REOWAVE passive The new generation of harmonic filters NEW Overcurrent indication signal Temperature monitoring Potential-free signal contact
REOWAVE passive The new generation of harmonic filters Fulfill with REOWAVEpassive the following standards: Electrical components are continually becoming smaller, more efficient and cheaper. To achieve this, most applications include components such as thyristors or frequency converters. The components are also known as non-linear loads because their characteristic curve is not a straight line, which leads to many u ndesirable problems. In particular, these include harmonics. Harmonics are an example of the type of problem that are often simply not recognised correctly, but can cause significant malfunctioning particularly with the increasing use of non-linear loads. Harmonics cause, for example, interference phenomena such as: Creating additional losses resulting in unnecessary consumption of energy Reduced lifetime of transformers due to destruction of the insulation Resonances in the supply networks Measurement errors Errors in tripping fuses Serious faults in IT systems. The solution for these problems is the REOWAVE passive! This device is used at the place where the problems arise where the biggest effect can be achieved. REOWAVE passive is based on proven components of the REO CNW family such as REO mains filters and REO harmonic filters which, thanks to their excellent characteristics and the special circuit design of REOWAVE passive, efficiently keep the harmonics away from the mains network. Mains Netz Nichtlineare Non-linear load Mains Last Netz Nichtlineare Non-linear load Last REO WAVE Diagram 1: Uncontrolled rectifier Diagram 2: Diode rectifier with REOWAVE passive Diagram 3: Current (blue) und voltage (red) for a B6 rectifier configuration with scaled values Diagram 4: Current (blue) und voltage (red) for a B6 rectifier with REOWAVE passive; scaled values
REOWAVE passive Save money with less reactive power In the course of rising energy costs and growing CO 2 emissions minimizing losses in the transmission grid gains more and more importance. An important factor are the reactive currents. These currents do not contribute to the effective power, but stress all components in the current path and cause additional losses to the ohmic resistance component of the lead. Reactive currents are, for example, harmonics caused by the usage of frequency. However, reducing the energy efficiency is not only a burden on the environment because more energy is consumed for a steady performance - at the same time the costs increase for the operator of the installations, as they have to pay the reactive power. Mains chokes, DC chokes or Harmonicfilter of REO filter unwanted harmonics and help to counteract the resulting reactive current. Thus, the reactive power is diminished, the energy requirement and the running costs are reduced. Measurements at a frequency converter of 22 kw to the motor shaft Non unfiltered filtro Induttanza 1% Ukmains 1%Uk di linea Induttanza 2% Ukmains 2%Uk di linea Induttanza 4% Ukmains 4%Uk di linea REOWAVE passive choke choke choke l input [A] 42,4 41,6 37,7 3,8 32,0 Q [kvar] 19,6 18,0 1,2 10,2 2, Current and power factor at a REOWAVEpassive CNW 8981 / 6-1200A / 400V / 0Hz Our favorite: REOWAVEpassive - save up to 30% energy
REOWAVE passive Automatically monitor filter performance more security for your systems d Loa % Load 0 8 % d n Loa 00 e 1 e % Gr low 10 > Yel d e R NEW Overcurrent indication signal Temperature monitoring Potential-free signal contact In additon to providing excellent harmonic filtering performance, the REOWAVEpassive can also besupplied with these additional options: Overcurrent indication signals Temperature monitoring Floating signalling contacts Automatic disconnection of the filter in the event of a system problem Monitoring and shutdown - temperature and filter circuit supervision The options allow optimisation of the mains network quality and overall system security and allow better monitoring by a PLC or supervisory system. Further details of the additional features: Onsite measurement of power failures FLUKE, ELSPEK Overcurrent indication signal The REOWAVEpassive includes compact measurement and monitoring electronics, which constantly measure the current and indicates status accordingly GREEN = power consumption approx 80% (based on the rated current of the filter) YELLOW = power consumption approx 100% (based on the rated current of the filter) Customized Power Quality solutions RED = power consumption above 10% (based on the rated current of the filter) The status is signalled via a potential-free signal contact and may initiate further action.
