Earth-Rite MGV Mobile Grounding Verification. White Paper. Author Details: Page 1 of 5

Similar documents
Static Discharge Ignition of Combustible Atmospheres. White Paper. Author Details: ungrounded vacuum tankers and road tankers.

Static Discharge Ignition of Combustible Atmospheres. White Paper. Author Details:

Static Discharge Ignition of Combustible Atmospheres

Cen. -Stat Static Grounding clamps, cables and reels. Leading the way in hazardous area static control

The Earth-Rite MGV is designed to enable operators establish safe grounding of their vehicle in accordance with these recommended practices.

Earth-Rite MGV. IECEx SIL 2. Leading the way in hazardous area static control. Mobile Ground Verification System

Hazardous areas, as found around a service station, are classified into three zones as follow: Table 1: Zone Classification for Vapours

SAFE USE AND HANDLING OF HOSES AND FLEXIBLE CONNECTIONS IN THE SOLVENTS INDUSTRY

Working Principle of Earth Leakage Circuit Breaker (ELCB) and Residual Current Device (RCD)

EARTHING YOUR QUESTIONS ANSWERED

SPRAYSHOP ANALIZER IMPORTANT : TO BE READ BEFORE USING THE HIGH VOLTAGE FUNCTION

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

Lumenition Optronic Ignition System PMA 50 Power Module. Fitting Instructions

Electrical. Earthing & Bonding. Installation Techniques. Learning Notes MODULE 2.2 UNIT PHASE:2

Table of Contents Foreword I. Product Introduction II. Notice For Safety III. Main Technical Parameters IV.

PowerCORE 8.8mm Hybrid Super Conducting Wire CORETECH OVERVIEW

Safer and Easier with Conductive Piping. Making Fuel Flow Safely.

FACT SHEET Standard: Electrical Safety

Atlas ESR and ESR + Equivalent Series Resistance and Capacitance Meter. Model ESR60/ESR70. Designed and manufactured with pride in the UK.

EXTENSIVELY READ THE MANUALS AND HAVE SOME TRAINING. THIS TYPE OF CONNECTION IS NOT EVEN LISTED IN THE TM

ECET Distribution System Protection. Overcurrent Protection

Earth-Rite II RTR Static Earthing System

Installation Guide Galvanic Isolator Gi50/32/S/SA - 120a Surge Current

LABORATORY SAFETY SERIES: Electrical Safety

Why Orion BMS Internal Fuses Blow

G76x Direct Spark Ignition Controls

Enelion Vertica. Installation manual. 22 kw. for the specialists

Ensuring the Safety Of Medical Electronics

NZQA registered unit standard version 1 Page 1 of 5. Apply and remove portable earths in an electricity supply system

MegaPulse 1.2x50-8 PV

P.O. Box 435 Saratoga Springs, NY 12866

Regulated Hose Supply Installation, Operation & Maintenance Manual

SENTINEL BATTERY MONITORING

REFERENCE MANUAL FORM: MX-TRM-E REL REV MTE

Forecourt safety Competent persons

Instructions for use

Diesel Engine Runaway The risks revealed by Test Results

HI-POT/CONTINUITY TESTER Model PLEP01

ELECTRIC FENCE ENERGIZER SERVICE MANUAL MODEL 950 SERVICE MANUAL FOR OLLI 950 FENCE ENERGIZERS

Chapter 4 Ignition & Electrical Systems

DTC P0A04 - Open Wiring Fault

Series Base mounted pump. Installation and operating instructions

1) Activity Description: Management of Petroleum Storage Tanks and Containers

Safe, fast HV circuit breaker testing with DualGround technology

Power Break Circuit Breakers

Integrated Inverter/Battery Monitoring System (IBMS)

Surface Wetness Sensor

Error codes Diagnostic plug Read-out Reset Signal Error codes

Air Operated Diaphragm Pumps Operating and Maintenance Instructions

Introduction to Electricity & Electrical Current

Installation, Operation & Maintenance Manual

Grounding Of Standby & Emergency Power Systems

ACE Variable Frequency Drive System

MP V 8A Electronic Smart Charger. Instruction and Information Manual

The Power Systems Industry Experts. Installation Instructions. PT100 Stationary Generator Monitoring System

