit A26 installation instructions

COOPER POWER SERIES. S.T.A.R. Hot line voltage indicator installation instructions. Fault Indicators MN320011EN. Indicator boot.

COOPER POWER SERIES. RTE EL-BAY-O-NET FUSE Re-Fusing Instructions. Fusing Equipment MN132024EN

COOPER POWER SERIES. ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions. Fusing Equipment MN132017EN

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

COOPER POWER SERIES. Expulsion fuse installation instructions. Capacitors MN230005EN. Effective November 2016 Supersedes November 2001 (S )

COOPER POWER SERIES. KA662R tank-lifting windlass assembly and installation instructions. Recloser Mountings MN280071EN

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN

COOPER POWER SERIES. Edison Modular Fuse (EMF) Installation Instructions. Fusing Equipment MN132031EN

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN

Effective June 2016 New Issue

COOPER POWER SERIES. UltraSIL polymer-insulated D-73P disconnect switches installation instructions. Switches MN008004EN

COOPER POWER SERIES. KA1169R Closing Coil Transfer-Switch Accessory Operation. Reclosers MN280069EN

COOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN

COOPER POWER SERIES. High-voltage primary bushings installation instructions. OEM Equipment MN800008EN

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. Dielectric grease application to recloser cable instructions. Reclosers MN280070EN

COOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

Effective March 2015 Supersedes S August 2012

COOPER POWER SERIES. S.T.A.R. type LVR faulted circuit indicator installation instructions. Fault Indicators MN320005EN

COOPER POWER SERIES. Pad-mounted Switchgear MN285019EN. Effective March 2017 Supersedes February 2007 (S )

High-voltage primary bushings installation instructions

Effective November 2016 Supersedes February 2012 (S )

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

COOPER POWER SERIES. Electronic control battery testing, charging, and replacement instructions. Reclosers MN280074EN

Type NR oil switch installation and operation instructions

COOPER POWER SERIES. Types 4H single-phase and 6H three-phase vacuum interrupter conversion kits. Reclosers MN280014EN

COOPER POWER SERIES. KA146W5 single pole-mounting hanger; KA146W2 tank lifting windlass assembly and installation instructions. Reclosers MN280039EN

Effective May 2017 Supersedes January 2003 (S )

COOPER POWER SERIES. Quick Connect Assembly (QCA) Retrofit Kit, General Electric Installation Instructions. Voltage Regulators MN225075EN

COOPER POWER SERIES. Surge arrester interchangeable fuse cutout combination installation instructions. Surge Arresters MN235004EN

Effective May 2017 Supersedes December 2004 (S )

COOPER POWER SERIES. KA716L7001 adjustable control valve kit for Types L, E, 4E, V4E, and V4L reclosers installation and adjustment instructions

COOPER POWER SERIES. Mercury switch to microswitch retrofit kit KA349WE installation instructions. Reclosers MN280022EN

COOPER POWER SERIES. Fused loadbreak elbow connector installation instructions. Loadbreak Apparatus Connectors MN650014EN

COOPER POWER SERIES. Metal-enclosed capacitor banks installation instructions. Power Capacitors MN230010EN

COOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN

COOPER POWER SERIES. Types D and DV recloser installation instructions. Reclosers MN280030EN

COOPER POWER SERIES. Metal-enclosed, pad-mounted capacitor banks installation instructions. Power Capacitors MN230009EN

S Voltage Regulators GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage. Standards

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN

S Fault Indicators. S.T.A.R. Type TPR Faulted Circuit Indicator Installation Instructions. Contents INSTALLATION PROCEDURES

COOPER POWER SERIES. Manually-Operated M-Force Switch Installation and Operation Instructions. Switches and Disconnects MN008003EN

Removal/installation instructions for Series NRX (IZMX) drawout levering (racking) mechanism

COOPER POWER SERIES. Externally fused block banks installation instructions. Capacitors MN230004EN

Installation Instructions for Interlocking Trip Indicator with Remote Reset for Magnum Low Voltage Circuit Breakers

Factory Authorized Mechanism Enhancement (FAME)

Figure 1. Kearney Type HX cutout.