REOWAVE passive PE L1 L2 L3 Mains Mains choke Load PE L1 L2 L3 Display Current Absorption circuit 10% Red 100% Yellow 80% Green Logic module Signals Fan Overtemperature Overcurrent 230 V Fan Principle of operation REOWAVE passive The REOWAVE passive filters harmonics, and ensures: Temperature monitoring Bespoke electronics monitor the operating temperature of the inductive components, used within the filter. If these exceed the safe operating temperature, a potential-free contact will indicate this. Disconnection of the filter function in case of failure If an overtemperature condition is discovered the mains is automatically disconnected after a pre-determined delay in order to avoid permenant system damage. All error messages are reset when the power is again returned to the rated operating condition. Optionally with corresponding plugs and sockets for immediate use without large installations, - like that, immediate beginning of the savings! Reduction of the THDI value Increasing network stability Reduction of current consumption Calculate your savings http://reowavepassive.com Reduction of equipment costs Simple integration into existing systems Increase of operational safety
The REOWAVE passive Plus Reactive power optimization - reduce additional costs -REOWAVEpassive Plus - Reduce power consumption by approx. 20% Specially developed control circuitry in the REOWAVEpassive Plus ensures optimum performance, not only is the unit protected in the case of Overtemperature and Overload but it can also be safely used in the start-up mode of a Variable Speed Drive, by bypassing the internal shunt element of the circuit. This minimize the absorbed reactive power and protects the internal REOWAVE filter capacitors. The absorbed reactive power is reduced over the entire range by 30%. In order to optimize the reactive power, the filter circuit is only switched on from a certain current, preventing a reactive current component through the filter choke Traffic function - Monitoring and indication of the rated current Potential-free outputs for temperature / overcurrent Protection and deactivation of filter function for overheating and reactive power optimization
REOWAVE passive REOWAVE passive harmonic filter with a potential for savings REOWAVE passive doesn t only give protection against harmonics significant reduction of costs is also possible. The way that REOWAVE passive works results in reductions in current and current harmonics, enabling significantly smaller fuses, cabling and transformers to be used. REOWAVE passive therefore enables not only energy cost savings but also savings in equipment costs. Measurement on a converter without REOWAVE passive Measurement on a converter with REOWAVE passive Current 2,7 A I 67 % I7 43 % THDI 81% Current 19,7 A I 2,7 % I7 1,8 % THDI 4,4 l [A] 22,00 20,00 18,00 Converter without REOWAVE passive Converter with REOWAVE passive Limit value by EN 61000-3-12 16,00 14,00 12,00 12,00 10,00 10,00 8,00 8,00 6,00 6,00 4,00 2,00 4,00 2,00 0,00 0,00 1 21 32 43 4 6 67 7 8 8 9 9 10 1011 12 13 14 1 16 17 18 19 20 21 22 23 24 2 26 27 28 29 30 Harmonics
REOWAVE passive Image 1: The design allows for the parallel connection of two REOWAVEpassive to increase the power capacity. Mains Netz REO WAVE Non-linear Nichtlineare load Last REO WAVE Mains Netz REO WAVE Non-linear Nichtlineare loadlast Image 2: Naturally several nonlinear loads can be suppressed with a single REOWAVEpassive. The filter must merely be suitably rated for the required power. REOWAVE passive approved REO quality REOWAVEpassive is a filter unit which consists out of approved REO CNW components. This filter unit includes a REO mains filter and a REO harmonics filter. The mains filters function is the pre-supression of the mains as well as the shielding against external harmonics. It filters the harmonics caused by the B6 circuit (thyristor, diode bridge etc.), effects a preliminary suppression of network interference, screens the application from extraneous harmonics and enables a cost-saving in equipment selection and energy consumption. Mains Netz Non-linear Nichtlineare loadlast REO WAVE REO Mains Netzfilter REO Oberwellen- Harmonics filter Umrichter/ Prüfling Manufactured by UL-guidelines!
