INSTALLATION INSTRUCTIONS Model FPT 50

Similar documents
Instruction Bulletin. Jockey Pump Controller

DC400 Dispensing Cutoff System

- Wiring Brochure Zone Manager 335

- Wiring Brochure Zone Manager 336

A419ABG-3C Electronic Temperature Control

- Wiring Brochure Mixing Expansion Module 440

Operations Manual. Zero Speed Switch Sensor Model ZS09P

2904 Power Supply Installation Instructions I-EA00041

Nuheat WEATHER-READY HEAT TRACE PIPE FREEZE PROTECTION SYSTEM. Self-Regulating Heating Cable Installation Guide. UV Resistant Polyolefin Outer Jacket

Installation and Operating Manual

A419 Series Electronic Temperature Controls with NEMA 1 or NEMA 4X Watertight Enclosures

COOKSON OWNER S MANUAL

Product Instructions. Mixing Station. Features. Specifications. Materials

FM200 FLOW/NO-FLOW MONITOR INSTALLATION AND TECHNICAL MANUAL 120 VAC MODEL 6/1/2017

ACCESSORY KIT INSTALLATION INSTRUCTIONS

MAXIGARD A2000 SPEED SWITCH. Introduction

Series BFM Bulk Flow Monitor 1A FUSE RED LED RELAY. Part Number BFM-1 BFM-2 BFM-3 BFS-1

Feed Scale Installation & Operator s Instruction Manual

Utility Distribution Systems Installation, Operation, and Maintenance Manual

- Wiring Brochure tekmarnet 4 Thermostat 545

Application Engineering

TMS Series MP46x Flex Probes* Installation Instructions

SYMBOL LEGEND DANGER WARNING NOTE THIS INDICATES DANGER TO THE LIFE AND HEALTH OF THE USER IS APPROPRIATE PRECAUTIONS ARE NOT TAKEN

MP461SC Flex Probes* Installation Instructions

Matrix AP 400V 690V INSTALLATION GUIDE. Quick Reference. ❶ How to Install Pages 6 20 ❷ Startup/Troubleshooting Pages WARNING

50 AMP TRANSFER RELAY DELAY - DUAL INPUT GENSET

GRUNDFOS PRODUCT GUIDE. Redi-Flo3 and CU 300. Environmental Pumps 60Hz

Maintenance Instructions & Parts List

F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide

CIVACON GROUND VERIFICATION RACK MONITOR SYSTEM and ASSOCIATED EQUIPMENT

Continuing Education Course #206 Introduction to Designing Machine Control Systems Part 2

Sentinel Field Satellite Controller

Model LA 4100 Time Delay OFF Controller

INSTALLATION INSTRUCTIONS FOR Owner's Copy FILTERED AND REGULATED POWER SUPPLY VOLTS DC INPUT: Hz.

Analog Condensate Monitor Instruction & Maintenance Manual

Materials. Contact Ratings. Conduit Entrances

Model APS 3B Snow and Ice Melting Control

4" Motors and Controls

Eaton LifeSense Wired System Quick Setup Guide

- Wiring Brochure Universal Reset Module 422

Installation Instructions

BOILER BLOWDOWN CONDUCTIVITY CONTROLLER (CONTINUOUS METHOD)

INSTRUCTION MANUAL MODEL # YEAR WARRANTY KUSSMAUL ELECTRONICS CO., INC.

Product Instructions. Diverting Valve. Valve Cross Section. Features. Specifications. Operations

LTX RF LEVEL SENSOR. Instruction Manual

U00X ULTRASONIC LEVEL SWITCH. Ultrasonic Liquid Level Switches INSTALLATION AND OPERATIONS MANUAL. For Models: U002, U003 & U004

Installation Instructions Mineral Insulated (M.I.)

