Installation Instructions

Similar documents
Installation Instructions

Installation Instructions

Installation Instructions

Installation Instructions

Installation Instructions

Installation Instructions

Installation Instructions

Installation Instructions

Installation Instructions

Installation Instructions

Installation Instructions

ISC Series Innovative Standard Cartridge Seals

Installation Instructions

Vogt Valves The Connection Bulletin for Forged Steel Globe Valves for Water-Free Chlorine Service Class 300, 600 & 800 CB 07

Kämmer Series Low Flow Valves

Vogt Valves The Connection Bulletin for Y Pattern Globe & Check Valves Class 1690 & Class 2680 CB 18

Valtek Spring Cylinder Linear Actuators

Valtek Flow Boosters

Kämmer Series Low Flow Valve

Desuperheater FCD VLENTB /11. Experience In Motion

Kämmer Series Split Body Valves

MARPAC K SERIES. Full Bore Fire Safe Flanged Ball Valves

Figure 1 Figure 2 Double Acting Actuator Spring Return Actuator

TECHNICAL BULLETIN. Audco Ball Valve. Reduced Bore Fire safe Flanged Ball Valves 51/52 Series. Experience In Motion

INSTRUCTION MANUAL. Anchor Darling 1878 Swing Check Valves. Installation Operation Maintenance. Sizes 1/2 through 2 FCD ADENIM

USER INSTRUCTIONS. Installation Operation Maintenance. NAF Setball SF Ball Sector Valves. Experience In Motion FCD NFENIM A4 09/16

Kämmer Multi-Z Severe Service Valves

Solenoid Block Kit for Series 90 Modular Accessory System Installation, Operation and Maintenance Instructions

flowserve.com Kämmer Multi-Z Kämmer Multi-Z Severe Service Valves

USER INSTRUCTIONS. Valtek Control Products Spring Cylinder Linear Actuators. Installation Operation Maintenance. Experience In Motion

WORCESTER CONTROLS F519/529/819/829. Full Bore Fire Safe Flanged Ball Valves

Series 72 Electri-SAFE On/Off Operation Including CLC Option Installation, Operation and Maintenance Instructions

NAF Duball DL Pocket Ball Valves TECHNICAL BULLETIN FCD NFENTB A4 11/17

Worcester Controls Directional Ball Valves

RVX Upgrade. ISO 13709/API 610 back pullout retrofit. Experience In Motion

User Instructions -Original Instruction-

Limitorque Accutronic MX/WTR Performance and Dimensions. Limitorque Actuation Systems

USER INSTRUCTIONS. NAF Trunnball DL Ball Valves. Installation Operation Maintenance. Experience In Motion FCD NFENIM A4 01/15

Flowserve Anchor Darling Isolation Valve Application

USER INSTRUCTIONS. Limitorque TM V Series. Installation Operation Maintenance. Experience In Motion FCD LMENIM AQ 02/15

Valtek Valdisk 150. Valtek Valdisk 150. Control Valves. Flowserve Corporation, Valtek Control Products, Tel. USA

Installation Instructions

Logix 3800 Digital Positioner

Edward. Equiwedge Forged Gate Valvee. Experience In Motion

McCANNA Actuation Systems B

Plug Valve Solutions for the Upstream Exploration and Production Pipelines Production manifolds, test manifolds and other dirty services

Limitorque Actuation Systems B320 Series. Rugged and dependable bevel gear operators for manual or motorized valve control applications

TECHNICAL BULLETIN. NAF Setball SF Ball Sector Valves. Experience In Motion. flowserve.com. NAF Setball FCD NFENTB A4 02/16

TECHNICAL BULLETIN. NAF Trunnball DL Ball Valves. Experience in Motion FCD NFENTB A4 09/14

Experience In Motion. Flowserve Control Valve Products North American Quick Response Centers

Tri-Pac E325 / E525 Ball Valve Three-Piece Bolted Body, In-Line Maintainable, Regular and Full Port. McCANNA/MARPAC Valves RO400-R4

TECHNICAL BULLETIN. NAF Duball DL Ball Valves. Experience in Motion FCD NFENTB A4 12/14

