Installation and Operations Manual

Similar documents
DP140e. Installation & Operations Manual

Uninterruptible Power System

Uninterruptible Power System

Installation and Operation Manual Back-UPS BX1100CI-CN

Uninterruptible Power System

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

Back-UPS CS Back-UPS CS 350

Match 19" GE Digital Energy. Uninterruptible Power Supply VA. Technology for the Digital World. Match 19" UPS.

Sola 3000 Guide Specifications

Liebert GXT & 10000VA RT208 Rack-Tower models, Dual Inverter GUIDE SPECIFICATIONS 1.0 GENERAL

Innovative Circuit Technology Ltd.

800VA/ 1000VA/ 1200VA/ 1500VA 2200VA/ 3000VA USER S MANUAL

User Manual Back-UPS BX650CI-MS 230 Vac with AVR

User Manual Digital Energy Uninterruptible Power Supply ML Series UPS VA GE Digital Energy Power Quality

3 Uninterruptible Power Systems

Uninterruptible Power System

Installation and Operation Manual Back-UPS BX800CI-ZA/BX1100CI-ZA

Liebert PowerSure PSI UPS

Sola/Hevi-Duty S3K Series Mini-Tower UPS

M T E C o r p o r a t i o n MATRIX FILTER. SERIES B Volts, 50HZ USER MANUAL PART NO. INSTR REL MTE Corporation

3000VA 120/208/230VAC

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE

User Manual. Digital Energy Uninterruptible Power Supply ML Series UPS VA. GE Digital Energy Power Quality. GE imagination at work

Back-UPS ES APC Back-UPS ES, 6 outlet 350VA, 120V, without auto shutdown software

The Power of Reliability INSTRUCTION MANUAL

Innovative Circuit Technology Ltd.

Dimensions 12/800N 12/1200N D. DC to AC Power Inverters. OWNERS MANUAL for Models: OWNERS MANUAL April ISO 9001:2000 Certified Company

Installation and Operation Back-UPS BX550CI-CN

Installation and Operation Manual Back-UPS BR1000-CH

M T E C o r p o r a t i o n. dv/dt Filter. Series A VAC USER MANUAL PART NO. INSTR REL MTE Corporation

1250W APS X Series 12VDC 230V Inverter/Charger with Auto Transfer Switching, 2 C13 Outlets

Westell FUSE PANEL. Technical Practice N Position Type VDC Floating

Liebert GXT VA RT230 Rack-Tower model GUIDE SPECIFICATIONS 1.0 GENERAL

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

Users Manual. Cobra Plus Stand-By Emergency Lighting Inverter. Technical Manual # Revision B

COMPACT GLYCOL FEED SYSTEMS OPERATION & MAINTENANCE MANUAL

Users Manual. Defender 1 8.0KW to 14.0KW Online Emergency Lighting Inverter. Technical Manual # Revision B

ADI-125/750 ADI-125/1500 ADI-125/2500

Installation Instructions

DC to AC Power Inverters

3 Uninterruptible Power Systems

DC to AC Power Inverters

SENS DC PowerCab 120 Installation, Operation, & Maintenance Manual

USER MANUAL. Power GUARD UPS. Uninterruptible Power System

dv Sentry TM 208V 600V INSTALLATION GUIDE Quick Reference ❶ How to Install Pages 6 14 ❷ Startup/Troubleshooting Pages WARNING

MODEL NUMBER: APS2424

Installation Manual. AC Edge. Split Phase 60 A (6/6) AC Power Distribution Unit. AC Edge. Model AC60DF 6/6 Part#

Pure Sine Wave Inverter GP-HS1500. Owner s Manual

Installing Power Components

RT Series Step Down Transformer for RT Series UPS 6-10kVA UL Input Vac Output Vac User Guide

