PRESENTATION ON STANDARDSDISTRIBUTION TRANSFORMERS BUREAU OF INDIAN STANDARDS BHOPAL

Similar documents
/ I S S : / S T S I

Distribution transformers Efficiency over life-cycle

COMMISSION REGULATION (EU) / of XXX

Comparison of Indian Electricity Rules, 1956 Vs CEA (Measures relating to Safety and Electric Supply) Regulations, 2010

Guideline No.: E-07(201610) E-07 TRANSFORMERS. Issued date: October 28,2016. China Classification Society

Guideline No.: E-07(201712) E-07 TRANSFORMERS. Issued date: December 26, China Classification Society

ABB Transformers Egypt

TGK Prefabricated Substation Technical Data

Guideline No.: E-07(201501) E-07 TRANSFORMERS. Issued date: October 20,2015. China Classification Society

Technical Requirements of Fuel Tanks for Agricultural Tractors

INTER PLANT STANDARD STEEL INDUSTRY SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION)

ABB Ltd. FACTORY IN HANOI

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

Fuji Electric. Oil immersed. Transformer FTU08A1-E-0024

CLARK PUBLIC UTILITIES TECHNICAL SPECIFICATIONS THREE-PHASE PADMOUNTED TRANSFORMERS

Sarah Hatch, Senior Project Officer - Lighting and Equipment Energy Efficiency Team DEWHA October 2008

INTERNATIONAL STANDARD

TRANSFORMERS UP TO 750 kv

SWITCHGEAR FOR SERVICE UP TO 36kV (CABLE AND OVERHEAD CONDUCTOR CONNECTED)

(A Government Company) CENTRAL WORK SHOP KOTHAGUDEM

TECHNICAL SPECIFICATION

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD

Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear

Single phase pole mounted. 11kV. Electrical Engineer KEU ID#:

AGREEMENT TECHNICAL CO-OPERATION BETWEEN ISO AND CEN. (Vienna Agreement)

34-SDMS-01 SPECIFICATIONS FOR

COMMISSION REGULATION (EC)

This document is a preview generated by EVS

UniPack compact secondary substations (CSS) upto 36 kv For safe, reliable and space saving power distribution solutions

AS/NZS :2016. Grid connection of energy systems via inverters AS/NZS :2016. Part 1: Installation requirements

1500 kva Pad Mount Transformer GRDY/14400V Primary - 208Y/120 Wye Secondary - Oil Cooled

Technical Specification of GECOL. Packaged Transformers

INESING GROUP. Power System Solution

Scale of Inspection Fees of Electrical Inspectorate Schedule. I. Fees for Initial Inspections:

GENERAL INFORMATION POLE MOUNT TRANSFORMER SINGLE PHASE PAD MOUNT TRANSFORMER SINGLE PHASE POLE MOUNT TRANSFORMER THREE PHASE 17

56-SDMS-07 REV. 01 SPECIFICATIONS FOR

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT

1 [94. NOISE LIMIT FOR GENERATOR SETS RUN WITH DIESEL

Key features. DESIGNS: - Conservator type - Hermetically sealed

PHILIPPINE DISTRIBUTION CODE 2017 EDITION

Teepak Totally Enclosed Tube Ventilated High Voltage Induction Motors. A Regal Brand.

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

INTER PLANT STANDARD STEEL INDUSTRY. Corresponding IS does not exist

SSC-JE STAFF SELECTION COMMISSION ELECTRICAL ENGINEERING STUDY MATERIAL. Estimation and Costing & Utilization of Electrical Energy

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

FSSC 22000: Based on ISO Standards

Drive Duty Transformer Specification Virginia Transformer Corp. Power Up! Selecting the Right Transformer

YOUR KEY ENERGY EFFICIENCY PARTNER CAST RESIN DRY-TYPE TRANSFORMERS

Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated Medium-Voltage Switchgear.

7.0 Technical Guarantee Specification of 60MVA, 132/33kV Mobile Substation. TECHNICAL DATA SCHEDULE 60MVA, 132/33 kv MOBILE SUBSTATION

Technical Specifications

This standard covers the requirements of lighting chains. This standard covers only the safety requirements.