Limitorque Actuation Systems PT Series Worm Gear Operator

Valtek VL-HC Spring Cylinder Linear Actuators

Valtek Tek-Check Control Valves Valtek Tek-Check

MERIDIAN, 2 or 3 PIECE, TRUNNION MOUNTED BALL VALVES

Flowserve Spring Diaphragm Rotary Actuators

OpTK. Product Instruction Manual. Spring Cylinder Rotary Actuators INTRODUCTION SAFETY INFORMATION INSTALLATION. Leading Technologies For Control

E818/828 Series Fugitive Emissions 150# and 300# Flanged 2" - 8" Two-Piece Ball Valves Installation, Operation and Maintenance Instructions

S-17 CATALOG. Forged Steel Strainers

Logix 3800 Digital Positioner

flowserve.com Flowserve Solenoid Valves Namur, Remote and Banjo Mounted Designs for Precision Control

CONNECTION BULLETIN. Vogt Valves. Experience In Motion. Zero Leakage Forged Steel Check Valves Class 800. FCD VVABR /04 (Replaces CB-03)

Rotary Valve Maxflo + 60 and 80 Opening type NT

Limitorque HBC Series Worm Gear Operators

USER INSTRUCTIONS. Spring Diaphragm Rotary Actuators. Installation Operation Maintenance. Experience In Motion FCD VLAIM /12

Product Specification

flowserve.com Durco PlugSeal Valve ASME Class 600 Plug Valves Serving the Worldwide Desalination Industry Experience In Motion

Valtek Tek-Check. Check Valves

flowserve.com Limitorque LRP Limitorque Rack & Pinion Pneumatic Actuator

USER INSTRUCTIONS. Serck Audco Slimseal Wafer-Type Butterfly Valves. Installation Operation Maintenance. Experience In Motion SREEIM /13

PMV. P5 Pneumatic Positioner. Product Information

Limitorque. HBC Series Worm gear operators proven in the most demanding situations

THD-SERIES S11DA280 THRU S27DA1020 & S11SR280 THRU S27SR1020 DOUBLE ACTING & SPRING RETURN SCOTCH YOKE ACTUATORS

Mark 100. Technical Bulletin F C D F C A T B

Accord DS/DM Series UltraSwitch Switch box

Installation, Operation and Maintenance Instructions Series 608 Ball Valve

V-SEGMENT SERIES V-Port Segment Control Valves (VS/VV/VM) Installation & Maintenance Manual

Valtek MaxFlo Control Valves

SPECIFICATIONS. Limitorque MX. Selection Data. Experience In Motion. Performance and Dimensions for MX Series 05 through 150 Electric Actuators

SY-SERIES S04DA75 THRU S06DA180 & S04SR75 THRU S06SR180 DOUBLE ACTING & SPRING RETURN SCOTCH YOKE ACTUATORS

TECHNICAL BULLETIN. Valdisk TX3 Triple Offset Butterfly Control Valve. Experience In Motion FCD VLENTB A4 1/16

Flow Solutions Division. ISC2PP Dual Pusher Seal ISC. Repair Instructions

Pleuger PMM. High-Efficiency Submersible Motor With Permanent Magnet Technology for Electrical Submersible Pumps (ESP) Experience In Motion

Valtek Valdisk 150. Valtek Valdisk 150. Control Valves

Valtek XL Series High Performance Positioner. for Control Valves

Valtek Beta Positioner. Valtek Beta Positioners. for Control Valves

USER INSTRUCTIONS. Limitorque HBC Series. Installation Operation Maintenance. Experience In Motion FCD LMENIM A4 (10/14)

CHESTERTON FLOW GUARDIAN S50 AND SP50 SINGLE FLOWMETER INSTALLATION INSTRUCTIONS

Valtek Survivor Control Valves

Mounting: The following instructions apply to rotary actuators only. Linear applications require special mounting and coupling (consult factory).

