DISTRIBUTION SOLUTIONS. GSec Gas-insulated switching and isolating apparatus

Similar documents
AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR

Medium Voltage Products. SHS2 Gas-insulated switching and isolating apparatus

General. Main electric circuits Fuses compartment Operating mechanisms Cables connection compartment

PIX-H Metal-clad switchgear up to 17.5kV

Air-insulated switchgear UniGear type ZS1

Product catalogue. ABB AS, Power Products Division SF 6. -insulated Ring Main Unit, SafeRing 36 and -insulated Compact Switchgear SafePlus 36

CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka Up to 38 kv / 2000 A / 31.5 ka IEEE Standards

Medium voltage products UniSec DY800 New 24 kv air-insulated medium voltage switchgear to e-distribuzione specifications

MV Air Insulated Switchgear TAP17. Technical Data TGOOD

SF 6. -insulated Ring Main Unit, SafeRing 36 and -insulated Compact Switchgear SafePlus kv ABB

CGMCOSMOS. Reliable innovation. Personal solutions. Fully gas insulated modular and compact (RMU)system.

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE

SYSclad switchboard equipped with draw out type vacuum circuit breaker closed dooroperationoperation. SYSclad 12 17,5kV A.

MEDIUM VOLTAGE PRODUCTS. Powerbloc Pre-assembled modules for building medium voltage switchgear

MESG 12 / 17.5 / 24 / 36 KV

SF6 Load Break Switch 2017 FIL3 - S. Indoor Medium Voltage LBS With or without fuse 12kV- 24kV FIL3 D FIL3. 24KV SF6 Load Break Switch

abb SafeLink SF 6 Insulated Ring Main Unit Installation and Operating Instructions Switchgear Division Auckland, New Zealand SLMIO ver 2.

ATR-MIX. METAL ENCLOSED SWITCHGEAR kV A ka

UniGear. Technical Guide

Medium Voltage Distribution PIX. Air Insulated Switchgear up to 24 kv PARS TABLEAU

Medium voltage compact switchgears. rated voltage 12 and 25 kv rated current 400 and 630 A

COMPACT AND EXTENSIBLE RING MAIN UNIT. insulated Ring Main Unit with load break switch or integrated vacuum circuit breaker

NXPLUS C Single busbar. Maintenance-free for lifetime

Content. Uniswitch. 1. Design philosophy Applications Switchgear construction Cubicle types... 9

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment)

High voltage products PASS M0S 252 kv Innovative solution for transmission substation up to 252 kv

ZX-Family Gas-insulated medium voltage switchgear

SION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG

Switchgear Type 8BT1, up to 24 kv, air-insulated. Medium Voltage Switchgear Catalog HA 26.

CPG.0 Single busbar gas-insulated cubicles

ZX1.5-R. Gas-insulated medium voltage for railway application DISTRIBUTION SOLUTIONS. Gas-insulated medium voltage for railway application ZX1.

3TM Vacuum Contactors

UniPack compact secondary substations (CSS) upto 36 kv For safe, reliable and space saving power distribution solutions

Modular medium-voltage switchgear. NorMax

SION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure

24kV Medium Voltage Switchgear Metal-Enclosed (LSC2A)

Power IT Air Insulated Cubicle Uniswitch

Benefits, typical uses

UniSec Operation and maintenance manual

CATALOGUE. ON Medium Voltage Outdoor Disconnectors

11kV Compact Switchgear. tec - range. Minimum to Zero SF6 Insulation Gas. Outec Controls

GE Consumer & Industrial Power Protection. New. SecoGear kV Metal-clad Switchgear. GE imagination at work

Unified requirements for systems with voltages above 1 kv up to 15 kv

Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A

DMX 3 -I 2500 switch disconnectors

CONTENT. EPE METALCLAD SWITCHGEARS AMS SERIES 12kV AMS METALCLAD SWITCHGEAR 24kV AMS METALCLAD SWITCHGEAR 40.5KV AMS METALCLAD SWITCHGEAR

CGMCOSMOS Fully gas-insulated modular and compact (RMU) system Up to 24 kv

OVERVIEW DESCRIPTION AND CHARACTERISTICS APPARATUS AND TYPES AVAILABLE SWITCHGEAR CHARACTERISTICS INSTRUMENT TRANSFORMERS MEASUREMENT SENSORS

Medium Voltage Distribution FBX. Gas insulated switchgear up to 24 kv. Technical Characteristics Catalogue 2011

8DJ. Maintenance-free for lifetime

Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear

R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A

DPX moulded case circuit breakers

SF6 Gas-Insulated Metal Enclosed Switchgear

SF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS)

Metal Clad Switchgears

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kv, SF 6 -Insulated. Medium-Voltage Switchgear Catalog HA 35.

All rights reserved. Neither this catalogue nor any part of it may be copied using any method or for any purposes. Most studies are legally protected.

UniSec Maintenance solutions

PowerCube type PB series A complete solution for OEMs

Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.