Certified for best-in-class performance, reliability, and safety. Trihal sets a new standard for dry-type cast resin transformers

(i) in paragraph 9, for sub-paragraph (i) the following shall be substituted, namely:-

Electric vehicle charging system

شركة كهرباء محافظة القدس المساهمة المحدودة

7 The revised IS 8034:2002 and revised STI be implemented w.e.f. 1 Feb 2005.

Tamilnadu Trade Promotion Organisation, Chennai-89

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Interconnected Electric System Protection Requirements

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

Technical Specification for 33 KV 200 AMPs,H.G,Fuse set.

Distribution Transformers. The most comprehensive range of solutions for distribution transformer applications

TECHNICAL SPECIFICATIONS FOR 11KV AIR BREAK (A.B.) SWITCHES :

SOUTH AFRICAN NATIONAL STANDARD

This document is a preview generated by EVS

MT/T Translated English of Chinese Standard: MT/T COAL INDUSTRY STANDARD

Minera. Oil distribution transformers up to kva. eco design. Minera at a glance. Standards

MEDIUM POWER TRANSFORMER

INTERNATIONAL STANDARD

Chapter 6 Generator-Voltage System

532: 2006 Bicycle tube valves and valve tubing Specification (third revision) 2414: 2005 Cycle and rickshaw pneumatic tyres (fourth revision)

500 kva Pad Mount Transformer V Delta Primary - 208Y/120 Secondary - NEMA 4X - Oil Cooled

PRE-RELEASE VERSION (FDIS)

INTER PLANT STANDARD STEEL INDUSTRY NO CORRESPONDING IS

Maximum temp. rise in oil by 40 thermometer above design ambient (deg C) specified time Short circuit rating (Sec) for As per IS 2026

Small craft Electric propulsion system

TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH

Australian/New Zealand Standard

MATERIAL STANDARD ELECTRIC OPERATIONS ORGANIZATION. ****Supercedes BECo Standard E and ComElectric Spec ****

Switchgear Type 8BT1, up to 24 kv, air-insulated. Medium Voltage Switchgear Catalog HA 26.

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

PUBLIC NOTICE. 1. Central Electricity Authority (Technical Standards for Connectivity of Distributed Generation Resources) Regulations, 2013.

ISO :2015/DAM 1

Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum.

SERIES 802 / 812 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTERS AND FUSE ASSEMBLIES

TECHNICAL SPECIFICATION

Terms of Reference (ToR) Trade & Traceability Standing Committee (T&T SC)

HPS EnduraCoil. Cast Resin Transformer

Guideline No.: E-03(201806) E-03 MOTORS. Issued date: June 7, China Classification Society

CAST RESIN TRANSFORMERS

EU-Mexico Free Trade Agreement EU TEXTUAL PROPOSAL

34-SDMS-02 SPECIFICATIONS FOR

P2 : About Us. P3 : Elsewedy Transformers. P4 : Why Elsewedy Dry Type Transformer? P6 : Cast Resin Dry Transformers. P7 : Technical Data Sheets

INTERNATIONAL STANDARD

Electric Power Train Vehicles Measurement of Net Power and The Maximum 30 Minute Power

Benefits, typical uses

A. Motors shall be designed, built, and tested in accordance with the latest revision of the following standard documents.

Date of hosting on website: 26 th October 2017 Last date for comments: 25 th November 2017

Review Section: 3. Definitions..the surrounding air in contact with the apparatus onto which the bushing is mounted, not inside bus duct or enclosure.

Transcription:

PRESENTATION ON STANDARDSDISTRIBUTION TRANSFORMERS BUREAU OF INDIAN STANDARDS BHOPAL

BIS Act WTO Principle on Standard Process for development of Indian Standard Standards on Transformers Detailed provision of IS 1180-1 Proposed Changes in IS 1180-1

National Standards Body constituted under the Act of Parliament (1986) New BIS Act 2016 has been notified Indian Standards developed by BIS through technical committee involving all concerned Stakeholders BIS standard development process in compliance with WTO-TBT principles

WTO Agreements Rules for international trade being written through various WTO Agreements Rules pertaining to Standards, Regulations and Conformity Assessment for Trade in Goods are laid down in: Agreement on Sanitary and Phyto Sanitary Measures (SPS) Agreement on Technical Barriers to Trade (TBT)

Technical Regulation Standard Mandatory Measures Voluntary Measures Conformity Assessment Procedure

Transparency Openness Impartiality and consensus Effectiveness and relevance Coherence Development dimension Compliance of Code of Good Practice for the Preparation, Adoption and Application of Standards

