Off Grid Solar Inverter. LVS 50M User Manual

Similar documents
Manual. BlueSolar Grid Inverter 1500 / / / / / 230

STONESTAR AUSTRALIA PTY LTD

User Manual. Solar Charge Controller 3KW

On Line UPS. LUC 1000E / LUC 2000E / LUC 3000E User Manual

User Manual Solar Charge Controller 3KW

SOLAR INVERTER/CHARGER 1000VA/1500VA/2000VA. Appliances. PC TV Light Electricfan

RESISTIVE LOAD XP300C

Solar Charge Controller

SCC-MPPT Solar Charge Controller

User Manual 1KVA-5KVA INVERTER / CHARGER

HYBRID 5048E. Hybrid Inverter INSTALLATION AND OPERATION MANUAL. Version 2.0E

User manual. Solar Hybrid 1-5KVA. Uninterruptible Power Supply / Charger

User Manual 1.5KVA-3KVA INVERTER / CHARGER. Version: 1.1

Sine Wave Solar UPS. Owner s Manual. Thank you for choosing the intelligent NON STOP Solar UPS with state of art technology.

User Manual. Hybrid PV Inverter. Version: 2.1

Maximum Power Point Tracking (MPPT) KA1224MPPT20A KA1224MPPT40A. Solar Charge Controller. User Manual 20A

Solar Hybrid Power Generating System CPS1200EOH12SC CPS2200EOH24SC CPS3000EOH24SC. User s Manual K01-C

User Manual. 3kW Hybrid PV Inverter HX-3000

SCC-MPPT Solar Charge Controller

SCC-MPPT Solar Charge Controller

User Manual 1.5KVA-3KVA INVERTER / CHARGER

User Manual 4KVA/ 5KVA INVERTER / CHARGER. With MPPT Controller

User Manual LV 3KVA-24V INVERTER / CHARGER. Version: 1.1

SOLAR INVERTER/CHARGER SOLAR INVERTER/CHARGER MPPT 2KVA- 3KVA. Appliances. Airconditioning Fridge. Washing machine

User Manual / Manuel utilisateur

1KVA/ 2KVA/ 3KVA/ 4KVA/ 5KVA MS, LV MPPT INVERTER / CHARGER. User Manual. Version: 2.3

UGE-4K Off-Grid Controller OWNER S MANUAL

User Manual 5KVA/5KW INVERTER / CHARGER. Version: 1.3

USER MANUAL. Blazer Vista 1000/1400/2000. Uninterruptible Power System

8 Troubleshooting and Maintenance

MPPT Controller PVTS Series User Manual. User Manual. 800W-4000W Hybrid solar inverter. Version: 1.4

Solar Hybrid Inverter SP Brilliant Grid Series

Solar Hybrid Inverter SP Efecto Series

User Manual 1KVA/ 2KVA/ 3KVA INVERTER / CHARGER

POWER TROLLEY 8 INSTRUCTION MANUAL POWER TROLLEY 8. Model: SINE Instruction Manual for: Self-Contained Sinewave Mobile Power Backup System

Solar Hybrid Inverter SP Brilliant Series

CX-SERIES ADVANCED BATTERY CHARGER

MPPT Solar Integrated Inverters (500VA~2500VA) User Manual THE SOLAR TECH CO.,LTD. Solar Integrated Inverter Series 500VA~2500VA 13.

Power Inverter. User s Manual. Diamond Series CPD1200EILCD

1. Important Safety Warning

User Manual 1KVA-5KVA INVERTER / CHARGER. Version: 2.1

User Manual Digital Energy Uninterruptible Power Supply ML Series UPS VA GE Digital Energy Power Quality

CP-250E-60/72-208/240-MC4 Microinverter with Modular Trunk Cable

Users Manual. Defender 1 8.0KW to 14.0KW Online Emergency Lighting Inverter. Technical Manual # Revision B

Users Manual. Cobra Plus Stand-By Emergency Lighting Inverter. Technical Manual # Revision B

:43 1/13 Victron & BYD B-Box

UPS Wizard User s Manual

User Manual. Digital Energy Uninterruptible Power Supply ML Series UPS VA. GE Digital Energy Power Quality. GE imagination at work

