Data Sheet Manual Motor Starter Ex9S32 Series

Similar documents
Data Sheet Manual Motor Starter Ex9S32 Series

Data Sheet Manual Motor Starters Ex9SN Series

Thermal Overload Relays

Data Sheet DIN Rail Miniature Circuit Breakers Ex9 Series - B1NQ

Data Sheet Molded Case Circuit Breakers Molded Case Motor Circuit Protectors Molded Case Switches. Ex9 Series - M. na.noark-electric.

Data Sheet Molded Case Circuit Breakers Molded Case Motor Circuit Protectors Molded Case Switches Ex9 Series - M

Data Sheet DIN Rail Miniature Circuit Breakers Ex9 Series - B1

Electronic overload relays EF205 and EF370

Data Sheet Definite Purpose Contactors Ex9CK Series

Electronic overload relay EF65, EF96 and EF146

Thermal overload relay TF65 and TF96

System pro M compact Miniature Circuit Breaker SU200M for branch circuit protection acc. to UL 489

Thermal overload relay TF140DU and TF140DU-V1000

SU200M Datasheet. Branch protection acc. to CSA C22.2 No.5 / UL 489

MS /27/2015. ABB contact for United States of America. General Information Extended Product Type: Categories

Mini contactors B6, BC6 with 3 pole

MS General Information Extended Product Type: MS

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases

System pro M compact Supplementary protector S 200 PR for ring-tongue applications acc. to UL1077

AF / AF38Z pole Contactors AC / DC Operated - with Screw Terminals

AF / AF09Z pole Contactors AC / DC Operated - with Screw Terminals

AF / AF30Z stack 3-pole Contactors AC / DC Operated - with Screw Terminals

AF / AF16Z pole Contactors AC / DC Operated - with Screw Terminals

Short form catalogue Motor protection and control Manual motor starters

Manual motor starters Overview and benefits

NF31E-.. / NFZ31E-.. Contactor Relays AC / DC Operated - with Screw Terminals

AF / AF09Z pole Contactors AC / DC Operated - with Screw Terminals

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Standard Features

AF40... AF96 3-pole contactors Technical data

Manual motor starter MS132

cor Long Run Experience

Manual motor starter MS116

Manual Motor Starters. Meta-MEC

Manual motor starter MS132

Circuit-Breakers M4 166 for motor protection. Auxiliary contacts 167 Signalling switch Auxiliary releases

Manual motor starter MS132

Series KTU7 UL489 Molded Case Circuit Breakers

1489-M Circuit Breakers

Product index. 4 - Manual motor protectors. Manual motor protectors. Manual motor protectors Low Voltage Products & Systems 4.

Manual motor starter magnetic only MO325

Introduction. Standard Features. GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Introduction

Manual motor starter MS116

3 - Protection components Motor circuit-breakers

Technical Information

System pro M compact Miniature Circuit Breaker S 200 M UC for DC and AC applications

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

Product index. 4 - Manual motor protectors. Phone: Fax: Web: -

C60H-DC C curve. Catalogue numbers

Contact us. ABB France Electrification Products Division Low Voltage Products and Systems 3, rue Jean Perrin F Chassieu cedex / France

Ideal for use as a manual starter

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC

I r A short-circuit protective device: Observe the maximum permissible fuse of the contactor with direct device mounting.

Technical data for manual motor starters Type MS325

AF40... AF96 3-pole contactors 30 to 60 hp at 480 V AC AC / DC operated with 1 N.O. + 1 N.C. auxiliary contacts

Protection Equipment

Protection and Connection Motorized and automatic transfer switches IEC Technical guide

B115...B180 RF200 RFN200 B250...B400 RF400 RFN400

KT4 Manual Motor Starter

Series KTU7 UL489 Molded Case Circuit Breakers

Circuit Breakers Ex9M

SIRCO UL98 Non-fusible switches standards UL and CSA 100 to 1200 A

249.1 m3/h m3/h 7.23 MW m3/h 50.0 m3/h

US Catalog January Motor protection and control Manual motor starters, contactors and overload relays