REOWAVE passive in IP 00 Image 1 - u D=7mm Image 2 - v D=7mm Image 3- w D=7mm CAPACITORS
REOWAVE passive 400 V / 0 Hz Electrical and mechanical data Insulation class: F Climate class: 2/08/21 DIN IEC 68 Teil 1 Ambient temperature: 40 C Protection: IP 00 The components are delivered as separate components for customer mounting Typ CNW/ Image Nr. Choke1/ Choke2 Rated current [A] Losses [W] L B/ B2 Chokes 1 Chokes 2 Capacitors H N1 N2 L B H N1 N2 L B H N1 N2 N3 N4 Weight [kg] 8981/6 8981/9 8982 8986 8981/22 8981/32 8981/36 8981/4 8981/ 8981/70 8981/90 89810 8984 89880 8981/200 8981/230 8981/270 8981/330 8981/370 8981/400 8981/40 8981/0 8981/60 6 9 190 82 210 170 8 12 8 12 100 00 200 100 40 470 100-12, 9 120 190 92 210 170 68 1 77 1 130 7 00 200 100 40 470 100-16,2 12 120 190 92 210 170 68 1 92 18 130 72 00 260 230 40 470 100-17, 16 160 230 90 28 176 71 190 82 210 170 8 00 200 100 40 470 100-2 22 230 230 114 260 176 9 190 82 210 170 8 00 30 100 40 470 100 12 31,4 32 241 240 117 270 18 9 210 97 238 17 77 00 200 230 40 470 100 12 42,9 36 300 240 132 270 18 109 210 97 238 17 77 00 200 230 40 470 100 12 42, 4 313 300 120 33 224 94 210 107 238 17 87 00 200 100 40 470 100-7,1 420 300 12 330 224 119 210 117 238 17 97 00 30 200 40 470 100 12 9,8 70 487 300 16 330 224 132 230 114 260 176 9 00 260 230 40 470 100-67,3 90 80 360 193 330 264 167 230 114 263 176 9 00 260 100 40 470 100-81,8 110 710 420 189 367 316 19 240 122 280 18 100 00 30 230 40 470 100 12 110, 14 860 420 204 369 316 174 26 133 270 200 103 00 30 230 40 470 100 12 130 180 1000 420 234 368 316 204 300 13 31 224 107 00 260 200 40 470 100-160 200 1100 420 234 369 316 204 300 10 280 224 120 00 260 400 40 470 100-167 230 90 480 220 417 36 184 300 170 280 224 13 00 30 100 40 470 100 12 180 270 1140 480 20 416 36 214 360 223 310 264 142 00 200 300 40 470 100-226 330 170 480 20 46 36 214 360 223 310 264 142 00 370 160 40 470 100 12 249 370 1680 480 20 467 36 214 420 206 364 316 143 00 00 160 40 470 100 27 29 400 1410 480 20 464 36 214 420 204 363 316 143 00 370 400 40 470 100 12 266 40 100 480 20 10 36 214 420 220 363 316 18 00 0 160 40 470 100 27 296 0 180 480 20 06 36 214 420 23 364 316 174 00 0 160 40 470 100 27 310 60 2090 480 20 89 36 214 420 268 363 316 204 00 0 10 40 470 100 27 369 8981/800 898000 898200 800 210 40 234 603 470 194 480 241 414 36 18 00 60 10 40 470 100 12 431 Due to the special conception a special design is required - please contact us! 1000 260 40 234 617 470 194 40 290 48 40 184 00 60 10 40 470 100 12 6 1200 3030 40 234 732 470 194 40 308 28 40 204 00 60 10 40 470 100 27 64