User Manual 1KVA-5KVA (PF1) INVERTER / CHARGER. Version: 1.0

BRAVER UPS. (Uninterruptible Power System) User s Manual

4KVA/5KVA Parallel Installation Guide

Multifunction Electronic Load (EBC-A10) User Manual EBC-A10 User Manual Copyright (C) ZKE Technology

Accessories for Stand-alone inverter SUNNY ISLAND GENMAN

KIT-STCS60D KIT-STCS100D Solar Suitcase 60W and 100W Owner s Manual

3KW Off-grid Solar Power System LFP Battery

SOLARINVERTER MPPT 4KVA - 5KVA

User Manual. Axpert King 3.2KW/5.2KW 48V MPPT SOLAR INVERTER. Version: 1.0

User Manual 1KVA-5KVA INVERTER / CHARGER

Villager III. User Instructions. GTIS Power Systems

Solar Hybrid Inverter SP Efecto Series

c-go 12V/10A 12V/20A Power supply and battery charger Instruction manual

FlinSlim Lite Solar Hybrid Inverter 1KVA-5KVA USER MANUAL. Version: 1.3

User Manual. SP10000 Premium

User Manual 3KVA-5KVA INVERTER / CHARGER. Version: 1.1

3 40W. Product Introduction. 1440mm(56.7in) 560mm (22in) 440mm (17.3in

Duo Battery Charge Controller

MPPT SOLAR CONTROLLER FOR MODELS: 20A baterai 12V 24V

APPENDIX: APPROCIMATR BACK-UP TIME TABLE

Solar inverter with MPPT AX II - M series: 4 / 5 kva, AX II - P series: 3 kva. With integrated star point grounding* according to VDE AR-E 2510-

DC TO AC POWER INVERTER PWRIC150012W INSTRUCTION MANUAL

CONTENTS 1. INTRODUCTION SAFTY INSTRUCTION CABLE CONNECTION SYSTEM DESCRIPTION INVERTER OPERATION...

USER MANUAL. PowerMust 1400/2000 LCD. Uninterruptible Power System

c-go 24V/6A 24V/8A 24V/12A

USER MANUAL. E4 LCD TX 5000(S) / 6000(S) / (S) With Output Isolation Transformer. Uninterruptible Power Supply System

User Manual SOLARMAX 1KVA/ 2KVA/ 3KVA INVERTER / CHARGER

User Manual. Hybrid 4KW PV Inverter. Version: 1.2

Super Brain 989 The Pinnacle of Performance with Power to Spare User s Manual Model Rectifier Corporation

DC TO AC POWER INVERTER

Subject Underhood G System Error Codes and Symptoms System or Parts affected

Solar Hybrid Inverter SP Initial Series

PANcharge1k Battery Charger User's Manual

USER S MANUAL CONTENTS. Uninterruptible Power Supply 1. INTRODUCTION SAFTY INSTRUCTION CABLE CONNECTION... 4

User Manual 3KW/5KW INVERTER / CHARGER. Version: 1.0

OPERATIONAL MANUAL EMBC-8025 INTELLIGENT BATTERY CHARGER. Version 1.5

User Manual G1 Solar MPPT Inverter Solar MPPT Charger English version..1

& Operation Manual. Growatt 10000HY. Installation GR-UM-A03-A-00

User Manual. 3/1 10K~30K Online UPS

USER S MANUAL SOLAR POWER INVERTER KW-6KW

PFC W HF/PFC Battery Charger

USER MANUAL. IPS home inverters with UPS function. IPS home inverter manual

HPP1 MK5 Owner s Manual

User Manual 1KW-5KW SOLAR INVERTER / CHARGER. Version: 1.2

StorEdge TM Solution Applications with the StorEdge Interface and LG Chem Batteries Connection and Configuration (Europe, APAC, South Africa)

The function of this Dynamic Active Probe has divided into three preferences on the screen main Menus:

βeta 20A AUTO 12V/24V SOLAR CHARGE CONTROLLER WITH REMOTE METER

Pure Sine Wave Inverter GP-HS1500. Owner s Manual

SBC V In-Car Charger Dual Input (Solar MPPT & DC)

