SIEMENS-ALLIS. Medium Voltage. Metalclad Switchgear. www. ElectricalPartManuals. com

Similar documents
Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

Power/Vac OEM Express Switchgear

www. ElectricalPartManuals. com

MV Metalclad Switchgear 4760V-15000V 20KA-63KA. AC Power Circuit Breaker Rating Structure. Test Procedures for Power Circuit Breakers

Medium Voltage Equipment 5-15 kv GM-SG and 38 kv GM38 Metal-Clad Switchgear General

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

Chapter 6 Generator-Voltage System

Medium voltage switchgear SafeGear HD 63 ka arc resistant metal-clad switchgear. ABB Group February 25, 2015 Slide 1

Selection and Application Guide E50001-U229-A320-X-US00. GM38 Switchgear. 38kV. Power Transmission & Distribution

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

Medium Voltage. ANSI C37.20 and NEMA SG-5

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure

SIEMENS. Series 8100oT Vacuum Controllers. www. ElectricalPartManuals. com. Bulletin CC

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

SafeGear TM Motor Control Center Arc resistant metal-clad construction

Type SDV6 distribution circuit breaker. Top performance - proven reliability. Answers for energy.

Typical Specification

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Specification Guide. for RMVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

SWITCHGEAR DIVISION PRODUCT PROFILES

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications

POWERCON CORPORATION

Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

33KV INDOOR SWITCHGEAR

ATLV MaxSG. Low Voltage Metal Enclosed Switchgear

Critical Power Switchboards. Selection and Application Guide

R-MAG. Vacuum Circuit Breaker with Magnetic Actuator Mechanism

Detail Bill of Material Page 1 of 1 Project Name: Amphi School - MVS Replacement Negotiation No: TU700213X7K2 General Order

with Vacuum Circuit Breaker HAF

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Solid Dielectric, Single Phase Recloser

Advance design OEM L-Frames, cell kits, & enclosures Metal-clad switchgear components OEM catalog & pricing

Digital Paralleling. PowerCommand Medium Voltage Digital Paralleling Systems

Westinghouse Electric Corporation Switchgear Division East Pittsburgh, PA 15112, U.S.A.

Power/Vac Vacuum Replacement Breakers for GE Magne-Blast Type AM & AMH Breakers

Cobra-S. Catalog Cobra-S

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

AMVAC TM technical guide Vacuum circuit breaker with magnetic actuator mechanism

Section 18. Medium Voltage Equipment. BuyLog Catalog 18-1

Solid Dielectric, Single Phase Reclosers

Power systems Protection course

Solid Dielectric, Three Phase Reclosers CATALOG VS11

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

Three-Phase Pole Mounted Recloser

SION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG

Contents. Page INTRODUCTION Power/Vac GUIDE FORM SPECIFICATION thru

Air-insulated switchgear UniGear type ZS1

Electrical Switchgear Replacement Montgomery County Community College

DO-III Fuse Holder TPL , May 2000, Page 1 of 4. General Information on the DO-III Draw Out Load Break Expulsion Fuse Holder. ABB Inc.

STANDARD SPECIFICATION FOR TYPE PLD LIVE-FRONT/DEAD-FRONT PAD-MOUNTED SWITCHGEAR 15kV 25kV A. General

Medium Voltage Metal-Enclosed Switches

Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9928C

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

Extensible Unit - VCE2a

SIMOVAC and SIMOVAC-AR. Medium-voltage controllers 2.3 kv kv. usa.siemens.com/simovac

R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS

VersaRupter 5-38 kv Load Interrupter Switch. Technical Guide

Underground Distribution Switchgear

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES

IEC Standard Compliant Vacuum Circuit-Breaker (12 kv, 24 kv) for Southeast Asian Markets

FEBRUARY 14, 2017 Joslyn Hi-Voltage Capacitor switches customer presentation

(Under Two Part Bid System) Tender No: NFV/ PUR/ BEC K for VCB

SECTION MOTOR STARTERS (AMPGARD) MEDIUM VOLTAGE

Longest Life Product for Electric Furnace Applications! 100,000 Operations No Routine Maintenance Required!