TECHNICAL BROCHURE BSPDDRIVE. Aquavar SPD (Single Pump Drive) SIMPLEX VARIABLE SPEED PUMP CONTROLLER FOR SUBMERSIBLE AND CENTRIFUGAL PUMPS

Installation and Maintenance Manual

UNDERGROUND SERVICES - SECONDARY

Digital II Pressure Control Module. Model IN64235 August Installation Instructions. Applicable addition manuals:

INSTALLATION AND OPERATING INSTRUCTIONS

CONTROL FEATURES AVAILABLE OPTIONS

Tooling Assistance Center

P66 Series Electronic Fan Speed Controls

Installation & Operation Manual

Model LA 4300 Time Delay OFF Controller

SUBMERSIBLE TRANSDUCER CABLE REPAIR

M9206-Bxx-2S Series On/Off Electric Spring Return Actuators

General Precautions. Personnel Precautions

Selection Guide Motor Control Device Solutions

Instructions for Installation, Operation, Care and Maintenance

UNIVERSAL PUMP HANGER INSTALLATION INSTRUCTIONS

INSTALLATION MANUAL & OPERATING INSTRUCTIONS

Heavy Duty Electric Hydraulic Pumps PN and

CSR COMPACT FUSED INTERLOCKED ARKTITE RECEPTACLE - 30 & 60 AMP Installation & Maintenance Information IF 1440

M9106-AGx-2N0x Series Electric Non-spring Return Actuators

SYMBOL LEGEND DANGER WARNING NOTE THIS INDICATES DANGER TO THE LIFE AND HEALTH OF THE USER IS APPROPRIATE PRECAUTIONS ARE NOT TAKEN

Installation Instructions Electric Heaters 5 20 kw

User s Manual. Automatic Switch-Mode Battery Charger

Grundfos Variable Speed GRUNDFOS INSTRUCTIONS. Installation and Operation

Trouble Shooting. Symptom Possible Cause Solution Power switch ON but switch Light is Off. Main power to unit Off. Switch light defective.

SERVICE MANUAL (INTERNATIONAL)

Application Engineering

SmartBob AO. BinMaster: Division of Garner Industries 7201 N. 98th St., Lincoln, NE

General Description. Product Specification. Document Digital Temperature Interlock

P445 Series Electronic Lube Oil Control

Mizer Single Pump and Starter Box

MAx1-720x Two Position Series MFx Floating Series MSx Proportional Series

Quick Start Guide TS 910

70 Series 8700 Coupler 2-pc Hub & Shaft Three Phase Brake Instructions IP43 & IP56 (NEMA 2 & 4) Housing

A1500, A1500NF SPEED SWITCH SINGLE SET POINT - SELF CONTAINED. Introduction

PRODUCT INFORMATION BULLETIN

Cleaning Systems Inc. 2 P Rev:03

GLYCOL FEED SYSTEMS OPERATION & MAINTENANCE MANUAL

6. Electrical. 7. Settings. 8. Quick

SERIES VAC Microprocessor Based Direct Spark Ignition Control FEATURES DESCRIPTION APPLICATIONS THE TOTAL SOLUTION FOR GAS IGNITION CONTROL

TS Series TS Series

B21 Series BASOTROL Gas Valve

CVR-625. Compact Vibrating Rod Instruction Manual

Installation and Operation

Jandy Pro Series WaterColors LED Lights Underwater Large and Small Light

ClipperCreek, Inc. Innovative Infrastructure for Electric and Hybrid Vehicles. User s Manual. Model ACS

Installation or Inspection Checklist

TE-6100 Series Temperature Sensors and Completed Sensor/Hardware Assemblies

DuraMAC LIGHT COMMERCIAL & IRRIGATION WATER PRESSURE BOOSTER SYSTEM INSTALLATION INSTRUCTIONS

Sentinel Field Satellite Controller Metal Pedestal, Plastic Pedestal and Wall Mount Models Installation Instructions

Potter Electric Signal Company, LLC St. Louis, MO Tech Support: / Customer Service:

Installation Instructions

Manual PN: Rev 01. Otterbine Barebo Inc. Fractional Series 50Hz Installation Manual

Transcription:

INSTALLATION INSTRUCTIONS Model FPT 50 Electronic Water Level Control Systems WATERLINE CONTROLS is the optimum choice for any situation requiring precise control of a water level. It is ideal for automatically maintaining the correct water level in cooling towers, storage tanks, or process water applications. WATERLINE CONTROLS FPT 50 models achieve control and maintain correct water levels using electronics and a microprocessor to provide signals that open/close valves and remotely signal Fire Panel and/or other control/recording devices. WATERLINE CONTROLS uses corrosion/plating resistant sensor probes that are not prone to degradation. IMPORTANT SAFETY INSTRUCTIONS 1. Call the factory with any questions. 1-888-905-1892 or write to: System Dynamics, P.O. BOX 12544, Scottsdale, AZ 85260 2. Read and follow all instructions. 3. Disconnect all power before opening the internal cover/s or making any connections to the unit. 4. Do not install in locations where sprinklers or other watering devices will allow water to impinge on the unit. 5. Sensor wires must be continuous and not spliced. Call factory if there is a need to be spliced. 6. Make sure the unit is connected properly to earth ground. 7. Only qualified personnel should install this unit or replace the "replaceable" parts. 8. Only factory supplied parts should be used whenever a replaceable part is needed. 9. The manufacture will not be liable for any injury or damage that may arise from the misuse of this unit or from failure to follow all of these instructions. 10. Save these instructions and provide them to the end user. 11. This unit shall not be used in any "safety critical" application or where the failure of any function or component may cause death or personal injury. 11. Ne pas utilisez cet élément quand les blessures oú la mort peuvent les présenter. 12. Use copper (CU) wire only for all connections. MANUAL FPT 50 080118 1

The Waterline Controls panel is NEMA 4X rated for indoor or outdoor installation. The panel is powered by 110 VAC. The power relay(s) included are switched by the microprocessor and may be used to control valves or solenoids directly (120 VAC @ 40A max.) The power relays can also be used as pilot relays to contactors for larger devices such as motors or three-phase circuits. POWER ALARM FILL 1 HIGH ALARM LOW ALARM A low voltage dry contact set is provided for each output function of the model. Included in all models is a dry contact set for the fault condition (defined in next paragraph). The dry contacts are (FORM A) SPST relays rated 60 VAC/DC @ 0.5 A. These used for remote monitoring and indication to or other remote recording devices. The power on indicator for the unit is a solid green POWER/ALARM LED. Upon fault condition the POWER/ALARM LED will either flash red at one second intervals or display red continuously, indicating a system alarm. The POWER/ALARM LED will flash red when the microprocessor detects out of sequence submersion of the water level sensor. The POWER/ALARM LED will light red continuously for one minute, then reset, when the "Fill" relay has been continuously switched on for 6 hours. The other LEDs along the top of the unit correspond to each output function of the model. These LED are lit solid when the relay contacts are closed and remain lit until the water level changes. Upon change in the water level, the microprocessor provides the necessary control changes to the power relay(s). FROM POWER SUPPLY: COLORED 110 VAC NEUTRAL 110 VAC LINE WIRE PAIR Sensor Low Voltage Raceway Sensor Wire & Dry Contact Low Voltage Raceway Brown Pair COMMON SWITCH LOW ALARM TESTING Green Pair COMMON BUZZER HIGH ALARM WHITE BLK (Bottom faceplate removed in illustration) PRESS TO TEST WHITE Red Pair COMMON FILL VALVE WIRE 2 (LOAD) VALVE WIRE 1 (LOAD) IN OUT COM POWER RELAY DRY CONTACT SPDT RELAY(S) FORM C: 120V @ 40 A max. Sensor multiconductor wire Fire wires 110 VAC Line to Device(s) Green (GND) Black White *Use separate earth grounded metal electrical conduit to house low-voltage sensor wires and high-voltage wires. 2