CONTENTS 1. INTRODUCTION SAFTY INSTRUCTION CABLE CONNECTION SYSTEM DESCRIPTION OPERATION... 9

PV Master OPERATION MANUAL

USER S MANUAL CONTENTS. Uninterruptible Power Supply 1. INTRODUCTION SAFTY INSTRUCTION SYSTEM DESCRIPTION... 4

Transcription:

Off Grid Solar Inverter LVS 50M User Manual

Save This Manual Please read this manual carefully prior to installation, wiring, operation and maintenance of the LVS M Series. This manual contains important instructions and warnings that you should follow during the installation, wiring, operation and maintenance of the LVS M Series. Failure to follow these instructions and warnings will void the warranty. Please note that only qualified and trained technician can do installation, wiring, operation and maintenance of the LVS M Series.

Contents Section 1: Safety Precautions 1 Section 2: Warranty Information 2 Section 3: Demonstration 3 Section 4: Operation Principles 4 4 1 On Grid Power Manager 4 4 2 Off Grid Power Supply 4 4 3 Charge/Discharge Controller 4 Section 5: Product Overview 5 Section 6: Installation 6 6 1 Inside the Package 6 6 2 Assembly Chart 6 6 3 Choosing Proper Location 7 6 4 Mounting Properly 7 6 5 Mounting Procedure 8 Section 7: Wire Connections 11 7 1 Bottom View 11 7 2 Connecting AC Mains 11 7 3 Connecting Loads 12 7 4 Connecting PV 12 7 5 Disconnect PV 13 7 6 Connecting Generator 13 7 7 Connecting Battery Bank 14 7 8 Connecting RS485 16 7 9 Ready to Start 18 7 10 Start up Procedure 18 Section 8: Operation 19 8 1 Display and Buttons 19 8 2 Operation Chart 19 8 3 Settings 20 8 3 1 Set Clock 21

8 3 2 Buzzer Configuration 21 8 3 3 PV String Configuration 21 8 3 4 Battery Configuration 22 8 3 5 Frequency Configuration 22 8 3 6 Main Charging Battery 22 8 3 7 Set RS485 Address 23 8 4 Normal Setting 23 8 5 Factory Setting 23 8 6 Manual ON/OFF 23 8 7 DC Switch of PV (optional) 24 Section 9: LCD Display 25 9 1 LCD Display Chart 25 9 2 Home Frame 25 9 3 Power Frame 1 26 9 4 Power Frame 2 26 9 5 Battery Frame 26 9 6 Setting Frame 27 9 7 Error Frame 27 9 8 System Frame 27 9 9 Voltage Frame 27 9 10 Event Frame 28 Section 10: Interface 29 10 1 RS485 29 10 2 USB 29 10 2 1 Download Data to USB Stick 29 10 2 2 Firmware Upgrade 29 Section 11: Trouble Shooting 31 Section 12: Maintenance 32 12 1 Regular Maintenance 32 12 2 Replacing Fans 32 12 3 Replacing Fuse 33 Appendix: Battery Charging/Discharging Parameter 34

Section 1: Safety Precautions AC and DC sources are connected to this device. To prevent risk of electric shock during maintenance or installation, please ensure that all AC and DC connections are disconnected. High voltage inside device can cause electric shock, even when converter is not operating. Wait for 10 minutes before opening it. Danger voltage exists on all conductive wires and terminals of battery circuit. Please protect and prevent touching of them. Solar input is designed for solar power conversion only, do not use it for other DC sources and purpose. If the product is used in a manner that is not covered by the scope of warranty, the protection provided by the product may be impaired. Must be installed by a competent person. Do not stay permanently at a distance of less than 30cm to this converter. Device generates electromagnetic radiation could be harmful in such a close range. Some metallic parts of enclosure may be hot during operation. Do not throw this electronic device into the trash when discarding. To minimize pollution to environment, please handle according to local regulation. 1

Section 2: Warranty Information Warranty will be void if damage caused by any, but not limited to the followings: Unauthorized opening of the unit. Installation faults such as improper environment, wiring and application. Working conditions beyond the unit specifications. Improper operation of the unit. Violation of safety instructions inside this manual. Damage during transportation. Any internal modification. Replacing or installation of unauthorized software. Unforeseen calamity or force majeure. 2