MODEL NUMBER: APS2012

UTILITY INPUT MAINS OUTLET

OWNERS MANUAL JANUARY 2007 ISO

Limousin II User Manual

SmartOnline 120V 2.2kVA 1.8kW Double-Conversion UPS, 2U, Extended Run, Network Card Slot, LCD, USB, DB9

APC Smart-UPS. GUIDE SPECIFICATIONS FOR 1000VA & 2000VA Smart-UPS 230VAC Uninterruptible Power Supply

Valcom Failsafe Unit. 1620ESv2 SERIES. Operation and Maintenance Manual

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version

2400W APS INT Series 24VDC 230V Inverter/Charger with Auto-Transfer Switching, Hardwired

Liebert GXT & 6000VA RT230 Rack-Tower models GUIDE SPECIFICATIONS 1.0 GENERAL

Uninterruptible Power Systems

MODEL NUMBER: APS3636VR

Solar Hybrid Power Generating System CPS1200EOH12SC CPS2200EOH24SC CPS3000EOH24SC. User s Manual K01-C

MINUTEMAN UPS Endeavor Series Product Specifications 5,000VA 10,000VA Single-Phase Uninterruptible Power Supply 1.0 GENERAL

MODEL NUMBER: APS750. Highlights. Package Includes. Description

MF4E MF4E

User Manual. NetGuard IMPORTANT. PSD 650/1200/1600 Line Interactive UPS Uninterruptible Power Supply System. UPS Monitoring Software

ALLIANCE SERIES OWNER'S MANUAL

MM-AVR UPS Series User s Manual

MIL-24/2600Q MIL-24/3200DQ

Application. Battery. Public Grid GS HYBRID INVERTER

Matrix AP 400V 690V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 20 ❷ Startup/Troubleshooting Pages WARNING

MODEL NUMBER: APS2448UL

TPM Fuse Panel Installation Guide. Document INS-727XXXXXXX This manual covers the following part numbers- Trimm 727XXXXXXX Family

IV. PROOF OF PURCHASE: A warranty claim must be accompanied by proof of the date of purchase.

3 Uninterruptible Power Systems

DIN Rail UPS DC UPS/Battery Detection System Model: BDS-DIN-UPS Installation/Operation Manual

ACSI MODEL 1406BB-04-AO POWER SUPPLY INSTALLATION INSTRUCTIONS

Back-UPS 650 VA 230 V with AVR (BX650CI-ZA)

MINUTEMAN POWER TECHNOLOGIES Endeavor LCD Series Product Specifications 1000VA 3000VA Single-phase Uninterruptible Power Supply 1.

OWNERS MANUAL JANUARY 2007 ISO

VP-6124/VP-6124-E 24 VOLT DC SWITCHING POWER SUPPLY

Airpax Dimensions, Inc.

Security Plus Online Uninterruptible Power Supply

TECHNICAL SPECIFICATION FOR A 10 TO 50 KVA THREE PHASE, UNINTERRUPTIBLE POWER SYSTEM WaveRider III

E-Series and EF-Series Systems

BR62 Battery Rack Installation, Operation, & Maintenance Manual

Uninterruptible Power Systems. SDU DC Series

Table of Contents 文管中心 發行章

INSTALLATION INSTRUCTIONS FOR SYMCOM'S MODEL 777-HVR-SP ELECTRONIC OVERLOAD RELAY

Installation Guide Smart-UPS On-Line SRT1000/SRT1500 XLA Tower/Rack-Mount

SineWave Guardian TM 380V 600V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 17 ❷ Startup/Troubleshooting Pages WARNING

Uninterruptible Power Supply

Art. No. EC-315. Art. No. EC-330. Art. No. EC-340 SWITCH-MODE BATTTERY CHARGER CONTENTS IMPORTANT SAFETY PRECAUTIONS... 2

BRAVER UPS. (Uninterruptible Power System) User s Manual

MATRIX FILTER USER MANUAL. SERIES D 600 Volts, 60HZ PART NO. INSTR 026 REL MTE Corporation

