Actuator type ABNM with Theft Protection, 0-10 V Proportional

Similar documents
Actuator ABNM A V Proportional For Use with RA2000 Valves

Functions Technical information - Actuator 24 V. Features. General information. lindab we simplify construction

High Capacity Valve Body, Type RA-G

EMO TM. Actuators High performance proportional actuator For modulating control

TECHNICAL CATALOGUE. Electrothermal actuator

Integrated Valve with Presetting for Manifolds in Two-Pipe Heating Systems

Integrated Presetting Valves for Normal (013G0380) and Small (013G0381) Volume Flows

Integrated Presetting Valves - for Normal Volume Flows RA-N and for Small Volume Flows RA-U

Suitable to Johnson Controls and almost all of terminal unit valve on the market

EMO T. Actuators High performance thermoelectric actuator For ON/OFF or PWM control

Premounted Midi Shunts

ChangeOver6 and NovoCon ChangeOver6 - Motorized 6-port Ball Valves

EMOtec. Actuators Thermal actuator for heating, ventilation, and air conditioning systems

Actuators for modulating control AME 110 NL, AME 120 NL

ESBE Series 60 Electronic Motor Actuator (Combined with ESBE 3&4-way rotary valves)

ESBE Series 90 Electronic Motor Actuator (Combined with ESBE 3&4-Way Rotary Valves)

M4410C/L SMALL LINEAR THERMOELECTRIC ACTUATORS

Power consuption motor (motion) Power consuption standby (end position) Auxiliary switch Contact load Switching point

Valve bodies type RA-N with integrated presetting

SonoSensor 30 Ultrasonic flow sensor

Power consumption In operation At rest For wire sizing. Functional data Torque Motor Spring return. Rated impulse voltage Control pollution degree 3

SAX Electronic Valve Actuator

EMUJC Series. Electronic actuator. Technical Data Sheet. WattsIndustries.com

AXS 215S: Continuous actuator for unit valves, with stroke indicator

MT4-024/MT4-230 MT8-024/MT8-230

Power consuption Motor (Motion) Power consuption Standby (end position) Auxiliary switch Contact load Switching point

NV Direct Coupled Globe Valve Actuator

Extensions to a comprehensive product range

Technote. Frese OPTIMA Compact DN10-DN50 - pressure independent balancing & control valve. Application. Features. Benefits.

Electronic Globe Valves

I ntroduction. VA-7450 Electronic Terminal Unit Valve Actuator. Features and Benefits

HERZ Motorised Actuator

ELECTRIC POWER REGULATION TEMPERATURE CONTROLLERS. room C

Let motorized intelligence solve your application challenges

LF Series Spring Return Direct Coupled Actuator

VA-707x. Thermal Valve Actuators. Product Bulletin. Low and line voltage models available

Power consuption Motor (Motion) Power consuption Standby (end position) Auxiliary switch Contact load Switching point

Technote. Frese OPTIMIZER - pressure independent 4-pipe coil control unit. Application. Benefits. Features.

MT4-024/MT4-230 MT8-024/MT8-230

Damper Actuators Non-Spring Return

Zone Valves and Parts (Honeywell)

RUS-L24-MOD Electric 24 Volt Modulating Control Damper & Louver Actuator

VA-640GSX024P. Overview. Applications. Features & Benefits. Datasheet. Large Globe Valve Actuators

Premounted Midi Shunts

Reliable season change

24 V AC/DC, -10%..+20%, 0-60Hz. 250 ma for max 2 min

Nessie 3/2-Way Zone-Drain-Valves types VDM 2E, VDHT 15E, VDHT 15EC and VDH 30EC "Soft-Charge"

CP (Vdc) CP (Milliamp) CP (Slidewire)

Minimum 27 in-lb Torque

Technical Instructions Flowrite 599 Series SKD6xU Electronic Valve Actuators 24 Vac Proportional Control Description Features Application

Manual presetting valve MSV-C

D4SL. Safety Interlock Switches. Compact 6-Contact Guard Lock Safety-Door Switch NEW! Specifications. Standards and EC Directives

VA-7450 Series. Electric Valve Actuators

Model Number Structure

HERZ-Pressure Independent Control Valves

D4BL. Protective Doors Are Locked Until Machines Completely Stop Operating. Guard Lock Safety-door Switch. Model Number Structure.