NORTH COUNTY FIRE AUTHORITY POLICY & PROCEDURE MANUAL OPERATIONS

KEWTECH. KT56 digital multi function tester. Instruction manual

1.0 Installation Wiring

M503, M504. M503, M504 Pneumatic Control Box * * Product Data Sheet. Features & Benefits

Chapter: Electricity

"ELECTRICAL SAFETY IN THE LABORATORY"

Sources of Ignition and Hazardous Area Classification Core

The Knowledge Bank at The Ohio State University. Ohio State Engineer. Electrolysis in Underground Structures

AccuSpark. Fitting and Information Guide For. Modules Distributors coils Tools. Modern Ignition for Classic cars

PREVENTION OF STRAY CURRENT BY THE MAINTENANCE-OF-WAY

Installation Example and Guide

Shock Tube Saver System Installation and Operation Manual Duke Part No Rev. B

Automatic Garage Door Operator

2 TONNE TROLLEY JACK

Safety Design of CHAdeMO Quick Charging System

Sensors & Controls. Everything you wanted to know about gas engine ignition technology but were too afraid to ask.

Matrix AP 400V 690V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 20 ❷ Startup/Troubleshooting Pages WARNING

National Aluminium Company Limited TRAFFIC RULES AND PROCEDURES

EXPERIMENTAL VERIFICATION OF INDUCED VOLTAGE SELF- EXCITATION OF A SWITCHED RELUCTANCE GENERATOR

Introduction. Prevention and Control

Installation Instructions for Remote Mount HMI 211 Display Panel Kit A045J206

3 TONNE TROLLEY JACK

BEFORE USING THE PRODUCT

EPC DC MOTOR SPEED CONTROL

Hybrid & Electric Cars Guidance for organisers of Speed events

LiquidPower Specialty Products Inc. PIPELINE FLOW IMPROVER SOLUTIONS

Battery Charger Retrofit Kit Q-DCCHG1 for DC Cabinet Retrofit Manual

Installation & Maintenance Manual

DTC P0324, P0325, P0326, P0327, P0328, P0330, P0332, or P0333

DL-300 Charge Controller User Manual

SPARKSCAN1 HIGH VOLTAGE CLAMP OPERATING MANUAL

G72x Series Direct Spark Ignition Controls

DTC P0351, P0352, P0353, P0354, P0355, P0356, P0357, or P0358

Polypropylene Piston Drum Pumps

Inspecting Airport Fueling Systems

Part Number: DBDC10 / DBDC20 DC to DC Dual Battery Charger Manual

Underground Storage Tank Guidance for Commercial Building Inspectors

Ignition control. The ignition system tasks. How is the ignition coil charge time and the ignition setting regulated?

Control of Static Electricity during the Fuel Tanker Delivery Process

Instructions for use Attention

Bulk Storage and Handling of Isobutyronitrile and n-butyronitrile

Constant Running Hydraulic Pump Installation Guide. Document Number: Date: March 2006

Earthing UNIT. Learning Objectives. Introduction. To understand purpose of Earthing. To learn system of earthing.

"U" TROUGH SCREW CONVEYOR CNU SERIES. OPERATING MANUAL FOR INSTALLATION, OPERATING AND MAINTENANCE

TC Series Cooling Systems

Transcription:

White Paper Author Details: Mike O Brien, Head of Marketing and Sales for Newson Gale If you have any questions relating to the topics discussed in this article, you can contact Mike directly at: mike.obrien@hoerbiger.com Enquiry > Click here to submit a product related query or a request for quotation. This article will explore the current methods used to provide static earthing protection for vehicles operating in locations that do not have installed, or correctly specified, static earth monitoring systems. Although primarily designed to provide all tankers with mobile ground (earth) verification capability, the has proven to be a success for vacuum tankers used by contractors providing cleaning, spill and material recovery services to companies with classified hazardous areas. The MGV is also utilised on tankers that must collect from, or deliver product to, locations that do not have satisfactory static earthing protection for road tankers in place. Vacuum tankers provide a wide range of services to the hazardous process industries ranging from storage tank cleaning to the recovery of combustible materials resulting from leaks and spills. A key feature of this type of service is the recovery of materials in locations with potentially combustible atmospheres. Static electricity is a well known ignition source within the hazardous process industries and because the generation and accumulation of static electricity is not visible to the naked eye, this below the radar characteristic, makes it an exceptionally precarious and dangerous hazard. Normally, the only evidence of static electricity being present during a transfer operation is when somebody sees or hears a static spark discharge. By then it may be too late to prevent the ignition of the surrounding atmosphere if it is in its combustible range. Earthing vacuum tankers operating in hazardous areas eliminates the threat posed by static electricity and is an action that effectively connects the tanker to the general mass of the Earth, which is sometimes called True earth. The voltage induced on the tanker by the charged material is the key factor in a static spark discharge. Earthing ensures that no voltages are generated and permitted to accumulate on the tanker. A solution that is appropriate to the potential hazard For over twenty years dedicated static earth monitoring systems have replaced basic earthing reels on the road tanker loading gantries of petrochemical and chemical sites, pharmaceutical sites, tank farms and food and beverage manufacturing sites. Due to the combination of the large quantities of combustible material being processed, the amount of charge that can be induced on tankers and the potential outcome of the ignition of the atmosphere, bonding reels were replaced with earth monitoring systems that were designed to monitor the integrity of the road tanker s connection to earth so that electrostatic charge could not accumulate on the tank or chassis of the road tanker while product was being transferred. To enhance the safety of transfers at these locations, gantry mounted earth monitoring systems normally have an interlock function that stops the movement of product if the earthing system is disconnected from the road tanker. Even though the potential and consequences of fires is, at the very least, the same for road tankers at dedicated loading gantries, vacuum tanker service providers have not been in a position to provide this level of safety and protection of their personnel and tankers, or for their customer s personnel and property. Until now, vacuum tanker service providers have had to rely on very basic devices to earth their vehicles. This is simply because technology that is capable of verifying the quality of static earthing points in a mobile, quick and user-friendly way has not been available to drivers and operators. The method currently used consists of a simple earthing clamp attached to single core braided cable wound onto a reel. Page 1 of 5

Very often, vacuuming operations will be carried out on facilities and remote locations where designated earthing points may not be tested on a regular basis, are not accessible or do not exist. (More detail on earthing points is provided at the end of this article). Bulk transportation companies can also have the same difficulties when they deliver product to customer sites where earthing systems are not up to current specifications, or worse still, are not installed. When compared to the performance and safety of static earth monitoring systems, single core bonding reels have several major drawbacks. = Bonding reels cannot inform the driver that the clamp has penetrated through potential resistors to the flow of static electricity. Rust and paints coatings can prevent clamps from making a solid, low resistance connection to the metal of the object performing the earthing function. = Bonding reels cannot monitor the tanker s connection to the earthing point for the duration of the transfer process. If the clamp s connection to the earthing point is compromised, the drivers and operators will have no way of knowing this as they will be concerned with the safe and secure transfer of material. = When the driver needs to connect the reel to secondary earthing points (e.g. pipe or structural support beam), the bonding reel cannot verify that the earthing point actually has a verifiable connection to a True earth ground. = On many customer sites electricians are required to perform resistance readings with multi-meters to verify that the tanker has a 10 ohm or less bonded connection to a designated earthing point, via the bonding reel. This method has several major drawbacks. = The resistance check is a one-time bond resistance check between the points the tanker is connected to. It does not verify if the structure the reel is connected to has a connection to a True earth ground. = Because the resistance check is a one-time check, the drivers will not know if the clamp s connection is compromised during the transfer. Unlike the security provided to road tanker drivers and loading gantry operators by gantry mounted earth monitoring systems, the vacuum tanker team running the recovery or transfer operation has no way of knowing if their tanker is connected to a good earth. Contract service providers, and customers, have concerns due to such limitations because the teams are connecting reels to earthing points that have neither been tested nor verified as being connected to a True earth ground. In order to remove this uncertainty and provide vacuum tanker service providers with the same level of protection that gantry mounted static earth monitoring systems provide, Newson Gale developed the Earth Rite MGV, which is a vehicle mounted static grounding verification system. MGV stands for Mobile Ground Verification. Newson Gale developed the to give the providers and customers of vacuum tanker services the same level of safety and performance that a gantry mounted static earthing system can provide. The only difference between a gantry mounted system and the MGV is that the MGV is a permanent component of the tanker for which it is providing static earthing protection. = The electrician needs to be taken off maintenance, repair and installation work to perform this test and may be delayed, even up to a few hours, in performing the resistance check. This has the knock on effect of delaying the vacuum tanker team in proceeding with the cleaning, spill recovery or tanker offloading operation. = In an emergency situation, like a spill or leak, the vacuum tanker team may not have time to wait for an electrician to conduct a bond resistance test and will have to bond the tanker to points that have not been designated as verified earthing points. In that situation, they will be hoping that the object they have bonded to will have a connection to True earth. Page 2 of 5