Installation Instructions

Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications

Technical data sheet VH UL. Digital Energy Uninterruptible Power Supply. GE Digital Energy Power Quality

Transcription:

Installation and Operations Manual SEI 150/48-SEL-XXX DC-UPS SEI Incorporated 5115 Pegasus Court, Suite Q Frederick, Md 21704 Phone 301-694-9601 Fax 301-694-9608 Email Info@seipower.com Web http://www.seipower.com

TABLE OF CONTENTS Table of Contents... 1 Description... 2 Technical Specifications... 3 Environmental Specifications... 4 Safety Information... 4 Installation Instructions... 5 Startup and Checkout... 9 System Shutdown... 10 Repair and Maintenance... 10 Storage... 10 Theory of Operation... 11 LED indicators... 12 Alarm Contact Closures... 13 Fuses... 13 1

DESCRIPTION The SEI 150/48-SEL-XXX DC-UPS is a compact unit designed to power a wide range of customer equipment requiring battery-backed 48 Vdc power. The unit comes equipped with 150 Watts of rectifier power. The power distribution is provided on the rear of the unit via a fuse protected terminal block. The Alarm Contact Closures (ACC) are also accessed via this rear panel terminal block. Commercial (AC) power is applied to the left side of the rear unit. The SEI 150/48-SEL-XXX is designed to be mounted on a 19-inch rack and occupies 5.25 inches of rack space. The SEI 150/48-SEL-XXX comes equipped with a field replaceable, non-spillable sealed lead acid battery pack. Circuitry within the DC UPS monitors and periodically tests the condition of the batteries and displays the results via front panel LEDs as well as Alarm Contact Closures (ACC). Loss of AC power is also communicated via the ACC. The DC UPS utilizes a Low Voltage Disconnect (LVD) circuit that prevents damage to the Battery Packs due over-discharge during an extended AC outage. 2

TECHNICAL SPECIFICATIONS SEI 150/48-SEL-XXX AC Input Power Voltage Frequency Current DC Output Power Voltage Nominal (on AC) Power Current Continuous (on AC) Surge Current Batteries Installed Batteries Removed Or Depleted Fuse Rating 85-264 Vac 47-63 Hz 1.6 Amps Typical (115 Vac input, 150 W output) 2.3 Amps Max 42.0 55.0 Vdc 54.8 + 0.2 Vdc 150 W max 2.7 Amps 30 amps for 200ms, once per 15 seconds 5 Amps for 100ms 15 amps Alarm Contact Closures Rated Voltage (max) 380Vac Switched Current (max) 240 Vac 10 amps 24 Vdc 8 amps Switched Power (max) AC 2000VA DC 200W Terminal Block Torque Rating Battery Pack Battery Type Capacity Fuse Rating Front Panel Fuse Battery Pack Fuse 5.3 inch-lbs (0.6 Nm) Valve Regulate Sealed Lead Acid 9 Ahr 15 amps 40 amps Mechanical Dimensions Width Depth Height Weight 19.00 Inches 8.25 Inches 5.25 Inches 32 lbs 3

ENVIRONMENTAL SPECIFICATIONS Temperature Operating Storage Battery Charging Humidity Thermal Load SEI-150-20 C to +50 C -20 C to +50 C -20 C to +40 C 0-95% non-condensing 70 BTU/hr max SAFETY INFORMATION Always insure that the person assigned to the job can perform the job safely. Always lift all equipment properly. Always disconnect commercial power and remove the battery fuse before working on the unit. Always replace the batteries with batteries of the same type and style. DO NOT work on this equipment during an electrical storm. DO NOT work in locations where there is condensing moisture or standing water. Service to the DC UPS should be performed by a qualified technician. 4

