Types of Motor Starters There are several types of motor starters. However, the two most basic types of these electrical devices are:

Similar documents
THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing

Starting of Induction Motors

MOTOR TERMINAL CONNECTIONS

Chapter 8. Understanding the rules detailed in the National Electrical Code is critical to the proper installation of motor control circuits.

Direct On Line (DOL) Motor Starter. Direct Online Motor Starter

A few tips on how to select contactor for use in direct on line starter

SECTION MOTOR CONTROL

AF series contactors (9 2650)

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

AF series contactors (9 2650)

Electrical Control System Components Basics of Magnetic Control :

Electrical Motor Controls Chapter 4 (Fourth Edition) Chapter 2 (Fifth Edition)

ECET 211 Electric Machines & Controls Lecture 8 Motor Control Circuits (1 of 2) Lecture 8 Motor Control Circuits

AF09... AF30 3-pole Contactors up to 20 HP / 480 VAC

Application Description

RVS-AX Instruction Manual

ECET 211 Electric Machines & Controls Lecture 6 Contactors and Motor Starters. Lecture 6 Contactors and Motor Starters

Motor Protection Fundamentals. Motor Protection - Agenda

MAGNETIC MOTOR STARTERS

Selection Guide Motor Control Device Solutions

Low Voltage Fuses For Motor Protection

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC

The Enclosed Altistart 22 Soft Start/Soft Stop Motor Controller

Protectors. Manual motor. Types MS116, MS132, MS45x, MS49x. MS Series. Manual motor protectors. Type MS116. Type MS132. Type MS45x.

Exercise 5-1. Primary Resistor Starters EXERCISE OBJECTIVE DISCUSSION. Understand how primary resistor starters operate.

2.1 Warnings & Agency Approvals Electrical Connections - Specifications Standard Wiring Configurations...2 4

3. Coils shall be of molded construction

Basics of Control Components

825-P Modular Protection System for motors Specification Guide

MOTOR TERMINAL CONNECTIONS

Open & enclosed. Spec Tech Industrial 203 Vest Ave. Valley Park, MO Phone: 888 SPECTECH. Reduced voltage starters. Overload relay protection

Coil Data Nominal Current MA Nominal VA Sealed Single Pole Normally Open (SPNO) White Rodgers Q

Full Voltage Starting (Number of Starts):

SOLSTART Instruction Manual

Programmable Logic Controller. Mat Nor Mohamad

Ch 4 Motor Control Devices

ADS7 AC Contactor Starters

EXPERIMENT 2 THREE PHASE INDUCTION MOTOR, PART 1

CSDA Best Practice. Hi-Cycle Concrete Cutting Equipment. Effective Date: Oct 1, 2010 Revised Date:

Enclosures. See Section Typical Description

Induction Motor Control

Pretest Module 21 Units 1-4 AC Generators & Three-Phase Motors

Product guide. Enclosed NEMA starters. usa.siemens.com/controls

ECET 211 Electric Machines & Controls Lecture 2-3 (Part 3 of 3) Symbols and Drawing for Electric Motor Control Systems

KD LV Motor Protection Relay

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES UNIT OBJECTIVES 3/21/2012

DRAFT 1400HP 1000HP 100HP. Reduced Voltage Solid State Starters. Softstarters SOFT. PF Controller PCS Controller PDS Controller V 1...

team master medium voltage solid state starters

Motor Starters. Reduced Voltage. Reduced Voltage Motor Starters 1. Contents

MOTOR CONTROLLERS. STATE the function of motor controllers.

ROTATING MAGNETIC FIELD

ICT TRANSFORMERS. Industrial Control Transformers provide a low and safe control voltage for the operation of many electromagnetic devices

SHORT-STOP. Electronic Motor Brake Type G. Instructions and Setup Manual

Product Guide. enclosed NEMA STARTERS

Government Polytechnic Muzaffarpur Name of the Lab: Electric Traction-II Lab

Adapted from presentation developed by Scott Fausneaucht

TRI-SERVICE ELECTRICAL WORKING GROUP (TSEWG) 03/05/09 TSEWG TP-11: UFC N BEST PRACTICES

AF40... AF96 3-pole contactors Technical data

Starters. Overview. Siemens caters with following types of starters to agricultural and industrial sector.

B BASIC HEAT TREATMENT CONSOLE

Power Electronics. Motor brake relay GA 9031 ministop

Contact us. ABB France Electrification Products Division Low Voltage Products and Systems 3, rue Jean Perrin F Chassieu cedex / France

PAC TRAINING PUMP MOTORS

Manual motor protectors Type MS116 Type MS325 Type MS45X Type MS49X

EPS-ECONOMY PUMP STARTER

Features and Benefits. Control Features

Product Description. Application Description

Controls. CONTACTORS CWB Line (up to 40A)

Electrical Motor Controls (Fourth Edition)

Enclosed Full-Voltage Starters

Product guide. Enclosed NEMA starters. Answers for industry.

