PFA LINED BALL VALVES Installation, Operation and Maintenance Manual

Similar documents
INSTALLATION - MAINTENANCE MANUAL Severe Service Series M4 Ball Valve

Bray/ VAAS Slurry Series Knife Gate Valve 760/762/765/766/767/768 Series Operation and Maintenance Manual

Bray/McCannalok High Performance Butterfly Valve Operation and Maintenance Manual

COMMERCIAL. BV & BVM Series Installation Instructions 06/29/15

5000/6000 SERIES BALL VALVES INSTALLATION - MAINTENANCE MANUAL

McCannalok HIGH PERFORMANCE BUTTERFLY VALVE OPERATION AND MAINTENANCE MANUAL. The High Performance Company

MK Series - High Performance Butterfly Valves Operation and Maintenance Instructions

YOUR GLOBAL FLOW CONTROL PARTNER. BRAY/MCCANNALOK EN High Performance Butterfly Valve Operation and Maintenance Manual

NYL Resilient Seated Butterfly Valves Operation and Maintenance Instructions

Installation, Operation and Maintenance Manual

IOM Manual. IOM Manual. Series 76/77.

INSTALLATION & MAINTENANCE MANUAL

Scope. Applicability. Caution. I & M CV3000 Series. Storage. Installation & Maintenance Instructions for Marwin CV3000 Series Three Piece Ball Valves

KEYSTONE. Butterfly valves Figure 9 Installation & Maintenance Instructions. Please read these instructions carefully

Installation, Operation, and Maintenance Manual

Installation, Operation, and Maintenance Manual

CompoSeal butterfly valves, wafer style Installation & Maintenance Instructions

Installation, Operation and Maintenance Guide II NIBCO High Performance Butterfly Valves Series 6822 and 7822

Installation, Operation and Maintenance Instructions Series 608 Ball Valve

Railroad Ball Valves Series 5REB3

Butterfly valves Figure 56 Installation & Maintenance Instructions

KEYSTONE SERIES 320 BUTTERFLY VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

DA Series Diaphragm Valve

A Bray High Performance Company A Subsidiary of BRAY INTERNATIONAL, Inc. Ball Valve Selection Guide

LOW PRESSURE BALANCED VALVE DIAPHRAGM BALANCED

I & M 8000 Series. Ideal Installation Schematic. Preferred Installation. Trouble Shooting

HIGH PRESSURE CONTROL VALVE PISTON BALANCED

USER INSTRUCTIONS. NAF Trunnball DL Ball Valves. Installation Operation Maintenance. Experience In Motion FCD NFENIM A4 01/15

DP Series Diaphragm Valve Installation and Maintenance Instructions

KEYSTONE OPTISEAL F14/16-15/17 AND BREWSEAL BUTTERFLY VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

IOM Manual. IOM Manual. Series 20/21.

26 Series Stainless Steel 2-way Ball Valves

TBV OPERATION AND MAINTENANCE MANUAL SERIES 1800: FLANGED BALL VALVE. For technical questions, please contact the following:

Keystone Series GR resilient seated butterfly valves GRW/GRL Installation and operation manual

HAYWARD FLOW CONTROL TBH SERIES TRUE UNION BALL VALVE INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS

Apollo Standard Port, Full Port & One Piece Flanged Ball Valves Installation, Operation, & Maintenance Guide

Fisher RSS Lined Globe Valve

Recommended BFV Installation, Maintenance & Repair Procedures Ultraflo 300 & 400 Series Valves

Fisher RSS Lined Globe Valve

Installation, Operation, and Maintenance Manual

Bray/Mckannalok Butterfly Valve Series 40/41/42/43/44/45 Installation Manual Technical Bulletin No Date: May 2004/Page 1 of 6

Flow Line Controls. Installation & Operations Manual SERIES 20/21 Pneumatic Actuators

Installation, Operation, and Maintenance Manual

OPERATING AND MAINTENANCE MANUAL

When installing the screwed end, socket weld & flanged end valves the following respective procedures shall be followed for better performance.