COOPER POWER SERIES. Instructions for oil-filled, single-phase overhead distribution transformers. Distribution Transformers MN201003EN

Reprogramming guide. Power Defense ICCB. Instructional Leaflet IL EN WARNING WARNING. Instructions apply to:

Two-way cable interlock kit for Magnum drawout circuit breakers

3-way multi-family drawout cable interlock kit - type 32 - RF

Installation and removal instructions for Series NRX RF fixed breaker three-way Type 32 cable interlock kit

CCP2-FLR1-21_ flange-rod operating mechanism

Two-way cable interlock kit for Magnum fixed circuit breakers

S Voltage Regulators PRODUCT INFORMATION GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage.

S Voltage Regulators PRODUCT INFORMATION GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage

This Kit Is for Use with Types RE, RVE, WE, WVE, VWE, VWVE27, and VWVE38 Reclosers.

Instruction Booklet IB E. Contents

S Voltage Regulators GENERAL. PRODUCT INFORMATION Introduction. Contents. Acceptance and Initial Inspection. Handling and Storage.

Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version

Effective October 2016 Supersedes January 2014 (S )

COOPER POWER SERIES. Types VWE, VWVE27, VWVE38X, WE, WVE27, and WVE38X; threephase electronically controlled; installation and operation instructions

COOPER POWER SERIES. VFI tester operating instructions. Underground Distribution Switchgear MN285001EN

Installation Instructions for KPS and KPH Circuit Breakers and Molded Case Switches

COOPER POWER SERIES. RVAC Fluid-insulated Vacuum Switchgear; Installation, Operation, and Maintenance Instructions. Switchgear MN285005EN

Direct-connected capacitor fuse

O & M Manual for the EATON Generator Ready Loadcenter

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

COOPER POWER SERIES. Type MOST Fluid-Insulated Switchgear; Installation, Operation, and Maintenance Instructions

Installation Instructions For Motor Control Center (MCC) Units

GWI Rev. 1 October 2007 Supersedes Rev. 0 Dated February 2004

Installation Instructions for R-Frame G-Series (RG) 310+ Trip Unit

II DISTRIBUTION & SUBSTATION TYPE C

Flush Mount AIN ALPHA Meters. General. Hardware Kit

KFE10010-E. Reclosers. Contents. Type KFVE and KFVME (27kV) Bus Bar Kit KRK710-1 Installation Instructions. Cooper Power Systems

Type 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear

CM52 Network Protector with Arc Flash Reduction Module

100 A externally operated one-, twoand three-phase tap-changer switch

Digitrip Retrofit System for General Electric AKR/AKRU-6D/7D-30S Series Breakers

Magnum Breaker Remote Racking Device (MRR1000)

SPX9000 FR10 FR12 Adjustable Frequency Drives

K-Limiter high ampere Companion II fuse

BlinkerBeam Solar Controller

Instructions for using Functional Test Kit on Digitrip 520 and 1150 family of Power Circuit Breaker Trip Units and Series G and FD MCCB Trip Units

Advanced Test Equipment Rentals ATEC (2832)

www. ElectricalPartManuals. com Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers

25 kv class fused loadbreak elbow connector

COOPER POWER SERIES. Type VSA12, VSA12B, VSA16, VSA20, and VSA20A operation and installation instructions. Reclosers MN280063EN

SIEMENS. XJ-L Busway Systems. Storage, Installation and Maintenance Instructions for... Piece No. 32-J Rev 3

S Contents. Applicable to Serial Numbers A101 and above or beginning with CP57.

A 1.2 kv class externally removable secondary bushing

TVSS Installation for RLCM/CHGENLC, RLCU, and CHGEN ATSs

dfdf 34.5 kv and 69 kv, Type O Plus C II Condenser Bushings Technical Guide

Transcription:

Fusing Equipment MN132014EN Effective November 2016 Supersedes July 2005 (S240-61-1) Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions COOPER POWER SERIES

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation s ( Eaton ) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein. The information contained in this manual is subject to change without notice. ii

Contents DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY... SAFETY FOR LIFE... iv SAFETY INFORMATION... iv Safety instructions...iv GENERAL.... 1 REMOVAL.... 1 INSTALLATION.... 1 ii iii