UTS400 SELECTION GUIDE CATALOG NUMBERING [PRODUCT SELECTION] UTS400 NT ATU 400A 3P LL LSIS UL MCCB

DATASHEET - ZB Delivery program. Overload relay, 50-65A, 1N/O+1N/C. Catalog No Eaton Catalog No. XTOB065DC1 EL-Nummer

CTX 3 Control relays Cat. N (s) : /06/09..14/16/19..24/26/29

Protection Equipment. 5/2 Introduction

B6, B7, BC6, BC7, TBC7 3- and 4-pole mini contactors VB6, VB7, VBC6, VBC7 3- and 4-pole mini reversing contactors Technical data

Interchangeable Built-in Fixed thermal Adjustable thermal Magnetic Fixed Adjustable Adjustable Electronic RMS 7 LS LSI

SIRCO UL98 Load break switches standards UL and CSA 100 to 1200 A

DPX Thermal magnetic and trip-free switches DPX 3 -I 160

MSW. MSW Catalog Number Sequence. Standard Features MSW 25 B- 3

Series L9 UL489 Miniature Circuit Breakers


FMotor Circuit Controllers

VB6, VB7 3-pole mini reversing contactors with screw terminals 4 to 5.5 kw AC operated

DRX 125 Circuit breaker (not adjustable)

Index. Manual Motor Starters 1. Auxiliary Contact Blocks 1. Trip Alarm Auxiliary 1. Switch. Shunt Release 1. Under-voltage Release 2.

Protection components

Motor-protectivecircuit-breaker,3p,Ir=2.5-4A. Product range PKZM01 motor protective circuit-breakers up to 16 A with pushbutton actuation

AF / AF12Z pole Contactors AC / DC Operated - with Screw Terminals

D509E. Manual Motor - Starters

Manual motor protectors Type MS116 Type MS325 Type MS45X Type MS49X

SACE Emax 2/ML Low-voltage air circuit breakers for naval applications

Thermal Overcurrent Circuit Breaker 3120-F...

ACW Molded-Case Circuit Breaker UL 489 Listed

Thermal Overcurrent Circuit Breaker 3120-F...

AF09... AF30 3-pole Contactors up to 20 HP / 480 VAC

Selective main circuit breakers S 750 series Technical Data

SD Series Non-Fused Load Switches

ASL09..S 3-pole Contactors - Spring Terminals

DPX Thermal magnetic and trip-free switches DPX 3 -I 250

Technical Data Accessories MCBs Ex9B.

and other modular devices for low voltage installation

ZS10-ST Screw Clamp Terminal Blocks Test disconnect with sliding link

ACW. Molded-Case Circuit Breaker UL 489 Listed. ACW Catalog Number Sequence

DPX Magnetic only

UMBW-UL489 and UL1077 Listed

The breakers offer thermal-magnetic trip protection according to Z and K characteristics.

Protectors. 35mm DIN rail snap-on mounting. Wide range of accessories

Transcription:

Data Sheet Manual Motor Starter Ex9S32 Series na.noark-electric.com

NOARK Ex9S32 Series Features Ex9S32 Manual Motor Starter provides manual isolation, manual motor control, and overcurrent protection in one unit. Ex9S32 Manual Motor Starters are electro-mechanical devices combining functions below in one unit. Disconnect for Motor Branch Circuit Manual Motor Control Branch-Circuit Short Circuit Protection (Magnetic Protection) Overload Protection (Thermal Protection) - Trip Class 10 Switching (Manual) In North American Electrical Codes require an individual Motor Branch Circuit be protected by a UL/CSA Listed Fuse, Circuit breaker or Self-Protected Combination Motor Controller. Available with: Up to 32A @600Vac Type E and F combination Built-in fault indication Full range of accessories Lockable handle Certifications UL60947-1/UL60947-4-1A listed, file No. E467185 UL508 listed, file No. E476273 IEC/EN 60947-2/-4-1 CCC Approved Standards Compliance IEC/EN 60947-1, -2, -4-1, -5-1 UL 508 UL 60947-1; -4-1A UL 489 GB 14048.2 GB 14048.4 2 2019 NOARK Electric