RA-N Valve Bodies with Pressfit Connection and Self-Sealing Tailpiece for Two Pipe Systems

Electrical data Nominal voltage AC/DC 24V Nominal voltage frequency 50/60Hz

Combined automatic balancing valve AB-PM valve DN 10-32, PN 16

Minimum 27 in-lb torque

22C, 22CX, 22CX5, 26LC Series

Solenoid valve VDHT Standard BSP (British Standard Pipe)

Switching Power Supply

NMQB24-MFT, NMQX24-MFT Quick Proportional Control, Non-Spring Return, Direct Coupled, 24V, Multi-Function Technology

Power consumption In operation At rest For wire sizing. Connection Motor. Auxiliary switch

Versatile and Powerful

Versatile and Powerful

Thermal Overcurrent Circuit Breaker 3130

Small Limit Switch D4V

Assisted lift operated 2/2-way solenoid valves Type EV251B

MS Application. Features. Proportional Valve Actuator General Instructions

CI-tronic Soft starters for Danfoss commercial compressor applications Type MCI 15C, MCI 25C, MCI 50CM-3 I-O

MAKING MODERN LIVING POSSIBLE. UniLynx Indoor Installation Manual. ULX 1800i ULX 3000i ULX 3600i ULX 5400i SOLAR INVERTERS

Mount directly to 1.05 jackshafts. (new ZG-120 bracket shown) EFB24-S N4, EFX24-S N4(H) EFB24-S, EFX24-S (p. 21)

ON/OFF zone valves AMZ 112, AMZ 113

CCO kit. Compact Change Over - 6-way switch valve with motor QUICK FACTS

Thermal Overcurrent Circuit Breaker 3130

3/2-Way Zone-Drain-Valves VDHT 2E, VDHT 15E and VDHT 15EC

lindab comfort Regula Control er

Connections (*) Actuator Power MVX V ON/OFF MVX41 MVR24V MVR24MV (3) 24 V. Rev. h 07/10 1 DBL199E

System 350 P352AB Electronic Pressure Control Series

Electric Actuator Instructions

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW

ML7420A/ML7425A,B. Honeywell. Electric Linear Valve Actuator FEATURES SPECIFICATIONS GENERAL SPECIFICATION DATA

ELECTRIC ACTUATOR MOD. VB015 MAINTENANCE AND INSTALLATION INSTRUCTIONS OF VALBIA ELECTRIC ACTUATORS

Ordering Information. Switching Power Supply S82F. Industrial-Grade Power Supply for General or Peak Load Applications SWITCHING POWER SUPPLIES

Pre-Fabricated Flushing Bypass Assembly for Plant Applications Hero Plant DN15-150

Pressure Independent Control Valve

HANDBOOK VALVES. Ed VALVES VR-ED 02/ ENG 1

Type A - PICV Actuator Series

Thermal Overcurrent Circuit Breaker 3130

NMB (X) 24-MFT. Proportional Control, Non-Spring Return, Direct Coupled, 24V, Multi-Function Technology

Pressure Independent Control Valve

Minimum 18 in-lb Torque

Electrical data Nominal voltage AC 24 V, 50/60 Hz DC 24 V

General_technical_data Series

Function Relays, Interfaces and Converters

VG8000N Series PN16, DN15 - DN150

SAV Electronic Valve Actuator

Safety Limit Switch

Transcription:

Actuator type ABNM with Theft Protection, 0-10 V Proportional Application The ABNM actuator is a thermoelectric actuator for opening and closing valves in the fields of heating, ventilation and air conditioning systems (HVAC). Control is by a 0-10 V signal which is provided either by a room thermostat or, in most cases, by a central direct digital control (DDC) system. The actuator converts the 0-10 V signal into a proportional actuator travel. Ideal use in heating/cooling systems and in combination with central direct digital control (DDC) systems in building management systems (BMS). Function The actuator mechanism of the ABNM actuator uses a positive temperature coefficient (PTC) resistorheated wax element and a compression spring. The wax element is heated by applying the operating voltage and moves the integrated piston. The force generated by this movement is transferred to the piston, thus opening or closing the valve. The closing force of the compression spring (100N actuating force) is matched to the closing force of the valves and keeps the valve closed when de-energized. When the control voltage is applied (0-10 V), the wax element is heated under electronic control. The actuator provides active regulation in a defined range (see characteristic curve between 0.5 V and 10 V). In the range of 0 0.5 V, the actuator remains in a quiescent state in order to ignore ripple voltage occurring in long cables. The relation between control voltage and actuator travel is balanced by optical path measurement, allowing very accurate positioning. When the control voltage is outside of the active range, the valve is kept closed by the closing force of the compression spring. during the carcass construction phase even when the electric wiring is not yet complete. During the later electrical start-up, the first open function is unlocked by applying the operating voltage for more than 6 minutes and the ABNM will then be completely operable. Automatic calibration During the electrical start-up the valve closing point is detected. This ensures an optimum match with the specific valve used. Function display The function display (all-round display) of the ABNM shows at the first glance whether the valve is open or closed. Theft protection If the shield is taken off, it is not possible to part the thermal actuator from the adapter. First open function (for NC only) In its delivery condition, the ABNM is kept open when de-energised due to the first open function (filling). This enables heating/cooling operation Danfoss Heating Solutions VD78H602 Danfoss 06/2012 1

Actuator type ABNM with Theft Protection, 0-10 V Proportional Code Nos. and Technical Data Type With adapter for Danfoss RA valves Supply voltage Control voltage 24 V AC 0-10 V DC Valve function NC (normally closed) Cable length Code no. 1 m 082F1091 Accessories Valve adapters Connection Danfoss RA 2000 (VA78) M30 x 1.5 Heimeier, MNG, Oventrop Code no. 082F1071 082F1073 Note: For AB-QM adaptor order 082F1072 or 082F1075 for ABNM LOG/LIN actuator. Cable (halogen free) Length Code no. 1 meter 082F1081 5 meter 082F1082 10 meter 082F1083 Data Version Closed when de-energized Voltage 24 VAC 50/60 Hz (-20% to 40%) Max. inrush current 250 ma during approx. 2 min. Operating current 83 ma Operating power 2 W Control voltage 0-10 V DC Proportional conversion range of control voltage 0.5-10 V DC Input resistance 100 kω (10 kω possible, if ordered) Actuator travel 4 mm (minus over-elevation); max. 3.5 mm Average actuation delay 30 s/mm Actuating force 100 N +/- 5% Operating temperature 0-60 C Fluid temperature 0-100 C Storage temperature -25 to 65 C Ambient temperature 0 to 60 C Relative humidity max. 80% Degree/class of protection IP54/Safety extra-iow voltage CE conformity according to 60730 Housing / housing colour Polyamid/white RAL 9003 Weight 100 g without adapter and cable Connecting cable / cable length 3 x 0.22 mm 2 PVC, white/1 2 VD78H602 Danfoss 06/2012 Danfoss Heating Solutions

Actuator type ABNM with Theft Protection, 0-10 V Proportional Characteristic Curves Characteristic curve 1 2 4 3.5 3 2.5 2 1.5 1 0.5 0 1 2 3 4 5 6 7 8 9 10 (U ST in V) 3 1 Actuator travel (mm) 2 Valve adapter margin 3 Active control voltage range Spindle travel Active regulation Overclosing ABNM actuator The actuator converts the 0-10 V signal into a proportional actuator travel of 4 mm. Dimensions Connections min. 0 C max. 60 C 55 mm + 5 mm 3 Black, 24 VAC 2 Blue, 0 1 Red, 0-10 VDC 44 mm 64 mm 1 2 3 Transformer Rule-of-the-thumb formula for dimensioning transformer: P transformer = 6 W x number of ABNM actuators Calculation of max. cable length (copper cable) L = K x A / n L: Cable length in m A: Conductor cross-section in mm 2 K: Constant for copper (269 m/mm 2 ) n: Number of ABNM actuators Danfoss Heating Solutions VD78H602 Danfoss 06/2012 3

