INSTALLATION INSTRUCTIONS SHEAR LOCKING MAGNET 1561TJ MAX. HOLDING FORCE 2000 lbs.

Similar documents
SECURITY DOOR CONTROLS 801 Avenida Acaso, Camarillo, Ca (805) Fax: (805)

INSTALLATION INSTRUCTIONS MICRO SHEAR EMLOCKS 1561 & 1562 MAX. HOLDING FORCE 2000 LBS.

2965 Magnetic Shear Lock Installation Instructions

INSTALLATION INSTRUCTIONS E300 SERIES MAGNETIC CABINET/DISPLAY CASE LOCK

Security Door Controls

INSTALLATION INSTRUCTIONS 1576DE DELAYED EGRESS EMLOCK

S6100 SERIES REVERSIBLE PANIC/FIRE EXIT RIM DEVICES INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS 410/420 SERIES PUSH SWITCH

SECURITY DOOR CONTROLS

INSTALLATION INSTRUCTIONS MINI EXIT CHECK DELAYED EGRESS EMLOCK 1581S

EMLock 1500 Series. MEA Listed. New Modular Kits. Online System Wizard and Project Manager at

HANDLING MECHANICAL INSTALLATION

280+ SHEARLOCK INSTALLATION AND WIRING MODELS: 280+ and 280+TRD TRD

EZ-B-10 MAGNETIC BOND SENSOR EZ-T-10 TIMER INPUT MODULE. Modular Kit. Modular Kit. EZ-D-10: DOOR POSITION SENSOR Modular Kit

Installation Instructions

MODEL 600LB 600 POUND SINGLE MAGNETIC LOCK WITH LED, BOND SENSOR & DOOR STATUS SENSOR SPECIFICATIONS

Electro-Mechanical Swing Operator. Table of Contents

Requirements LEO Power Operator Installation Instructions Patents: 5,881,497; 7,316,096; 7,484,333 CAUTION CAUTION WARNING

1-3/4" MOUNTING INSTRUCTIONS: 1150 SERIES SURFACE MOUNTED 1500 LB. ELECTROMAGNETIC LOCK

cel SECURITY DOOR CONTROLS Value Engineered Access Hardware sdcsecurity.com Power Supplies Exit Switches

Requirements LEO Power Operator Installation Instructions Patents: 5,881,497; 7,316,096; 7,484,333 CAUTION CAUTION WARNING

Model 2300DL Installation Guide

DynaLock 705 Emmett Street Bristol, CT Phone:(860) Fax:(860)

MODEL 3002xTJ32 ELECTROMAGNETIC LOCK INSTALLATION INSTRUCTIONS

Model 2300JL Installation Guide

M670/M680BD MAGNALOCK SERIES Installation Instructions

MODEL 1200S MAGNETIC LOCK

Package Contents. Mounting Hardware

8. Do not install this product on the exterior of buildings. 9. Do not use as a doorstop. This will void warranty. Installation Instructions

MODEL 600S 600 POUND SINGLE MAGNETIC LOCK SPECIFICATIONS

Motorized Electric Latch Retraction

INSTALLATION DESCRIPTION

EMLock 1500 Series. MEA Listed

MODEL 1200LB 1200 POUND MAGNETIC LOCK WITH LED, BOND SENSOR & DOOR STATUS SENSOR

SHEAR ALIGNING MAGNALOCK MODEL SAM2-24 INSTALLATION AND OPERATING INSTRUCTIONS

INSTALLATION 8310/8320

* * M400 Series. Features. Models. Trims. UL Requirements. Single Electromagnetic Locks: M420, M450, M490. Installation Instructions

MODEL 1200S MAGNETIC LOCK

SERVICE MANUAL for. Engine-to-Generator. Part Number used on. John Deere Engine Driven Aircraft Ground Power Single-Bearing Generator Sets

M400 Series Double Locks. Features

56- Electric Latch Retraction Exit Devices Installation and Wiring Instructions

Tooling Assistance Center

INSTALLATION EML375. Pre-Installation Instructions. Electromagnetic Locks

Excel Series Value Engineered Access Hardware

5000 SERIES POWER SUPPLY/CHARGERS INSTALLATION GUIDE

92-00 Civic/ Integra/ Del Sol/ Accord/ CRX

* * M400 Series Double Locks. Double Electromagnetic Locks: M422, M452, M492. Installation Instructions. Mounting Bracket (2)