INSTALLATION INSTRUCTIONS GENERAL The installation section of this manual will provide all the necessary information for room requirements, proper inspection, and installation. Inspection The equipment has been fully tested and inspected prior to shipment. Although the unit has been packed in accordance with good commercial practices, it does not preclude damage in transit. The following actions should be taken on receipt of the equipment: Visually inspect the shipping container for damage. If damaged, request that the carrier inspect the shipment. Unpack the inner container from the shipping container and remove the unit from the packaging. Inspect the unit for visible damage. If a claim for damages is to be made, it should be filed promptly with the transportation company. In addition, notify SEI within two days of delivery. SEI will advise the customer of any further procedures that may be required, including an RMA number, in the event that the unit has to be returned to the factory for repair. Make sure the following items are included inside the package: SEI 150/48-SEL-XXX DC-UPS One AC Power Cord. ( IEC versions only) One Installation and Operations Manual. One 15A Front Panel Battery Fuse 5

Installation Requirements AC Electrical Requirements The last three letters of the part number determines the method used to connect AC power to the unit. a. For 0XX suffix units, the DC-UPS is equipped with a set of un-terminated 14 AWG wires, penetrating the rear panel. The value of the 0XX suffix denotes the length, in feet, of the wires. The Black wire is AC Line and the White wire is AC neutral. b. For IEC suffix units, the DC-UPS is equipped with an IEC-320 C14 AC entry module. A 7 foot 6 inch power cord with a molded NEMA 5-15 plug is supplied. Mounting Instructions 1. Unit Weight - The SEI 150/48-SEL-XXX weighs 32 lbs with the battery pack installed and 12 lbs with the battery pack removed. It may be advantageous to remove the battery pack before mounting the unit. 2. Battery Pack Removal a. Remove and retain the front panel battery fuse. (Not installed when unit ships.) b. Loosen the four cover retention screws and remove the front cover. c. Disconnect the 2-Pin Battery Pack connector on the left side of the battery pack. Figure 1 Disconnect Battery Pack Connector 6

d. Remove and retain the two Battery Pack retention screws on the top of the battery pack. Figure 2 Remove Battery Pack Retention Screws e. Slowly slide the battery pack out of the unit. When the rear of the battery pack contacts the retaining bracket, lift the front of the battery pack up and continue to slide the battery pack until it is out of the unit. Figure 3 Slide Battery Pack Out Lift Up to Remove 3. Rack Mounting - The SEI DC-UPS is designed to mount to a 19 rack using two rack screws per side. The mounting slots on each rack adapter are spaced in conformance with EIA standard RS-310-B. 7

4. Ventilation - It is important that the DC-UPS s ventilation ports not be blocked. Therefore, leave adequate space on top and bottom of the unit to ensure unrestricted airflow to the unit. It is recommended that a minimum of 3 inches of space be allowed on the top and bottom of the unit. The unit should be installed in a clean dry area where the ambient temperature does not exceed 50 C. 5. Attach Customer Equipment - Attach the equipment to be powered to terminal block on the rear of the unit. The maximum screw torque value is 5.3 inch-lbs (0.6 Nm). Output Fuse 48Vdc Terminals ACC Terminals AC Power IEC Connector (-IEC version only) Figure 4 Rear Panel Connections 6. Attach to the ACC Connector If desired, attach customer monitoring or indicating equipment to the Alarm Contact Closure via the rear panel terminal block. 7. Install the Battery Pack If the battery pack was removed when mounting the unit a. Set the back of the Battery Pack into the unit. b. Lift the front of battery pack and slide the battery pack in until the rear of the battery pack clears the retention bracket. Lower the front of the battery pack and slide the battery fully into the unit. c. Install the two Battery Pack retention screws on the top of the battery pack. d. Connect the 2-Pin Battery Pack connector on the left side of the battery pack. Slide the battery cable harness to the left side of the battery pack. e. Install the cover and tighten the four cover retention screws. 8. Install the Battery Fuse Install the ATO Battery fuse on the front panel of the unit. 9. Attach the AC-Power a. For standard units, attach the provided AC Power Cord to the IEC receptacle on the rear of the DC-UPS. 8