SafeLink The Ultimate RMU. Rex de Bruyn PTMV New Zealand. ABB Ltd - Page 1 ABB

Medium Voltage Metal-Enclosed Switches

Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable

Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated

I B D Q I B D Q O I B D Q O

Key features. DESIGNS: - Conservator type - Hermetically sealed

EMPAC Metal enclosed capacitor bank for wind applications

PowerCube type PB. Pre-assembled modules and enclosures for constructing medium voltage switchgear

Catalog HA Edition up to 24 kv, Air-Insulated, Extendable. Medium-Voltage Switchgear. siemens.com/simosec

Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kv, Gas-Insulated

CGM.3 System. Medium Voltage SF 6 gas-insulated cubicles up to 38 kv according to IEEE and CSA standards

Medium voltage products HD4/R MV gas circuit-breakers for secondary distribution. Power and productivity for a better world TM

SWITCHGEAR FOR SERVICE UP TO 36kV (CABLE AND OVERHEAD CONDUCTOR CONNECTED)

COMPACT SUBSTATION GUIDE

SD, SE, SDE, SCO series Multipole switchgear for rail vehicles: Disconnecting switches, Earthing Switches, Disconnector with Earthing Switches,

Switchgear Type 8DJH 36 for Secondary

Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated

Fuse-links type CEF-S Rated voltages: 6/12 kv 30/40.5 kv Rated currents: 6.3 A 63 A

R-MAG. Vacuum Circuit Breaker with Magnetic Actuator Mechanism

Medium Voltage Metal-Enclosed Switches

Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kv, Gas-Insulated

SF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy

AF series contactors (9 2650)

Product manual. SafeRing/SafePlus 36 kv SF 6. insulated Ring Main Unit and Compact Switchgear

Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated Medium-Voltage Switchgear.

NEXT STEP B) SAFETY :

Gas Insulated Metal-clad Switchgear, HMGS!

Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable

Voltage Rated operating voltage [kv] Rated power frequency withstand voltage [kv] Rated lightning impulse withstand voltage [kv]

CBGS-0. Medium voltage distribution

PT Guna Era Manufaktura. Catalogue GAE TPS \ Medium Voltage Switchgear 12kV - 24kV \ M GAE TPS. Medium Voltage Switchgear 12kV - 24kV

DPX Thermal magnetic and trip-free switches DPX 3 -I 160

Powered by Safety Powell GIS Type G81 Switchgear

High reliability against cyclic and peak current loads / age resistant due to high motor start up currents

TECHNICAL CATALOGUE TK 502/20 EN. ZX2 Gas-insulated medium voltage switchgear

EMC 24 SERIES METAL CLAD SWITCHGEAR. We engineer, we assure. Up to 24 kv - 25 ka With Withdrawable, Air-Insulated, Medium Voltage Distribution Panel

Transcription:

DISTRIBUTION SOLUTIONS GSec Gas-insulated switching and isolating apparatus

GSec is a three-position SF6 gas-insulated switchdisconnector designed for use in medium voltage switchgear for secondary distribution up to 24 kv, 800 A, 25 ka. GSec is used in line ingoing/outgoing panels, in those with circuitbreakers or in a combination with fuses. Typical applications are supplying lines, protecting transformers and use in ring networks. Thanks to its size, GSec can be installed in panels 375 mm in width or wider.

Table of contents 004 007 GSec: its strengths, your benefits 008 009 1. Description 010 021 2. Selection and ordering 022 027 3. Specific product characteristics 028 033 4. Overall dimensions

4 GSEC - GAS-INSULATED SWITCHING AND ISOLATING APPARATUS GSec: its strengths, your benefits Speed up your projects Services and training Safety and protection

DISTRIBUTION SOLUTIONS 5 Productivity Maximizing your output Speed up your projects Reduce number of components to be assembled, connected and interlocked Connection between the switch external earthing contact and earth of panel not needed thanks to metallic partition Capacitive sockets for voltage indicator (VPIS) already integrated in lower bushings Interlock with the door provided together with the apparatus Continuous operation Reduce spares and maintenance Up to 5,000 close-open operations (M2) for line contact Gas tightness guaranteed as Sealed for life for over 30 years Dedicated training for installation and maintenance Specialized ABB Service personnel for installation and maintenance Services and training Programs enabling OEMs to produce their own solution taking advantage of ABB products and know how Technical cooperation / license based on a modular concept of support allowing the OEM to choose in a flexible way the level of added value which better fits its individual needs

6 GSEC - GAS-INSULATED SWITCHING AND ISOLATING APPARATUS GSec: its strengths, your benefits Efficiency Optimizing your investments Affordable Range Panel material and time saving Lower part of enclosure in stainless steel providing metallic segregation, thus eliminating earthing bar need Additional capacitive post insulators not required thanks to capacitive dividers built into lower insulators Complete product, with front cover protecting the actuator and providing visual indications and synoptic Phase distance 230 mm, no need to add insulating dividers between phases

DISTRIBUTION SOLUTIONS 7 Reliability Protecting your assets Maximum level of safety for operators Lower part of enclosure in stainless steel provides Safety and protection metallic segregation between cable and busbar compartments (cable compartment fully earthed) Actuator operating speed independent on the operator Mechanical signaling of the state of apparatus connected straight to the operating shaft Hazardous operations prevented Interlock between the line and earthing operations (separate lever seats) Interlock between earthing switch and door of cable compartment Good performance in harsh environment Long-lasting protection against external factors thanks to upper part in resin, filled with SF6 Reliable in extreme conditions Version tested for low temperature applications available ABB by your side Count on a worldwide presence for any support you may Global availability need