EMLock Magnetic Locks

Vertical Housing EMLock Discount Code GK LIST. Retrofit Kit for Discontinued Locknetics 390+ PLUS

MODEL 600LB 600 POUND SINGLE MAGNETIC LOCK WITH LED, BOND SENSOR & DOOR STATUS SENSOR SPECIFICATIONS

Drop Feeder Control. Part Number Introduction. Setting the Control. Time Clock operation. Manual Operation

MOUNTING INSTRUCTIONS FOR TJ1000 SERIES INSWINGING DOORS ******READ THOROUGHLY BEFORE INSTALLING******

V2M1200/1290 Series Maglock Installation Instructions

At-FST Series I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N S W W W. A I G I S M E C H. C O M

Installation Instructions Series 78-B/FHA Hold Open

!!!! ! Lock housing dimensions: 230mm L x 44mm W x 44mm D! Receptacle housing dimensions: 120m L x 44mm W x 44mm D. ! Surface mount housing for LK120

MAGLOC660 ELECTROMAGNETIC LOCK

PFadvantage MF 6850/6855; Ideal 9080/9090

INSTALLATION & OWNER S MANUAL

Webasto Products N.A. Inc.

INSTALLATION INSTRUCTIONS CRL ESK2/ESP2

Headers - 4-1/8, 4-1/2, 6. with PT21 and Shear lock for single or double doors. Installation instructions

TOYOTA RAV DOOR SILL PROTECTORS Preparation

1.5 WIPER MOTOR INSTALLATION INSTRUCTIONS (ITEM # S: 71081, 71011, 71082, 71012, 71182, 71112)

Electromagnetic locks - Single Doors

8. Do not install this product on the exterior of buildings. 9. Do not use as a doorstop. This will void warranty.

Hunter Automatics HA-8. Installation Manual

Document number AMS & AMD Damper Series for Honeywell Spyder Controller Installation, Operation, and Maintenance Instructions

SAFETY REASONABLE EFFORT. ANY BINDING, SAGGING, LOOSE HINGES, OR DAMAGED HINGES MUST BE REPAIRED BEFORE CONTINUING WITH THIS INSTALLATION!

1PC TONNEAU COVER INSTALLATION INSTRUCTIONS IMPORTANT

Heavy Duty Miniature Quick-Change Applicator (End-Feed Type) with Mechanical or Air-Feed Systems

Electromagnetic Locks DORMA EML

Heavy Duty Miniature Quick-Change Applicator (Side-Feed Type) with Mechanical or Air Feed Systems

Plasma Display Electric Pop-Up Lift (PUL)

ASSA ABLOY Series Power Operator Installation and Instruction ASSA Manual ABLOY ASSA ABLOY

Locking Devices. Electromagnetic Locks. Security Door Controls 8 SECURITY DOOR CONTROLS

Opening Quality Doors Around The World. Installation Instructions Bi-Parting Freight Doors - Q Style (Power and Manual)

TS9356 PKT 90/119. Surface applied door closer. Installation instructions: Pocket door track mount in 90 /119 pocket (Closer on wall)

TS93 EMF T/PT/TDE. Surface applied door closer

Premium Dry Freight (Plywood) Door Installation REFERENCE FIGURE 1

B100S - Super Swing. Instruction Manual. Document number: B100S-C Release: V4.0 Date: May 08,2009

RECESSED MAGNALOCK MODEL M34R SERIES INSTALLATION AND OPERATING INSTRUCTIONS

REAR UPPER CONTROL ARM

Installation, Operation and Maintenance Manual

Pre-Installation Instructions

Power Supplies DORMA PS

Service Instructions. Syntron Light-Capacity Electromagnetic Model: F-T01-A DF-T01-A