Pump Division MSP. Vertical, In-line, Medium Speed Pump. Bulletin PS-10-1c (E/A4)

Experience In Motion UZDL. API 610 (BB1) Between Bearings, Two-Stage, Axially Split Pump

Edward Valves. Maintenance Manual for Edward Forged Steel Valves. Bolted and Screwed Bonnet Types V-376 R3

Product Specification

TYPE 5611/5611Q Elastomer Bellows Seals. ! Temperature: ! Pressure: 28 bar g/400 psig. ! Speed: ! End Play/Axial Float Allowance: 0.13mm/0.

BETTIS SERVICE INSTRUCTIONS DISASSEMBLY AND REASSEMBLY FOR CB DOUBLE ACTING SERIES PNEUMATIC ACTUATORS

V46 and V47. Repair Parts and Service Instructions. Applications. Adjustments. Installation Guidelines

Product Information ROSS CONTROLS

Pump Division. Durco Mark 3 In-Line. ASME (ANSI) B73.2 Vertical In-Line Chemical Process Pumps. Bulletin PS-10-15h (E/A4)

Transcription:

Installation Instructions Seal Gard Flowmeter TM Unitized construction Plug resistant float design Tamper resistant valve design Pressure gauge standard Check valve standard 0-20 gph or 0-40 gph standard Options available: Alarm, constant flow regulator, hoses, clamps, quick-connects, and wall, pipe stand, or pump flange mounting brackets UKDOOSG2020, Seal Gard II, 0-20 gph UKDOOSG2040, Seal Gard II, 0-40 gph UKDOOSG1020, Seal Gard I, 0-20 gph UKDOOSG1040, Seal Gard I, 0-40 gph Experience In Motion

Description The Seal Gard is engineered to regulate and monitor the flow of flush water, or other sealing fluids, to a seal chamber containing a single, double, or tandem Flowserve seal, or to protect compression packing. The Seal Gard I is equipped with a single flowmeter and one flow control valve to supply a flush to a single Flowserve seal, Plan 32 or to a lantern ring of a packed stuffing box. The Seal Gard II is equipped with dual flowmeters and two flow control valves. The two flowmeters are unitized and used to control and monitor both the inlet and outlet of a double seal barrier fluid system, Plan 54 or to and from lantern ring taps of a stuffing box with a "balanced" flush of compression packing. For a double seal, the barrier fluid is maintained at a pressure higher than that of the product. The Seal Gard II can also be used to monitor the buffer fluid between the inner and outer seal of a tandem Flowserve seal, Plan 52. Here the pressure between the seals is maintained at a pressure lower than that of the product acting on the inner seal. Tools needed for installation: Wrenches, piping, and fittings for 1/4 inch NPT. Screwdriver to set flow control valves. 1 Seal Gard I Installation (See Figure 1) 1.1 Mount the Seal Gard body in a vertical position to a: Control panel, the Seal Gard is supplied with taps for panel mount. Wall, an optional wall mounting plate is available. Pipe stand, an optional pipe stand mounting plate is available. Pump flange, an optional pump flange mounting plate is available. 1.2 Locate the Seal Gard in a convenient location: In easy view. It may be best to locate the Seal Gard in easy view of the operator and run the necessary tubing / piping. Accessible for cleaning. In an area free of vibration, traffic, or other conditions or equipment that could damage the Seal Gard. 1.3 Provide a supply of flush liquid (usually water) to the Seal Gard. Supply must be: reliable, clean, and compatible with acrylic (no steam, alcohol, etc.). constant pressure at least 1 bar (15 psi) above that of the product being sealed and below 7 bar (100 psi). The pressure upstream of the unit may have to be controlled by a pressure regulator if the supply pressure is variable. Options of a constant flow regulator and gauges with higher pressure ratings are available from Flowserve. Install a valve in the supply line (normally full open) to be closed while cleaning or repairing the Seal Gard. A bypass may be installed from the supply line to the line to the seal to maintain a flush to the seal during cleaning of the Seal Gard. 2