8 GSEC - GAS-INSULATED SWITCHING AND ISOLATING APPARATUS 1. Description GSec is a three-position SF6 gasinsulated switch-disconnector designed for use in medium voltage switchgear for secondary distribution. GSec is used in line ingoing/outgoing panels, in those with circuit-breakers or in a combination with fuses. Typical applications are supplying lines, protecting transformers and use in ring networks. 5 1 6 2 7 3 8 4 9 1 Opening and closing push-buttons 2. Line operating lever seat 3. Earth operating lever seat 4. Voltage indicators (if applicable) 5. Top insulators 6. Enclosure (power part) 7. Housing of the operating mechanism 8. Bottom insulators 9 Mimic diagram Line Open Earth

DISTRIBUTION SOLUTIONS 9 Thanks to its size, GSec can be installed in panels 375 mm in width or wider. The contacts of the three phases can be set to the following positions: LINE OPEN EARTH. The enclosure of the GSec switch-disconnector consists of two half-shells, the top part being made of resin and the bottom part in stainless steel. GSec apparatus is sealed for life in accordance with standard IEC 62271-1, wich means that the gas tightness is guaranteed for more than 30 years. GSec has a wide range of plug&play accessories that can be easily installed and replaced from the front part of the apparatus. The GSec series has been designed and tested in compliance with Standards IEC 62271-1, IEC 62271-102, IEC 62271-105 and IEC 62271-103. The switch-disconnector has also been tested for use at low temperatures and type-approved for naval applications (Germanischer Lloyd register). Safety The stainless steel bottom part of GSec provides metallic segregation between the cable and busbar compartments, ensuring that the two compartments are earthed and therefore making conditions safer for the personnel. Thanks to GSec design, it can be used to create switchgear with PM (Metallic Partitions) classification for the segregation between the busbar and cable compartments. Mechanical interlocks for the safety of the personnel. The door lock prevents the panel door from being opened when the GSec contacts are not in the earthed position. Vice versa, the lock prevents the switch-disconnector from setting to the open or line positions when the door is open. The operating lever with anti-reflex function. Maintenance free The enclosure of GSec is guaranteed sealed for life for more than 30 years, in accordance with IEC 62271-1 standards Up to 5000 mechanical operations without maintenance for GSec with the 1S - Single spring operating mechanism Up to 1000 mechanical operations without maintenance for GSec with the 2S - Double spring operating mechanism Reliability The apparatus can house VPIS voltage indicators in accordance with standard IEC 61958, for voltage detection on the cable side Mechanical signalling of the state of the apparatus connected directly to the operating shaft (Annex A of standard IEC 62271-102) Ease of use Both the GSec operating mechanisms are equipped with springs so the operating speed is independent of the operator. The operating mechanism has two separate seats, one for line operation and one for earthing operation. Customizing A full range of plug & play accessories that can be easily installed on the front part of the operating mechanism allows the apparatus to be adapted to suit many applications. GSec can be used for incoming/outgoing units, in combination with fuses, circuit-breakers with lateral operating mechanisms, current and voltage transformers. Compactness Thanks to the upper resin part it is possible to design small size apparatus and switchgear panel, while still ensuring a high level of insulation. The capacitive sockets for voltage indicator (VPIS) and the cable connections are already integrated in the apparatus bottom insulators. This allows to reduce the number of components of the the panel.

10 GSEC - GAS-INSULATED SWITCHING AND ISOLATING APPARATUS 2. Selection and ordering Types a. GSec/T1 Three-position switch disconnector with 1S - Single spring operating mechanism. Performs opening and closing operations at operating speeds independent of the operator. This type is generally used for creating incoming/ outgoing units. Fig. 1 Standard supply Switch-disconnector 1S - Single spring operating mechanism Door interlock Operating lever Optional accessories Auxiliary contacts Motor for the operating mechanism VPIS voltage indicators Key lock for line seat Key lock for earth seat Coil for preventing lever insertion in earth seat Gas presence indicators Coil for preventing lever insertion in line seat

DISTRIBUTION SOLUTIONS 11 b. GSec/T2 Three-position switch disconnector with 2S - Double spring stored energy operating mechanism. Performs opening and closing operations at operating speeds independent of the operator. This type is generally used for creating incoming/ outgoing units. Fig. 2 Standard supply Switch-disconnector 2S - Double spring operating mechanism Door interlock Operating lever Optional accessories Auxiliary contacts Motor for the operating mechanism VPIS voltage indicators Key lock for line seat Key lock for earth seat Coil for preventing lever insertion in earth seat Shunt opening release Shunt closing release Gas presence indicators

12 GSEC - GAS-INSULATED SWITCHING AND ISOLATING APPARATUS 2. Selection and ordering Types c. GSec/T2F Three-position switch disconnector with 2S - Double spring stored energy operating mechanism. Suitable for use in combination with fuses, e.g. for transformer protection units. Fig. 3 Standard supply Switch-disconnector 2S - Double spring operating mechanism Door interlock Operating lever Fuses blown indicator Tripping system in case of blown fuses Separate earthing switch 5 kap with relative transmission (*) Fuse holder (*) (*) Components supplied loose Optional accessories Auxiliary contacts Motor for the operating mechanism VPIS voltage indicator Fuses blown signalling contact. Key lock for line seat Key lock for earth seat Coil for preventing lever insertion in earth seat Shunt opening release Shunt closing release Gas presence indicators