Section 3: Demonstration LVS M Series: manage PV input, charging, discharging and load supplying functions. PV panels: receive sunlight and convert it into electricity. Battery bank: stores energy from mains and PV input. Protected loads: Appliances and devices need AC power from LVS M Series. Unprotected loads: loads supplied by grid or generator directly. In case no AC from grid or generator, unprotected loads are not powered any more. Usually loads larger than LVS M Series rating power should be connected here. Grid: Public AC Utility. Generator: supplies AC power by diesel engine or other means. Monitoring device: a device to monitor system performance by using RS485. 3

Section 4: Operation Principles The LVS M Series is an intelligent and automatic power manager. Its major principles are: 4 1 On Grid Power Manager In places with the Utility, the LVS M Series can manage the power from PV, grid and battery. For protected loads connected to the LVS M Series, during blackout, the LVS M Series can supply power to loads from PV and/or battery. 4 2 Off Grid Power Supply In places without the Utility, protected loads will be powered by the LVS M Series. The power may come from PV panels and/or battery. In case a generator is connected, whenever power from PV and battery are not enough, the LVS M Series switches loads to generator directly. 4 3 Charge / Discharge Controller While there is excess power from PV, the LVS M Series will direct it to battery. While PV power is not enough, the LVS M Series will supply loads from battery. In case you have set charging battery from the Utility, the LVS M Series will charge battery from the Utility after battery is fully discharged. 4

Section 5: Product Overview 5

Section 6: Installation 6 1 Inside the Package Item Description A. LVS M Series B. Mounting bracket C. User manual D. Plastic anchor & screws * 4, used to fix bracket on wall E. RS485 connector / plug F. Battery sensor G. Spared AC fuse * 1 (30A/250V) 6 2 Assembly Chart 6

6 3 Choosing Proper Location Do not expose the LVS M Series to sunlight, rain or water. Install the LVS M Series at visible level so you can see its status and fix it on a solid surface. Visible Level Mounting Surface Concrete Ok Metal Ok Stone Ok Wood Not recommended 6 4 Mounting Properly Direction: mount the LVS M Series in vertical direction; tilt or horizontal mounting should be avoided. 7

Keeping clearance: reserve at least 50cm distance between the LVS M Series. 6 5 Mounting Procedure Dimension of Bracket: the bracket is used to support the LVS M Series on the wall. Before fixing it, refer to drilling locations and dimension below. 8

Mounting Bracket: place the bracket in place you choose. Drill at the correct positions and fix bracket with the screws in the accessories. Attaching the LVS M Series: 9

1. Lift the LVS M Series slightly higher then bracket. Make sure all fixing points on back are at right positions. 2. Attach the LVS M Series close to bracket. 3. Hang the LVS M Series on bracket slowly. 4. Fix lock caps with screws in accessories. Checking: 1. Check all supporting points and make sure they are in the right positions. 2. Lock caps are fixed with screws. 3. Make sure the LVS M Series is well installed and fixed on the wall. 10

Section 7: Wire Connections 7 1 Bottom View 11

1. Battery socket (Negative & Positive) 2. Battery temperature sensor socket 3. PV1 & PV2 input 4. DC switch (optional) 5. Battery RS485, for Lithium battery pack with battery management system 6. RS485 connector, for monitoring and communication 7. Cable gland for generator remote control 8. AC input 9. AC output 7 2 Connecting AC Mains 1. Open side cover for wiring. 12

2. Select wires as below figure. 3. Insert wires through the cable gland. 4. Crimp the wire with Y terminal. 5. Insert wires with terminals, fix them according to polarity and torque on terminals as figure. 6. Tighten the cable gland. 7 3 Connecting Loads 1. Prepare similar wire as AC mains. 2. Repeat steps as AC mains connection. 3. Fix them on AC Loads terminals. 7 4 Connecting PV 13