Flow Solutions Division 1.4 Remove the plastic pipe plugs from the Seal Gard and pipe the seal flush liquid to the SUPPLY female 1/4 inch NPT fitting on the bottom front of the Seal Gard. use caution, do not strip the threads in the acrylic body of the Seal Gard. 1.5 Pipe the seal flush liquid from the female 1/4 inch NPT fitting of the check valve fitted to the TO SEAL tap on the bottom back of the Seal Gard to the flush tap of the Flowserve seal gland. (In the case of packing, pipe to the lantern ring tap of the stuffing box housing) Seal Gard I Figure 1 Pressure gauge Clean-out Supply flow control valve 50 PSI/kPa 100 Seal Gard I Flow To gland flush tap, flush mixes with pumped fluid 20 GPH H 2 O 10 LPM H 2 O 30 Alarm probe option Check valve 4 15 Durametallic Float flow reading Supply of clean flush On/off supply Single Flowserve seal (PSS III with Split Flow Reducer, ISC2, MSS, SL-5000, etc.) 3

2 Seal Gard II Installation (See Figure 2) 2.1 Follow steps 1.1 through 1.4 above. 2.2 Pipe the seal flush liquid from the female 1/4 inch NPT fitting of the check valve fitted to the TO SEAL tap on the bottom back of the Seal Gard to the flush tap of the seal chamber. (In the case of packing, pipe to the bottom lantern ring tap of the stuffing box housing). 2.3 Pipe the seal flush liquid from the top flush tap of the seal gland to the female 1/4 inch NPT fitting on the Seal Gard marked FROM SEAL tap on the bottom front of the Seal Gard. (In the case of packing, pipe from the top lantern ring tap of the stuffing box housing). 2.4 Pipe the seal flush liquid from the female 1/4 inch NPT fitting marked DISCHARGE on the bottom back of the Seal Gard to a seal water recovery system. Seal Gard II Figure 2 Pressure gauge Clean-out port Return From Seal control valve Normally adjust flow from seal here Close when inner seal fails 50 PSI/kPa 100 Seal Gard II Supply flow control valve Valve normally open 1/8 turn from Return From Seal control flow Adjust to control dilution if inner seal fails Supply float Return From Seal float Return From Seal line GPH H 2 O 20 10 4 LPH H 2 O Flow tubes High supply alarm probe option Low supply alarm probe option Clean supply Discharge to recycle On/off supply valve Check valve To gland or seal chamber inlet tap Dual Flowserve seal (Dual ISC2, SL-5200, etc.) 4

3 Operation Following these recommendations will ensure maximum MTBPM of the Flowserve seal being protected by the Seal Gard. 3.1 A clean source of seal water, or compatible sealing fluid, must be supplied to the Seal Gard at a constant pressure at least 103 kpa (15 psi) above the product pressure acting on the seal chamber or stuffing box. The Seal Gard is constructed of 316 SS and acrylic resin. The acrylic is not compatible with alcohol or steam. It will resist corrosion by most chemicals. However, do not expose Seal Gard to steam, alcohol, or other materials that will attack acrylic resins. The Seal Gard body will turn white and it will be impossible to see the float to set the flow rate. 3.2 Seal Gard I for a Single Flowserve seal Clean External Flush, Plan 32 (also for Packed Stuffing Box) Type of Installation Single Flowserve seal or flush to lantern ring Flush Plan 32 Part Codes UKDOOSG1020 0 to 20 gph UKDOOSG1040 0 to 40 gph Operation (See Figure 1) Open flush supply valve Open control valve Start up equipment Set control valve flow rate adequate to remove seal generated heat and to prevent product contamination of the seal while limiting product dilution Set optional low flow alarm Record flow and pressure on the operators log This arrangement can also be used to quench the outboard side of a single Flowserve seal, Plan 62; supply buffer fluid between the inner and outer seals of a tandem Flowserve seal, Plan 52; or supply seal water to the lantern ring tap of a packed stuffing box. 5