Actuator type ABNM with Theft Protection, 0-10 V Proportional Installation Danfoss RA 2000, VA78, code no. 082F1071 Danfoss 82F163.10 Danfoss 82F164.10 Power on >6min. Power off ABNM can be mounted in 360. A 2 mm Allen key is used to fit the valve adapter. Danfoss A/S Heating Solutions Haarupvaenget 11 8600 Silkeborg Denmark Phone:+45 7488 8000 Fax: +45 7488 8100 Email: heating.solutions@danfoss.com www.heating.danfoss.com Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss Heating Solutions and the Danfoss Heating Solutions logotype are trademarks of Danfoss A/S. All rights reserved. 4 VD78H602 Danfoss 06/2012 Danfoss Heating Solutions

ABN A5 Actuator for AB-QM, ON/OFF Application Features include: Actuator travel 5.0 mm Available as normally closed (NC) or normally open (NO) Power consumption 1/1.2 W Plug-in cable Simple snap-on installation IP54 in any installation position First-Open function Compact size, small dimensions All round function indicator Noiseless and maintenance-free Certified by TÜV The ABN A5 on/off thermal actuator has been specifically designed for use with AB-QM valve sizes ½ to 1¼ for heating and cooling applications. The actuator can be controlled with an on/off or PWM controller which is provided either by a room thermostat or by a central direct digital control (DDC) system. Function The actuator mechanism of the ABN A5 actuator uses a positive temperature coefficient (PTC) resistor heated wax element and a compression spring. The wax element is heated by applying the operating voltage and moves the integrated piston. The force generated by this movement is transferred to the piston, thus opening or closing the valve. First open function (for NC versions only) In its delivery condition, the ABN A5 is partially open to assist in the mounting of the actuator and filling of the system. Until the actuator is energized, the actuator is partially open. When power is wired to the actuator the first open function is unlocked and by applying the operating voltage for more than 6 minutes the ABN A5 will then be completely operable. Version NC normally closed (valve closed) In case of the normally closed version, when the actuator is powered the actuator steadily opens. When power is removed and after expiry of the hold time, the actuator closes in the same steady rate by the closing force of the compression spring. The closing force of the actuator is matched to AB-QM ½ to 1¼ valves and keeps the valve closed when de-energized. Fig. 1: Example of opening curve. Version NC with end switch (082F1154) The integrated micro switch is switched at a travel path of approx. 2 mm or 50% open. After the operating voltage is removed and after expiry of the hold time the valve is closed evenly by the closing force of the compression spring. The micro switch is closed after the actuator travels approx. 2 mm (50% closed) from full open Fig. 2: Example of opening curve. Version NO normally open VDHUQ122 Danfoss 10/2015 1

ABN A5 Actuator for AB-QM, ON/OFF In case of the normally open version, the actuator will close when the operating voltage is applied to the actuator. After the operating voltage is removed and after expiry of the hold time, the actuator evenly opens by the compressive force of the internal actuator spring. Fig. 4: Function display for NC versions extends proportionally with actuator opening from 0 mm to 5-6 mm. Fig. 3: Example of closing curve. Function display The function display, or position indicator of the ABN A5 is located on the top of the actuator. This position feedback allows identifying the operating condition (valve open or closed) at a glance. Fig. 5: Function display for NO versions extends only when valve is fully closed by approx. 0.5 mm. Ordering Type Supply voltage Normally Open/ Normally Closed Cable End Switch Code no. 24 VAC/DC NC Plug-in, not included No 082F1150 ABN A5, ON/OFF with VA 41 adapter, w/o cable (ordered separately, see below) 24 VAC/DC NO 120 VAC NC 120 VAC NO Plug-in, not included Plug-in, not included Plug-in, not included No No No 082F1151 082F1156 082F1157 Pre-wired, 24 VAC/DC NC 3 ft (1 m) (082F1154 is pre-wired to the actuator, no additional ordering of cable is required) Yes 082F1154 Cables Cables are not included and should be ordered separately (not valid version with end switch). It is possible to select between different lengths and standard or halogen free material. Cables Material Code no. 3ft (1m) Standard (PVC) 082F1144 16ft (5m) Standard (PVC) 082F1145 10 metres Standard (PVC) 082F1146 2 VDHUQ122 Danfoss 10/2015