REOWAVE passive 480 V / 0 Hz Electrical and mechanical data Insulation class: F Climate class: 2/08/21 DIN IEC 68 Teil 1 Ambient temperature: 40 C Protection: IP 00 The components are delivered as separate components for customer mounting Typ CNW/ Image Nr. Choke1/ Choke2 Rated current [A] Losses [W] L B/ B2 Chokes 1 Chokes 2 Capacitors H N1 N2 L B H N1 N2 L B H N1 N2 N3 N4 Weight [kg] 8981/9 8982 8986 8981/22 8981/32 8981/36 8981/4 8981/ 8981/70 8981/90 89810 8984 89880 8981/200 8981/230 8981/270 8981/330 8981/370 8981/400 8981/40 8981/0 8981/60 8981/60 6 9 190 82 210 170 8 12 8 12 100 00 200 100 40 470 100-12, 9 120 190 92 210 170 68 1 77 1 130 7 00 200 100 40 470 100-16,2 12 120 190 92 210 170 68 1 92 18 130 72 00 260 230 40 470 100-17, 16 160 230 90 28 176 71 190 82 210 170 8 00 200 100 40 470 100-2 22 230 230 114 260 176 9 190 82 210 170 8 00 30 100 40 470 100 12 31,4 32 241 240 117 270 18 9 210 97 238 17 77 00 200 230 40 470 100 12 40,4 36 300 240 132 270 18 109 210 97 238 17 77 00 200 230 40 470 100 12 41, 4 313 300 120 33 224 94 210 107 238 17 87 00 200 100 40 470 100 -,1 420 300 12 330 224 119 210 117 238 17 97 00 30 200 40 470 100 12 7,8 70 487 300 16 330 224 132 230 114 260 176 9 00 260 230 40 470 100-67,3 90 80 360 193 330 264 167 230 114 263 176 9 00 260 100 40 470 100-81,8 110 710 420 189 367 316 19 240 122 280 18 100 00 30 230 40 470 100 12 107, 14 860 420 204 369 316 174 26 133 270 200 103 00 30 230 40 470 100 12 128 180 1000 420 234 368 316 204 300 13 31 224 107 00 260 200 40 470 100-17 200 1100 420 234 369 316 204 300 10 280 224 120 00 260 400 40 470 100-16 230 90 480 220 417 36 184 300 170 280 224 13 00 30 100 40 470 100 12 17 270 1140 480 20 416 36 214 360 223 310 264 142 00 200 300 40 470 100-223 330 170 480 20 46 36 214 360 223 310 264 142 00 370 160 40 470 100 12 243 370 1680 480 20 467 36 214 420 206 364 316 143 00 00 160 40 470 100 27 22 400 1410 480 20 464 36 214 420 204 363 316 143 00 370 400 40 470 100 12 27 40 100 480 20 10 36 214 420 220 363 316 18 00 0 160 40 470 100 27 284 0 180 480 20 06 36 214 420 23 364 316 174 00 0 160 40 470 100 27 298 60 2090 480 20 89 36 214 420 268 363 316 204 00 0 10 40 470 100 27 37 8981/800 898000 898200 800 210 40 234 603 470 194 480 241 414 36 18 00 60 10 40 470 100 12 431 Due to the special conception a special design is required - please contact us! 1000 260 40 234 617 470 194 40 290 48 40 184 00 60 10 40 470 100 12 6 1200 3030 40 234 732 470 194 40 308 28 40 204 00 60 10 40 470 100 27 64
