MEDIUM VOLTAGE PRODUCT TJC 4 Indoor voltage transformers
2 TJC 4 INDOOR VOLTAGE TRANSFORMERS Parameters Highest voltage for equipment Power frequency test voltage, 1 min. Lightning impulse test voltage Values 3.6-12 kv 10-42 kv 40-75 kv Max. rated burden, classes 25/0.2-75/0.5-150/1 VA/cl Residual winding 50-200/6P VA/cl Description The TJC 4 single-pole insulated voltage transformers are cast in epoxy resin and designed mostly for insulation voltages of 3.6 kv to 12 kv. If no other value is required the transformers are manufactured with a overvoltage factor of 1.9 x Un/8 hrs. One outlet of the primary winding, including the respective terminal is insulated from the earth to a level which corresponds to the rated insulation value. The transformer is mostly equipped with two secondary windings, the first one for either measuring or protection purposes, the other for being connected into an open-delta connection in a threephase system. One terminal of each secondary winding and one of the open-delta connected terminals have to be earthed during the transformer operation. When not required otherwise, the secondary windings are lead out into a casttype secondary terminal board. The transformer can be mounted in any position. The transformers are fixed by four screws, the M8 bolted earthing clamp is located on the transformer base plate. The secondary terminal board is covered with a transparent and sealable cover made of plastic material. Rated primary voltages 3/ 3 kv; 3.3/ 3 kv; 6/ 3 kv; 6.6/ 3 kv; 10/ 3 kv; 11/ 3 kv. Other primary voltages can also be supplied on request. Rated secondary voltages 100/ 3 V; 110/ 3 V accuracy classes 0.2; 0.5; 1 (measuring winding) or 3P; 6P (protection winding). Other secondary voltages can also be supplied on request. Rated voltages for open-delta connection 100/3 V; 110/3 V - class 6P. Other voltages for open-delta connection can also be supplied based on customer requirement. Rated frequency 50 Hz; 60 Hz. Based on a discussion with the manufacturer the transformer can also be designed for two primary voltage levels (with change over secondary side). The transformers are manufactured conformably to the requirements and recommendations of the following standards and regulations: IEC, VDE, IEEE, BS, GOST and CSN. For marking of the voltage transformer outlets see picture 01 a-e Optional accessory The TJC 4 can be delivered together with an external fuse holder as an option in case of interest. The fuse holder is equipped with JT6 fuse with tripping current 300 ma (recommended for system voltage above 6,6 kv) or 600 ma (recommended for system voltage up to 6,6 kv). It is delivered separately, not mounted to TJC 4, but together with all mounting accessories for easy installation. Fuse holder with fuse can be delivered fully separately as well.
3 01 Marking of the voltage transformers outlets a Single-pole insulated transformer b Single-pole insulated transformer with a tap c Single-pole insulated transformer with two secondary windings d Single-pole insulated transformer with two secondary windings, with one of which being the auxiliary (residual) winding e Single-pole insulated transformer with two secondary, tapped windings, with one which being the auxiliary (residual) winding a c d e b 01 Standard execution of the transformers Primary voltage, [V] Secondary voltage Residual winding voltage, [V] accuracy burden, [VA] voltage, [V] accuracy burden, [VA] 3 000/ 3 100/ 3 0.2 10;15;25 3 000/ 3 100/ 3 0.2 10;15;25 100/3 6P 50 3 000/ 3 100/ 3 0.2 10;15;25 