GOVERNANCE FRAMEWORK DG + 9 members Ministry 2 Consumer 1 Industry/trade 2 Scientific/ research 1 Technical/ Educational1 Bureau members -2 : Plus 9 Special invitees Bureau Minister in Charge Minister of State Secretary of MoCA Director General + Other members appointed by Govt from GoVt, Industry, Scientific & research Institutions and other interests 1 Standards Advisory Committee 1 Division Councils 14 Sectional Committees 322 Advisory Committee regulations 1987 1.Harmonious Development of Standards 2. Establishment Publication and promotion of Standards 3.Collaboration with SDO s of Country and Abroad 4. Formulation of guidelines for effective functioning of DC 5. Other Matters regarding Standardization Rule 7: Consumers, regulatory and other Government bodies, industry, scientists, technologists and testing organizations. These may also include consultants. An officer of the Bureau shall be the Member Secretary Panel/ Sub-Committees 509 Experts involved approx 15000.

Bureau of Indian Standards (BIS) Areas of Standardization Chemical Food and Agriculture Metallurgical Engineering Civil Engineering Management and Systems Petrochemical, Coal & Related Products Transport Engineering Electronics and Information Technology Electro-technical Mechanical Engineering Medical Equipment and Hospital Planning Production and General Engineering Water Resources Textiles

Bureau of Indian Standards (BIS) Stages of Standards Formulation BIS Procedure compliant to WTO-TBT Code of Practice Stage 2 : Building consensus among committee members Stage 3: Building national consensus International Training Programme, 10 May 2012

Priority I 12 Months Priority II 24 Months

14% Standards as on date Others 19300 4% Product Standards 9450 3% Product standards Test methods Code of Practice 11% 51% Codes of practice Terminology Dimensions & Symbols Test Methods 17% Others

Chairman (Independent Body) Member Secretary (BIS) Professional & Academic Bodies Consulting Firms Public Sector Units COMPOSITION of STANDARD FORMULATION COMMITTEE Manufacturer Laboratories/ R&D Institutions Government & Regulatory Bodies Industry Association Consumer/ User Organization

COMMENTS NEW WORK ITEM FIRST DRAFT CIRCULATION TO COMMITTEE MEMBERS P-DRAFT COMMENTS CIRCULATION TO COMMITTEE MEMBERS COMMENTS MEETING WC DRAFT MEETING PUBLIC CIRCULATION +Web (30 to 90 Days) F-DRAFT STANDARD ADOPTION BY DIVISION COUNCIL NATIONAL STANDARD 13

ETD 16 Transformers 40 Standards published Power Transformer Distribution Transformer Dry type transformer Accessories/Fittings Reactors Voltage Corrrector Tap Changer Code for selection, installation and maintenance

EARLIER INDIAN STANDARDS ON DISTRIBUTION TRANSFORMERS IS 1180(Part 1): 1989: Outdoor type three phase distribution transformers upto and including 100kVA 11 kv Part 1: Non sealed type. IS 1180(Part 2): 1989: Outdoor type three phase distribution transformers upto and including 100kVA 11 kv Part 2: Sealed type. Scope was limited upto three phase 100 kva, 11kV.

NEED AND OBJECTIVE FOR REVISION The main objective in formulation of IS1180 Part 1 was to bring uniformity in technical specifications of DTs by various stakeholders in power industry. IS1180 is a National Standard formulated by BIS, taking into account needs of Stakeholders and various guidelines issued by Ministry of Power, Ministry of Heavy Industries, Ministry of Commerce, CEA, REC, BEE and various Electricity Boards/Discoms. All the stakeholders need to respect the standard in toto unless there is a serious objection which is impractical to achieve or implement.

REVISED VERSION OF IS ON DISTRIBUTION TRANSFORMERS IS 1180(Part 1) - Outdoor type, insulated liquid immersed Distribution Transformers up to and including 2500 kva, 33kV (Part 1: Mineral Oil Immersed) Published in 2014

SALIENT FEATURES OF IS 1180(Part 1): 2014 SCOPE Includes Outdoor type three phase Distribution Transformers upto and including 2500 kva with nominal system voltage upto and including 33 kv (both sealed and non-sealed) Includes Single phase Distribution Transformers upto and including 25 kva (sealed type) Proposed Amendment No. 1 To include indoor type transformers relevant CEA guidelines must be followed while using mineral oil filled DT s indoor. In case of indoor transformers and transformers installed in an enclosure, suitable ventilation, if required, shall be provided to maintain service conditions as per IS 2026 (Part 1).