REOWAVE passive 690 V / 0 Hz Electrical and mechanical data Insulation class: F Climate class: 2/08/21 DIN IEC 68 Teil 1 Ambient temperature: 40 C Protection: IP 00 The components are delivered as separate components for customer mounting Typ CNW/ Image Nr. Choke1/ Choke2 Rated current [A] Losses [W] L B/ B2 Chokes 1 Chokes 2 Capacitors H N1 N2 L B H N1 N2 L B H N1 N2 N3 N4 Weight [kg] 8981/6 8981/9 8982 8986 8981/22 8981/32 8981/36 8981/4 8981/ 8981/70 8981/90 89810 8984 89880 8981/200 8981/230 8981/270 8981/330 8981/370 8981/400 8981/40 8981/0 8981/60 9 170 240 107 26 18 8 1 92 18 130 72 00 200 100 40 470 100-28 12 210 240 117 26 18 9 190 82 210 170 8 00 200 100 40 470 100-31 16 230 240 127 26 18 10 190 92 210 170 68 00 260 230 40 470 100-39 22 230 300 122 330 224 94 190 92 210 170 68 00 200 100 40 470 100-48 32 290 300 147 330 224 119 240 97 26 18 7 00 30 100 40 470 100 12 70 36 310 300 162 330 224 134 240 97 270 18 7 00 200 230 40 470 100 12 73 4 380 300 173 33 224 14 240 107 270 18 8 00 200 230 40 470 100 12 84 10 360 168 312 264 142 240 107 27 18 8 00 200 100 40 470 100-91 70 60 420 174 367 316 144 240 122 27 18 100 00 30 200 40 470 100 12 98 90 860 420 189 369 316 19 300 13 330 224 107 00 260 230 40 470 100-111 110 810 420 239 366 316 209 300 13 33 224 107 00 260 100 40 470 100-164 14 1130 480 234 418 36 198 300 13 34 224 107 00 30 230 40 470 100 12 187 180 1190 480 234 418 36 198 300 173 310 224 14 00 30 230 40 470 100 12 200 200 1400 480 244 414 36 208 360 183 31 264 17 00 260 200 40 470 100-229 230 1410 480 264 413 36 228 360 193 31 264 167 00 260 400 40 470 100-26 270 1490 40 289 460 40 199 360 219 309 264 177 00 30 100 40 470 100 12 308 330 1840 40 299 461 40 209 420 268 362 316 219 00 200 300 40 470 100-360 370 1830 40 309 461 40 219 480 266 41 36 208 00 370 160 40 470 100 12 407 400 2040 40 314 461 40 224 480 280 413 36 228 00 00 160 40 470 100 27 434 40 2110 40 319 17 40 229 480 289 414 36 238 00 370 400 40 470 100 12 473 00 2440 40 324 18 40 234 480 29 416 36 238 00 0 160 40 470 100 27 487 600 2330 0 284 94 40 248 480 29 416 36 238 00 0 160 40 470 100 27 70 60 2090 480 370 89 36 214 420 268 363 316 204 00 0 10 40 470 100 27 369 8981/800 898000 898200 800 0 470 194 00 60 10 40 470 100 12 Due to the special conception a special design is required - please contact us! 1000 4790 720 464 824 470 194 600 288 611 00 264 00 60 10 40 470 100 12 1088 1200 120 780 48 83 470 194 660 37 628 20 264 00 60 10 40 470 100 27 1270
REOWAVE passive in IP 20 Image 1 Image 2 Image 3 Image 4 Image Image 6
Electrical and mechanical data Insulation class: F Climate class: 2/08/21 DIN IEC 68 Teil 1 Ambient temperature: 40 C Protection: IP 20 Different housings, depending on the power REOWAVE passive 400 V / 0 Hz Type Image Nr. Rated current [A] Losses [W] Housing dimensions in mm L B H/H1 H2 N1 N2 N3 D Weight [kg] Terminals [mm²] CNW 8981/6 1 CNW 8981/9 1 CNW 8982 1 CNW 8986 2 CNW 8981/22 2 CNW 8981/32 2 CNW 8981/36 2 CNW 8981/4 3 CNW 8981/ 3 CNW 8981/70 3 CNW 8981/90 4 CNW 89810 4 