Keystone Butterfly valves ParaSeal Installation and maintenance instructions

Installation, Operation, and Maintenance Manual GENERAL VALVE GENERAL VALVE TRUSEAL / IOM-GEN-TRUSEAL. Installation, Operation, and Maintenance Manual

Model DF269 Control Valve

GT-200 GATE VALVES PN16, Screwed end

Double Offset High Performance Butterfly Valve

The Solution For The Valve Problems Plug Valves

Installation, Operation and Maintenance Instructions

Model DFR 070/156/220 Rotary Actuator

Installation, Operation and Maintenance Manual

INSTALLATION, OPERATION, MAINTENANCE MANUAL FOR MANUALLY OPERATED STOP CHECK VALVE

OPERATION AND MAINTENANCE INSTRUCTIONS

DL/DS Series Diaphragm Valve

ANDERSON GREENWOOD. Before installation these instructions must be fully read and understood.

Fisher TBX Hydro Plug Fixture

METERING VALVE 2" STEM GUIDED

CONTROLS RESILIENT SEATED BUTTERFLY VALVES 20/21, 22/23, 30/31, 3A/3AH, 31H, 31U, 32/33, 35/36, 36H. The High Performance Company

Series A Floating Ball Valve Installation, Operation & Maintenance XXXX - X X X X X X X. Base Part Numbers. Trim Option Suffix Code

Model DF233 Control Valve

Operating & Maintenance Manual For Steam Conditioning Valve

Installation Operation Maintenance

ONYX VALVE CO MODEL CAR, CAP-PFO Installation & Maintenance

MERIDIAN, 2 or 3 PIECE, TRUNNION MOUNTED BALL VALVES

GL Ludemann Y-Strainers

V-SEGMENT SERIES V-Port Segment Control Valves (VS/VV/VM) Installation & Maintenance Manual

OPERATION AND MAINTENANCE MANUAL 2-66 SERIES 2500 RESILIENT WEDGE GATE VALVE

MEMORY SEAL BALL VALVES MAINTENANCE MANUAL 2 12, Class 150 & 300, Regular Port, Flanged Unibody

KEYSTONE SERIES GRF RESILIENT SEATED BUTTERFLY VALVES INSTALLATION AND OPERATION MANUAL

Installation, Operation & Service Manual. PPL Bag Filter Housings. Table of Contents Page No. Eaton Filtration, LLC

CV Control Valves Installation and Operation Manual

Installation Operation Maintenance. LSSN Butterfly Valve AGA Approved 50MM - 150MM. QAD#IM6055.REVA

OPERATING AND MAINTENANCE MANUAL

ONYX VALVE CO MODEL DAO-ADA Installation & Maintenance

ACHL Series Pump. Operation and Maintenance Manual Air Driven, Hand Operated High Pressure Liquid Pump

KTM Hindle Series 300 Ultra-Seal two piece metal seated ball valves Installation and Maintenance Instructions

Danfoss Butterfly Valve

Fisher 657 Diaphragm Actuator Sizes and 87

MODEL 5800 CONTENTS. Installation, Operation, and Maintenance Instructions 1.0 GENERAL

Power-Seal High Performance Butterfly Valve: Series P1 Installation & Maintenance Manual

INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

ONYX VALVE CO MODEL DAO-PFC Installation & Maintenance

DeZURIK " BAW AWWA BUTTERFLY VALVES WITH EPOXY-RETAINED SEAT

Standard Bore Flanged Ball Valves Series 7150, 730S & , 4 & 6 (DN 80, 100 & 150) Class 150 & 300

Fisher 2052 Diaphragm Rotary Actuator

MODEL 5540 CONTENTS. Installation, Operation and Maintenance Instructions 1.0 GENERAL

back to main page Type: Butterfly valves Instructions and Operation Manual Warning! Warning! Danger for life! 1. Intended use Danger for life!

ANDERSON GREENWOOD SERIES 500 PILOT OPERATED SAFETY RELIEF VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

BETTIS SERVICE INSTRUCTIONS DISASSEMBLY AND REASSEMBLY FOR CB-SR-S SEISMIC SPRING RETURN SERIES PNEUMATIC ACTUATORS

OPERATING AND MAINTENANCE MANUAL

INSTALLATION & MAINTENANCE MODEL mm

I & M Mark 78 Series. Ideal Installation. Start-Up. Installation & Maintenance Instructions for Mark 78 Control Valves (1-1/2-2 )

Triad Series. 3 Piece Ball Valves Full Port: 1 /4-4 Standard Port: 3 /4-2 1 /2. Model FP - Full Port Model SP - Standard

JT SERIES ANGLE STEM TANK BOTTOM BALL VALVE DN25 DN150. Installation, Maintenance and Operating Instructions

USER INSTRUCTIONS. Installation Operation Maintenance. NAF Setball SF Ball Sector Valves. Experience In Motion FCD NFENIM A4 09/16