DISTRIBUTION SOLUTIONS 13 d. GSec/IB Three-position switch disconnector with 1S - Single spring operating mechanism. Suitable for use in panels with circuit-breaker for incoming/outgoing use. Fig. 4 Standard supply Switch-disconnector 1S - Single spring operating mechanism Door interlock Operating lever Separate earthing switch 62.5 kap with relative transmission (*) (*) Components supplied loose Optional accessories Auxiliary contacts Motor for the operating mechanism VPIS voltage indicator Key lock for line seat Key lock for earth seat Coil for preventing lever insertion in earth seat Gas presence indicators Coil for preventing lever insertion in line seat

14 GSEC - GAS-INSULATED SWITCHING AND ISOLATING APPARATUS 2. Selection and ordering Electrical characteristics GSec/T1 and GSec/IB Rated voltage kv 12 17.5 24 Power frequency withstand voltage (50/60 Hz, 1 min) - Line to line and line to earth kv 28 (1) 38 50 - Between open contacts kv 32 45 60 Lightning impulse withstand voltage (BIL 1.2/50 µs) - Line to line and line to earth kv 75 95 125 - Between open contacts kv 85 110 145 Rated frequency Hz 50 / 60 50 / 60 50 / 60 Rated current (40 C) A 800 800 630 Rated short-time withstand current ka 21 (3s) / 25 (2s) 21 (3s) / 25 (2s) 21 (3s) / 25 (2s) Making capacity (peak current) kap 65 54.5 54.5 Making capacity of separate earthing switch (GSec/IB) kap 62.5 62.5 62.5 Breaking capacity - Active load A 800 800 630 - No-load transformers A 16 16 16 - No-load lines A 25 25 25 - No-load cables A 50 50 50 - Ring circuits A 800 800 630 Electrical characteristics GSec/T2 and GSec/T2F Rated voltage kv 12 17.5 24 Power frequency withstand voltage (50/60 Hz, 1 min) - Line to line and line to earth kv 28 (1) 38 50 - Between open contacts kv 32 45 60 Lightning impulse withstand voltage (BIL 1.2/50 µs) - Line to line and line to earth kv 75 95 125 - Between open contacts kv 85 110 145 Rated frequency Hz 50 / 60 50 / 60 50 / 60 Rated current (40 C) A 800 800 630 Rated short-time withstand current ka 21 (3s) / 25 (2s) 21 (3s) / 25 (2s) 21 (3s) / 25 (2s) Making capacity (peak current) kap 41.5 41.5 41.5 Making capacity of separate earthing switch (GSec/T2F) kap 5 5 5 Breaking capacity - Active load A 630 630 630 - No-load transformers A 16 16 16 - No-load lines A 25 25 25 - No-load cables A 50 50 50 - Ring circuits A 630 630 630 (1) Consult ABB for 42 kv version

DISTRIBUTION SOLUTIONS 15 Mechanical and electrical performance Electrical endurance of the line contact class Electrical of the earth contact class E2 - up to 5 makings Mechanical endurance of the line contact with operating mechanism 1S - Single spring Mechanical endurance of the line contact with operating mechanism 2S - Double spring Mechanical endurance of the earth contact class class class E3 - up to 5 makings and 100 rated current interruptions M2 5000 mechanical operations M1 1000 mechanical operations 1S - Single spring M1-2000 mechanical operations 2S - Double spring M0-1000 mechanical operations Other characteristics Distance between the phases mm 230 SF 6 gauge pressure bar 0.48 Weight of SF6 contained kg 0.21 Internal volume l 25 IP protection class IP2X Operating temperature (4) - Min C -25 - Max C +40 (5) Storage temperature - Min C -25 (7) - Max C +40 (5) Maximum installation altitude (6) m 4000 (4) In accordance with standard IEC 62271 (5) Consult ABB for higher values (6) Consider the KA correction factor for the insulating components, in accordance with standard IEC 62271-100 (7) Dedicated version for storage temperature -40 C available. Please ask ABB. Standards used Standard IEC 62271-1 IEC 62271-102 IEC 62271-103 IEC 62271-105 Title High-voltage switchgear and controlgear - Part 1: Common specifications. High-voltage switchgear and controlgear - Part 102: Alternating current disconnectors and earthing switches. High-voltage switchgear and controlgear - Part 103: Switches for rated voltages above 1 kv up to and including 52 kv. High-voltage switchgear and controlgear - Part 105: Alternating current switch-fuse combinations.

