Air Conditioners Technical Data O u t d o o r u n i t E E D E N 2-0 0 RXG-K
Outdoor Unit Pair application RXG-K TABLE OF CONTENTS RXG-K Features............................................................. 2 2 Specifications....................................................... 3 Nominal Capacity And Nominal Input................................ 3 Technical Specifications............................................. 5 Electrical Specifications.............................................. 6 3 Electrical data....................................................... 7 Electrical Data........................................................ 7 4 Options.............................................................. 9 Options............................................................... 9 5 Capacity tables.................................................... 0 Cooling/Heating Capacity Tables................................... 0 6 Dimensional drawings............................................ 6 Dimensional Drawings.............................................. 6 7 Centre of gravity................................................... 7 Centre of Gravity.................................................... 7 8 Piping diagrams................................................... 8 Piping Diagrams.................................................... 8 9 Wiring diagrams................................................... 9 Wiring Diagrams - Single Phase................................... 9 0 Sound data......................................................... 20 Sound Pressure Spectrum.......................................... 20 Operation range................................................... 22 Operation Range.................................................... 22 Split - Sky Air Outdoor Unit
k i ni l p- pr ao t o i dr - l ti pau Outdoor Unit Pair application RXG-K Features c S U K G X PS O R Outdoor units for pair application Energy efficient units: full range A class energy labels Outdoor unit silent operation: "silent" button on the remote control lowers the operation sound of the outdoor unit by 3dBA to ensure a quiet environment for the neighbourhood. Outdoor units are fitted with a swing compressor, renowned for its low noise and high energy efficiency Energy saving during standby mode: reduces current consumption by about 80% when operating In standby. If no people are detected for more than 20 minutes, the system will automatically switch to the current-saving mode. Daikin outdoor units are neat, sturdy and can easily be mounted on a roof or terrace or simply placed against an outside wall 2 Split - Sky Air Outdoor Unit
2 Specifications Outdoor Unit Pair application RXG-K 2- Nominal Capacity And Nominal Input FTXG25JA / RXG25K FTXG35JA / RXG35K FTXG50JA / RXG50K Cooling capacity Min. kw.3.4.7 Btu/h 4,400 4,800 5,800 kcal/h,20,200,460 Nom. kw 2.5 (3) 3.5 (3) 5.0 (3) Btu/h 8,500 (3),900 (3) 7,00 (3) kcal/h 2,50 (3) 3,00 (3) 4,300 (3) Max. kw 3.0 3.8 5.3 Btu/h 0,200 3,000 8,00 kcal/h 2,580 3,270 4,560 Heating capacity Min. kw.3.4.7 Btu/h 4,400 4,800 5,800 kcal/h,20,200,460 Nom. kw 3.4 (4) 4.0 (4) 5.8 (4) Btu/h,600 (4) 3,600 (4) 9,800 (4) kcal/h 2,920 (4) 3,440 (4) 4,990 (4) Max. kw 4.5 5.0 6.5 Btu/h 5,400 7,00 22,200 kcal/h 3,870 4,300 5,590 Power input Cooling Min. kw 0.350 0.360 0.450 Nom. kw 0.560 0.890.560 Max. kw 0.820.220.880 Heating Min. kw 0.320 0.520 Nom. kw 0.780 0.990.600 Max. kw.320.500 2.500 EER 4.46 3.93 3.2 COP 4.36 4.04 3.63 Annual energy consumption kwh 280 445 780 Energy label Cooling A Heating A Piping connections Liquid OD mm 6.35 Gas OD mm 9.52 2.7 Drain OD mm 6 or 8 8.0 Heat insulation Both liquid and gas pipes Notes () Energy label: scale from A (most efficient) to G (less efficient) (2) Annual energy consumption: based on average use of 500 running hours per year at full load (nominal conditions) (3) Cooling: indoor temp. 27ºCDB, 9.0ºCWB; outdoor temp. 35ºCDB, 24ºCWB; equivalent piping length: 5m (4) Heating: indoor temp. 20ºCDB; outdoor temp. 7ºCDB, 6ºCWB; equivalent refrigerant piping: 5m (5) When connected with multi-system outdoor unit, refer to the specifications of the multi outdoor unit to be connected. 3 2 2-2 Nominal Capacity And Nominal Input FTXG25JW / RXG25K FTXG35JW / RXG35K FTXG50JW / RXG50K Cooling capacity Min. kw.3.4.7 Btu/h 4,400 4,800 5,800 kcal/h,20,200,460 Nom. kw 2.5 (3) 3.5 (3) 5.0 (3) Btu/h 8,500 (3),900 (3) 7,00 (3) kcal/h 2,50 (3) 3,00 (3) 4,300 (3) Max. kw 3.0 3.8 5.3 Btu/h 0,200 3,000 8,00 kcal/h 2,580 3,270 4,560.0 Split - Sky Air Outdoor Unit 3
2 Specifications Outdoor Unit Pair application RXG-K 2 2-2 Nominal Capacity And Nominal Input FTXG25JW / RXG25K FTXG35JW / RXG35K FTXG50JW / RXG50K Heating capacity Min. kw.3.4.7 Btu/h 4,400 4,800 5,800 kcal/h,20,200,460 Nom. kw 3.4 (4) 4.0 (4) 5.8 (4) Btu/h,600 (4) 3,600 (4) 9,800 (4) kcal/h 2,920 (4) 3,440 (4) 4,990 (4) Max. kw 4.5 5.0 6.5 Btu/h 5,400 7,00 22,200 kcal/h 3,870 4,300 5,590 Power input Cooling Min. kw 0.350 0.360 0.450 Nom. kw 0.560 0.890.560 Max. kw 0.820.220.880 Heating Min. kw 0.320 0.520 Nom. kw 0.780 0.990.600 Max. kw.320.500 2.500 EER 4.46 3.93 3.2 COP 4.36 4.04 3.63 Annual energy consumption kwh 280 445 780 Energy label Cooling A Heating A Piping connections Liquid OD mm 6.35 Gas OD mm 9.5 2.7 Drain OD mm 6 or 8 8.0 Heat insulation Both liquid and gas pipes Notes () Energy label: scale from A (most efficient) to G (less efficient) (2) Annual energy consumption: based on average use of 500 running hours per year at full load (nominal conditions) (3) Cooling: indoor temp. 27ºCDB, 9.0ºCWB; outdoor temp. 35ºCDB, 24ºCWB; equivalent piping length: 5m (4) Heating: indoor temp. 20ºCDB; outdoor temp. 7ºCDB, 6ºCWB; equivalent refrigerant piping: 5m (5) When connected with multi-system outdoor unit, refer to the specifications of the multi outdoor unit to be connected. 2-3 Nominal Capacity And Nominal Input FVXG25K / RXG25K FVXG35K / RXG35K FVXG50K / RXG50K Cooling capacity Min. kw.3.4.7 Btu/h 4,400 4,800 5,800 kcal/h,20,200,460 Nom. kw 2.5 (3) 3.5 (3) 5.0 (3) Btu/h 8,500 (3),900 (3) 7,00 (3) kcal/h 2,50 (3) 3,00 (3) 4,300 (3) Max. kw 3.0 3.8 5.6 Btu/h 0,200 3,000 9,00 kcal/h 2,580 3,270 4,820 Heating capacity Min. kw.3.4.7 Btu/h 4,400 4,800 5,800 kcal/h,20,200,460 Nom. kw 3.4 (4) 4.5 (4) 5.8 (4) Btu/h,600 (4) 5,400 (4) 9,800 (4) kcal/h 2,920 (4) 3,870 (4) 4,990 (4) Max. kw 4.5 5.0 8. Btu/h 5,400 7,00 27,600 kcal/h 3,870 4,300 6,970 Power input Cooling Min. kw 0.300 0.30 0.450 Nom. kw 0.550 0.950.520 Max. kw 0.790.50 2.000 Heating Min. kw 0.290 0.500 Nom. kw 0.780.20.580 Max. kw.270.460 2.660 EER 4.55 3.68 3.29 4 Split - Sky Air Outdoor Unit