b. For XXX option units, connect the hardwired AC power wires to the AC power feed. A 10-24 grounding stud is provided next to the AC power cable strain relief. Hardwired AC Cable External Grounding Stud Figure 5 HW option AC connection START UP AND CHECKOUT Power On Checkout. 1. Once the unit is properly mounted, you may begin the checkout procedure. First, insure that all the equipment to be powered by the unit is installed. 2. Turn on the AC power feed to the unit. 3. When power is first applied, the front panel LEDs will go through a three second start-up sequence of red, green and flashing. 4. After the start-up sequence, the DC power output will turn on. Verify that the connected customer equipment is receiving power. 5. The Battery Charge Status LED will flash green. This indicates that the Battery Pack is charging. 6. Disconnect the AC feed. Verify that the Battery Charge Status LED is red. If there is no load on the DC-UPS this may take several seconds. Verify that the connected equipment is still receiving power. 7. Reconnect the AC power feed. The Battery Charge Status LED will flash green. This indicates that the batteries are charging. 8. If you have a specific question not addressed in this manual, please call 301-694- 9601, for technical support. 9

SYSTEM SHUTDOWN 1. The SEI 150/48-SEL-XXX DC-UPS is an uninterruptible power system. Therefore, cutting the AC power feed to the unit will not shutdown the DC power distributed to the loads until the battery pack is full discharged. 2. Disconnect the AC power feed. 3. Once the System Status LED turns red, press and hold the Battery Test Switch for 5 seconds. The front panel LEDs will turn off, indicating no power output. a. Alternatively, remove the Battery Fuse on the front panel of the unit. b. Wait a least 10 seconds before re-installing the Battery Fuse. REPAIR AND MAINTENANCE The SEI DC-UPS is engineered to operate unattended and with low maintenance overhead for extended periods of time. Although the electronics within the DC-UPS require no routine maintenance, the battery pack will have to be replaced periodically. When the unit indicates a Battery Test Failure via the front panel LED and the Alarm Contact Closure, the battery pack should be replaced immediately to ensure continued back-up power operation. The battery pack can be removed and replaced without taking the power unit off-line. Follow the procedures outlined in the mounting instructions above to remove and re-install the battery pack. STORAGE The SEI 150/48-SEL-XXX may be stored at temperatures of 25 C or below for up to six months. The DC-UPS must be powered up for at least 48 hours every six months to maintain the batteries. For storage temperatures between 26 C and 40 C, the un-powered storage time must not exceed three months. For storage temperatures above 40 C, the unpowered storage time must not exceed one month. Failure to maintain the batteries will result in decreased battery capacity, decreased battery life and battery failure. Note: The front panel battery fuse must be installed to charge the battery pack. 10

THEORY OF OPERATION Theory of Operation The following will provide you with an outline of operations and a list of modules found in the DC-UPS. Modules Rectifier System Controller/LVD Battery Pack Output Terminal Block Alarm Contact Closure (ACC) ACC 150 WATT RECTIFIER SYSTEM CONTROLLER TERMINAL BLOCK BATTERY PACK Rectifier Figure 6 Functional Block Diagram DC-UPS The 150W rectifier converts AC input power to regulated DC power to properly charge the battery pack. The input of the rectifier is fused for protection. This fuse is not user accessible. System Controller/LVD The System Controller has the following functions: Distribution of the DC power Battery charge voltage and current control and monitoring Battery Low Voltage Disconnect Function (LVD) Battery charge and test status indicators Automatic (every 24 hours) and manual battery test 11