WHAT IS A DISTRIBUTION TRANSFORMER As per definition, DTs are meant for stepping down voltage used in distribution lines to the levels used by the customers Transformer with Primary voltage of 3.3, 6.6, 11, 22 or 33 kv and secondary voltage of 433 Volt, 3 Phase (250 volt for single phase ) are called Distribution Transformers. Proposed Amendment No. 1 Amended definition of Distribution Transformer A distribution transformer is a transformer that provides the final voltage transformation by stepping voltages down within a distribution circuit or from a distribution circuit to an end user or application. NOTE The distribution circuit voltages are 3.3 kv, 6.6 kv, 11 kv, 22 kv and 33 kv in the country. The power supply for the end users is 415 volt, 3 Phase (240 volt, 1 phase), 50 Hz. Transformers with primary voltages of 3.3, 6.6, 11, 22 or 33 kv and secondary voltage of 433 volt, 3 Phase (and 250 volt single phase) are called Distribution Transformers. The maximum rating of these transformers for the purpose of this standard is considered up to 2 500 kva, 3 Phase.

LIST OF STANDARDS NOT COVERED To clarify and for ease in implementation, following exclusion list is being added through Amendment No. 1: a) Inverter duty transformers; b) Traction transformers; c) Instrument transformers; d) Transformers for static converters; e) Starting transformers f) Testing transformers; g) Welding transformers; h) Earthing transformers; i) Mining transformers; j) Transformers for solar, wind power application; k) Transformers for railways (locomotive and other applications); l) Furnace transformers; m) Rectifier transformers; and n) Dual ratio in primary/secondary windings transformers

RATING Given in Tables 1, 4, 7: Preferred Non-preferred (Maximum total losses are subject to agreement between the user and the supplier) Proposed Amendment No. 1 Following ratings are being added through amendment no. 1: a) Preferred rating: 800 kva (3 phase, upto 33 kv) b) Non preferred ratings: 50 kva, 75 kva, 100 kva (single phase, 11 kv, 22 kv, 33 kv)

BASIC INSULATION LEVEL Rated BIL values for Nominal System Voltages are given in Table 2, Table 5 and Table 8. Propose Amendment No. 1 The BIL values as minimum values. However, insulation coordination of all relevant fitting corresponding to higher BIL may be ensured.

TAPPINGS No taps are generally required upto 100 kva, unless specified Transformer range of tap Voltage variation Standard tapping range is No. given below: positions 3 phase transformers upto and including 200 kva 4 +2.5% to -5% of HV in steps of 2.5 percent 3 phase transformers higher than 200 kva and upto and including 2500 kva 7 +5% to -10% of HV in steps of 2.5 percent for variation of HV NOTE: 1) For ratings greater than 500 kva, on load tap changers may be provided for variation of HV voltage from +5 percent to 15 percent in steps of 2.5 percent 2) Off-circuit tap-changing is permitted Proposed Amendment no. 1 It has been decided to make the provision of Tappings (both range and steps) subject to agreement between the user and the supplier for which amendment is being issued.

LOSSES Losses given in Table 3, Table 6 and Table 9 are MAXIMUM total losses These losses are only for transformers upto 11kV voltage class For 22 kv and 33 kv class higher losses values permitted No load losses are dependent on so many factors including design, therefore not given separately Proposed Amendment no. 1 Losses for non-preferred ratings have been added through amendment which is being issued.

Maximum total losses for voltage class above 11 kv is given in table below: Voltage class Maximum total losses for 3 phase transformers upto and including 200 kva Maximum total losses for 3 phase transformers higher than 200 kva and upto and including 2500 kva Maximum total losses for single phase transformers upto and including 25 kva Above 11 kv and upto and including 22 kv Shall not exceed by 5% of the maximum total losses given in Table 3 Shall not exceed by 5% of the maximum total losses given in Table 6 Shall not exceed by 7.5% of the maximum total losses given in Table 9 Above 22 kv and upto and including 33 kv Shall not exceed by 7.5% of the maximum total losses given in Table 3 Shall not exceed by 7.5% of the maximum total losses given in Table 3 Shall not exceed by 10% of the maximum total losses given in Table 3

NO LOAD CURRENT AND FLUX DENSITY Maximum Flux density variation shall not exceed 1.9 Tesla with voltage and frequency variation (Design calculation to be submitted) No load current shall not exceed 2 % (3% for 1 Ph) of full load current No Amendment proposal