CNW 8984 4 CNW 89880 CNW 8981/200 CNW 8981/230 CNW 8981/270 CNW 8981/330 CNW 8981/370 CNW 8981/400 CNW 8981/40 CNW 8981/0 CNW 8981/60 CNW 8981/800 6 CNW 898000 6 CNW 898200 6 6 9 70 240 17-4 10-9 20 10 9 120 70 240 17-4 10-9 2 10 12 120 70 240 17-4 10-9 30 10 16 160 670 27 17-64 200-9 3 10 22 230 670 27 17-64 200-9 40 10 32 241 820 340 17-79 20-9 0 10 36 300 820 340 17-79 20-9 0 10 4 313 1000 360 260-92 298 0 13 6 16 420 1000 360 260-92 298 0 13 6 16 70 487 1000 360 260-92 298 0 13 80 16 90 80 76 47 20-67 316-13 12 0 110 710 76 47 20-67 316-13 17 0 14 860 76 47 20-67 316-13 200 0 180 1000 600 600 1800 200 - - - - 340-200 1100 600 600 1800 200 - - - - 34-230 90 600 600 1800 200 - - - - 32-270 1140 600 600 1800 200 - - - - 370-330 170 600 600 2000 200 - - - - 427-370 1680 600 600 2000 200 - - - - 427-400 1410 600 600 2000 200 - - - - 442-40 100 600 600 2000 200 - - - - 473-0 180 800 800 2000 200 - - - - 40-60 2090 800 800 2000 200 - - - - 97-800 210 1200 800 2000 200 - - - - 790-1000 260 1200 800 2000 200 - - - - 89-1200 3030 1200 800 2000 200 - - - - 990 - The REOWAVE passive is used in the following markets: Drives technology Renewable energies Railway technologies
REOWAVE passive 480 V / 60 Hz Electrical and mechanical data Insulation class: F Climate class: 2/08/21 DIN IEC 68 Teil 1 Ambient temperature: 40 C Protection: IP 20 Different housings, depending on the power Type Image Nr. Rated current [A] Losses [W] Housing dimensions in mm L B H/H1 H2 N1 N2 D Weight [kg] Terminals [mm²] CNW 8981/9 1 CNW 8982 1 CNW 8986 2 CNW 8981/22 2 CNW 8981/32 2 CNW 8981/36 2 CNW 8981/4 3 CNW 8981/ 3 CNW 8981/70 3 CNW 8981/90 4 CNW 89810 4 CNW 8984 4 CNW 89880 CNW 8981/200 CNW 8981/230 CNW 8981/270 CNW 8981/330 CNW 8981/370 CNW 8981/400 CNW 8981/40 CNW 8981/0 CNW 8981/60 CNW 8981/800 6 CNW 898000 6 CNW 898200 6 9 120 70 240 17-4 10 9 2 10 12 120 70 240 17-4 10 9 30 10 16 160 670 27 17-64 200 9 3 10 22 230 670 27 17-64 200 9 40 10 32 241 820 340 17-79 20 9 0 10 36 300 820 340 17-79 20 9 0 10 4 313 1000 360 260-92 298 13 6 16 420 1000 360 260-92 298 13 6 16 70 487 1000 360 260-92 298 13 80 16 90 80 76 47 20-67 316 13 12 0 110 710 76 47 20-67 316 13 17 0 14 860 76 47 20-67 316 13 200 0 180 1000 600 600 1800 200 - - - 340-200 1100 600 600 1800 200 - - - 34-230 90 600 600 1800 200 - - - 32-270 1140 600 600 1800 200 - - - 370-330 170 600 600 2000 200 - - - 427-370 1680 600 600 2000 200 - - - 427-400 1410 600 600 2000 200 - - - 442-40 100 600 600 2000 200 - - - 473-0 180 800 800 2000 200 - - - 40-60 2090 800 800 2000 200 - - - 97-800 210 1200 800 2000 200 - - - 790-1000 260 1200 800 2000 200 - - - 89-1200 3030 1200 800 2000 200 - - - 990 -