3.3 Seal Gard II for a Double Flowserve seal Circulation of Clean External Flush, Plan 54 (also for a Tandem Flowserve seal or a Packed "Balanced" Stuffing Box) Type of Installation Double Flowserve seal or flush to and from lantern ring taps Flush Plan 54 Part Code UKDOOSG2020 0 to 20 gph UKDOOSG2040 0 to 40 gph Operation (See Figure 2) Open flush supply valve or flush to and from Open supply control valve and close return-from-seal control valve Start up equipment Set return-from-seal valve to flow needed to remove seal generated heat Gradually close supply control valve until flow in return-fromseal drops slightly, then open supply control valve 1/8 turn For packing, balance the flows of the two meters to minimize product dilution and product loss Record supply flow, return-from-seal flow, and pressure on operators log. Flows will not match exactly, ±10%, due to system pressure drop, Set optional low flow alarm Set optional high flow alarm Note: With double or tandem seals, any outer seal leakage can be observed and reported. The condition of the inner seal in a double seal can be checked by closing the outlet valve. If the supply flowmeter shows no flow, the inner seal is intact. If the supply flowmeter shows a flow, the inner seal is leaking and repairs should be scheduled. As a temporary measure, leave the return-from seal valve closed and set the supply valve to minimize the flow of barrier water into the product. This arrangement can also be used to supply the buffer fluid between the inner and outer seals of a tandem Flowserve seal, Plan 52. Here, the buffer fluid is maintained at a pressure below that of the product acting on the inner seal and is often atmospheric. Set the desired flow rate to remove seal generated heat by adjusting the supply control valve. Set the return-from-seal control valve to maintain the desired pressure between the inner and outer tandem seals. When the inner seal of a tandem seal fails, the flow from the seal assembly will be higher than the flush supply to the seal and the pressure gauge will show product pressure. 6

The optional alarm features can also be set to respond to a high or low flow or both high and low flows as needed. Two alarm probes are required to respond to both high and low flows. With this arrangement, the low flow alarm indicates inadequate flow to the seal. The high flow alarm indicates that the inner seal is leaking seal barrier or buffer fluid into the product. Close the Seal Gard returnfrom-seal valve and reset the supply control valve to minimize product dilution until the seal can be scheduled for repair. 4. Cleaning and Repairs 4.1 To clean the Seal Gard: shut down the pump or provide a bypass flush system to the Flowserve seal. close the valve from the flush fluid supply line to Seal Gard. relieve any pressure on the Seal Gard. remove the threaded cap(s) from the top of the flow tube(s). clean the flow tube(s) using soap and water. (Steam and alcohol will turn the acrylic resin white and make the meter unreadable). re-install the threaded cap(s) making sure that the float(s) is in position. open inlet valve to renew flow to the seal adust flow control valves as indicated in steps 3.2 or 3.3. 4.2 To repair the Seal Gard: shut down the pump or provide a bypass flush system to the Flowserve seal. close the valve from the flush fluid supply line to Seal Gard. relieve any pressure on the Seal Gard. disconnect pipe connections and remove the Seal Gard from its mounting. remove the threaded cap(s) from the top of the flow tube(s). clean the flow tube(s) using soap and water. (Steam and alcohol will turn the acrylic resin white and make the meter unreadable). replace the float(s), valve(s), and O-rings (repair kit available). re-install Seal Gard to its mounting and reconnect piping. re-install the threaded cap(s) making sure that the float(s) is in position. open inlet valve to renew flow to the seal adust flow control valves as indicated in steps 3.2 or 3.3. A Seal Gard can normally be reconditioned. Return the Seal Gard to Flowserve Corporation with an order marked "Repair or Replace." It will be inspected and, if repairable, it will be rebuilt, tested, and returned in its original condition. 7

Use of the Seal Gard to troubleshoot sealing system problems Type of Observation Cause Suggested Action Installation Flowserve seal Seal Gard I Single no flow in tube seal fluid flow check supply pressure low flow alarm interrupted clean control valve pressure correct back pressure reversal problem Seal Gard II Double no flow in tube seal fluid flow check supply pressure low flow alarm interrupted clean control valves low pressure high pressure pressure correct back pressure reversal problem high flow alarm inner seal close return-from-seal low pressure failure control valve adjust supply control valve to acceptable dilution & schedule seal repair Seal Gard II Tandem no flow in tube seal fluid flow check flush source low flow alarm interrupted high pressure primary (inner) close supply control product in outlet seal failure valve adjust return-fromseal valve to acceptable loss level route discharge to approved disposal schedule seal repair 8