SION Vacuum Circuit-Breakers. Answers for energy. Medium-Voltage Equipment Selection and Ordering Data. Catalog HG

Horizontal Circuit Switchers

Underground Distribution Switchgear

STANDARD SPECIFICATION FOR LIVE-FRONT 15KV AND 25KV PSI/II PAD-MOUNTED SWITCHGEAR

SPECIFICATION BULLETIN

ADVAC - Advanced Design Vacuum Circuit Breakers Technical Guide

Circuit breaker interlocking and operation requirements SIEMENS

A. Submit manufacturer's literature and technical data before starting work.

Specifications. S&C Alduti-Rupter Switches with Power Fuses Outdoor Distribution (14.4 kv through 46 kv)

Power Break II Switchboard

Descriptive Bulletin. R-MAG TM magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv

Padmount Solid Dielectric Switchgear Catalog

Type 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear

Magnetic and Hydraulic-Magnetic Circuit Breaker

solutions RUS accepted

GE CONSUMER & INDUSTRIAL

Solid Dielectric, Triple Option Reclosers Catalog O-vst14

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications

Solid Dielectric Load Break Switch SPECIFICATION. 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER

Medium Voltage Metal-Enclosed Switches

Type MC Metal-Clad Switchgear

Metal-Clad Indoor Switchgear

S&C Recloser Bypass Disconnects

MASTERCLAD Metal-Clad Indoor Switchgear

Vacuum Circuit Breakers (Vehicle)

Instructions for Installation, Operation and Maintenance of Type VCP-W Vacuum Circuit Breakers IB131006EN

Specifications. S&C Power Fuses Types SM- 4, SM-5, SMD-20, and SMD-40 Outdoor Distribution (4.16 kv through 34.5 kv)

MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI

Transcription:

SEMENS-ALLS Medium Voltage Metalclad Switchgear

Page 2 Typical Arrangements Auxiliary Cell Over 2000A Breaker Cell A Breaker Cell Over A Breaker Cell --!1 A Breaker Cell Over 2000A Breaker Cell Auxiliary Cell Over Auxiliary Cell

Circuit Breaker Ratings (ANS Symmetrical Basis) Note: The ratings shown generally correspond to the preferred ratings listed in ANS Standard C37.06-1971. This standard is on the symmetrical basis rating and is supplementary to ANS-C37.6 (total current- or asymmetrical-rating basis) and does not replace it. ANS-C7.6 will be withdrawn at such time that the changeover from total current rating to symmetrical has been accomplished. As recommended in the Foreward of C37.06-1971, users should confer with the manufacturer on the status of various circuit breaker ratings. Medium Voltage Vacuum Circuit Breaker, With 3AF Operator, Rating Table dentification Circuit Rated Values Voltage nsulation Level Current Nominal Nominal Rated Rated Rated Withstand Rated Rated Voltage 3-Phase Max. Voltage Test Voltage Cont. Short Breaker kv mva Class mva Voltage Range Current Circuit Class Factor Current 0 (i) (at rated Max. kv) Low mpulse @ Fre- E k quency Type Class Class kv rms kv rms kv rms Am peres karms 5-3AF-250 250 4.76 1.24 4.16 19 60 2000 1000 5-3AF-350 350 119 2000 41 3000 7-3AF-500 7.2 500 8.25 1.25 36 95 2000 33 15-3AF-500 500 15-3AF-750 13.8 15.0 1.30 36 750 95 3000 2000 29 18 2000 28 3000 15-3AF-1 000 1000 2000 37 3000 Rated Rated Rated nter- Perm is- Max. rupting sible Voltage time Trip- Divided CD Special high close and latch (momentary) rating available for some special applications @ Maximum voltage for which the breaker is designed and the upper limit for operation @ k is the ratio of rated maximum voltage to the lower limit of the range of operating voltage in which the required symmetrical and asymmetrical interrupting capabilities vary in inverse proportion to the operating voltage. @) To obtain the required symmetrical interrupting capability of a circuit breaker at an operating voltage between 1/k times rated maximum voltage and rated maximum voltage, the following formula shall be used Required Symmetrical nterrupting Capability= Rated Short-Circuit Current Times the Ratio of (Rated Max. Voltage) (Operating Voltage) For operating voltages below 1 /k times rated maximum voltage. the required symmetrical interrupting capability of the circuit breaker shall be equal to k times rated short-circuit current @ With the limitations stated in 04-4 5 of ANS Standard C37 04-1964. all values apply tor polyphase and line-to-line faults. For single phase-to-ground faults. the specific conditions stated in 04-4 5 2.3 of ANS Standard C37 04-1964 apply Current values in this column are not to be exceeded even for operating voltages below 1/k times rated maximum voltage For voltages between rated maximum voltage and 1/k times rated maximum voltage, follow (4) above. Q) Current values in this column are independent of operating voltage up to and including rated maximum voltage ping Delay y by k E/k Cycles Sec. kv rms 3 2 3.84 3 2 6.6 3 2 11.5 Related Required Capabilities (i) Current Values Max. 3-Sec. Closing Sym. Short- and nter- Time Latching rupting Current Capability Capability Carrying (Momentary) Capability 00 k Times Rated Short Circuit Current kl 1.6 k times Rated Short Circuit Current ka rms ka rms karms 36 36 58 49 49 78 41 41 66 23 23 37 36 36 48 48 58 77 Page 3