16 GSEC - GAS-INSULATED SWITCHING AND ISOLATING APPARATUS 2. Selection and ordering Accessories a. Key locks Allow each of the operation seat of the apparatus (line and earth) to be locked in the open or closed positions. Up to a maximum two keys for the line and two keys for the earth can be used. Three types of keys are available. standard, Ronis and Profalux. The line switching lock of switch-disconnectors with the 2S - Double spring operating mechanism cannot be locked in the closed position. b. Pre-engineering for padlocks Allows padlocks to be housed so as to lock the apparatus in the open, line or earthed positions. Up to three padlocks can be used per apparatus. The maximum diameter of the padlock latch is 6 mm. It is part of the standard equipment for all GSec apparatus. The padlocks are not supplied. Key locks Line Earth 2 free keys - 1 open and 1 closed x Gsec/T1 Gsec/IB 1S operating mechanism - Single spring 1 key free - open x x 1 key free - closed x 2 free keys - 1 open and 1 closed x x 1 key free - open x x 1 key free - closed x x Gsec/T2 Gsec/T2F 2S operating mechanism - Double spring

DISTRIBUTION SOLUTIONS 17 c. Auxiliary contacts Allow the position of the apparatus to be signalled to a remote location. 4 auxiliary contacts are available for the line and 4 for the earth. Each contact can be used as a normally closed (NC) or normally open (NO) circuit. Maximum rating AC DC Voltage [V] 250 250 Current [A] 16 0.3 d. VPIS voltage signalling devices The switch-disconnector can be equipped with VPIS (Voltage Presence Indicating System) voltage signalling devices in accordance with standard IEC 61958. These indicators detect the presence of voltage in the cables connected to the switch-disconnector itself. Phase concordance can also be performed with these devices. Note: the voltage signalling devices do not require the use of additional capacitive dividers and post-insulators. GSec is equipped with capacitive dividers built into the lower insulators.

18 GSEC - GAS-INSULATED SWITCHING AND ISOLATING APPARATUS 2. Selection and ordering Accessories e. Motor for the GSec/T1 and GSec/IB (-MAD) operating mechanism The motor automatically loads the spring of the 1S Single spring operating mechanism for line operations. This allows the switch-disconnector to be operated by remote control. The switch-disconnector s closing (Tclose) and opening (Topen) times are less than 5 seconds (see diagram in Fig. 5). Characteristics DC DC / AC (50-60Hz) Power supply voltage [V] 24 48 110 220 Power consumption at full rate [A] <4 <2 <1 <0.5 Inrush current [A <4 <2 <1 <1 If the motor functions in a faulty way, the switchdisconnector can always be operated in the manual mode with the operating lever. f. Motor for the GSec/T2 and GSec/T2F (-MAD) operating mechanism The motor automatically loads the spring of the 2S Double spring operating mechanism for line operations. Thanks to this motor and the closing and opening releases, the switch-disconnector can be operated by remote control. When the motor is installed, the springs take less than 4 seconds to load, as indicated in the diagram of Fig. 6. Characteristics DC DC / AC (50-60Hz) Power supply voltage [V] 24 48 110 220 Power consumption at full rate [A] <11 <6 <2.5 <1.3 Inrush current [A] <25 <14 <2.5 <2.5 The motor unit is available with the following operating modes: CCO (Charge - Close - Open) in three separate operations: the motor loads the springs of the operating mechanism, then closing and successive opening are obtained in two separate actions performed by push-buttons or releases. CO (Charge and close - Open) in two separate operations: the motor loads the springs of the operating mechanism and the release closes the disconnector. Opening is obtained by means of a separate action. If the motor functions in a faulty way, the disconnector can always be operated in the manual mode with the operating lever.

DISTRIBUTION SOLUTIONS 19 g. Opening shunt release -MBO4 (for GSec/T2 and GSec/T2F) This electromechanical device opens the line contact of the apparatus after the electromagnet has been energized. The total opening time of the switch-disconnector contacts (Topen, see Fig. 6) is 300 ms. h. Closing shunt release -MBC4 (for GSec/T2 and GSec/T2F) This electromechanical device closes the line contact of the apparatus after the electromagnet has been energized. The total closing time of the switch-disconnector contacts (Tclose, see Fig. 6) is 300 ms. Characteristics AC (50-60 Hz) DC Power supply voltage LV [V] 48, 60 24, 48, 60 Power supply voltage HV [V] 110-127, 220-250 110-132, 220-250 Inrush power consumption 200 VA 200 W Characteristics AC (50-60 Hz) DC Power supply voltage LV [V] 48, 60 24, 48, 60 Power supply voltage HV [V] 110-127, 220-250 110-132, 220-250 Inrush power consumption 200 VA 200 W

20 GSEC - GAS-INSULATED SWITCHING AND ISOLATING APPARATUS 2. Selection and ordering Accessories j. Coil to prevent the operating lever insertion in the line seat -RLE5 (for GSec/T1 and GSec/IB) When the coil is not supplied, it prevents the lever from being fitted into the line seat. This accessory is only available for the 1S - Single spring operating mechanism. DC Power supply voltage [V] 24, 30, 48, 60, 110, 220, 240 Rated power [W] 250 Continuous power [W] 5 Inrush time [ms] 150 l. Fuses blown signalling contact When a fuse blows, a kinematic chain activates an indicator that can be seen on the front of the panel (part of the standard equipment for all GSec/T2F devices). A signalling contact can also be requested so as to transmit information about blown fuses by remote control. The contact can be normally closed (NC) or normally open (NO). k. Coil to prevent the operating lever insertion in the earth seat -RLE3 When the coil is not energized, it prevents the lever from being fitted into the earth seat. This accessory is supplied as an alternative to the key lock for the earth switching lock. DC Power supply voltage [V] Rated power [W] 250 Continuous power [W] 5 Inrush time [ms] 150 24, 30, 48, 60, 110, 220, 240 m. Pressure gauge / Density switch The pressure gauge displays the pressure of the gas inside the apparatus and provides an analog indication of the value. Pressure gauge Two types are available: m1 Pressure gauge: the information can only be seen on the front of the panel m2 Pressure gauge with remote signalling: the information is displayed on the front of the panel and can also be transmitted by means of wiring and a terminal box. The alarm value setting is 0.30 bar gauge (1.30 bar absolute), while the blocking value setting is 0.25 bar gauge (1.25 bar absolute). m1