Ex9S32 Product Selection and Packaging Product Selection Guide Ex9S 32 A 25A NOARK Manual Motor Starter Frame Sizes Operation Type Setting Current 32: Up to 32A A: Rotary Operation 0.16A: 0.1-0.16A 0.25A: 0.16-0.25A 0.4A: 0.25-0.4A 0.63A: 0.4-0.63A 1A: 0.63-1A 1.6A: 1-1.6A 2.5A: 1.6-2.5A 4A: 2.5-4A 6.3A: 4-6.3A 10A: 6-10A 14A: 9-14A 18A: 13-18A 23A: 17-23A 25A: 20-25A 32A: 24-32A Packaging Weight/Pcs lb(g) Pieces/Box Box Dimension in(mm) Full Box Weight lbs(kgs) Pieces/Carton Carton Dimension in(mm) Full Carton Weight lbs(kgs) 0.16-1A 0.58 (257.5) 1 4.25x4.33x1.97 (108x110x50) 68.01(30.85) 30 14.73x9.45x11.22 (365x240x285) 22.05 (10) 1.6-32A 0.72 (325) 1 4.25x4.33x1.97 (108x110x50) 82.89 (37.60) 30 14.73x9.45x11.22 (365x240x285) 26.46 (12) All Rights Reserved 3

Ex9S32 Specifications Technical Data (Table 1) Description Rated operational current I e (A) Conventional rated thermal current Ith (A) Ex9S32 32A 0.16~32A Tripping Class 10 Rated insulation voltage U i (Vac) 690/IEC; 600/UL, CSA Rated operational voltage U e (AC) 230/240, 400/415, 460/480, 575/600 Rated impulse withstand voltage U imp (AC) Rated Operational Frequency (Hz) Enviornmental Temperature Service life* (cycles) Resistance to shock Resistance to vibrations Transportation or Storage Working at Testing at 6000V 50/60Hz 30 gn -11 ms 5gn (5-150Hz) -76 to 176 F (-60 to 80 C)¹ -4 to 158 F (-20 to 70 C)² 23 to 104 F (-5 to 40 C) Altitude ft (m) Not to exceed 6,562 (2,000) Environment Pollution Grade Mounting Conditions At mounting site, relative humidity not exceed 90% at the max testing temperature 104 F (40 C), higher relative humidity is allowable under lower temperature III The inclination between the mounting plane and the vertical plane shall not exceed 5 ; The product shall be installed and operated at a place without obvious shake, impact and vibration. Interrupting Rating Icu Check Table 3 & 4 Duty Class (cycles/hr) Electrical 100,000* Mechanical 200,000* 30, max. operating rate Degree of Protection IP 20 1: 24 hours max. at the ultimated temperature 2: with temperature reduction factor, table 8 *: close/open operation, and 30 cycles/hr for AC-3 Duty@400/415 Vac 4 2019 NOARK Electric

Ex9S32 Specifications (Table 2) Overload Protection Properties Series Number Multiple of Setting Current Initial Status Time Expected Results Ambient Temperature 1 1.05 Cold Status t 2h Non-Tripping 2 1.20 Heat Status t<2h 3 1.50 (right after test 1) 10 t<4 min 4 7.20 Cold Status 10 4s<t 10s Phase Failure Protection Properties Series Number Interrupting Capacity For IEC (Table 3) Multiple of Setting Current Any 2 Phase The Other Phase Tripping Initial Status Time Expected Results 1 1.0 0.9 Cold Status t 2h Non-Tripping 2 1.15 0 Temperature Compensation Properties Heat Status (right after test 1) t<2h Tripping Series Number Multiple of Setting Current Initial Status Time Expected Results 1 1.0 Cold Status t 2h Non-Tripping 2 1.2 Heat Status (right after test 1) t<2h Tripping 3 1.05 Cold Status t 2h Non-Tripping 4 1.3 Heat Status (right after test 1) t<2h Tripping 68 F to ±35.6 F (+20 C to ±2 C) Ambient Temperature 68 F to ±35.6 F (+20 C to ±2 C) Ambient Temperature 104 F to ±35.6 F (+40 C to ±2 C) -23 F to ±35.6 F (-5 C to ±2 C) 400Vac 690Vac Icu Ics Icu Ics Type ka ka ka ka 0.16A 100 100 100 100 0.25A 100 100 100 100 0.4A 100 100 100 100 0.63A 100 100 100 100 1A 100 100 100 100 1.6A 100 100 100 100 2.5A 100 100 6 4 4A 100 100 6 4 6.3A 100 100 6 4 10A 100 100 6 4 14A 50 30 6 4 18A 50 30 6 4 23A 50 30 6 4 25A 50 30 6 4 32A 50 30 6 4 All Rights Reserved 5