% IMPEDENCE VALUES Values of % impedance given in IS 1180 (Part 1) : 2014 are only RECOMMENDED values. Manufacturers can prefer other while designing Higher impedance values might lead to poor regulation, more stray losses and heating, therefore small variation in these values can be made No Amendment proposal

MARKING PLATE DIMENSIONS MARKING: Proposed Amendment No. 1 Dimensions of Rating Plate, Terminal Marking Plate and Combined Rating and Terminal Plate have been made subject to agreement between the user and the supplier

LIMITS OF TEPERATURE RISE Limits are given as below: Transformer class Limits for temperature rise 3 phase transformers upto and including 200 kva For transformer winding - 40 C (when measured by resistance method) For top oil - 35 C (measured by thermometer) 3 phase For transformer winding - 45 C (when measured by transformers resistance method) For top oil - 40 C (measured by thermometer) higher than 200 kva and upto and including 2500 kva single phase transformers upto and including 25 kva For transformer winding - 40 C (when measured by resistance method) For top oil - 35 C (measured by thermometer) No Amendment proposal

LIMITS OF TEPERATURE RISE These are maximum limits of temperature rise These limits in IS 1180 (Part 1) : 2014 are more stringent compared to International standards Lower temperature rise limits are acceptable but it might increase the cooling equipment cost No Amendment proposal

TERMINAL ARRANGEMENTS For Cable box, following provisions have been added through amendment: bus duct arrangement may be provided on low voltage side by agreement between the user and the supplier Porcelain/ Epoxy/Silicon Rubber Bushing may also be used subject to agreement between the user and the supplier. For bushings, following notes has been added through amendment: For heavily polluted atmosphere, dimensions of bushings shall confirm to IS 8603. Cast resin or polymer bushing can also be used with performance requirements as per IS 2099 and IS 7421 LV Bushing Voltage Class: It has been decided to change LV Bushing Voltage Class from 1.1 kv to 1 kv

MINIMUM CLEARENCES IN AIR Specified clearances values are MINIMUM values Clearances above these values are acceptable as per IS 1180 (Part 1) : 2014 Clearances between coils and no. of coils are not given as these are design parameters No Amendment proposal

MOUNTING ARRANGEMENT Mounting arrangement is given in cl 14 Bidirectional rollers can also be used as per mutual agreement between the user and the supplier Proposed Amendment no. 1 a) Upto 200 kva: two channels of minimum size 75 mm 40 mm shall be provided Note added under Fig. 6 Any other mounting dimensions are subject to agreement between the user and the supplier b) Beyond 200 kva Preferred mounting dimensions given under table in Fig 7 have been modified Note added under Fig. 7 Any other mounting dimensions are subject to agreement between the user and the supplier

PAINT THICKNESS Measuring Paint Thickness is not a part of the tests specified in IS 1180 (Part 1). This is for guidance for manufacturers only. It is to be ensured by the Inspecting agencies at the time factory visit. No Amendment proposal

CONSTRUCTION REQUIREMENTS FOR TRANSFORMER TANK Proposed Amendment No. 1 Given under clause 15 Minimum thickness at the corrugations has been specified as 1.0 mm through amendment

CHANGES IN STANDARD FITTINGS given under clause 20.1 Existing standard fitting Changes to be made through amendment Two earthing terminals with the earthing symbol = ; No change Oil level gauge indicating oil level at minimum, 30 C and maximum operating temperature; NOTES 1 Minimum and maximum positions correspond to the operating temperature of 5 C and 90 C respectively (for non-sealed type transformer). 2 Minimum position corresponds to the operating temperature of 30 C (for sealed type transformers). Oil level gauge indicating oil level at minimum, 30 C and maximum operating temperature; NOTES 1 Minimum and maximum positions correspond to the operating temperature of 5 C and 90 C respectively (for nonsealed type transformer). 2 Only minimum position corresponding to the operating temperature of 30 C (for sealed type transformers). Air release device (for non-sealed type transformers) No change Rating and terminal marking plates; No change Plain breathing device for non-sealed type transformers which would not permit ingress of rain water and insects up to 200 kva transformers. Above 200 kva transformers dehydrating breather shall be provided Dehydrating breather shall be provided for non-sealed type transformers; Drain-cum-sampling valve (¾ nominal size thread, IS 554) preferably steel with plug for three phase transformers; Drain-cum-sampling valve preferably steel with plug for three phase transformers (for ratings above 500 kva); NOTE Valve size shall be as per agreement between the user and the supplier.