DISTRIBUTION SOLUTIONS 21 Density switch m3 The density switch allows to monitor the gas pressure taking into account also the temperature and provides an alarm that signals when the pressure is low, according the indication in the table below. The state of the signals can also be transmitted by remote control via dedicated wiring and a terminal box. Signal Description Gauge pressure (bar) Ok Correct operating pressure 0.48-0.30 Low Very low Indicates the minimum gas level for which operation of the switch-disconnector is guaranteed The switch-disconnector cannot be operated 0.30-0.25 <0.25 Replacement of the accessories Some of the GSec accessories can be replaced by the customer (c), while others must be replaced in the ABB factory or by authorized Service personnel (S). Accessory a Key locks S b Provision for padlocks S c Auxiliary contacts C d VPIS voltage signalling devices C e f g h j k Motor for GSec/T1 and GSec/IB (-MAD) operation Motor for GSec/T2 and GSec/T2F (-MAD) operation Shunt opening release MBO4 (for GSec/T2 and GSec/T2F) Shunt closing release MBC4 (for GSec/T2 and GSec/T2F) Coil to prevent operating lever from entering line position -RLE5 (for GSec/T1 and GSec/IB) Coil to prevent operating lever from entering the earth position -RLE3 l Fuses blown signalling contact S m Pressure gauge S n Temperature compensated gas density gauge C: customer S: ABB factory or Service center Fitting or Replacement S S C C S S S m2 m3

22 GSEC - GAS-INSULATED SWITCHING AND ISOLATING APPARATUS 3. Specific product characteristics a. Power part The enclosure of the GSec switch-disconnector consists of two half-shells, the top part being made of resin and the bottom part in stainless steel. Smaller sized apparatus can be created thanks to the top part in resin while still guaranteeing a high insulation capacity. The stainless steel part provides metallic segregation between the cable and busbar compartments, ensuring that the cable compartment is fully earthed and therefore making conditions safer for the personnel. GSec can be used to create panels in the PM (Metallic Partitions) class because it provides metallic segregation between the busbar and cable compartments of the panel. The power section of GSec is filled with SF6 gas at 0.48 bar gauge pressure. The gas is used as an interruption and insulation medium. Gas tightness is guaranteed for 30 years, in accordance with the specifications established by standard IEC 62271-1. GSec apparatus is called sealed for life for this reason. The GSec contacts can set to the following positions: LINE: The line contacts are closed OPEN: the apparatus ensures that there is insulation between the cable side and busbar side EARTH: the contacts on the cable side are earthed. A mechanical signal visible from the front of the apparatus indicates the position of the contacts. In accordance with annex A of standard IEC 62271-102, this device is connected straight to the operating shaft. The capacitive sockets for the voltage signalling devices (accessory available on request) are housed inside the three bottom insulators. Moreover, the cable connection can be created on the apparatus without the need for a cross-beam for the insulators. This cuts down on the number of components that need to be installed in the panel.

DISTRIBUTION SOLUTIONS 23 b. Operating mechanism The GSec switch-disconnector can be equipped with two types of operating mechanisms: 1S - Single spring 2S - Double spring. Both operating mechanisms have separate lever seats for the line and earthing operations and both can be equipped with a motor for loading the springs. Even when a motor is installed for loading the springs, it is always possible to operate GSec in the manual mode in case of emergency. 1S - Single spring operating mechanism It opens and closes the GSec line contacts. The energy required for the operation is obtained by compressing a spring with a lever, which closes (or opens) the device once dead center has been passed. The operating speed is independent of the operator. It opens and closes the earth contact at operating speeds independent of the operator. In the case of GSec/IB units, it also closes and opens the separate earthing switch at operating speeds independent of the operator. Manual operation: with the operating lever Automatic or remote controlled operation: with motor 100% 0% time Ts1 Tc Ts1 Tc T close T open Position of the line contact Ts1 Spring load state Spring loading time - manual operation: depends on the operator - motor-driven operating mechanism = 3-4 s. Tc Contact opening or closing time < 0.3 s. Tclose Topen Total closing time < 5 s. (motor driven operating mechanism) Total opening time < 5 s. (motor driven operating mechanism) Fig. 5 - Diagram of 1S - Single spring operating mechanism operation.