Current-Limiting Type NXC (C-Rated) Fuse! SAFETY FOR LIFE Safety for life! SAFETY FOR LIFE Eaton meets or exceeds all applicable industry standards relating to product safety in its Cooper Power series products. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Eaton employees involved in product design, manufacture, marketing, and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high voltage lines and equipment, and support our Safety For Life mission. Safety information The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians who are familiar with this equipment should install, operate, and service it. A competent technician has these qualifications: Is thoroughly familiar with these instructions. Is trained in industry-accepted high and low-voltage safe operating practices and procedures. Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment. Is trained in the care and use of protective equipment such as arc flash clothing, safety glasses, face shield, hard hat, rubber gloves, clampstick, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. Hazard Statement Definitions This manual may contain four types of hazard statements: DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in equipment damage only. Safety instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. DANGER Hazardous voltage. Contact with hazardous voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around highand low-voltage lines and equipment. G103.3 Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. G101.0 This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury and equipment damage. G102.1 Power distribution and transmission equipment must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install or maintain power distribution and transmission equipment can result in death, severe personal injury, and equipment damage. G122.2 iv

Current-Limiting Type NXC (C-Rated) Fuse General Standard safety procedures should be followed when removing and installing NXC fuses on capacitor blocks. Bolt or Stud Mounting Bus Bar Removal 1. Remove all power from capacitor block. 2. Allow capacitors to discharge internally for five minutes; then manually discharge all capacitors, including the suspected failed capacitor unit. 3. Remove fuse leader from capacitor bushing. 4. Remove fuse from bus bar and retain mounting hardware for installation of replacement fuse. 3.0" (+ 1 /2", -0") NXC Fuse Blown Fuse Indication Capacitor Installation NXC fuses may be mounted by various means on capacitor blocks. This instruction bulletin provides information for the four standard configurations as shown in Figure 1 through Figure 4. NXC fuses should be installed with the leader pointing down (see Figure 1 through Figure 4). 1. Verify that the proper rated fuse is being installed by checking information provided on fuse identification label. 2. Remove leader wire from the hex-head bolt supplied with the fuse. If a hose clamp is supplied with the replacement fuse, remove the clamp from the fuse before fuse installation (see Figure 5). 3. Secure the fuse to the bus bar with the.50-13 UNC-2A x.75 stainless steel hex reg bolt supplied with the fuse or use the mounting hardware retained from the fuse that was removed. CAUTION Do not apply any type wrenching tool directly on the fuse when installing it. Sufficient torque can be applied with the hand for a proper fit. 4. Check that the recommended spacing exists between end of main fuse housing and closest conductive part on capacitor. Refer to Figure 1 through Figure 4 as applicable. Figure 1. NXC fuse angle-mounted on vertical capacitor bank. Bus Bar NXC Fuse Bolt or Stud Mounting 4.0" (+ 1 /2", -0") Capacitor Figure 2. NXC fuse vertically mounted on vertical capacitor bank. 1

Current-Limiting Type NXC (C-Rated) Fuse Bolt or Stud Mounting Bus Bar NXC Fuse 3.0" (+ 1 /2", -0") 5. Secure fuse leader to capacitor bushing connector and recheck spacing. Leader should be snug and not contain any slack. 6. Cut off excessive leader wire which extends beyond capacitor bushing. NNote: A blown fuse is indicated by the fuse leader hanging from the capacitor bushing and not connected to the fuse. CAUTION Capacitor This product as designed and packaged by Eaton is classified by the USDOT as Not Regulated as an Explosive. The leader wire must be held in place by attaching the wire under the hex-head bolt or clamped to the fuse body to maintain this classification when an un-operated fuse is transported. Hose Clamp Figure 3. NXC fuse mounted on horizontal capacitor bank. Bolt or Stud Mounting NXC Fuse 4.0" (+ 1 /2", -0") As Shipped from the Factory Figure 5. NXC fuse shown with leader retained for transportation. Capacitor Figure 4. NXC fuse vertically mounted on horizontal capacitor bank. NNote: The following recommended spacing between potentially live elements of a blown fuse and conductive parts of a capacitor is the same for all recommended applications of the NXC fuse. Smaller spacing will result in reduced system BIL after the fuse has blown. Larger spacing will create an excessively long fuse leader which could bounce over and short out adjacent capacitors when it is ejected from a blown fuse. 2

Current-Limiting Type NXC (C-Rated) Fuse T his page is intentionally left blank. 3

! SAFETY FOR LIFE Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton s Power Systems Division 2300 Badger Drive Waukesha, WI 53188 United States Eaton.com/cooperpowerseries 2016 Eaton All Rights Reserved Printed in USA Publication No. MN132014EN November 2016 Eaton is a registered trademark. All trademarks are property of their respective owners. For Eaton s Cooper Power series product information call 1-877-277-4636 or visit: www.eaton.com/cooperpowerseries.