2 Specifications Outdoor Unit Pair application RXG-K 2-3 Nominal Capacity And Nominal Input FVXG25K / RXG25K FVXG35K / RXG35K FVXG50K / RXG50K COP 4.36 3.72 3.67 Annual energy consumption kwh 275 475 760 Energy label Cooling A Heating A Piping connections Liquid OD mm 6.35 Gas OD mm 9.5 2.7 Drain OD mm 8 Heat insulation Both liquid and gas pipes Notes () Energy label: scale from A (most efficient) to G (less efficient) (2) Annual energy consumption: based on average use of 500 running hours per year at full load (nominal conditions) (3) Cooling: indoor temp. 27ºCDB, 9ºCWB; outdoor temp. 35ºCDB, 24ºCWB (4) Heating: indoor temp. 20ºCDB; outdoor temp. 7ºCDB, 6ºCWB (5) When connected with multi-system outdoor unit, refer to the specifications of the multi outdoor unit to be connected. 3 2 2-4 Technical Specifications RXG25K RXG35K RXG50K Casing Colour Ivory white Dimensions Unit Height mm 550 735 Width mm 765 825 Depth mm 285 300 Packed unit Height mm 62 797 Width mm 906 960 Depth mm 364 390 Weight Unit kg 34 48 Packed unit kg 38 53 Packing Weight kg 4 5 Heat exchanger Length mm 805 845 Rows Quantity 2 Fin pitch mm.4.8 Stages Quantity 24 32 Tube type ø7 Hi-XA ø8 Hi-XA Fin Type WF fin Fan Type Propeller fan Air flow rate Cooling High m³/min 33.5 36.0 50.9 cfm,83,27,797 Super m³/min 30. 48.9 low cfm,063,727 Heating High m³/min 30.2 45.0 cfm,066,589 Super m³/min 25.6 43. low cfm 904,522 Fan motor Model ARS640DA KFD-380-50-8C Output W 23 53 Speed Cooling High rpm 860 920 780 Super rpm 780 670 low Heating High rpm 860 720 Super low rpm 740 670 Sound power level Cooling High dba 6 63 Sound pressure level Cooling High dba 46 48 Silent operation dba 43 44 Heating High dba 47 48 Silent operation dba 44 45 Compressor Model YC23AEXD 2YC36BXD Type Hermetically sealed swing compressor Output W 600,00 Split - Sky Air Outdoor Unit 5
2 Specifications Outdoor Unit Pair application RXG-K 2 2-4 Technical Specifications RXG25K RXG35K RXG50K Operation range Cooling Ambien Min. ºCDB -0 (4) t Max. ºCDB 46 Heating Ambien Min. ºCWB -5 t Max. ºCWB 20 Refrigerant Type R-40A Charge kg.05.6 Refrigerant oil Type FVC50K Charged volume l 0.375 0.65 Piping connections Drain ID mm - Piping length OU - IU Max. m 20 30 System Chargel ess m 0 Level difference IU - OU Max. m 5 20 2-5 Electrical Specifications RXG25K RXG35K RXG50K Power supply Phase ~ Frequency Hz 50 Voltage V 220-240 Current Nominal running Cooling A 3. () / 2.92 (2) / 2.82 (3) 4.97 () / 4.68 (2) / 4.48 (3) 7.04 () / 6.75 (2) / 6.46 (3) current (RLA) Heating A 4.28 () / 4.09 (2) / 3.99 (3) 5.44 () / 5.5 (2) / 4.96 (3) 7.2 () / 6.92 (2) / 6.63 (3) Starting current Cooling A 4.4 5.6 7.4 Heating A 4.4 5.6 7.4 Wiring connections For power supply Quantity 3 For connection with Quantity 4 indoor Remark Earth wire included Notes () 220V (2) 230V (3) 240V (4) Operation range in combination with Nexura, FVXG-K: min. 0ºCDB ~ max. 46ºCDB 6 Split - Sky Air Outdoor Unit