Ex9S32 Specifications Interrupting Capacity continued For UL (Table 4) Short-Circuit Rating Manual motor controllers for motor disconnect 1 Max. Horsepower Rating Type 240/ 480Vac 600Vac 600 Vac 1PH 3PH ka ka ka 110/120Vac 230/240Vac 200/208Vac 230/240Vac 460/480Vac 575/600Vac 0.16A 65 30 5 - - - - - - 0.25A 65 30 5 - - - - - - 0.4A 65 30 5 - - - - - - 0.63A 65 30 5 - - - - - - 1A 65 30 5 - - - - - 1/2 1.6A 65 30 5-1/10 - - 3/4 3/4 2.5A 65 30 5-1/6 1/2 1/2 1 1.5 4A 65 30 5 1/8 1/3 3/4 3/4 2 3 6.3A 65 30 5 1/4 1/2 1 1.5 3 5 10A 65 30 5 1/2 1.5 2 3 5 7.5 14A 65 30 5 3/4 2 3 3 10 10 18A 50 30 5 1 3 5 5 10 15 23A 50 30 5 1.5 3 5 7.5 15 20 25A 50 30 5 2 3 5 7.5 15 20 32A 50 30 5 2 5 7.5 10 20 25 Short-Circuit Current Rating Type E: Self-Protected Combination Motor Controller (with CCT51) (Table 5) Max. HP Rating Type Overload Trip Range 1PH 3PH SCCR (ka) 110/120Vac 230/240Vac 200/208Vac 230/240Vac 460/480Vac 575/600Vac 240/480V 600V Ex9S32A 0.16A 0.1-0.16A 65 10 Ex9S32A 0.25A 0.16-0.25A 65 10 Ex9S32A 0.4A 0.25-4A 65 10 Ex9S32A 0.63A 0.4-0.63A 65 10 Ex9S32A 1A 0.63-1A 1/2 65 10 Ex9S32A 1.6A 1-1.6A 1/10 3/4 3/4 65 10 Ex9S32A 2.5A 1.6-2.5A 1/6 1/2 1/2 1 1.5 65 10 Ex9S32A 4A 2.5-4A 1/8 1/3 3/4 3/4 2 3 65 10 Ex9S32A 6.3A 4-6.3A 1/4 1/2 1 1.5 3 5 65 10 Ex9S32A 10A 6-10A 1/2 1.5 2 3 5 7.5 65 10 Ex9S324A 9-14A 3/4 2 3 3 10 10 65 10 Ex9S328A 13-18A 1 3 5 5 10 15 42 Ex9S323A 17-23A 1.5 3 5 7.5 15 20 42 Ex9S325A 20-25A 2 3 5 7.5 15 20 42 Ex9S32A32A 24-32A 2 5 7.5 10 20 25 42 6 2019 NOARK Electric