Page4 Stored Energy Operator..._----3AF Vacuum Circuit Breaker Type 3AF circuit breakers are compact and lightweight and have a long expected life due to optimally designed mechanism and linkage to operate the minimum maintenance interrupters. Most 3AF circuit breakers have a theoretical mechanical life of 30,000 operations. Removable Operator Cover Operator cover can be easily removed to expose the operator (see photo below) for inspection and maintenance. This feature eliminates the need to tilt or turn over the circuit breaker for normal service. --..,r Operator These circuit breakers use our type 3AF electric motor charged spring stored energy operator, which is mechanically trip free. The operator is designed to require minimum maintenance for 10 years or 10,000 operations under normal operation conditions.

Vacuum Breaker Construction The breaker is comprised of an CD operating mechanism, the post insulators @complete with the upper and lower interrupter supports @and the interrupters themselves. nsulating struts ensure that the interrupters are relieved of mechanical stresses regardless of the operating state. This means that neither switching forces nor short-circuit forces or forces applied to the terminals are transferred to the interrupters. Vacuum nterrupters These high speed interrupters provide quiet operation and are essentially maintenance free. Due to extensive factory tests interrupters have a theoretical shelf life of 100 years. Due to the design of this interrupter, and the special chrome copper contact material composition a low 5 amp maximum chopping current is obtained. A keyed movable stem guide prevents accidental damage to the bellows during assembly or maintenance, assuring long vacuum life. Over 45,000 interrupters furnished worldwide attest to its reliable operation.

Page 6 Breaker Cell Construction: Mechanical nterlock j nterlock prevents the insertion of a non-matching breaker into a unit. Current Transformers CT's are accessible from the front when the unit is deenergized. Up to 4 CT's can be provided, two on the bus side and two on the load side. Metal Shutters Grounded metal shutters are breaker actuated.* This mechanism is positively driven in both directions which eliminates the possibility of shutter assembly malfunction due to defective springs. *Shutters are shown in the Open Position for illustrative purposes only. Screw Type Racking Mechanism This mechanism provides reliable racking to and from all positions. Racking can be accomplished with door closed. Secondary Disconnect The secondary disconnect is automatically engaged by the circuit breaker in the connect position.

Bus Compartment Construction Main Bus Aluminum main bus is standard with all ratings, with copper bus optionally available. All bolted bus joints are tin-plated aluminum, or silver plated copper...,_.,...,_... nsulated Bus Bars Bus bars are encased with high dielectric, thermosetting epoxy insulation using the fluidized-bed process. This method of insulation eliminates voids between molded insulation and bus bars for longer life. Glass Polyester nsulation Flame retardant, track resistant glass polyester insulation is standard. Porcelain inserts and standoff insulators are optionally available. Page 7

SEMENS-ALLS COMPT A - - - COMPT 8 >--- l21l00a COMPT A COMPT B j A! 1 A 1 0 COMPT A COMPT 8 J3000A COMPT A COMPT 8 ' A Siemens-Allis, nc. Switchgear Division P. 0. Box 29503 Raleigh, N.C. 27626 (919) 365-6660 TWX 510-920-0771 --- 1 T - 3 6 "---"""*<---- 36" ----+-<--- 3 6.. ""*', 36" ---->of' DMENSONS The information contained herein is general in nature and is not intended for specific application purposes. Siemens-Allis reserves the right to make changes in specifications shown herein or add improvements at any time without notice or obligation. SG-3119 7184 20M -..--- 95".:L_ Pnnted in USA