24 GSEC - GAS-INSULATED SWITCHING AND ISOLATING APPARATUS 3. Specific product characteristics 2S - Double spring operating mechanism It opens and closes the GSec line contact using the energy stored in two springs: the springs of the operating mechanism are loaded by means of a lever, after which the switch-disconnector is operated by pressing the closing and opening push-buttons. The springs must be reloaded after a closing and opening cycle. The operating speed is independent of the operator. It opens and closes the earth contact at operating speeds independent of the operator. In the case of GSec/T2F units, it closes and opens the separate earthing switch at operating speeds independent of the operator Manual operation: using the operating lever and push-buttons Automatic or remote controlled operation: with a motor and opening and closing coils The contacts of the switch-disconnector also open even if only one fuse blows (GSec/T2F) The load state of the springs is signalled by an indicator on the front of the panel 100% 50% 0% Ts2 Tc Tc time T close T open Position of the line contact Spring load state Ts2 Spring loading time - manual operation: depends on the operator - motor-driven operating mechanism = 3-4 s. Tc Contact opening or closing time < 0.3 s. Tclose Total closing time < 0.3 s. Topen Total opening time < 0.3 s. Fig. 6 - Diagram of 2S - Double spring operating mechanism operation.

DISTRIBUTION SOLUTIONS 25 c. Front cover 7 8 2 5 1. Lever seat line operating 2. Lever seat earth operating 3 Mimic diagram 4. Operating mechanism push-buttons 5. Voltage signalling device 6. Springs loaded indicator (only for the 2S - Double spring operating mechanism) 7. Blown fuses indicator (only for GSec/T2F) 8. Pre-engineering for padlocks 4 3 1 6 d. Mechanical interlocks GSec has been designed to ensure maximum safety for the operators. It therefore features the following interlocks: Interlock between the line and earthing operations obtained by means of separate lever seats Panel door interlock thanks to the door lock device: the cable compartment can only be accessed when the earthing switch is closed. Moreover, the earthing switch cannot be opened or the panel be put into service unless the door has been closed. The cables can still be tested with the door open by removing the front guard from the apparatus. Interlock for the push-buttons of the 2S - Double spring operating mechanism: these push-buttons cannot be operated when the operating lever is connected. Motor interlock: if the operating mechanism is a motor operator, operation of the motor is disabled when the operating lever is in the line lock.

26 GSEC - GAS-INSULATED SWITCHING AND ISOLATING APPARATUS 3. Specific product characteristics GSec has been tested with ABB CEF fuses for transformer protection to IEC 60282-1/ DIN 43625 standards. Three fuses (one for each phase) for transformer protection can be connected in series with the switch-disconnector. Selection of the fuses according to the voltage and power of the transformer, must be made in conformity with the data indicated in the table below. Transformer protection and choice of fuses When the isolators are used to control and protect transformers, they are fitted with a particular type of current-limiting fuses which guarantee selectivity with other protection devices and can take the high transformer connection currents without deteriorating. In this case, protection against overcurrents on the medium voltage side of the transformer is not indispensable since this task is carried out by the protection provided on the low voltage side. Protection on the medium voltage side can be entrusted just to the fuse, which must be chosen taking into account the no-load connection current since this can be the same or 10 times more that the rated current depending on the power of the transformer and the type of laminations used (hot-rolled or grain oriented). Maximum inrush current occurs when the circuitbreaker closes at peak voltage. A further result to be guaranteed is protection against faults in the low voltage winding and in the part of the connection between this and the circuit-breaker on the secondary, thus avoiding the use of fuses with rated current which is too high, in order to ensure tripping within a short time even under these fault conditions. Rapid calculation of the short-circuit current at the secondary terminals of the transformer and on the supply side of the circuit-breaker on the secondary, if installed at a significant distance, allows the tripping time to be verified on the fuse blowing curve. The usage table given below takes both the required conditions into account, i.e. rated current high enough to prevent untimely fuse blowing during the no-load connection stage and, in any case, of a value which guarantees protection of the machine against faults on the low voltage side. Choice of fuses for transformer protection Rated voltage of the transformer [kv] Transformer power rating [kva] 25 50 75 100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 Rated current of fuse I N [A] 3 16 25 25 40 40 50 63 80 100 125 160 (1) 5 10 16 25 25 25 40 40 50 63 80 100 125 160 (1) 6 6 16 16 25 25 25 40 40 50 63 80 100 125 160 (1) Rated voltage of fuses U N [kv] 3.6/7.2 10 6 10 16 16 16 20 20 25 31,5 40 50 63 80 100 125 160 (1) 12 12 6 6 10 16 16 16 20 20 25 40 40 50 63 80 100 125 160 (1) 15 6 6 10 10 16 16 16 20 20 25 40 40 50 63 80 100 125 (1) 17,5 20 6 6 6 10 10 16 16 16 20 20 25 31,5 40 50 63 80 100 (1) 24 24 6 6 6 6 10 10 16 16 16 20 20 25 40 40 50 63 80 100 (1) (1) SIBA fuse