REMOVAL & INSTALLATION

Owners Manual. Dearborn Deuce Convertible

EMLock Magnetic Locks

COLD AIR INTAKE INSTALLATION INSTRUCTIONS. # D Fits: F10 M5 # D Fits: F06/F12/F13 M6 PARTS LIST

INSTALLATION INSTRUCTIONS

2300 OPERATING/APPLICATION/INSTALLATION INSTRUCTIONS

12 Series Linear Actuators. Operation & Maintenance Manual, Analog Positioner Installation

AA4006 Speed Sensitive Trip Unit. User Manual

ASSA ABLOY. Installation Instructions. MP9800 Series Multi-Point Lock with MELR Option (Electric Latch Retraction)

TYPE KF UNDER-FREQUENCY RELAY A. Figure 1: Type KF Relay for 60 Hertz without Case. (Front & Rear View.) Front View Rear View

FULL HEIGHT ALUMINUM TURNSTILE DOUBLE UNIT AT-FAL SERIES I N STALLATION AND O P E RATING I N STRUCTIONS

stanley door closers d-4550/d-4551 D-4550 / D-4551 SERIES DOOR CLOSERS

ASSA ABLOY Universal Door Closers with Heavy Duty Spring Stop Parallel Arms

Transcription:

801 Avenida Acaso, Camarillo, Ca. 93012 (805) 494-0622 www.sdcsecurity.com E-mail: service@sdcsecurity.com INSTALLATION INSTRUCTIONS SHEAR LOCKING MAGNET 1561TJ MAX. HOLDING FORCE 2000 lbs. REFER TO THE PROPER TEMPLATE ACCORDING TO THE TYPE OF DOOR AND FRAME APPLICATION. READ THESE INSTRUCTIONS AND STUDY THE TEMPLATE THOROUGHLY BEFORE BEGINNING THE INSTALLATION IMPORTANT NOTES: Although electromagnetic shear locks provide the utmost in aesthetics for fail-safe applications, they are less forgiving than electric bolt locks and direct pull magnetic locks where alignment problems exist. Therefore, great care must be taken during preparation and installation of the frame, door hardware and the shear locking magnet to attain proper alignment and insure positive lock operation. Unbalanced air conditioning (stack pressure) can hinder door alignment and must be corrected to help insure positive locking. Use only the highest quality door closer. Door latching problems must be corrected prior to installation. INSTALLATION 1. Make sure the clearance between the door top rail and frame header is 1/8. Make adjustments to the door as required. 2. Adjust single acting door and door closer to insure the door settles immediately and is fully closed and at rest against the stop allowing for mutes, smoke seals or weather striping where applicable. 3. Locate the vertical centerline of the locking magnet and armature as close as possible to the leading door edge. 4. Mark the door per the template. 5. Before determining the frame header, centerline single acting doors must be fully closed and at rest against the stop allowing for mutes, smoke seals or weather stripping where applicable. 6. Mark the frame header per Fig 1. 7. Prepare the door and frame per Fig 1. 8. An auto relock time delay (built-in with the 1561TJ) is recommended for all installations to delay relocking 1 to 6 seconds after initial door closure. This will help insure the door is fully closed and at rest to obtain optimum alignment before the locking magnet is energized. See Fig 2. With the power off, make all wire connections to a properly fused power source. P:\INSTALLATION INSTRUCTIONS\ELECTROMAGNETIC LOCKS\INST-SHEAR 61TJ.vsd REV A 08-11 Page 1 Any suggestions or comments to this instruction or product are welcome. Please contact us through our website or email engineer@sdcsecurity.com