Low Voltage Disconnect Function The low voltage disconnect function will disconnect the battery when the battery voltage drops below 42.0 Vdc. This is done to prevent deep discharge of the batteries, which can adversely affect battery life. LED Indicators There are two LED indicators on the front of the unit; Battery Charge Status and Battery Test Status. The functions of these indicators are as follows: Battery Charge Status: Constant Green Fully Charged Flashing Green Charging Constant Red On Battery Battery Test Status: Constant Green Battery Good Fast Flash Red Wait, Then Test Slow Flash Red Replace Battery Manual Battery Test Switch Push to Test NOTE: The Manual Battery Test switch is disabled when the battery is charging. Also, to prevent unnecessary battery discharge, the Manual Battery Test is disabled for 1 minute following a Battery Test. In both cases, the Wait, Then Test indication is displayed. When a battery test is applied (either automatically or by pressing the battery test button) the Battery Test Status LED will turn off. Once the test is complete, the Battery Test Status LED will either be a Slow Flash RED for a failed test or Constant GREEN for a successful test. Additionally, once the test is complete the Battery Charge Status LED will Flash GREEN indicating the unit is charging the battery. During the battery test cycle, a load is applied to the battery. The system detects this discharge from the battery, as it would any other discharge, and automatically recharges the battery. Battery Pack The 9 Ahr non-spillable valve-regulated sealed lead acid battery pack provides DC power to load in the event of AC power loss. The battery pack will support a 150W load for up to 2 hours. Optimal battery life is achieved at an ambient temperature of 25 C. Under these conditions, the battery pack should last between three to five years, depending on frequency and depth of discharge. Operation at higher temperatures will decrease battery life. 12

Alarm Contact Closures The DC-UPS Alarm Contact Closures provide relay contacts to remotely monitor the status of the unit. The AC Fail relay indicates whether the unit is operating on AC power or on battery power. The function of the Battery Test Fail relay changes based on the status of the AC Fail relay. If the DC-UPS is operating on AC power, The Battery Test Fail Relay indicates the status of the last battery test. If the DC-UPS is operating on Battery power, the Battery Test Fail Relay indicates whether the battery voltage is greater than or less than 48Vdc. AC Fail Relay State Battery Test Fail Relay State DC-UPS Operating Status NO NC On AC Power, Battery Test Pass NO NO On AC Power, Battery Test Fail NC NC On Battery Power, Battery Voltage > 44.0Vdc Or DC-UPS shutdown NC NO On Battery Power, Battery Voltage < 44.0Vdc Fuses The SEI 150/48-SEL-XXX DC-UPS contains a total of four fuses. 1. Rectifier AC input fuse this fuse is not user accessible. If this fuse is blown the unit is no longer safe to operate. 2. Battery Pack Fuse The battery pack is assembled with a 40 amp fuse between the second and third battery. This fuse is intended to protect the battery pack from a short circuit when the pack is not installed in the DC-UPS. 3. DC Output Fuse On the rear panel of unit, next to the output terminal block, this fuse limits the output current of the DC-UPS. 4. Battery Fuse On the front panel of the unit next to the LED indicators. This fuse can be removed to shut down the DC-UPS when operating on battery. After removing this fuse, wait a least 10 seconds before re-installing it. The unit is shipped with 15 amp fuses for the output and battery fuses. This value is required in order to allow the unit to provide the 200 millisecond, 30 Amp pulse mode operation. If high current pulse operation is not required or is of a lower pulse current value, the fuse value may be reduced per the chart below to provide a greater level of overload protection. The two fuses should always be the same value. The minimum value of both fuses is 5 Amps, to support battery test load current. Fuse Value Part Number 80Vdc Part Number 58Vdc Max. Pulse (200mSec) 15 Amp Littlefuse 166.7000.5156 Littlefuse 142.6185.5156 30 Amps 10 Amp Littlefuse 166.7000.5106 Littlefuse 142.6185.5106 20 Amps 7.5 Amp Littlefuse 166.7000.4756 Littlefuse 142.6185.4756 15 Amps 5 Amp Littlefuse 166.7000.4506 Littlefuse 142.6185.4506 10 Amps 13