Ex9S32 Specifications Short-Circuit Current Rating Continued Type F: Manual Self-Protected Combination Motor Controller (Table 6) Manual Self- Associated Type of Overload Standard Motor Ratings@50/60 SCCR (ka) Combination Mounting Protected Cable, AWG Contactor Trip 1 PH 3 PH 240V 480Y/ 600Y/ Block Bracket Starter 75 C, Cu Required Range(A) 110/120V 230/240V 200/208V 230/240V 460/480V 575/600V 277V 347V Ex9S32A0.16A Ex9S32A0.63A 0.4-.63 Ex9S32A Ex9CS12/ 0.63-1 1/2 14 Ex9S32.6A Ex9C12 1-1.6 1/10 3/4 3/4 Ex9S32.5A 1.6-2.5 1/6 1/2 1/2 1 1.5 Thermal Settings And Magnetic Trip Current* *Rated supply current Ambient Temperature at 40 C (Table 7) Rated supply current (lth) at Ambient Temperature: Check Ex9S32 Temperature Reduction Factor table Temperature Reduction Factor For Ex9S32 (Table 8) 0.1-0.16 Ex9S32A0.25A 0.16-0.25 Ex9S32A0.4A 0.25-0.4 Ex9S32A4A 2.5-4 1/8 1/3 3/4 3/4 2 3 Ex9S32A6.3A 4-6.3 1/4 1/2 1 1.5 3 5 Ex9S320A 6-10 1/2 1.5 2 3 5 7.5 65 10 wcc51/cc52 Ex9S324A Ex9C18 9-14 3/4 2 3 3 10 10 CC52 12 Ex9S328A 13-18 1 3 5 5 10 15 Ex9C25 Ex9S323A 17-23 1.5 3 5 7.5 15 20 10 42 CC53 Ex9S325A 20-25 2 5 5 7.5 15 20 Ex9C38 Ex9S32A32A 8 24-32 2 5 7.5 10 20 25 Ex9S Heater Designation Thermal Setting (A) Minimum Maximum Magnetic Trip Rating (A) 0.16A 0.1 0.16 2.1 0.25.16 0.25 3.2 0.4A 0.25 4 4.8 0.63A 0.4 0.63 7.2 1A 0.63 1 11 1.6A 1 1.6 20 2.5A 1.6 2.5 30 4A 2.5 4 50 Device Ex9S32 0.16A Ex9S32 0.25A Ex9S32 0.4A Ex9S32 0.63A Ex9S32 1A Ex9S32 1.6A Ex9S32 2.5A Ex9S32 4A Ex9S32 6.3A Ex9S32 10A Ex9S32 14A Ex9S32 18A Ex9S32 23A Ex9S32 25A Ex9S Heater Designation Thermal Setting (A) Minimum Maximum Magnetic Trip Rating (A) 6.3A 4 6.3 72.5 10A 6 10 130 14A 9 14 175 18A 13 18 230 23A 17 23 280 25A 20 25 280 32A 24 32 416-20 C (-4 F) -5 C (23 F)1PH 0 C (-32 F) 20 C (68 F) 40 C (104 F) 60 C (140 F) 70 C (158 F) single group single group single group single group single group single group single group 1.00 1.00 1.00 1.00 Ex9S32 32A 0.95 0.95 0.95 1.00 1.00 1.00 1.00 1.00 0.95 0.92 0.90 -/DRA51 DRA51 0.95 0.91 0.87 0.83 All Rights Reserved 7

Ex9S32 Dimensions Ex9S32 Unit: in. [mm] 8 2019 NOARK Electric

Ex9S32 Accessories: Selection Guide Selection Ex9S AX51 A G NOARK Ex9S32 Series Description Auxiliary Contact Rated Voltage AX51: Auxiliary contact (front mount only) 11: 1NO+1NC (AX51,AX52,AL51) A: 100~130V 50/60Hz(SHT51) 110~120V 60Hz(UVT51) AX52: Auxiliary contact (left side only) 20: 2NO (AX51,AX52) B: 190~330V 50/60Hz(SHT51) 110~120V 50Hz & 127V 60Hz(UVT51) AL51: Fault Signaling Contact (left side only) 02: 2NC (AX52) C:330~440V 50/60Hz(SHT51) 208V 60Hz(UVT51) UVT51: Undervoltage release (right side only) D: 480~500V 50/60Hz(SHT51) 240V 60Hz(UVT51) SHT51: Shunt release (right side only) E: 575~600V 50/60Hz(SHT51) 480V 60Hz(UVT51) CCT51: Terminal Block F: 600V 60Hz(UVT51) G: 220~240V 50Hz(UVT51) H: 380~415V 50Hz(UVT51) CC 51 Description Type 51:Ex9CS 12A Combination Block 52: Ex9C 9-18A 53: Ex9C 25-38A DRA 51 Description Type Mounting Bracket 51: for mounting Ex9S32 with Ex9C 9-38A ERH 51 B Description Type Color of Handle Extended Rotary Handle 51: for Ex9S32 B: Black/Gray Y: Yellow/Red WPB 51 B Description Type Color of Handle Waterproof Enclosure 51: with rotary handle B: Black/Gray Y: Yellow/Red All Rights Reserved 9