Principles of iers (intelligent

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

PREVIEW ONLY - FULL COPY AVAILABLE TO CONSORTIUM MEMBERS. Escalator Specific Electrical Systems. Course 209 PARTICIPANT GUIDE

SECTION MOTORS, MOTOR STARTERS, VARIABLE FREQUENCY DRIVES AND ELECTRICAL WORK

WELLS RURAL ELECTRIC COMPANY Adopted: March 1976 Revised: March 21, 2017 Reviewed: August 21, 1998 RULE NO. 2

201 S. Anaheim Blvd. Page No Anaheim, CA RULE NO. 2 DESCRIPTION OF SERVICE

Technical Information

1.2. Reduced Voltage Motor Starters. Contents Description Type S611, Solid-State Soft Starters... Type S801+, Soft Starters. Solid-State Starters

C E R T I F I C A T E O F C O M P L I A N C E

Components for EEx e Panels

ATS22D88Q soft starter-ats22-control 220V-power 230V (22kW)/ V(45kW)

Size for Size Best Value in the Industry

Design Standards NEMA

Star Series Motor protection & control

Protectors. 35mm DIN rail snap-on mounting. Wide range of accessories

A. Motors shall be designed, built, and tested in accordance with the latest revision of the following standard documents.

MCD 200 Series Soft Starters

SD Series Non-Fused Load Switches

General + Definite Purpose Contactors

Softstarters. Softstarters Type SSM Medium voltage ,800V 1

EE6351 ELECTRIC DRIVES AND CONTROL UNIT-1 INTRODUTION

Jogging and Plugging of AC and DC Motors. Prepared by Engr. John Paul Timola, LPT

Enclosed Full-Voltage Starters

Medium Voltage Metal-Enclosed Switches

TABLE OF CONTENTS. Description Page Description Page. SETI Finland. Approvals:

MaxPak Plus Analog DC V S Drive

1-3 MANUAL STARTERS EXERCISE OBJECTIVE. Examine and describe the operation of manual motor starters. DISCUSSION

MAKING MODERN LIVING POSSIBLE. Technical brochure. Minicontactors CI 5-

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase

Transcription:

Introduction Motor starters are one of the major inventions for motor control applications. As the name suggests, a starter is an electrical device which controls the electrical power for starting a motor. These electrical devices are also used for the purpose of stopping, reversing and protecting electric motors. The following are the two major components of a starter: 1. Contactor: The main function of the contactor is to control the electric current to the motor. A contactor can make or break power to the circuit. 2. Overload Relay: Overheating and drawing too much current can cause the motor to burn out and become practically useless. Overload relays prevent this from happening and protect the motor from any potential danger. A starter is an assembly of these two components, which allows it to turn on or off an electric motor or motor controlled electrical equipment. The starter also provides the necessary overload protection to the circuit. Types of Motor Starters There are several types of motor starters. However, the two most basic types of these electrical devices are: 1. Manual Starters Manual starters are devices that are operated manually. These starters are extremely easy and straightforward to operate and do not require expert intervention. The starter includes a button (or rotary knob) which enables a user to turn the connected equipment on or off. The buttons feature mechanical linkages, which make the contacts open or close, starting or stopping the motor. The following features of a manual starter make it a preferred choice over other types: These starters deliver a safe, as well as economical operation. The compact size of these devices make them suitable for a wide range of applications. They provide overload protection to the motor, protecting it from any potential damage. These devices come with a vast choice of enclosures. The initial cost of the manual starter is low. 2. Magnetic Motor Starters This is the other main type of motor starter. It is operated electromagnetically. It means that the motor load connected to the motor starter is typically started and stopped using a lower and safer voltage than the motor voltage. Just like other motor starters, the magnetic starter also has an electrical contactor and overload relay to protect the device from too much current or overheating. Page 1 of 9 THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing

Magnetic Motor Starter Circuitry & Operation Figure 1: Motor Starter Power Circuitry There are two circuits in a motor starter, which are as follows: 1. Power Circuit: The power circuit connects the line to the motor. It provides transmission of electricity through the starter contacts, overload relay, and then to the motor. The motor current is carried by the power (main) contacts of the contactor. 2. Control Circuit: This is the other motor starter circuit, which operates the contactor to turn it on or off. The contactor main contacts are responsible for allowing or interrupting the flow of current to the motor. To do this, the contacts in the control circuit are either opened or closed. The control circuit energizes the contactor coil, which creates an electromagnetic field. The power contacts are pulled by this electromagnetic field to a closed position. This completes the circuit between the motor and the line. This way, remote operations are made possible by the control circuit. The control circuit can be wired in the following two ways: Method 1: One of the most widely used methods employed for wiring the control circuit is referred to as the Two-wire method. A maintained contact type of pilot device like presence sensor, thermostat, or float switch is used in the two-wire method of wiring the control circuit. Method 2: Unlike the two-wire method, the Three-wire method of wiring the control circuit uses a holding circuit contact and the momentary contact pilot devices. The control circuit can derive the power from either of the following three ways: Common Control: This type of control is when the power source of the control circuit is the same as the motor. Separate Control: This is the most popular type of control. As the name suggests, the control circuit derives power from a separate source in this arrangement. Generally, the power derived is lower in voltage as compared to the motor s power source. Transformer Control: As the name suggests, the control circuit derives power from a control circuit transformer. Generally, the power derived is lower in voltage as compared to the motor s power source. Page 2 of 9

Types of Magnetic Motor Starters Depending on how they are connected in a circuit, there are many types of magnetic motor starters, such as: 1. Direct-On-Line Starter Figure 2: Direct-On-Line Starter The direct-on-line starter is the simplest form of motor starter, other than a manual starter. The controller of this starter is typically a simple push button (but could be a selector switch, limit switch, float switch, etc.). Pressing the start button closes the contactor (by energizing the contactor coil) connected to the main supply and motor. This provides the supply current to the motor. To turn the motor off, a stop button is provided. To protect it from over current, the control circuit is wired through a normally closed auxiliary contact of the overload relay. When the overload relay trips, the normally closed auxiliary contact opens, and de-energizes the contactor coil, and the contactor main contacts open. The Advantages of Using Direct-On-Line Motor Starters: They have a compact design. They are cost-effective. They have a simple construction. Page 3 of 9

2. Rotor Resistance Starter Figure 3: Rotor Resistance Starter In the rotor resistance starter, the three resistances are connected such that they are in series with the rotor windings. This helps reduce the rotor current considerably, as well as increases the motor torque. The Advantages of Using Rotor Resistance Motor Starters: They are cost-effective. They have a simple speed control method. They provide low starting current, large starting torque, and large pull-out torque. 3. Stator Resistance Starter Figure 4: Stator Resistance Starter The stator resistance starter consists of three resistors, which are connected in series with each phase of the stator windings. At each resistor, a voltage drop is caused, so it becomes necessary to apply low voltage to each phase. These resistances are set at the start or maximum position during the motor start stage. The starting current is kept at a minimum in this type of starter. Also, the starting torque to the motor needs to be maintained. The Advantages of Using Stator Resistance Motor Starters: They are suitable for use in speed control applications. They have extremely flexible starting characteristics. They provide smooth acceleration. Page 4 of 9

4. Auto Transformer Starter Figure 5: Auto Transformer Starter With an auto transformer starter, the transformer supplies a certain percentage of the primary voltage to the secondary of the transformer. The auto transformer is connected in a star configuration. The three tapped secondary coils of the transformer are connected to the three motor phases in this type of starter. This helps in reducing the voltage that is being applied to the motor terminals. The Advantages of Using Auto Transformer Motor Starters: They can be used for manual speed control, but with limited options. They have extremely flexible starting characteristics. They have a high output torque. Page 5 of 9

5. Star Delta Starter Figure 6: Star Delta Starter Compared to the other types of starters, the star delta starter is used on a large scale. As the name suggests, the three windings are connected in a star connection in the star delta starters. A certain time is set by the timer or any other controller circuit. After this time is passed, the windings are then connected in the delta connection. The phase voltage in the star connection is reduced to 58%, and the total current drawn is 58% of normal current. This results in a reduced torque. The Advantages of Using Star Delta Motor Starters: They are ideal for long acceleration times. They have a lower input surge current when compared to other starters. They have a simpler construction as compared to other starters. Page 6 of 9