Existing standard fitting Changes to be made through amendment Thermometer pocket with cap; No Change Oil filling holes having (1¼ nominal size thread) with cover (for sealed type transformers without conservator) Oil/Nitrogen/Air filling hole having (1¼ nominal size thread) with cover (for sealed type transformers without conservator); An extended pipe connection on upper end with welded cover for sealed type transformers. The pipe should be suitably threaded over a sufficient length to enable use of a refilling/siphon connection after removing the welded cover or any other similar arrangement capable of reuse; Deleted Lifting lugs for the complete transformer as well as for core and winding assembly; No Change Nitrogen/air filling device/pipe with welded cover capable of reuse (for sealed type transformer); Deleted Pressure relief device or explosion vent above 200 kva; Pressure relief device or explosion vent [for sealed type transformers (for all ratings) and non-sealed type transformers (for ratings above 200 kva)]; One filter valve on the upper side of the tank (for transformers above 200 kva); No Change Unidirectional flat rollers (for transformers above 200 kva) Deleted Inspection hole (for transformers above 200 kva); Deleted Pressure gauge for sealed transformers with radiators and nitrogen cushion (above 200 kva); Deleted HV side neutral grounding strip (where one of the HV bushing terminal is connected to earth); No Change LV earthing arrangement for single phase transformers; No Change Buchholz relay for transformers above 1 000 kva. No Change New fittings added Arcing horns for HT side (one number per phase)

CHANGES IN OPTIONAL FITTINGS given under clause 20.2: Existing Optional fittings Changes Filter valve (1¼ nominal size thread) for transformers up to 200 kva; Filter valve for transformers up to 200 kva; Arcing horns or suitable rating lightning arrestors for HT side 3 Nos. for transformers up to 200 kva; c) Suitable rating lightning arrestors for HT side (one number per phase); Pressure relief device or explosion vent (up to 200 kva) Pressure relief device or explosion vent (upto 200 kva for non-sealed type transformers); Protection relay for sealed type transformers for internal parameters that is pressure, temperature, oil level and gas detection (above 1 000 kva) Protection relay for sealed type transformers for internal parameters that is pressure, temperature, oil level and gas detection New Fittings q) Unidirectional flat rollers (for transformers above 200 kva); NOTE Valve size shall be as per agreement between the user and the supplier. r) Drain-cum-sampling valve preferably steel with plug for three phase transformers (for transformers upto 500 kva); and NOTE Valve size shall be as per agreement between the user and the supplier. s) Self protection/disconnection devices subject to agreement between the user and the supplier: 1) Thermo-magnetic circuit breaker as self protection device on secondary side as per IS/IEC 60947-2 : 2003; and 2)Expulsion fuse as disconnection device on primary side as per IS 9385 (Part 2): 1980. NOTE Additional requirements for transformers with self protection/disconnection devices are under preparation.

Proposed Amendment No. 1 -CHANGES IN TEST REQUIREMENTS a) ROUTINE TESTS Separate-source voltage withstand test: Following note has been added under this test: For single phase transformer with 11/ 3 or 22 / 3 or 33/ 3 kilo volts and with 1.0 kv neutral bushing, this test shall be conducted at test voltage of neutral (3 kv rms for one minute). b) TYPE TESTS Temperature-rise test: Note given under this test was deleted. Pressure test a) Upto 200 kva: Test requirements for corrugated tanks added Limits of deflection of flat plates from 1251 mm to 1750 mm has been added Note added that permanent deflection is not applicable for corrugations

Proposed Amendment No. 1 b) Beyond 200 kva Test requirements for corrugated tanks added Note added that permanent deflection is not applicable for corrugations Leakage test Annexure providing additional information on Leakage test has been added. SPECIAL TESTS These are to conducted on one unit and shall be subject to agreement between user and supplier Paint adhesion test and BDV and moisture content on oil in the transformer may be carried out on more than one unit subject to agreement between user and the supplier

METHOD OF DECLARING EFFICIENCY The efficiency to be declared is the ratio of the output in kw to the input in kw and calculated as under. Efficiency = output/input = input- total losses/ input Total losses comprise: No-load loss, which is considered to be constant at all loads : and Load loss, which varies with load. The total loss, on load is the sum of above losses.