Ex9S32 Accessories: Specifications Description Mounting Location Max. No. of Blocks Contact Type SKU NO+NC AX5111 Front 1 NO+NO AX5120 Auxiliary Contact Blocks NO+NC AX5211 2 NO+NO AX5220 Left Side NC+NC AX5202 Fault Signaling Contact 1 NO+NC AL5111 Electrical Trip Unit Description Mounting Location Voltage Hz SKU 110-120V 60 UVT51A 127V 60 UVT51B 110-120V 50 UVT51B 208V 60 UVT51C Undervoltage Release Right Side 240V 60 UVT51D 480V 60 UVT51E 600V 60 UVT51F 220-240V 50 UVT51G 380-415V 50 UVT51H 100-130V 50/60 SHT51A 190-330V 50/60 SHT51B Shunt Release Right Side 330-440V 50/60 SHT51C 480-500V 50/60 SHT51D 575-600V 50/60 SHT51E Terminal Block Busbars Description Monting Location Pole SKU Large spacing, UL 508 Type E and F Line-in Side 3 CCT51 Description Sets of 3-pole, 63A Busbar Wiring Accessories No. of Ex9S32 Starter 2 3 4 5 No. of Side-Mounted Aux Contact on Busbar Pitch (mm) SKU each Ex9S32 starter None 45 CBB510 1 of AX52, AL51 54 CBB51B21 2 of AX52, AL51 or 1 UVT51, SHT51 63 CBB51C22 None 45 CBB51A30 1 of AX52, AL51 54 CBB51B31 2 of AX52, AL51 or 1 UVT51, SHT51 63 CBB51C32 None 45 CBB51A40 1 of AX52, AL51 54 CBB51B41 2 of AX52, AL51 or 1 UVT51, SHT51 63 CBB51C42 None 45 CBB51A50 1 of AX52, AL51 54 CBB51B51 2 of AX52, AL51 or 1 UVT51, SHT51 63 CBB51C52 Description Application SKU Input Terminal for CBB51 Busbar Terminal block for power supply to one or more CBB51 bus bar FD51 Protective end cover For unused busbar outlets PC51 Mounting Accesories Enclosures Description Application SKU Between Ex9S32 and Ex9C Mini Type Contactor, 09-12A CC51 Combination Block Between Ex9S32 and Ex9C Standard Type Contactor, 09-18A CC52 Between Ex9S32 and Ex9C Standard Type Contactor, 25-38A CC53 Mounting Bracket For mounting a Ex9S32 to a Ex9C Standard Type Contactor, 09-38A DRA51 Description Type Color Rating SKU Waterproof Enclosure; Black/ Gray WPB51B Ex9S32 Protectors Operation by rotary handle Yellow/ Red NEMA 4X/4, IP 65 WPB51Y Operation Handle The extended rotary handle makes it possible for a door-mounted rotary handle to operate starter installed on the inside back panel of an enclosure. The extended rotary handle consists of the following: - a set of screws onto the handle of the starter - an assembly (handle and front plate) that fits on the enclosure door - an extension shaft which must be adjusted according to the distance between the mounting surface and the door: 9 inch (230 mm) - a bracket that install with starter and the shaft through Description Type Color Rating SKU 9 inch (230mm) shaft, Black/ Gray ERH51B Extended Rotary Handle with bracket Yellow/ Red NEMA 4X/4, IP65 ERH51Y AX51 UVT51 CCT51 AX52 SHT51 AL51 Ex9S32 + CC53 + Ex9C32 + DRA51 CC51 WPB51B CBB51 CC52 ERH51B DRA51 CC53 10 2019 NOARK Electric