INSTRUCTION MANUAL. Anchor Darling 1878 Swing Check Valves. Installation Operation Maintenance. Sizes 1/2 through 2 FCD ADENIM

TWO-STAGE HYDRAULIC PUMP. RWP55-IBT-Air

Transcription:

ACRIS PFA LINED BALL VALVES WWW.AMRESIST.COM

Table of Contents Safety Instructions - Definition of Terms............................................2 Introduction..............................................................2 Shipment Handling and Storage................................................. 2 Installation.............................................................. 3 Full Port Dimensions.....................................................3 Standard Port Dimensions................................................. 3 Operation............................................................... 3 Mounting................................................................4 Disassembly and Reassembly...................................................4 Full Port Disassembly.................................................... 4 Full Port Reassembly.....................................................5 Full Port Testing........................................................6 Standard Port Disassembly.................................................6 Standard Port Reassembly................................................. 7 Standard Port Testing.................................................... 8 FOR MORE INFORMATION ON THIS PRODUCT AND OTHER AMRESIST PRODUCTS PLEASE VISIT OUR WEBSITE WWW.AMRESIST.COM 1

Read and Follow These Instructions Save These Instructions Safety Instructions - Definition of Terms Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. NOTICE Used without the safety alert symbol indicates a potential situation which, if not avoided, may result in an undesirable result or state, including property damage. Introduction The Acris PFA lined standard and full port ball valves are engineered for zero leakage shutoff in demanding corrosive and ultra-pure industrial applications. These fully lined ball valves offer unsurpassed resistance to corrosion, permeation and microbial contamination for maximum purity and reliability with minimal maintenance. Engineered for bi-directional zero leakage shutoff, Acris PFA lined ball valves are the high performance solution for critical applications. Available in standard and full port designs and with a vented ball for chlorine applications. Vented ball valves are uni-directional and must be installed in the preferred direction with the ball cavity venting to the upstream side. Shipment Handling and Storage 1. Make sure that the valves are stored with their flange protectors in place. For areas with dust, sand or particulate matter in the air, it is advisable to wrap each individual valve in plastic to add a layer of protection for the PFA parts. The object is keep the valve in the asmanufactured condition prior to installation. 2. Preferably, valves should be positioned in the open position for shipment and storage. The handle should be parallel to the valve body (fully counter-clockwise) in the open position. 3. Preferably, valves should be stored indoors. 4. Ship and store the valves so that no heavy loads are applied to the valve bodies, handles, or actuators (if so equipped). 2

Installation Acris PFA lined ball valves may be installed in any position in the pipeline flanges. When equipped with an actuator, it is recommended to avoid installing the valve/actuator upside down in the piping. NOTICE Before installing lined valves in newly fabricated piping, the piping system should be flushed of any solids, debris, welding residue, etc. or the seats and ball surface may be damaged. NOTICE If an actuator is to be field mounted, manually cycle the ball valve several times with the handle before installing the actuator. Manual cycling of the valve will reduce the stiction that can occur if valves have been stored for long periods of time. Full Port Dimensions (inches) Size A B1 C D PCD E F G F ½ 5.12 0.59 0.55 3.50 2.38 0.62 7.00 4.30 3/4 5.90 0.78 0.55 3.85 2.75 0.62 7.00 4.92 1 5.00 0.98 0.67 4.25 3.12 0.63 7.00 4.75 G PCD D C B1 E 1 ½ 6.50 1.58 0.74 5.00 3.88 0.63 10.00 5.00 2 7.00 1.97 0.80 6.00 4.75 0.75 10.00 5.60 A 3 8.00 3.15 0.98 7.50 6.00 0.75 12.00 7.00 4 9.00 3.93 0.98 9.00 7.50 0.75 12.00 8.20 6 10.50 5.90 1.10 11.00 9.50 0.88 Gear Gear Standard Port Dimensions (inches) Size A B1 B2 C D PCD E F G F 1 5.00 0.98 0.75 0.67 4.25 3.12 0.63 7.00 4.30 C 1 ½ 6.50 1.58 0.98 0.74 5.00 3.88 0.63 10.00 5.00 2 7.00 1.97 1.58 0.80 6.00 4.75 0.75 10.00 5.60 G PCD D B2 B1 E 3 8.00 3.15 2.56 0.98 7.50 6.00 0.75 12.00 7.00 4 9.00 3.93 3.15 0.98 9.00 7.50 0.75 12.00 8.20 A Operation Operation of the valve is done by turning the handle a 1/4 turn (90 degree turn). Clockwise to close, counter clockwise to open. Valve In Open Position The handle is parallel with the pipeline. Valve In Closed Position The handle is perpendicular to the pipeline. Valves with actuators should be checked for actuator-valve alignment. Misalignment will result in high operational torque and damage to stem and seals. 3