100/3 6P 100 3 000/ 3 100/ 3 0.5 15;25;50 3 000/ 3 100/ 3 0.5 15;25;50 100/3 6P 50 3 000/ 3 100/ 3 0.5 15;25;50 100/3 6P 100 3 000/ 3 100/ 3 1 50;75;100 3 000/ 3 100/ 3 1 50;75;100 100/3 6P 50 3 000/ 3 100/ 3 1 50;75;100 100/3 6P 100 3 300/ 3 110/ 3 0.2 10;15;25 3 300/ 3 110/ 3 0.2 10;15;25 110/3 6P 50 3 300/ 3 110/ 3 0.2 10;15;25 110/3 6P 100 3 300/ 3 110/ 3 0.5 15;25;50 3 300/ 3 110/ 3 0.5 15;25;50 110/3 6P 50 3 300/ 3 110/ 3 0.5 15;25;50 110/3 6P 100 3 300/ 3 110/ 3 1 50;75;100 3 300/ 3 110/ 3 1 50;75;100 110/3 6P 50 3 300/ 3 110/ 3 1 50;75;100 110/3 6P 100 6 000/ 3 100/ 3 0.2 10;15;25 6 000/ 3 100/ 3 0.2 10;15;25 100/3 6P 50 6 000/ 3 100/ 3 0.2 10;15;25 100/3 6P 100 6 000/ 3 100/ 3 0.5 15;25;50 6 000/ 3 100/ 3 0.5 15;25;50 100/3 6P 50 6 000/ 3 100/ 3 0.5 15;25;50 100/3 6P 100 6 000/ 3 100/ 3 1 50;75;100 6 000/ 3 100/ 3 1 50;75;100 100/3 6P 50 6 000/ 3 100/ 3 1 50;75;100 100/3 6P 100 6 600/ 3 110/ 3 0.2 10;15;25 6 600/ 3 110/ 3 0.2 10;15;25 110/3 6P 50 6 600/ 3 110/ 3 0.2 10;15;25 110/3 6P 100 6 600/ 3 110/ 3 0.5 15;25;50 6 600/ 3 110/ 3 0.5 15;25;50 110/3 6P 50
4 TJC 4 INDOOR VOLTAGE TRANSFORMERS Primary voltage, [V] Secondary voltage Residual winding voltage, [V] accuracy burden, [VA] voltage, [V] accuracy burden, [VA] 6 600/ 3 110/ 3 0.5 15;25;50 110/3 6P 100 6 600/ 3 110/ 3 1 50;75;100 6 600/ 3 110/ 3 1 50;75;100 110/3 6P 50 6 600/ 3 110/ 3 1 50;75;100 110/3 6P 100 10 000/ 3 100/ 3 0.2 10;15;25 10 000/ 3 100/ 3 0.2 10;15;25 100/3 6P 50 10 000/ 3 100/ 3 0.2 10;15;25 100/3 6P 100 10 000/ 3 110/ 3 0.2 10;15;25 10 000/ 3 110/ 3 0.2 10;15;25 110/3 6P 50 10 000/ 3 110/ 3 0.2 10;15;25 110/3 6P 100 10 000/ 3 100/ 3 0.5 15;25;50 10 000/ 3 100/ 3 0.5 15;25;50 100/3 6P 50 10 000/ 3 100/ 3 0.5 15;25;50 100/3 6P 100 10 000/ 3 110/ 3 0.5 15;25;50 10 000/ 3 110/ 3 0.5 15;25;50 110/3 6P 50 10 000/ 3 110/ 3 0.5 15;25;50 110/3 6P 100 10 000/ 3 100/ 3 1 50;75;100 10 000/ 3 100/ 3 1 50;75;100 100/3 6P 50 10 000/ 3 100/ 3 1 50;75;100 100/3 6P 100 10 000/ 3 110/ 3 1 50;75;100 10 000/ 3 110/ 3 1 50;75;100 110/3 6P 50 10 000/ 3 110/ 3 1 50;75;100 110/3 6P 100 11 000/ 3 100/ 3 0.2 10;15;25 11 000/ 3 100/ 3 0.2 10;15;25 100/3 6P 50 11 000/ 3 100/ 3 0.2 10;15;25 100/3 6P 100 11 000/ 3 110/ 3 0.2 10;15;25 11 000/ 3 110/ 3 0.2 10;15;25 110/3 6P 50 11 000/ 3 110/ 3 0.2 10;15;25 110/3 6P 100 11 000/ 3 100/ 3 0.5 15;25;50 11 000/ 3 100/ 3 0.5 15;25;50 100/3 6P 50 11 000/ 3 100/ 3 0.5 15;25;50 100/3 6P 100 11 000/ 3 110/ 3 0.5 15;25;50 11 000/ 3 110/ 3 0.5 15;25;50 110/3 6P 50 11 000/ 3 110/ 3 0.5 15;25;50 110/3 6P 100 11 000/ 3 100/ 3 1 50;75;100 11 000/ 3 100/ 3 1 50;75;100 100/3 6P 50 11 000/ 3 100/ 3 1 50;75;100 100/3 6P 100 11 000/ 3 110/ 3 1 50;75;100 11 000/ 3 110/ 3 1 50;75;100 110/3 6P 50 11 000/ 3 110/ 3 1 50;75;100 110/3 6P 100
5 Dimensional Drawings TJC 5 TJCH 4 TJCH 5 TJC 4 Weight: appr. 20 kg Creepage Distance: 280 mm 266 M10x15 38 28 20 209 220 Pg16 14 M8 27 11 10 140 338 270 130 125 4 148 11 107 11 Drawing n. 44203570
6 TJC 4 INDOOR VOLTAGE TRANSFORMERS EXTERNAL FUSE COVER 17,5kV External fuse holder M8 49 346 35 4 10 175 13 fuse JT6 300 ma 75 1VL4200499R0101 fuse JT6 300, 600mA fuse JT6 600 ma 1VL4200499R0102
CONTACT US ABB s.r.o. EPDS Brno Videnska 117, 619 00 Brno, Czech Republic Tel.: +420 547 152 021 +420 547 152 854 Fax: +420 547 152 626 E-mail: kontakt@cz.abb.com www.abb.com NOTE We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents - in whole or in parts - is forbidden without prior written consent of ABB. Copyright 2018 ABB All rights reserved 1VLC000520 Rev.5, en 2018.05.25