1. If there is DC switch on the LVS M Series, SWITCH OFF it in advance. 2. Using following connectors for PV DC cables: Wieland PST40i1 (preferred). Multi contact MC4. 3. Plug connectors to the LVS M Series. 7 5 Disconnect PV To disconnect PV cables, please: 1. Turn off DC switch if available in advance. 2. Push in the inter locker on PV connectors. 3. Pull of the connectors & cables. 7 6 Connecting Generator To connect a generator, please use the AC MAINS terminals as described in 7 2 Connecting AC Mains. You can either connect grid or generator only. These 2 sources can not be connected to the LVS M Series in the same time. Control your generator: if your generator is equipped with remote start/control function, you can connect a wire to Generator Remote Control to control it. It is a normally open dry contact inside the terminal. Before end of discharging, those 2 terminals will be short; this can 14

be used to enable a generator. Once this contact is active, it will remain short until AC mains come back. To connect this control, please: 1. Prepare a wire cable. 2. Unplug the socket on Remote Generator Control. 3. Connect and secure cable terminals on this plug. 4. Insert this plug back. To turn on/off your generator, your generator also needs to have remote on/off connectors (terminal). Please refer to the specifications and manual of the generator. 7 7 Connecting Battery Bank The voltage of battery bank is 48VDC. The recommended numbers of battery packs are 1~5. Please refer to specification for recommended battery type. There will be some other batteries can be used, please contact your local dealer and service for latest information. Official batteries are designed for the LVS M Series considering safety, life and performance. Using other batteries may cause danger and /or poor performance. Before connecting battery wires, please switch off DC voltage from batteries and all AC in advance. Preparing wires and connectors for battery: 15

1. Select wires of cross section >50mm. Red color is for positive (+) wire and black for negative ( ). 2. Prepare a breaker/switch of 150A/125VDC 3. Prepare conduit for those wires. 4. Prepare cover or sleeve for battery terminals (refer to figures in Connecting ). Connecting batteries: 1. Pay attention and follow the instruction of warning label on the unit. 2. Crimp (+) and ( ) wires with ring terminals. 3. Watch out the polarities. 4. Fix wires on both sides of DC breaker/switch. 5. Protect and hide all the cables in conduits. 6. Use battery terminal covers on all battery wires. 7. Fix the wires on battery terminals as figures below. 8. Make sure all terminals are protected. Reverse connections of positive (+) and negative ( ) will damage the LVS M Series. Incorrect wiring is not covered by warranty. Make sure all the connections are well contacted. Any loosen may cause fire and damage 16

Connecting battery sensor: accessory F is the battery temperature sensor. It is used to measure battery temperature for optimized charging. Please connect and fix this sensor as figure in previous section. 7 8 Connecting RS485 To monitor and control the LVS M Series by external devices such as computer, you need to connect them by RS485. A typical RS485 connection diagram is shown below: 17

All wires between devices and computer shall be twisted. Maximum allowable wire length is 1000 meters. The terminal end device may need a terminal resistor. Due to multiple connections, each individual device should be assigned as address as to recognize by computer or device. 1. Connection: For single unit, please connect as figure below: Prepare a 2 wire cable. Take off the plug on RS485 connector. Fix cable on this plug. Take care of the polarity. Push back the plug. For multiple connections, please connect as figure below: The No.2 DIP switch is the terminal resistor switch of the RS485. The default position of this switch is off. However, if the communication does not work well, please try to switch it to on to improve. 2. Setting Address: For multiple connections, you need to assign each unit with different address. To set the address, please refer to section of Set RS485 Address. 18

7 9 Ready to Start Before starting the system, check below items: Item Point of Check Checked? Mounting The LVS M Series is firmly mounted on the bracket 2 lock caps are secured AC All wires are firmly fixed on terminals All polarities are correct Protective ground is available and connected PV All wires are firmly fixed on connectors Polarities are correct PV open voltage is less than maximum voltage of PV input Internal and /or external DC switch is on before operation RS485 Wires and cables are locked and fixed Polarities are correct For multiple units, be sure to set their RS485 in different address DC (Battery) All cables are firmly secured Polarity is correct Breaker/switch is on Battery sensor is installed and connected 7 10 Start up Procedure 19

Section 8: Operation 8 1 Display and Buttons Status LED Text display There are 2 LED s to indicate the LVS M Series status. In normal condition, green one turns on; in abnormal or warning conditions, red one turns on. In case green LED is flashing, there is internal comm. error, please call your local service. 2 lines, showing status, data and instructions. Exit to previous display Operation keys Menu up Menu down Enter or confirm a setting or selection 8 2 Operation Chart By pressing operation keys, different displays will follow the chart as below: 20