Mounting 1. Verify that the pipeline flanges are in proper alignment and are parallel. 2. Gaskets are optional in installations where the maximum flange bolt torque can be achieved (Steel and Alloy flanges for example). If the maximum bolt torque cannot be achieved due to flange type or material limits (FRP & PVC for example), gaskets may be required for proper flange sealing. 3. Spread pipe flanges to allow valve to freely slide between the two flanges. If the valve is equipped with a vented ball (Option VB), remove the desiccant bag from the valve. A valve with a Vented Ball is uni-directional and can only be installed in the pipeline with flow in one direction. Match the flow arrows on the valve with the media flow direction. 4. Install stud bolts and nuts. 5. Tighten the nuts progressively in an acceptable rotational pattern to a torque within the limits listed in the table below. 6. Cycle the valve several times to verify proper operation. 4 Size inches Bolt (nut) Torque in.-lb. Min Max ½ 60 85 ¾ 80 110 1 90 132 1 ½ 150 222 2 345 531 3 595 885 4 435 664 6 685 1025 Disassembly and Reassembly Pipeline must be depressurized before disassembly of the packing gland or removal of the valve from the pipe. Valve should be cycled several times to assure there is no trapped pressure in the ball cavity. Flush the pipeline with the valve half open to remove any hazardous media. Cycle the valve several times during flushing. DO NOT remove packing gland or any other valve parts while the pipeline is pressurized! If the valve has been used to control hazardous media, it must be decontaminated before disassembly. NOTICE Stem seal leakage may be corrected without disassembly by tightening the packing gland bolts until such leakage stops. If stem leakage continues or valve operating torque becomes excessive, the stem packing is worn and needs replacement. Full Port Disassembly To avoid damage to the PFA liner and internal parts, it is recommended to perform disassembly on a soft covered work bench (rubber or equivalent material). 1. Place the valve in the closed position. 2. Remove the handle bolt (18) with washer (17). 3. Remove handle (6) by pulling upward off the valve top shaft. 4. Loosen and remove the packing gland cover bolts and washers (16 and 15) and grounding spring. Remove the packing gland cover (14). 5. Remove Lock Out / Tag Out (LOTO) bracket (13) by loosening and removing bolts (12). 6. Loosen and remove body bolts and washers (9 and 10). Separate the body halves (1 and 2). 7. Remove the stem packing (7) and the PTFE stem bushing (5) from the packing gland bore. A special packing removal tool may be required to pick out the packing rings.

16. Install the body bolts and washers (9 and 10) to attach both body halves. Tighten in an acceptable rotational pattern to the recommended torque making sure the gap between the body halves remains equal as the body bolts are tightened. 8. With the ball in the closed position, tilt the onepiece ball/stem (3 and 4) carefully out of the valve body. Care should be taken no to damage the PFA liner in the body or the PFA over-molding on the ball. 9. Remove PTFE seats (8) from both body halves (1 and 2). 10. The handle stop (11) can be removed if required. Full Port Reassembly 11. Verify that all parts are clean and free from contaminants, lubricants, etc. prior to assembly. 12. Insert the PTFE seats (8) into both body halves (1 and 2). 13. Insert the one piece ball/stem (3 and 4) in the closed position into the larger body half (1) by tilting it in such a way that the stem enters and comes out the packing gland bore. Care should be taken not to damage the PFA liner in the body and the PFA over-molding on the ball. 14. Insert the PTFE stem bushing (5) into the packing gland to align and center the stem in the packing gland of the body half (1). 15. Place body half (2) on body half (1) and align the body bolt holes. Size inches Body Bolt Torque in.-lb. Packing Gland Bolt Torque in.-lb. ½ 75 25 ¾ 75 25 1 135 35 1 ½ 150 45 2 220 45 3 265 53 4 310 53 6 355 89 17. Insert PTFE packing (7) into the packing gland bore. 18. Install the packing gland cover (14), grounding spring, and packing gland cover bolts and washers (16 and 15). Tighten to the recommended torque as shown in Item 16, above. 19. Install the LOTO bracket (13) and bolts (12). 20. Install the handle (6) on the valve stem (4). Install the handle bolt (18) and washer (17) on the handle (6) and tighten. 21. If the handle stop (11) was removed, reinstall in the valve top plate. 22. Check for proper operation by slowly cycling the valve, with a gentle back and forth motion, building up to a full 90 rotation. By cycling slowly, the PTFE seats will more easily conform to the profile of the ball. 5