REO AG Brühler Straße 100 D-4267 Solingen Tel.: +49 (0)212 8804 0 Fax: +49 (0)212 8804 188 E-Mail: info@reo.de Internet: www.reo.de Version_03.2017_EN_1 Divisions: REO Vibratory Feeding and Power Electronics Division Brühler Straße 100 D-4267 Solingen Tel.: +49 (0)212 8804 0 Fax: +49 (0)212 8804 188 E-Mail: info@reo.de REO Train Technologies Division Erasmusstraße 14 D-103 Berlin Tel.: +49 (0)30 3670236 0 Fax: +49 (0)30 3670236 10 E-Mail: zentrale.berlin@reo.de REO Drives Division Holzhausener Straße 2 D-16866 Kyritz Tel.: +49 (0)33971 48 0 Fax: +49 (0)33971 48 90 E-Mail: info@reo.de REO Medical and Current Transformer Division Schuldholzinger Weg 7 D-84347 Pfarrkirchen Tel.: +49 (0)861 9886 0 Fax: +49 (0)861 9886 40 E-Mail: info@reo.de REO Test and PowerQuality Division Brühler Straße 100 D-4267 Solingen Tel.: +49 (0)212 8804 0 Fax: +49 (0)212 8804 188 E-Mail: info@reo.de PRODUCTION + SALES: China REO Shanghai Inductive Components Co., Ltd No. 36 ShangFeng Road Pudong, 201201 Shanghai China Tel.: +86 (0)21 88 0686 Fax: +86 (0)21 88 0289 E-Mail: info@reo.cn Internet: www.reo.cn India REO GPD INDUCTIVE COMPONENTS PVT. LTD 2/202 Luna Road Village Luna Taluka Padra Vadodara - 391440 India Tel.: +91 (2662) 221723, +91 (26) 2396148 Fax: +91 (26) 2396971 E-Mail: info@reogpd.com Internet: www.reo-ag.in USA REO-USA, Inc. 840 E. 47th St USA-Indianapolis, IN 46226 Tel.: +1 (317) 899 139 Fax: +1 (317) 899 1396 E-Mail: info@reo-usa.com Internet: www.reo-usa.com SALES: France REO VARIAC S.A.R.L. ZAC Du Clos aux Pois 1 6/8 rue de la Closerie-LISSES F-91048 Evry Cédex Tel.: +33 (0)1 6911 1898 Fax: +33 (0)1 6911 0918 E-Mail: reovariac@reo.fr Internet: www.reo.fr Great Britain REO (UK) Ltd. Units 2-4 Callow Hill Road Craven Arms Shropshire SY7 8NT UK Tel.: +44 (0)188 673 411 Fax: +44 (0)188 672 718 E-Mail: main@reo.co.uk Internet: www.reo.co.uk Italy REO ITALIA S.r.l. Via Treponti, 29 I-2086 Rezzato (BS) Tel.: +39 030 279 3883 Fax: +39 030 279 0600 E-Mail: info@reoitalia.it Internet: www.reoitalia.com Poland REO CROMA Sp.zo.o ul. Pozaryskiego 28, bud 20 PL-04-703 Warszawa Tel.: +48 (0)22 812 3066 Fax: +48 (0)22 81 6906 E-Mail: croma@croma.com.pl Internet: www.croma.com.pl Spain REO ESPAÑA 2002 S.A. C/Curt, 2-2 bis 08340 Vilassar de Mar Barcelona Tel.: +34 937 09 994 E-Mail: info@reospain.com Internet: www.reospain.com Switzerland REO ELEKTRONIK AG Im Halbiacker a CH-832 Elsau Tel.: +41 (0)2 363 2820 Fax: +41 (0)2 363 1241 E-Mail: info@reo.ch Internet: www.reo.ch Turkey REOTURKEY ELEKTRONIK San. ve Tic. Ltd. Şti. Halil Rıfatpasa Mah. Darülceze CD Perpa Tic Merkezi B Blok Kat 8 No:109 TR-34384 Sisli Istanbul Tel.: +90 (0)212 221 118 Fax: +90 (0)212 221 119 E-Mail: info@reo-turkey.com Internet: www.reo-turkey.com