ABN A5 Actuator for AB-QM, ON/OFF Data ABN A5 type 24 V Version Voltage Max. inrush current NC / NO / NC w/ endswitch 24 V AC/DC, +20%...-10%, 0-60 Hz < 300 ma during max. 2 min. Operating power 1 W (5 mm), 1.2 W (6.5 mm) 1) Control voltage Actuator travel Actuating force Closing and opening time Fluid temperature Storage temperature Ambient temperature Degree/class of protection CE conformity according to Housing/housing colour Connecting cable On/Off 5 mm 100 N ~4 min. 32 to 212 F (0 to 100 C) -13 to 149 F (-25 to 65 C) 32 to 140 F (0 to 60 C) IP54 2) /III safety extra-iow voltage EN60730, UL60730 Polyamid/White RAL9003 2 x 0.75 mm² PVC, or halogen free Adapter (included) VA 41 Overvoltage resistance EN60730-1 Weight min. 2.5 kv 0.22lb (0.1 kg) 1) Measured with precision reference instrument LMG95. 2) In all installation positions. Connections approx. 3.1 ft. yellow Operating Voltage 24 V AC/DC red End-Switch Cable connection of version with end switch 082F1154. VDHUQ122 Danfoss 10/2015 3

ABN A5 Actuator for AB-QM, ON/OFF Installation Installation with valve adapter Danfoss AB-QM VA41 max: 4mm Screw the valve adapter manually onto the valve. Connect cable and actuator. Click IP54 in any position with cable plugged in Place the actuator vertically on the valve adapter. The actuator snaps onto the valve adapter with a click when pressed down vertically by hand. Dimensions 2.1in 52,2 (52.2mm) 52,2 mm 1.9in 50,3 (50.3mm) 7 0.3in mm (7mm) 2.2in (56mm) 56 mm 1.7in 44,3 (44.3mm) Danfoss can accept no responsibility for possible errors in printed materials and reserves the right to alter its products without notice. All trademarks in this material are property of the respective companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved. Danfoss Toronto, ON Tel.: 866-375-4822, Fax: 416-352-5981 www.na.heating.danfoss.com Danfoss Baltimore, MD Tel.: 443-512-0266, Fax: 443-512-0270 www.na.heating.danfoss.com 4 VDHUQ122 Danfoss 10/2015

Actuator Type ABNM-LOG/LIN for AB-QM, 0-10 V Proportional Application Control is done by a 0-10 V signal, which is provided either by a room thermostat or, in most cases, by a central direct digital control (DDC) system. The actuator converts the 0-10 V signal into a proportional actuator travel, which can be either linear or logarithmic. The ABNM actuator is a thermoelectric actuator for opening and closing valves in the fields of heating, ventilation and air conditioning systems (HVAC). Ideal use in heating/cooling systems and in combination with central direct digital control (DDC) systems in building management systems (BMS). ABNM LOG for actuating valves controlling the flow of liquid to air heat exchanges, e.g. cooling fan coils or air handling units. ABNM LIN for actuating valves controlling the flow of liquid to liquid heat exchangers. Function The actuator mechanism of the ABNM actuator uses a positive temperature coefficient (PTC) resistorheated wax element and a compression spring. The wax element is heated by applying the operating voltage and moves the integrated piston. The force generated by this movement is transferred to the piston, thus opening or closing the valve. The closing force of the compression spring (100 N actuating force) is matched to the closing force of the valves and keeps the valve closed when de-energized. When the control voltage is applied (0-10 V), the wax element is heated under electronic control. The actuator provides active regulation in a defined range (see characteristic curve between 0.5 V and 10 V). In the range of 0 0.5 V, the actuator remains in a quiescent state in order to ignore ripple voltage occurring in long cables. The relation between control voltage and actuator travel is balanced by optical path measurement, allowing very accurate positioning. When the control voltage is outside of the active range, the valve is kept closed by the closing force of the compression spring. First open function (for NC only) In its delivery condition, the ABNM is kept open when de-energized due to the first open function (filling). This enables heating/cooling operation during the carcass construction phase even when the electric wiring is not yet complete. During the later electrical start-up, the first open function is unlocked by applying the operating voltage for more than 6 minutes and the ABNM will then be completely operable. Automatic calibration During the electrical start-up the valve closing point is detected. This ensures an optimum match with the specific valve used. Function display The function display (all-round display) of the ABNM shows at the first glance whether the valve is open or closed. Danfoss Heating Solutions VDSKF102 Danfoss 12/2010 1