Ex9S32 Accessories: Packaging and Specifications Product's Inner Box Carton N.W. Part Number (g) Qty/box (pcs) Dimensions (mm) G.W. (g) Full Carton Qty (pcs) Dimensions (mm) G.W. (kgs) AX51 16 10 81x63x58 189 720/72 405x265x265 14.2 AX52 42 2 98x82x27 106 192/96 415x240x285 10.8 AL51 43 1 98x82x27 65 96/96 415x240x285 6.9 UVT51 125 1 98x82x27 147 96/96 415x240x285 14.8 SHT51 102 1 98x82x27 124 96/96 415x240x285 12.6 CCT51 54 6 144x112x65 396 144/24 353x292x314 10.3 Technical Data Auxiliary contacts - AX51 Auxiliary contacts - AX52 Auxiliary contacts - AL51 Shunt Release - SHT51 Undervoltage Release - UVT51 Adapter - CCT51 Rated operational voltage Ue 300V 600V 600V Rated frequency 50/60Hz 50/60Hz 50/60Hz 50/60Hz 50/60Hz 50/60Hz Rated impulse withstand voltage Uimp 6000V 6000V 6000V Conventional rated thermal current (Ith)" 2.5A 5A 5A Mechanical life (C-O operations) 100000 100000 100000 Electrical life (C-O operations) (for AC-3 duty) (for AC-3 duty) AC-15 : 10,000 AC-15 : 10,000 AC-14 : 1000 Terminal Wiring Ex9S32 Main Terminal Screw Type M4, Phil-Slot head Pull wire length inch (mm) 0.4 (10) Wire range AWG (1)x14-(2)x8 Torques in-lb (N.m) 1.85 (2.5) Model Wire Ranges(AWG) Torques in-lb (N.m) Screw Type AX51 (1)x18-(2)x12 0.59 (0.8) M3 AX52 (1)x18-(2)x12 0.59 (0.8) M3 AL51 (1)x18-(2)x12 0.59 (0.8) M3 Phil-Slot UVT51 (1)x18-(2)x12 1.254 (1.7) M3.5 Head SHT51 (1)x18-(2)x12 1.254 (1.7) M3.5 CCT51 (1)x14-(2)x8 1.844 (2.5) M4 All Rights Reserved 11

Ex9S32 Accessories: Dimensions Ex9S32 + CC51 + Ex9CS06, 09, 12 3.86±0.02 [98±0.5] 3.47±0.02 [88±0.5] 3.36±0.02 [85.2±0.5] 0.583±0.007 [14.8±0.2] 0.197 [5] 0.197 [5] 1.378 [35] 0.34±0.01 [8.60±0.25] CC51 6.540 [166] 0.583±0.007 [14.8±0.2] 1.10 [28] 0.197 [5] 1.378 [35] 3.86±0.02 [98±0.5] 3.47±0.02 [88±0.5] 3.36±0.02 [85.2±0.5] 0.197 [5] 0.34±0.01 [8.60±0.25] 1.60 [40.8] 0.662 [16.8] 2.720 [69] 2.770 [70.3] 6.540 [166] 1.10 [28] 1.60 [40.8] 0.662 [16.8] Ex9S32 +CC51 + Ex9CS06, 09, 12 3.86±0.02 [98±0.5] 3.47±0.02 [88±0.5] CC51 2.720 [69] 2.770 [70.3] 3.36±0.02 [85.2±0.5] 0.583±0.007 [14.8±0.2] Ex9S32 + CC52 + Ex9C09, 12 18 1.380 [35] 0.195 [5] 3.86±0.02 [98±0.5] 3.47±0.02 [88±0.5] 0.34±0.01 [8.60±0.25] CC52 Ex9S32 +CC51 + Ex9CS06, 09, 12 0.583±0.007 [14.8±0.2] 7.84 [99] 5.89±0.02 [149.5±0.5] 1.380 [35] 1.380 [35] 3.36±0.02 [85.2±0.5] 0.195 [5] 0.34±0.01 [8.60±0.25] 2.100 [53.4] 1.260 [31.9] CC51 3.190 [81] 3.250 [82.4] 7.84 [99] 5.89±0.02 [149.5±0.5] 2.100 [53.4] 1.260 [31.9] 1.380 [35] 3.190 [81] 3.250 [82.4] Ex9S32 +CC52 + Ex9CS09, 12, 18 CC52 12 Ex9S32 +CC52 + Ex9CS09, 12, 18 CC52 2019 NOARK Electric