Full Port Testing 23. If a test flange or flanges and a gas pressure source are available (Air or Nitrogen), pressure test the valve prior to reinstallation. It is advisable to have a 3-way ball valve on the pressure inlet line or other means of relieving the internal test pressure. 24. If testing with 1 test flange, the valve will need to be in the vertical or near vertical position once installed. Be sure to install the test flange with full bolting and a gasket. 25. Once the valve body is secure in the vertical or near vertical position, slowly pressurize the valve with 80 psig Air or Nitrogen. Partially cycle the valve, under pressure, and then slowly close the valve to make sure the ball cavity is pressurized. 26. Pour clean and filtered water in the opposite side of the ball valve and look for bubbles. 27. If bubbles appear, shut off the air or nitrogen source and relieve the pressure inside the valve. Evacuate the water and cycle the valve several times and repeat the pressure test until satisfactory. Once complete, testing of the opposite ball/seat interface can be done by removing and installing the test flange on the other body flange and repeating the process. NOTE If valve is equipped with a vented ball (Option VB) for Chlorine service, the valve can only be tested in one direction. Apply pressure in the flow direction indicated by the arrows on the valve body tag. 28. Check the tightness of the packing gland by spraying soapy water or a leak detection liquid in and on the packing gland area. If bubbles appear, slowly tighten the packing gland bolts (16) just until the leakage stops. 29. If 2 test flanges are available, install the second flange on the other body flange. Using 2 test flanges will require the use of 2mm to 4mm ID flexible tubing and fittings secured to the 2nd test flange NPT port. The tubing end would then be placed in a beaker or jar of water to a depth of 3mm to 6mm. This is per API-598 (2016) standard. Slowly pressurize the ball valve with 80 psig gas. Partially cycle the valve, under pressure, and then slowly close the valve to make sure the ball cavity is pressurized. Look for bubbles exiting the tube in the water. 30. If bubbles appear, shut off the air or nitrogen source and relieve the pressure inside the valve. 6 Cycle the valve several times and repeat the pressure test until satisfactory. Once complete, testing of the opposite ball/seat interface can be done by removing and installing the test flanges on the opposite body flanges and repeating the process. NOTE If valve is equipped with a vented ball (Option VB) for Chlorine service, the valve can only be tested in one direction. Apply pressure in the flow direction indicated by the arrows on the valve body tag. 31. Check the tightness of the packing gland by spraying soapy water or a leak detection liquid in and on the packing gland area. If bubbles appear, slowly tighten the packing gland bolts (16) just until the leakage stops. Standard Port Disassembly To avoid damage to the PFA liner and internal parts, it is recommended to perform disassembly on a soft covered work bench (rubber or equivalent material). 1. Place the valve in the closed position. 2. Remove the handle bolt (16) with washer. 3. Remove handle (5) by pulling upward off the valve top shaft.