Actuator Type ABNM-LOG/LIN for AB-QM, 0-10 V Proportional Code Nos. and Technical Data Type Supply voltage Control voltage Valve function ABNM LOG with VA50 adapter ABNM LOG with VA50 adapter ABNM LIN with VA50 adapter ABNM LOG without adapter ABNM LIN without adapter 24 V AC 0-10 V DC 24 V AC 0-10 V DC 24 V AC 0-10 V DC 24 V AC 0-10 V DC 24 V AC 0-10 V DC NC (normally closed) NC (normally closed) NC (normally closed) NC (normally closed) NC (normally closed) Cable* length Code no. 1 m 082F1191 5 m 082F1192 1 m 082F1193 no no 082F1198 082F1199 * Halogen free Note: For theft protection order 082F1091 Accessories Valve adapters Connection Danfoss AB-QM VA50 Code no. 082F1075 Cable (halogen free) Length Code no. 1 meter 082F1081 5 meter 082F1082 10 meter 082F1083 Data Version Closed when de-energized Voltage 24 VAC 50/60 Hz (-10% to +20%) Max. inrush current Operating current Operating power Control voltage Proportional conversion range of control voltage Input resistance Actuator travel Average actuation delay <300 ma during approx. 2 min. 90 ma 0.4 W 0-10 V DC 0.5-10 V DC 100 kω (also 10 kω factory setting, if ordered) In the range 0.5-10V the actuator proportional controls (LOG or LIN) a 0-4 mm stroke, starting from the closing point of the valve. The stroke is mechanically limited at 4.5 mm. 30 s/mm Actuating force 100 N +/- 5% Operating temperature 0-60 C Fluid temperature 0-100 C Storage temperature -25 to 65 C Ambient temperature 0 to 60 C Relative humidity max. 80% Degree/class of protection CE conformity according to 60730 IP54/Safety extra-iow voltage Housing/housing colour Polyamid/white RAL 9003 Weight Connecting cable/cable length 100 g without adapter and cable 3 x 0.22 mm 2 PVC, white, halogen free/1 meter, 30 g 2 VDSKF102 Danfoss 12/2010 Danfoss Heating Solutions

Actuator Type ABNM-LOG/LIN for AB-QM, 0-10 V Proportional Characteristic Curves ABNM-LOG, transformation curve Relative stroke Input signal (volt) ABNM-LIN, transformation curve Relative stroke Input signal (volt) ABNM actuator The actuator converts the 0-10 V signal into a proportional actuator travel of 0-4.5 mm. Danfoss Heating Solutions VDSKF102 Danfoss 12/2010 3

Actuator Type ABNM-LOG/LIN for AB-QM, 0-10 V Proportional Dimensions Connections Transformer Rule-of-the-thumb formula for dimensioning transformer: P transformer = 6 W x number of ABNM actuators Calculation of max. cable length (copper cable) L = K x A / n A: Conductor cross-section in mm 2 n: Number of ABNM actuators K: Constant for copper (269 m/mm 2 ) L: Cable length in m 4 VDSKF102 Danfoss 12/2010 Danfoss Heating Solutions

Actuator Type ABNM-LOG/LIN for AB-QM, 0-10 V Proportional Installation Danfoss AB-QM VA50, code no. 082F1075 1. Screw the suitable valve adapter on the valve by hand. 2. The actuator is mounted on the adapter ring. ABNM can be mounted in 360. 3. Switch on the power supply. Danfoss Heating Solutions VDSKF102 Danfoss 12/2010 5

Actuator Type ABNM-LOG/LIN for AB-QM, 0-10 V Proportional 6 VDSKF102 Danfoss 12/2010 Danfoss Heating Solutions

Actuator Type ABNM-LOG/LIN for AB-QM, 0-10 V Proportional Danfoss Heating Solutions VDSKF102 Danfoss 12/2010 7

Actuator Type ABNM-LOG/LIN for AB-QM, 0-10 V Proportional Danfoss A/S Heating Solutions Haarupvaenget 11 8600 Silkeborg Denmark Phone:+45 7488 8000 Fax: +45 7488 8100 Email: heating.solutions@danfoss.com www.heating.danfoss.com Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved. 8 VDSKF102 Danfoss 12/2010 Danfoss Heating Solutions