Outdoor Unit Pair application RXG-K 3 Electrical data 3 - Electrical Data 3 3 Split - Sky Air Outdoor Unit 7
3 Electrical data 3 - Electrical Data Outdoor Unit Pair application RXG-K 3 8 Split - Sky Air Outdoor Unit
Outdoor Unit Pair application RXG-K 4 Options 4 - Options 3 4 Split - Sky Air Outdoor Unit 9
5 Capacity tables Outdoor Unit Pair application RXG-K 5 - Cooling/Heating Capacity Tables 5 0 Split - Sky Air Outdoor Unit
Outdoor Unit Pair application RXG-K 5 Capacity tables 5 - Cooling/Heating Capacity Tables 3 5 Split - Sky Air Outdoor Unit
5 Capacity tables Outdoor Unit Pair application RXG-K 5 - Cooling/Heating Capacity Tables 5 2 Split - Sky Air Outdoor Unit
Outdoor Unit Pair application RXG-K 5 Capacity tables 5 - Cooling/Heating Capacity Tables 3 5 Split - Sky Air Outdoor Unit 3
5 Capacity tables Outdoor Unit Pair application RXG-K 5 - Cooling/Heating Capacity Tables 5 4 Split - Sky Air Outdoor Unit
Outdoor Unit Pair application RXG-K 5 Capacity tables 5 - Cooling/Heating Capacity Tables 3 5 Split - Sky Air Outdoor Unit 5
Outdoor Unit Pair application RXG-K 6 Dimensional drawings 6 - Dimensional Drawings 6 6 Split - Sky Air Outdoor Unit
Outdoor Unit Pair application RXG-K 7 Centre of gravity 7 - Centre of Gravity 3 7 Split - Sky Air Outdoor Unit 7
8 Piping diagrams 8 - Piping Diagrams Outdoor Unit Pair application RXG-K 8 8 Split - Sky Air Outdoor Unit
Outdoor Unit Pair application RXG-K 9 Wiring diagrams 9 - Wiring Diagrams - Single Phase 3 9 Split - Sky Air Outdoor Unit 9
0 Sound data 0 - Sound Pressure Spectrum Outdoor Unit Pair application RXG-K 0 20 Split - Sky Air Outdoor Unit
Outdoor Unit Pair application RXG-K 0 Sound data 0 - Sound Pressure Spectrum 3 0 Split - Sky Air Outdoor Unit 2
Operation range - Operation Range Outdoor Unit Pair application RXG-K 22 Split - Sky Air Outdoor Unit
Daikin s unique position as a manufacturer of air conditioning equipment, compressors and refrigerants has led to its close involvement in environmental issues. For several years Daikin has had the intention to become a leader in the provision of products that have limited impact on the environment. This challenge demands the eco design and development of a wide range of products and an energy management system, resulting in energy conservation and a reduction of waste. The present leaflet is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this leaflet to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this leaflet. All content is copyrighted by Daikin Europe N.V. EEDEN 2-0 0 Please fill out the requested information Please fill out the requested information Daikin Europe N.V. participates in the Eurovent Certification programme for Air conditioners (AC), Liquid Chilling Packages (LCP), Air handling units (AHU) and Fan coil units (FCU), Check ongoing validity of certificate online: www.eurovent-certification.com or using: www.certiflash.com Daikin products are distributed by: Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 042 20 336 - RPR Oostende EEDEN2-00 05/2 Copyright Daikin The present publication supersedes EEDEN-00 Printed on non-chlorinated paper. Prepared by Goekint Graphics NV, Belgium Responsible Editor: Daikin Europe N.V., Zandvoordestraat 300, B-8400 Oostende