The MGV incorporates the recommendations of API RP 2219 Safe Operation of Vacuum Trucks in Petroleum Service, which is the most relevant standard to address the precautions that should be put in place when vacuum tankers are being used to transfer combustible materials or are carrying out transfers in potentially combustible atmospheres. clamp s connection to the earthing point is compromised or removed while a transfer is underway, the MGV system detects this. This function is called Continuous Ground Loop Monitoring. When it comes to earthing vacuum tankers the recommendations in API RP 2219 are: = To earth the truck before commencing with any operations, where a designated, proven ground source is preferred. = To ensure the electrical resistance between the truck and the grounding point does not exceed 10 ohms, the continuity should be verified with an ohmmeter following connection and prior to operations. = Focussing on the first requirement of the standard, it states that we need to establish that the earthing point we are connecting the tanker to, is a proven ground source. The ground source, in other words, is an object that has a direct electrical connection to a True earth ground. The MGV system matches this requirement by ensuring the earthing point to which it is connected, has a verifiable connection to True earth. This function is called Static Ground Verification. The Green Pulsing LEDs inform the team that the MGV is continuously monitoring the health of their tanker s static earthing circuit. To ensure the connection between the point the MGV has verified as having a connection to a True earth ground and the tanker is 10 ohms or less, the MGV will continuously monitor the tanker s connection to the now verified earthing point. In addition, the MGV monitors its own connection to the tanker. This is especially important as it ensures both the tank and chassis are connected to earth via the MGV system. This ensures that there is a continuously monitored circuit between the tanker and the verified earthing point which will enable static electricity flow off the tanker and into the ground. Because the MGV is now monitoring the circuit between the tanker and the verified earthing point, if the Both the SGV and CGLM checks of the must be positive in order for a static ground connection to be established. When both checks are positive three highly luminous green LEDs pulse to inform the drivers that the tanker is earthed. At this point, the transfer team can proceed with the next stage of the material transfer operation. Any static generated by the transfer process will immediately flow directly through the MGV to earth removing the risk of ignition of combustible atmospheres or shocks to operators caused by discharges of static electricity. From the driver s perspective, earthing the vehicle with the MGV couldn t be simpler. When the LED behind the system s window is red, it means the tanker does not have an earth connection. All the driver needs to do is connect the earthing clamp to an object that he wishes to test. If the object to which the clamp is connected has a verifiable static earth connection and the clamps connection resistance to the earthing point is 10 ohms or less, the LEDs will switch from red to pulsing green. The green pulsing LEDs inform the team that the MGV is continuously monitoring the health of their tanker s static earthing circuit. Page 3 of 5