SENSOR ASSEMBLY INSTALLATION (Sensor illustration for FPT 50) Figure 2 The Waterline Controls FPT 50 control panel should be mounted in a convenient location where water spray will not impinge upon the unit and at a height above the tank overflow level to prevent water from feeding in to the sensor wire conduit. The unit and the input/ output cabling must be securely attached to the mounting surface. Secure the probe assembly to a suitable mounting surface using one of the sensor mounting options (Pg.5). Be careful to ensure that the top portion of the assembly is not in contact with the water. The sensor probe assembly is supplied with a multi-conductor sensor cable pre-attached. Wall Sensor Wire (do not splice without using ) SENSOR 5/8" HOLE (2) 3 SLIP COUPLER Mounting Bracket 3 PVC Pipe "U" Bolts U2OP5-9 HIGH ALARM (Green) powers. If the depth of the probes need to be seen while the sensor assembly is installed, mark the sensor probe levels on the outside of the pipe or tank with a permanent marker. Sequence of Operation (SOO): Three function - shortest to longest rod length 1) When water level contacts GREEN rod, HIGH ALARM LED status indicator, Reference dry contact, and power relay are active. When water level falls below GREEN rod, HIGH ALARM LED status indicator, dry contact, and power relay are inactive. 1inch 2) RED AND WHITE rods are a differential function. When water level falls below WHITE rod, FILL LED status indicator, power relay, and dry contact are active. When water level contacts RED rod, FILL LED status indicator, power relay, and dry contact are inactive and remain inactive until water level falls below the WHITE rod. 3) Function 2 is active. When water level contacts BROWN rod, LOW ALARM LED status indicator, dry contact, and power relay are inactive. When water level falls below BROWN rod, LOW ALARM LED status indicator, dry contact, and power relay are active. Black Brown White Red Green FILL OFF (Red) FILL ON (White) LOW ALARM (Brown) WIRE COLOR & COLOR OF PROBES CORRESPOND PROBE LAYOUT (FPT 50) Sensor can be removed from housing PROBE WIRE SHIELD - Connect to Black sensor wire input (ground) Ground LA FILL START FILL STOP HA LENGTH 17" 17" 16 3/8" 14 7/8" 10 3/8" TE: Number/ color/ function/ length of probes differ by model 3

TEST INSTRUCTIONS To initiate the test, 1. Press the "PRESS TO TEST" push button momentarily. The yelllow LED will light and remain on until the "test function" is complete. 2. The controller automatically sequences through the functions and concludes with three red flashes of the Power/Alarm LED. TE: This test will take approximately 2 minutes and cannot be interrupted. It is intended to test the function of the dry contacts and power relays with devices connected. PARTS SUPPLIED REPLACABLE PART NUMBERS 1 - Waterline Controls Panel Control Panel...FPT 50 1 - Stainless steel probe assembly w/ 50 ft. multi-conductor wire Power Supply...PS-110 1 - Mounting kit Sensor (3 Plug)...Sensor 3050 3 - Power relays (Number of relays is a function of model) Power relay...pg8p Troubleshooting Guide LOW VOLTAGE RACEWAY FIRE PANEL DRY CONTACTS DEFINITIONS LOW ALARM: The water level is approaching the unsafe level. FILL: Make up on. The system is calling for water to be added. HIGH ALARM: The water level is approaching the maximum allowable level of the environment. DRY-CONTACTS The dry contact sets included in the Waterline Controls panel can be used as an aid to remotely signal the Fire Panel of the current status of the controller s output functions. There is a dry contact set corresponding to each controller output function. The dry contact changes from an open circuit to a closed circuit when the power relay is activated. (e.g. FPT 50 functions: LOW ALARM, FILL, HIGH ALARM). Other Waterline Controls FPT models may have a different number of dry contacts. The dry contacts are rated at 60 VAC/DC @ 0.5 Amps. A fault dry contact set is present on all models. This can be used as an aid to remotely signal the operator when 1) the system has lost power, 2) microprocessor detects out of sequence of submersion of the water level sensor, or 3) the fill function has been active for six hours. INSTALLATION CAUTIONS VFDs: The output of variable-frequency drives (VFDs) produce large, rapid voltage swings - generating significant electrical noise, or electromagnetic interference*. It is required to maintain as much distance as possible from VFD panels, wires, and devices when installing the Waterline Controls panel, sensor probe, and sensor probe cable in order to ensure proper function of the system - At least 15 feet from VFD panels, wires, and devices or behind an earth grounded metal barrier (e.g. earth grounded stainless steel cooling tower). Sensor wires should be housed in earth grounded metal electrical conduit separate from the earth grounded metal electrical conduit housing high voltage wires. Sensor Wire: Coiling excess wire from the sensor can gather ambient electronic noise like an antenna. It is recommended to use as short of a sensor wire as possible, leaving only enough excess wire to be able to remove the sensor from the housing should service be needed. It is also recommended to T run the sensor wire parallel to VFD control wires, ensuring electromagnetic interference is not picked up from the control wires. It is okay to cross these wires perpendicularly. * Information from article: Frank J. Bartos, P.E., Control Engineering 12/01/2009, Electromagnetic Interference: What Drive Users Need to Know 1 2 3 4 5 6 7 8 FAULT RED WHITE GREEN BROWN BLUE SENSOR PROBE WIRES Blue T USED Blue T USED Brown LOW ALARM Brown LOW ALARM Green HIGH ALARM Green HIGH ALARM { FAULT, BROWN, WHITE, RED, & GREEN Cable shield: Connect black sensor wire and cable shield to sensor input terminal. Example Electrical Illutsration: Red - FILL dry-contact wire pair Active dry-contact = closed switch Inactive dry-contact = open switch MANUAL FPT 50 080118 4