8 3 Settings 21

You need to set the LVS M Series after first installation so as to have proper operation in the future. After switching on the LVS M Series of the first installation, the initial setting frame comes out automatically. The chart is indicated. Initial setting is a one way flow. You can not come back to previous setting even you set wrong. In case incorrect operation during setting, please set it again later on. 8 3 1 Set Clock To set clock, press up and down buttons to increase or decrease on blinking characters. Press Enter to change among day, month, year, hour and minute; press Enter to confirm settings. Incorrect clock causes improper operations. Make sure the LVS M Series clock is correct all the time. In case switching off the LVS M Series for more than 5 days, the internal clock setting will lose and change back to the default setting. 8 3 2 Buzzer Configuration Press Enter button to start setting buzzer on/off. Press Up and Down to change setting. Press Enter again to confirm your selection. 8 3 3 PV String Configuration This function is to set the string configuration of PV panels for multiple MPPT model. There are 3 options: INDEPENDENT, PARALLEL and AUTO. Independent: 2 input strings are connected to different MPPT of the LVS M Series individually. Parallel: 2 strings are wired together before connecting to the LVS M Series. Auto: If you do not know exactly the configuration, select this. The LVS M Series will judge automatically. This is the default setting. 22

8 3 4 Battery Configuration This text shows the battery type and its string number. The available selections are: Generic: it is for general type of lead acid battery. If you are using types other than official ones, please select this type. YUASA NPA100 12I. CHLORIDE12CDC100. PANASONIC LC T12105X. 3K EBB100. After setting the type, you have to set string number, the numbers of battery bank in parallel, as well. The possible selections are 1~4 and >=5. Except Generic, all the other batteries are official ones. Each configuration has its own parameters. Please refer to Battery Charging/Discharging Parameter in Appendix for detail information. If you know parameters of non official; battery, please choose similar battery type of the list to have best performance. 8 3 5 Frequency Configuration The setting is to set the AC output frequency to 50Hz or 60Hz. You can set frequency once only in initial setting. Please select proper one for your applications. In case AC mains are connected during setting, the LVS M Series will follow AC mains frequency. In this case, frequency configuration frame will not appear during initial setting. 8 3 6 Mains Charging Battery This setting is to set whether the LVS M Series will use AC mains to charge battery or not. In some applications, you may need AC mains (Grid or Generator) to charge the battery bank when PV power is not enough and battery capacity is low. Select Enable so as to charge battery in this case; select Disable to skip this. Mains maximum current limits the charging current. Charging power equals mains power minus load power. 23

8 3 7 Set RS485 Address This is to set RS485 address. The selectable address is from 1 ~ 200. Default address is 1. To know the detail of addressing of RS485, please refer to section of Connecting RS485. 8 4 Normal Settings Normal setting is used to set the unit whenever you would like to. Its process is similar to initial setting except operation flow as below: In case you would like to set the LVS M Series, just use Menu Up and Menu Down buttons to Setting Frame and press Confirm button 3 times in 2 seconds to start. 8 5 Factory Setting The LVS M Series can be restored to factory setting. If you like to do this, please ask for your local service. 8 6 Manual ON/OFF The manual ON/OFF switch is beneath the LVS M Series as figure shown below: 24

This switch is used to turn ON/OFF the LVS M Series manually. In case battery capacity is enough, push the button to start the LVS M Series. The LVS M Series will supply power from battery bank to your loads. To turn off the LVS M Series, push the switch again, all the AC output will be off and the LVS M Series will shutdown itself. 8 7 DC Switch of PV (optional) This switch is used to turn on or off the PV inputs. The positions are shown as below figures. 25

Section 9: LCD Display 9 1 LCD Display Chart * Note: In case no operation for 1 minute, LCD will go back to home frame automatically. Event frame will not appear in case there is no error/event. To enter setting frame, you have to press Enter button three times in 2 seconds. 9 2 Home Frame Home frame shows the operation status and related data at first text line. It shows date and time at second line. 26