Both the Static Ground Verification and Continuous Ground Loop Monitoring checks need to be positive in order for the earth status indicators to change from red to green. And just like the levels of security provided by a gantry mounted static earthing system, the vacuum tanker provider has the option of interlocking a pair of volt free contacts with the pumping system. If the MGV detects a loose or broken connection in the earthing circuit when a transfer is underway it immediately shuts down transfer of material, which in turn, stops the generation and accumulation of static electricity on the tanker and the overall transfer system. Another interlock option is to mount a strobe light at an elevated position on the tanker to provide an additional indicator for the recovery team especially if they need to work in a position, or at a distance, that prohibits their view of the earth status indicators on the MGV system. Primary earthing points and Secondary earthing points The earth electrode, more commonly known as the earthing point, can be any metal object ranging from a network of earthing rods protruding from concrete to standard installations such as building structures and pipes entering the ground. The composition of the ground or soil surrounding the electrode is normally the component that presents the most resistance to the flow of static electricity. Different soils have varying levels of resistance due to soil type resistivities and moisture content which can vary dramatically throughout the seasons. For example, soils with high moisture content levels can have very low values of resistance to a True earth ground, but in winter, this water and moisture can freeze, dramatically increasing the resistance between the electrode and True earth, which could rise to a level that would impede the flow of static electricity. In effect, the soil can be described as a resistor in a circuit and we want to know if this resistance is low enough to safely and reliably channel the static charges from the tanker to earth. All sites with classified hazardous areas will have electrical fault and lightning protection systems that are connected to structures that will have been tested by engineers and will be defined as designated earthing points. These points can also be used to earth plant equipment and vehicles at risk of static charge accumulation. These primary earthing points should be regularly tested to ensure they will not only function as reliable paths to earth for stray currents and lightning strikes, but also protect against the accumulation of static electricity. When looking at static electricity as distinct and separate from the hazards of lightning strikes and stray currents, higher values of resistance to a True earth ground are permitted. Although the hazardous voltages associated with static electricity are very high, when compared with the currents resulting from lightning strikes and electrical faults, the magnitude of static charging currents is very low. Because the magnitude of static charging currents is low, secondary earthing points like pipes running beneath the ground, beams of building structures, storage tanks and temporary earthing rods can be tested by the MGV to determine if they have a resistance to a True earth ground that will easily channel static electricity off the tanker. These are structures that will not be tested to verify their suitability for fault current protection and lightning protection, however, because of their inherent and permanent contact below the surface of the ground, they can be tested to determine if they have resistance values to True earth that would permit the safe transfer of static electricity. Page 4 of 5

Conclusion Until now vacuum tanker service providers, and the customers of vacuum tanker services, have not had access to the levels of static earthing protection available to companies, who, for many years, have been operating tanker loading gantries with dedicated interlocking static earth monitoring systems. Additionally bulk transporters may be delivering combustible product to sites with out of date or non-existent static earthing protection measures. With the system vacuum tanker service providers and bulk transporters can now match the levels of control and safety that have been available to loading gantry operators ensuring their employees, tankers, customer employees and customer properties are fully protected from the ignition hazards associated with static electricity. If the validity of primary earthing points is not fully known, or secondary earthing points must be used, they should be tested by a system like the MGV prior to their use. A verified resistance will safely allow the rapid transfer of static charging currents to True earth, ensuring the tanker, hoses and any other equipment used in the transfer process are protected from incendive static spark discharges within a potentially combustible atmosphere. official distributor of Newson Gale Ltd. www.athex.eu info@athex.eu Tel: +32 (0)3 653 21 82 Headquarters Vierselbaan 40 unit 10 2240 Zandhoven, Belgium Tel: +32 (0)3 653 21 82 Pilot Office Rotterdam City Centre, Weena 290 3012 NJ Rotterdam, The Netherlands Tel: +31 (0)10 496 3614 Newson Gale Ltd Omega House Private Road 8 Colwick, Nottingham NG4 2JX, UK +44 (0)115 940 7500 NG UK White Paper 24 300916