DISTRIBUTION SOLUTIONS 27 The values in the table were calculated in accordance with Standards IEC 60787 and IEC 62271-105. The transformer is assumed to function in the following operating conditions: maximum long-time overload: 150% magnetizing inrush current: 12 x In for 100 ms transformer short-circuit voltage in accordance with Standard IEC 60076-5 operational ambient conditions of fuses: standard. The table gives the rated current of the fuses with reference to the supply voltage and transformer characteristics. The choice of fuse must be re-calculated if different specifications are concerned. Please consult ABB if fuses other than ABB CEF and SIBA SSK are used. Graph for establishing correction factor Ka depending on the altitude ka 1,50 1,40 1,30 1,20 m (H 1000)/8150 Ka = e m = 1 1,10 Altitude The insulating properties of the air diminish as the altitude increases. This must be taken into account with regard to the external insulation of the equipment. The phenomenon must always be considered when the insulating components of equipment that must be installed at more than 1000 m above sea level are designed. In this case, one must consider a correction coefficient that can be taken from the graph on the following page, created in accordance with the indications provided by Standards IEC 62271-1. The example below gives a clear interpretation of the indications described above. 1,00 1000 1500 2000 2500 3000 3500 4000H Example Installation altitude 2000 m Use at 12 kv rated voltage Power frequency withstand voltage 28 kv rms Impulse withstand voltage 75 kvp Ka factor found from the graph = 1.13. In view of the aforementioned parameters, the equipment must withstand (during tests at zero altitude, i.e. at sea level): power frequency withstand voltage: 28 x 1.13 = 31.6 kvrms impulse withstand voltage equal to: 75 x 1.13 = 84.7 kvp. In this case, equipment with 17.5 kv rated voltage characterized by 38 kvrms insulation levels at power-frequency with 95 kvp impulse withstand voltage is required for installations at an altitude of 2000 m above sea level with 12 kv operating voltage. H = altitude in meters; m = value with reference to power frequency and atmospheric impulse withstand and line-to-line voltages.

28 GSEC - GAS-INSULATED SWITCHING AND ISOLATING APPARATUS 4. Overall dimensions GSec/T1 TN 2RDA017740A0001 Type 12.08.25 17.08.20 24.06.16 24.06.20 Weight [kg] 70 222 230 230 A 36 37,5 141,5 141,5 37,5 M10x25 = = 66 430 32 35 22 95,5 138 A 165 138 138,5 694 352,5 341,5 192 448 9 (4x) Supporting Plane A-A M10x25 Detail B 385,4 (in-out) 26 134 237 531 370 943,5 720 167 167 M10 334 5 7 (8x) Door Interlocking. 10mm: Stroke necessary to release the system. 32mm: Extension necessary to release the system. 10 Detail C

DISTRIBUTION SOLUTIONS 29 GSec/T2 TN 2RDA017740A0001 Type 24.06.16 Weight [kg] 70 222 230 230 A 36 37,5 141,5 141,5 37,5 M10x25 = = 66 430 32 35 22 95,5 138 A 165 138 138,5 694 352,5 341,5 192 448 9 (4x) Supporting Plane A-A M10x25 Detail B 385,4 (in-out) 26 134 237 531 370 943,5 720 167 167 M10 334 5 7 (8x) Door Interlocking. 10mm: Stroke necessary to release the system. 32mm: Extension necessary to release the system. 10 Detail C

30 GSEC - GAS-INSULATED SWITCHING AND ISOLATING APPARATUS 4. Overall dimensions GSec/T2F TN 2RDA017731A0001 Type 12.08.25 17.08.20 24.06.16 24.06.20 Weight [kg] 70 65 222 230 230 A 36 37,5 141,5 141,5 37,5 370 = = 192 430 32 35 22 9 (4x) A 138 165 138 138,5 694 352,5 341,5 448 519 498 Supporting Plane 71 A-A 15 132 209 Fuse Holder Door Interlocking. 134 237 502 555 370 167 167 334 Detail B 7 (8x) 5 10mm: Stroke necessary to release the system. 32mm: Extension necessary to release the system. 10 943,5 720 M10 Detail C

DISTRIBUTION SOLUTIONS 31 840 150 150 320 581 272,5 180.5 180,5 238 238 238

32 GSEC - GAS-INSULATED SWITCHING AND ISOLATING APPARATUS 4. Overall dimensions GSec/IB TN 2RDA017728A0001 Type 12.08.25 17.08.20 24.06.16 24.06.20 Weight [kg] 70 222 A 230 230 36 37,5 141,5 141,5 M10x25 37,5 370 = = 65 430 32 95,5 A 138 165 138 138,5 192 448 A-A M10x25 26 134 237 531 35 22,3 694 352,5 341,5 9 (4x) 167 7 (8x) 370 334 Detail B 10 Supporting Plane 385,4 (In-Out) 5 Door Interlocking. 10mm: Stroke necessary to release the system. 32mm: Extension necessary to release the system. 944 720 167 32 Detail C

DISTRIBUTION SOLUTIONS 33 = = Fixing points on the sheet metal part needs 4 holes 5,2 170 233 M6x10(2x for contact) 12,4 140 735,7 249 61 308,5 25 200 9 (6x) 770 100 544.5

34 GSEC - GAS-INSULATED SWITCHING AND ISOLATING APPARATUS Notes

For more information please contact: More product information: abb.com/mediumvoltage Your contact center: abb.com/contactcenters More service information: abb.com/service Data and illustration are not binding. We reserve the right to make changes in the course of technical development. Copyright 2017 ABB. All rights reserved. 1VCP000470 - Rev. D, en - Technical catalogue - 2018.01 - (GSec) (gs)