Mode Display in First Line Description Normal Local Load XXXXW The LVS M Series supplies power of XXXXW from PV and/or battery to load. Display on Power frame 1 will show From Solar XXXXW and From BAT XXXXW. Bypass From Mains XXXXW Load power is from AC mains. Display on Power frame 1 will show From Mains XXXXW. Warning Refer to warning On warning or error happening, the LVS M Series shows message the warning messages. Error Refer to error On error happening, the LVS M Series shows the error message messages. Manual OFF Manual off, push ON/OFF to turn on Manual off. Load will continuously be supplied by Grid. 9 3 Power Frame 1 Showing the instant power from different sources: Display in First Line From Solar XXXXW From Grid XXXXW Description The power coming from PV under normal mode. The power coming from Grid (Mains) under bypass mode. Display in Second Line To BAT XXXXW From BAT XXXXW The power charged to battery. The power comes from battery. Description 9 4 Power Frame 2 Showing the accumulated energy of local consumption and grid: Display LEtoday XXXKWh GEtoday XXXKWh Description Local energy consumption of the day. Grid energy supplied of the day. 9 5 Battery Frame Showing battery status: 27

Display BAT Charging BAT Level Medium Description Battery status. Charging, Discharging, Standby or Disconnected. Battery capacity level. Full, High, Medium, and Low. Battery efficiency varies from many factors and is difficult to calculate. The power reading on the LVS M Series display is a calculation for indication of system operation. 9 6 Setting Frame Press Enter button 3 times in 2 seconds on setting frame, the setting procedure starts. Refer to setting in previous section for detail information. 9 7 Error Frame Display in First Line Error 0 Error XX Error number is zero. Total error accounts. Description Display in Second Line No Error Tap Enter button No error recorded. Description Press Enter button to see error detail. Total errors can be recorded are 50. For error large than 50, latest one will replace earliest one. If you like to see the error types, please tap Enter button and using UP and Down buttons to see the detail. The format will be: Line 1 Line 2 Description Error XX Error Message Line 1 shows the error number, line 2 tells you the error message. The messages are listed in tables of error and warning in section Event Frame. 9 8 System Frame The F/W version of the LVS M Series appears in this frame. In case service is required, please tell this information to your service agent. 9 9 Voltage Frame 28

This frame display major system voltage of PV1, PV2, Mains, Battery, alternatively. 9 10 Event Frame In the cases there are events such as errors, warnings and reminding, event frame will appear automatically. The prompt information is listed in error and warning tables below. Error Message Line 1 Line 2 Buzzer Description AC VOLT HIGH Vac XXX V Silent ACV is higher than upper limit AC VOLT LOW Vac XXX V Silent ACV is less than lower limit AC FREQ HIGH Fac XX.X Hz Silent AC frequency is more than upper limit AC FREQ LOW Fac XX.X Hz Silent AC frequency is less than lower limit PV VOLT HIGH Vpv XXX V Continue PV is higher than upper limit BAT VOLT HIGH Vbat XX.X V Continue Battery voltage is higher than upper limit OVERLOAD Output is off Continue Output is overload more than defined time, output is cutoff O/P SHORT CKT REMOVE CKT. Continue Output is short NO BATTERY Check BAT Conn. Continue Battery is not connected CX No Display C1 ~ C7 error, reserved for internal diagnose Warning Message Line 1 Line 2 Buzzer Description XX% Load Pay Attention Every 0.5 sec The load is between 85% and 100% 1XX% Load Pls. Reduce Load Every 0.5 sec The load is between 101% and 110% Low Bat. Cap. Will Shutdown Every 0.5 sec Battery low and will shutdown Fan Fails Check or Replace Every 0.5 sec External fan does not work properly 29