Ex9S32 Accessories: Dimensions Ex9S32 + CC52 + Ex9C09, 12, 18 + DRA51 0.583±0.007 [14.8±0.2] 0.217 [5.5] 4.765±0.020 [121±0.5] 4.40±0.02 [111.4±0.5] 4.280 [108.7] CC52 CC52 2.100 [53.4] 1.260 [31.9] 2.410 [61.1] DRA51 3.190 [81] 3.250 [82.4] 1.122 [28.5] 0.925 [23.5] 8.86 [225] 0.197 [5] 8.425 [214] 6.34±0.02 [161±0.5] 1.380 [35] 8.860 [225] 1.70±0.02 [43.2±0.5] 0.098 [2.5] 0.583±0.007 [14.8±0.2] 1.220 [31] ø0.197 [5] 0.275 [7] 0.195 [5] 3.86±0.020 [98±0.5] 3.47±0.02 [88±0.5] 3.36±0.02 [85.2±0.5] 0.34±0.01 [8.6±0.25] Ex9S32 + CC53 + Ex9C25, 32, 38 8.20 [208] Ex9S32 + CC52 + Ex9C09, 12, 18 + DRA51 0.583±0.007 [14.8±0.2] 5.89±0.02 [149.5±0.5] 1.380 [35] 3.86±0.020 [98±0.5] 3.47±0.02 [88±0.5] 3.36±0.02 [85.2±0.5] 0.195 [5] 0.34±0.01 [8.6±0.25] CC53 2.028 [51.5] 1.063 [27] DRA51 1.380 [35] 34.6 3.740 [95] 3.800 [96.5] 8.20 [208] 5.89±0.02 [149.5±0.5] 4.20 [106.6] 2.028 [51.5] 1.063 [27] 34.6 3.740 [95] 3.800 [96.5] Ex9S32 + CC53 + 9C25, 32, 38 CC53 4.20 [106.6] All Rights Reserved 13

Ex9S32 Accessories: Dimensions Ex9S32 + CC53 + Ex9C25, 32, 38 + DRA51 CC53 Unit: CC53in [mm] 4.765±0.020 [121±0.5] 0.583±0.007 [14.8±0.2] 4.40±0.02 [111.4±0.5] 4.28±0.02 [108.7±0.5] 0.217 [5.5] 2.028 [51.5] 1.063 [27] 2.41±0.2 [61.1±0.5] 1.70±0.02 [43.2±0.5] DRA51 1.122 [28.5] 0.925 [23.5] 3.740 [95] 3.800 [96.5] 8.86 [225] 0.197 [5] 8.425 [214] 6.34±0.02 [161±0.5] 8.86 [225] 1.380 [35] 0.098 [2.5] ø0.197 [5] 1.220 [31] 0.275 [7] 5.106 [129.7] ERH51 1 1/8 [ST2.9] Ex9S32 + CC53 + Ex9C25, 32, 38 + DRA51 DRA51 1 2.52 [64] 1.98 [50.4] 2.52 [64] 1.93 [49] 1.98 [50.4] 2 2 0.24 [6] 8.66 [220] 0.24 [6] 9.05 [230] 12.01-12.12 [305-308] 3 4 3 0.71 [18] 0.89 [22.7] 7.09 [82] 6.93 [176] 4 0.32 [8] 0.93 [23.6] 0.51 [13] 2.01 [51] 14 0.14 [3.5] 0.34 [8.6] 2019 NOARK Electric

Ex9S32 Accessories: Dimensions WPB51 4.57 [116] 6.30 [160] 5.71 [145] 5.86 [149] 0.18 [4.5] M21 M25 3.54 [90] 4.73 [120] 4.26 [108] 5.51 [140] 0.21 [5.5] All Rights Reserved 15

NOARK Electric North America 2188 Pomona Blvd, Pomona Ca 91768 (626) 330-7007 na.noark-electric.com nasales@noark-electric.com Note: NOARK Electric reserves the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. NOARK Electric nor any of its affiliates or subsidiaries shall be responsible or liable for potential errors or possible lack of information in this document. NOARK Electric reserves all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of NOARK Electric. 2019 NOARK Electric All Rights Reserved DSMMS201901NA