Type of Observation Cause Suggested Action Installation Compression Packing Stuffing Box Seal Gard I Normal flush no flow in tube flush flow check flush source of seal fluid low flow alarm interrupted clean control valve to lantern ring, some drippage some drippage normal none of flush to some dilution normal none atmosphere, most of flush excess drippage flange out of adjust follower flange into product excess dilution adjustment packing worn replace packing Seal Gard II "Balanced" no flow in tube flush flow check flush source stuffing box low flow alarm interrupted clean control valves with flow to and from excess drippage flange out of adjust follower flange lantern ring adjustment under pressure, with some excess dilution packing worn replace packing drippage to drippage or packing worn replace packing atmosphere, dilution cannot or misapplied change packing style minimum be controlled modify box arrangement dilution of product, product in pressure adjust flow control and most discharge fluctuations valves of flush returned to Seal Gard 9

Seal Gard I and II Specifications: Flow tube Acrylic Metal parts 316 SS Fittings 316 SS O-rings Fluoroelastomer Operating temperature: max. 66 C (150 F) min. 0 C (32 F) Connections 1 / 4 inch female NPT unless otherwise specified Accuracy ± 10% Repeatability ± 1% Valve assembly special, plug-resistant design Flow range 0 to 1.3 lpm (0 to 20 gph) or 0 to 2.6 lpm (0 to 40 gph) other non-seal Gard meters available for higher flows Pressure rating 21 bar (300 psig) max. Pressure gauge standard 2 1 / 2 " liquid filled 316 SS Dual Scale 0 to 7 bar (100 psi) other meters and gauges available for higher pressures Check valve standard, 316 SS Tubing option OPTION IA and IIA barb fittings, rubber tubing OPTION IB and IIB above plus quick disconnects 10

Mounting Control panel mount standard Wall plate, pipe stand, and pump flange mountings optional Temperature gauge 2 1 /2" dry gauge 316 SS 0 to 121 C (250 F) Level alarm AC or DC Proximity Sensor specify NO (normally open) or NC (normally closed) Cable length, 6.5 feet standard Constant Flow Regulator 316 SS, 21 bar (300 psig) 0 t0 2.6 lpm (0 to 40 gph) For any special problems encountered during installation, contact your nearest Flowserve Representative. 11

TO REORDER REFER TO B/M # F.O. FIS149eng REV 09/2018 Printed in USA To find your local Flowserve representative and find out more about Flowserve Corporation, visit www.flowserve.com USA and Canada Kalamazoo, Michigan USA Telephone: 1 269 381 2650 Telefax: 1 269 382 8726 Flowserve Corporation has established industry leadership in the design and manufacture of its products. When properly selected, this Flowserve product is designed to perform its intended function safely during its useful life. However, the purchaser or user of Flowserve products should be aware that Flowserve products might be used in numerous applications under a wide variety of industrial service conditions. Although Flowserve can provide general guidelines, it cannot provide specific data and warnings for all possible applications. The purchaser/user must therefore assume the ultimate responsibility for the proper sizing and selection, installation, operation, and maintenance of Flowserve products. The purchaser/user should read and understand the Installation Instructions included with the product, and train its employees and contractors in the safe use of Flowserve products in connection with the specific application. While the information and specifications contained in this literature are believed to be accurate, they are supplied for informative purposes only and should not be considered certified or as a guarantee of satisfactory results by reliance thereon. Nothing contained herein is to be construed as a warranty or guarantee, express or implied, regarding any matter with respect to this product. Because Flowserve is continually improving and upgrading its product design, the specifications, dimensions and information contained herein are subject to change without notice. Should any question arise concerning these provisions, the purchaser/user should contact Flowserve Corporation at any one of its worldwide operations or offices. Flowserve Corporation (2011) Europe, Middle East, Africa Etten-Leur, the Netherlands Telephone: 31 765 028 200 Telefax: 31 765 028 487 Asia Pacific Singapore Telephone: 65 6544 6800 Telefax: 65 6214 0541 Latin America Mexico City Telephone: 52 55 5567 7170 Telefax: 52 55 5567 4224 flowserve.com