9. Install the locking magnet and armature with the auto relock switch assembly towards the leading edge of door. The 1561TJ timer adjustment can be made after the locking magnet is installed through the small hole in the face of the magnet. Using a small flat blade screwdriver, turn clockwise to increase time, counter clockwise to decrease time. 10. For proper operation, the armature must be adjusted as close as possible and parallel with the locking magnet without interfering with opening or closing of the door. Proper operation cannot be expected with more than 1/8 clearance between the armature and the locking magnet. If you find the clearance to be more than 1/8, shim the assembly with the shims provided. 11. With the door closed, turn the lock power on. Check the lateral alignment. The armature shear stops should be centered between each pair of magnet shear stops. 12. If the clearance between the shear stops is sufficient, open and close the door a few times to insure the locking magnet will lock and unlock positively. 13. Adjust the auto relock switch magnet to avoid early activation and help insure positive locking on door closure. Adjust inward to delay locking magnet activation. Do not adjust higher than the armature rest position. 14. If the shear stops are too close or binding, double check the template and door alignment and make corrections as required. 15. If positive locking cannot be attained due to misalignment after the previous adjustments, the armature shear stops can be replaced with the wide clearance shear stops. See Fig 3. CAUTION: The use of armature offset shear stops may correct misalignment but should not be used when proper door latching is inhibited. 16. Repeat steps 10 through 14 as necessary following shear stop replacement. 17. Cycle the door and locking magnet several times after the completion of installation. MODEL # LOCK DIMENSION L W D HOLDING FORCE POWER CONSUMPTION MODEL # 12VDC 24VDC L ARMATURE DIMENSION W D 1561TJ 8" 1-3/4" 2000 650mA 350mA SURFACE 8" 1" P:\INSTALLATION INSTRUCTIONS\ELECTROMAGNETIC LOCKS\INST-SHEAR 61TJ.vsd REV A 08-11 Page 2

FIG. 1 1561TJ 3.00" MPM SOC CAP MIDPOINT IDENTIFICATION MPM = MIDPOINT MAGNET MPA = MIDPOINT ARMATURE LEADING EDGE OF DOOR MPA THE MOST IMPORTANT ELEMENTS FOR THE PROPER INSTALLATION OF THE HI/SHEAR MAGNET ASSEMBLY ARE THAT THE MIDPOINT OF THE ARMATURE AND THE MIDPOINT OF THE MAGNET MUST LINE UP EXACTLY. ALL CENTER LINES OF THE ARMATURE MUST LINE UP WITH THE RESPECTIVE CENTER LINES OF THE MAGNET. SEX BOLT SHIM INSTALLATION OF ARMATURE ASSEMBLY SOC CAP P:\INSTALLATION INSTRUCTIONS\ELECTROMAGNETIC LOCKS\INST-SHEAR 61TJ.vsd REV A 08-11 Page 3

FIG. 2 Model 1561TJ With built in Auto Relock Switch / Auto Relock Delay Timer LOCK RED/BLK WHT/BLK ACCESS CONTROL + - TO FUSED 12V or 24V DC POWER SUPPLY DPS OPTION YEL = N/O GRY = COM ORG = N/C BAS OPTION WHT = N/O BLK = COM RED = N/C FIG. 3 NOTE: The drawing in Fig. A shows two different alignments off center of the shear tab. For normal single acting door alignment, refer to Fig. B..343 For double acting doors, refer to Fig F. For slightly warped single acting doors refer to Fig. D. This also works well for quick release, when switch bars are used. The offset shear tab cannot be used on shear locks with bond sensors Fig. E & G. FIG. A WIDE FIG. C OFFSET SHEAR TABS ARMATURE TOP VIEW FIG. B FIG. D FIG. E ARMATURE SHEAR TAB INSTALLATION FIG. F EVEN SHEAR TABS ARMATURE TOP VIEW FOR LOCKS WITH BOND SENSOR FIG. G P:\INSTALLATION INSTRUCTIONS\ELECTROMAGNETIC LOCKS\INST-SHEAR 61TJ.vsd REV A 08-11 Page 4

MAINTENANCE INSTRUCTIONS The electromagnet and the armature should be handled carefully. Any damage to the surface such as paint, burrs, dirt or rust may hinder bonding of the surface and reduce holding power. IF THE SURFACE PLATING BECOMES DAMAGED; 1. Do not touch the lock face with your hands. 2. Use a soft clean, dry cloth or abrasive cloth (i.e. Scotch-Brite by 3M) to clean the lock face. 3. A rust inhibitor, such as M1 manufactured by Starret, or LPS3 manufactured by LPS Laboratories (available at most hardware stores) can then be applied to the lock face. 4. Apply a coat of rust inhibitor to the armature face also. P:\INSTALLATION INSTRUCTIONS\ELECTROMAGNETIC LOCKS\INST-SHEAR 61TJ.vsd REV A 08-11 Page 5