SENSOR MOUNTING OPTIONS A WALL MOUNT B EXTERIOR MOUNT C INSIDE TANK- BULKHEAD FITTING Riser pipe cut as needed PARTS 3 Bulkhead 2-3 SLpx NPT Coupler PARTS ILUDED Stainless steel mounting bracket 2-4 U-bolts 18 pipe 3 Coupler PARTS 2-1 Union Ball Valves 1-3 x 3 x 1 Tee 1-3 x 1 90 Elbow 1-18 Riser pipe with 3 Coupler SIDE WALL MOUNT D FLANGE E TOP OF TANK ADJUSTABLE MOUNTING SLEEVE FOR 4 3" Pipe Clamp used as adjustment sleeve TANK WALL TOP TANK WALL TOP TANK WALL TANK WALL 4" NTP

SENSOR EXTENSION ROD INSTALLATION ILLUSTRATION: Rods D and E have been extended. Rods A, B, and C haven t been extended. 3" Slip Style Coupler 3" slip plug with gasket fits into a 3" Slip style fitting. 3" Bulkhead Fitting Reference A Rod spacer disc B Rod spacer disc C *TES: Extension Rods are meant to extend the standard length of sensor probes to greater depths. Waterline Controllers require a specific sensor rod orientation that is tested by the controller on a continuous basis. The required orientation is Black-Blue-Brown-White-Red-Green (Colors determined by controller model, ie. the FPT 50 only has 5 colors, Black-Brown-White-Red-Green. These colors stay in the same order without the other colors. D E Jam Nut Coupling Nut Jam Nut Gel- Filled Heat Shrink The 2 longest rods may be the same length. ie. FPT 50, Brown & Black may be equal length. Cut to desired length Always use 2 wrenches when tightening these nuts. 1) Cut extension rods to desired lengths* (See TES above) & trim colored jacketing to expose rod tips 1-2" 2) Slide rod spacer disc on through all sensor rods, above all threads 3) Thread jam nut all the way onto threaded end of each sensor rod desired to be extended 4) Thread Coupling nut half way onto threaded end of each sensor rod 5) Thread jam nut all the way onto threaded end of each extension rod being used 6) Slide gel-filled heat shrink onto extension rod, past the jam nut 7) Thread each extension rod into the coupling nut that is extending beyond its color Waterline Controls corresponding sensor rod 8) Ensure extended rod lengths meet the length differential requirements* (See TES above) 9) Tighten jam nuts on each sensor rod using two wrenches, ensuring the coupling nut is bound TITLE: Tank Installation for Sensors over 17" by the two jam nuts WATERLINE CONTROLS 10) Slide gel-filled heat shrink above the coupling nut & jam nuts & tighten/shrink with heat gun SCALE: NTS 51216 P.O. Box 12544 Scottsdale, Arizona 85260 Toll Free: 888-905-1892 Fax: 480-629-8223 DATE: 4-2-18 DWN BY Pamela Peterson APPVD BY Bill Seneff DWG. EXT ROD INSTALLATION