Features of Motor Starters Today, motor starters are used on a large scale due to their list of beneficial features. The following are some features of these highly useful electrical devices: 1. They facilitate the starting and stopping of the motor. 2. The starters are rated by power (horsepower, kilowatt) and current (amperes). 3. They provide the necessary overload protection for the motor. 4. The electrical device facilitates remote on/off control feature. 5. These devices allow you to make and break current rapidly (plugging and jogging). Fundamental Functions of Motor Starters The following are the most fundamental functions that a starter has to perform: 1. Control: The control function is mainly carried out by the contactor component of a starter. It is controlling the opening and closing of the power electrical circuit. The switching is done by the main contacts (poles) of the contactor. An electromagnetic coil is energized, which open or close the contacts. This electromagnetic coil has a nominal control voltage, and can either be an AC or DC voltage. 2. Short-Circuit Protection: In industrial applications, normal load current can be up to thousands of amperes. In the case of a short-circuit fault, the fault current can go over 100,000 amperes. This can cause severe damage to the equipment. The short-circuit protection disconnects the supply and prevents the potential damage in a safe manner. Short circuit protection is provided by fuses or circuit breakers in a Combination Motor Controller. 3. Overload Protection: When a motor draws more current than it is designed to, an overload condition is caused. The main objective of an overload relay is to detect the excess currents. When an overload is detected, the auxiliary contact of the overload relay opens the circuit and prevents the motor from burning out or overheating. Electronic or electromechanical overload relays are used in combination with a contactor to provide the required overload protection. 4. Disconnecting and Breaking: In order to prevent an unintended restart, it is required to disconnect the motor from the main power circuit. In order to safely perform maintenance on a motor or starter, a motor must be able to switch off and be isolated from the power. The disconnect switch of the circuit provides this function. Disconnecting and breaking is provided by a disconnect switch or circuit breaker in a Combination Motor Controller (or can be installed remotely from the starter). Standards and Ratings There are many factors involved in motor starter ratings, such as thermal current, continuous current, motor voltage, and power. The thermal current is dependent on the thermal conductivity (k), which is the property indicating the heat conducting ability of a material. It means that thermal current is directly proportional to the thermal conductivity. The continuous current, which is also commonly referred to as the continuous ampere rating is a measure of the capability of the motor control starter to handle current for a continuous time. The power rating of the motor starter is based on the type of motor used. DC motor starters have ratings for DC horsepower. On the other hand, AC motor starters have a single-phase power and three-phase power rating. The rating of the motor starter is based on the size and type of load for which it was designed. Starters conform to the standards and ratings from Underwriters Laboratories (UL), Canadian Standards Association (CSA), International Electrotechnical Commission (IEC) and National Electrical Manufacturers Association (NEMA). Page 7 of 9

NEMA Rating The NEMA ratings of a starter depends largely on the maximum horsepower ratings given in the National Electrical Manufacturers Association ISCS2 standard. The selection of the NEMA starters is done on the basis of their NEMA size, which varies from Size 00 to Size 9. NEMA Contactor and Starter Sizes NEMA Size Continuous AMP Rating HP at 230 VAC HP at 460 VAC 00 9 1 2 0 18 3 5 1 27 5 10 2 45 15 25 3 90 30 50 4 135 50 100 5 270 100 200 6 540 200 400 7 810 300 600 8 1215 450 900 9 2250 800 1600 The NEMA starter, at its stated rating, can be used for a wide range of applications, ranging from simple on and off applications to plugging and jogging applications, which are more demanding. It is necessary to know the voltage and horsepower of the motor when selecting the proper NEMA motor starter. In the case where there is a considerable amount of plugging and jogging involved, then derating a NEMA-rated device will be required. IEC Rating The International Electrotechnical Commission (IEC) has specified the operational and performance characteristics for IEC devices in the publication IEC 60947. Standard sizes are not specified by the IEC. The typical duty cycle of IEC devices are defined by utilization categories. As far as general motor starting applications are concerned, the AC3 and AC4 are the most common utilization categories. Utilization Category AC1 AC2 AC3 AC4 AC11 IEC Rating IEC Category Description Non-inductive or slightly induction rows Starting of slip-ring motors Starting of squirrel-cage motors and switching off only when the motor is up to speed. (Make LRA, Break FLA) Starting of squirrel-cage motors with inching and plugging duty. Rapid Start/Stop. (Make and Break LRA) Auxiliary (control) circuits Unlike NEMA sizes, they are typically rated by their maximum operating current, thermal current, HP and/ or kw rating. There are other parameters that are important to consider, while selecting motor starters, such as timelimit acceleration, current-line acceleration, control voltage, number of poles, and operating temperature. We will cover those in a future white paper. We hope that this short white paper has given you a good, basic understanding of motor starters. Look for other papers from c3controls at c3controls.com/blog. Page 8 of 9

Disclaimer: The content provided in this white paper is intended solely for general information purposes and is provided with the understanding that the authors and publishers are not herein engaged in rendering engineering or other professional advice or services. The practice of engineering is driven by site-specific circumstances unique to each project. Consequently, any use of this information should be done only in consultation with a qualified and licensed professional who can take into account all relevant factors and desired outcomes. The information in this white paper was posted with reasonable care and attention. However, it is possible that some information in these white papers is incomplete, incorrect, or inapplicable to particular circumstances or conditions. We do not accept liability for direct or indirect losses resulting from using, relying or acting upon information in this white paper. Page 9 of 9 THE BEST ELECTRICAL CONTROLS BUSINESS ON THE PLANET! Unmatched Service Superior Product Quality Advantage Pricing