Section 10: Interface 10 1 RS485 RS485 interface aims to monitor the LVS M Series. You need to have RS485 connection and related software. Please refer to Connecting RS485 for proper connection and setting. Please refer to software manual for installation and application. 10 2 USB 10 2 1 Download Data to USB Stick You can plug in a pre formatted USB stick into USB port to download the operation data. The stick must be FAT or FAT32 formatted. To do this, plug in USB stick, LCD will show Download Data Processing. After plugging in the USB, all data inside the LVS M Series will be downloaded to the stick automatically. LCD will show corresponding status. After downloading, while LCD shows Download Data Finished, you can then pull off USB stick. Data download in USB disk are in a file of CSV format. If your USB disk contains firmware for an update, the LVS M Series not download data to USB stick. 10 2 2 Firmware Upgrade You can upgrade the LVS M Series by USB disk with official firmware. To do this, you need to have firmware in USB stick. To update by USB, please get the latest firmware, save it into a blank USB disk, plug USB disk to the LVS M Series, it will start the upgrade automatically. For detail information, please also consult your local service. To prevent unexpected stop, before starting upgrade, make sure PC or Mains are available. 30

The internal memory can store up to 1 month length of data. Data older than this period will be replaced by latest data automatically. Once data in the logger has been deleted, it cannot be recovered. Therefore it is recommended to backup data periodically if you wish to retain this information. 31

Section 11: Trouble Shooting Trouble No display or incorrect display Error on display C4 appears Unable to charge batteries RS485 does not work Internal Comm. error Solution 1. Make sure all PV and battery is properly connected. 2. Check battery fuse and switch (breaker) is on. 3. Check AC (Mains). If no AC, try to push Manual On/Off button. 4. If above actions are useless, please DO NOT push manual on/off any more, call your service immediately. 1. C# Error: switch off all AC and DC then switch on the DC and then the AC again. 2. If above error continues, please contact with local service. C4 means internal over temperature. Please: 1. Review installation location, cooler ambient is preferred. 2. Clean up dust on fans and ventilation holes. 3. If C4 continues, please contact with local service. 1. Improper battery type. Please use official batteries. 2. The life cycle of battery ends. Please replace batteries. 3. Improper battery connection. Please check the wirings between the LVS M Series and battery bank. 1. Check all wiring, connection and polarity. 2. Try to switch On or Off terminal DIP switch 1. Green status LED is flashing 2. Please contact with local service. 32

Section 12: Maintenance 12 1 Regular Maintenance Keep proper distance from other obstacles. Make sure air flow and heat dissipation path is cleared. Clean up any dust on this unit, especially on the ventilation holes. Check operation and status if possible. Check all wiring and cables. 12 2 Replacing Fans For years of operation, the fans of the LVS M series may be worn out. When the fans are very noisy or stopped, please replace fans. Please follow below steps: To replace the fan, it is required to have qualified and authorized technician. Before replacing fan, please turn both AC and DC off. 1. Switch PV, DC and AC off. 2. Remove screws, open fan cover. 3. Remove screws of fan. 4. Take fan out. 5. Unplug fan connector. 6. Replace new fan supplied by authorized dealer. 7. Close and fix this cover again with screws. 33

12 3 Replacing Fuse For some abnormal situations such as overload on AC out, the AC fuse may be broken. If this happens, you need to replace the fuse (35A/250VAC, fast acting). There is a spare fuse in accessory. Take that fuse and follow below figure and replace it. 34

Appendix: Battery Charging/Discharging Parameter Type No. Charging Current Charging Voltage Cutoff Voltage 1 20 13.7 10.8 2 40 13.7 10.8 Generic 3 60 13.7 10.8 4 80 13.7 10.8 >=5 100 13.7 10.8 1 25 14.5 9.9 2 50 14.5 9.9 Yuasa 3 75 14.5 10.2 NPA100 12I 4 100 14.5 10.2 >=5 100 14.5 10.2 1 20 14.7 9.9 2 40 14.7 9.9 Chloride 3 60 14.7 10.5 12CDC100 4 80 14.7 10.5 >=5 100 14.7 10.5 1 20 14.4 9.9 2 40 14.4 9.9 3K EBB 100 3 60 14.4 10.5 4 80 14.4 10.5 >=5 100 14.4 10.5 1 30 14.5 9.9 2 60 14.5 9.9 PANASONIC 3 90 14.5 10.2 LC T12015 4 100 14.5 10.2 >=5 100 14.5 10.2 * Note: The voltage indicated is for single 12V battery. Cutoff voltage is the voltage of rated power. E.G.: for one string, it is the voltage of 150A discharging. 35