4. Loosen and remove the packing gland cover bolts and washers (15 and 14) and grounding spring. Remove the packing gland cover (13). 5. Remove Lock Out / Tag Out (LOTO) bracket (10) by loosening and removing bolts (11). 6. Loosen and remove body bolts and washers (8 and 9). Separate the body halves (1 and 2). 7. With the ball in the closed position, carefully pull and tilt ball (3) outward out of the body. Care should be taken not to damage the PFA liner in the body or the PFA over-molding on the ball. 8. Remove the Stem (4) by pushing it down through the packing gland. Care must be taken not to damage the PFA body lining or the PFA stem over-molding. 9. Remove PTFE seats (7) from both body halves (1 and 2). 10. Remove the stem packing (6) from the packing gland bore. A special packing removal tool may be required to pick out the packing rings. 11. The handle stop (12) can be removed if required. Standard Port Reassembly 12. Verify that all parts are clean and free from contaminants, lubricants, etc. prior to assembly. 13. Insert the PTFE seats (7) into both body halves (1 and 2). 14. Insert the stem (4) into the valve body (1) by tilting it and guiding it up through the packing gland bore. The bare metal portion of the stem (4) should enter the valve body first. Once completely inserted, rotate the stem (4) so that the PFA flats (on the ball side) are in line with the valve body bore. Care should be taken to not damage the PFA liner in the body and the PFA over-molding on the stem. 15. Line up slot on top of the ball (3) with the PFA flats on the stem (4). Insert the ball (3) into the valve body (1) and onto the stem (4) by pushing the ball (3) with a slight downward motion into the valve body. Center the ball (3) on the PTFE seat (7) as much as possible. 16. Place body half (2) on body half (1) and align the body bolt holes. 17. Install the body bolts and washers (8 and 9) to attach both body halves. Tighten in an acceptable rotational pattern to the recommended torque making sure the gap between the body halves remains equal as the body bolts are tightened. Size inches Body Bolt Torque in.-lb. Packing Gland Bolt Torque in.-lb. 1 135 27 1 ½ 150 31 2 220 31 3 265 35 4 310 35 18. Insert PTFE packing (6) into the packing gland bore. 19. Install the packing gland cover (13), grounding spring, and packing gland cover bolts and washers (15 and 14). Tighten to the recommended torque as shown in Item 17, above. 20. Install the LOTO bracket (10) and bolts (11). 21. Install the handle (5) on the valve stem (4). Install the handle bolt (16) and washer on the handle (5) and tighten. 22. If the handle stop (12) was removed, reinstall in the valve top plate. 23. Check for proper operation by slowly cycling the valve, with a gentle back and forth motion, building up to a full 90 rotation. By cycling slowly, the PTFE seats will more easily conform to the profile of the ball. 7

Standard Port Testing 24. If a test flange or flanges and a gas pressure source are available (Air or Nitrogen), pressure test the valve prior to reinstallation. It is advisable to have a 3-way ball valve on the pressure inlet line or other means of relieving the internal test pressure. 25. If testing with 1 test flange, the valve will need to be in the vertical or near vertical position once installed. Be sure to install the test flange with full bolting and a gasket. 26. Once the valve body is secure in the vertical or near vertical position, slowly pressurize the valve with 80 psig Air or Nitrogen. Partially cycle the valve, under pressure, and then slowly close the valve to make sure the ball cavity is pressurized. 27. Pour clean and filtered water in the opposite side of the ball valve and look for bubbles. 28. If bubbles appear, shut off the air or nitrogen source and relieve the pressure inside the valve. Evacuate the water and cycle the valve several times and repeat the pressure test until satisfactory. Once complete, testing of the opposite ball/seat interface can be done by removing and installing the test flange on the other body flange and repeating the process. NOTE If valve is equipped with a vented ball (Option VB) for Chlorine service, the valve can only be tested in one direction. Apply pressure in the flow direction indicated by the arrows on the valve body tag. 29. Check the tightness of the packing gland by spraying soapy water or a leak detection liquid in and on the packing gland area. If bubbles appear, slowly tighten the packing gland bolts (16) just until the leakage stops. 30. If 2 test flanges are available, install the second flange on the other body flange. Using 2 test flanges will require the use of 2mm to 4mm ID flexible tubing and fittings secured to the 2nd test flange NPT port. The tubing end would then be placed in a beaker or jar of water to a depth of 3mm to 6mm. This is per API-598 (2016) standard. Slowly pressurize the ball valve with 80 psig gas. Partially cycle the valve, under pressure, and then slowly close the valve to make sure the ball cavity is pressurized. Look for bubbles exiting the tube in the water. 31. If bubbles appear, shut off the air or nitrogen source and relieve the pressure inside the valve. Cycle the valve several times and repeat the pressure test until satisfactory. Once complete, testing of the opposite ball/seat interface can be done by removing and installing the test flanges on the opposite body flanges and repeating the process. NOTE If valve is equipped with a vented ball (Option VB) for Chlorine service, the valve can only be tested in one direction. Apply pressure in the flow direction indicated by the arrows on the valve body tag. 32. Check the tightness of the packing gland by spraying soapy water or a leak detection liquid in and on the packing gland area. If bubbles appear, slowly tighten the packing gland bolts (15) just until the leakage stops 2045 Silber Road Houston, TX 77055 Phone: 713-682-0000 Fax: 713-682-0080 sales@amresist.com www.amresist.com 8 All statements, technical information, and recommendations in this bulletin are for general use only. Consult Bray representatives or factory for the specific requirements and material selection for your intended application. The right to change or modify product design or product without prior notice is reserved. Patents issued and applied for worldwide. Amrēsist is a registered trademark of BRAY INTERNATIONAL, Inc. 2018 Bray International. All rights reserved. Amresist_IOM_BV 03_2018