Development of the Small-Capacity UPS SANUPS A11K Series

Similar documents
Development of Uninterruptible Power Supply SANUPS A11J Three-phase, Four-wire Model

Development of Small-capacity OFF-LINE UPS

Development of the SANUPS P73K Power Conditioner with Peak Power Cut Function

Development of the Single Phase PV Inverter SANUPS P61A

SANUPS. Non Toxic Lead-Acid Batteries Online UPS. Maintenance-free for 10 Years. Compact and Lightweight. Constant, Stable-Quality Power Supply

Technology that Evolves in Line with Market Changes

Development of Power Conditioner with a Lithium Ion Battery

Development of the 3-phase PV Inverter SANUPS P83D

Hybrid UPS Saves Energy and Achieves High Reliability. Output capacity. 3 kva. 2 kva. Output capacity. 2.1kW. 1.4kW

Novel High Efficiency UPS System

Development of the Regenerative Power Compensation Device SANUPS K23A (R Type)

Technical data sheet VH UL. Digital Energy Uninterruptible Power Supply. GE Digital Energy Power Quality

TECHNICAL DATA SHEET KVA UPS Systemss

UPS5000-E (25-75 kva) Series

Eaton 93PS 8-40kW UPS Technical Specification Manufacturer s declaration in accordance with IEC

Application. Battery. Public Grid GS HYBRID INVERTER

Low Power Consumption Fan 60 mm Sq. 10 mm Thick San Ace 60 9GA Type

EFFEKTA Power Supplies

PowerValue 11/31 T kva

Development of Higher-voltage Direct Current Power Feeding System for ICT Equipment

PARALLEL PROCESSING UPS E33A

KEOR HP. THREE-PHASE UPS from 100 to 800 kva GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

SmartOnline SVTX Series 3-Phase 380/400/415V 20kVA 18kW On-Line Double-Conversion UPS, Tower, Extended Run, SNMP Option

gimagination at work Technical data sheet Uninterruptible Power Supply LP Series 6 & 10 kva GE Digital Energy

POWER+ PREMIUM CBS. BS-EN Emergency electrical installations Electric power systems Emergency lighting Escape lighting

Photovoltaics. MPI Hybrid Series

POWER kva

CENTAURI ENERGY SERVER TECHNICAL DATA kw POWER

POWER kva

KEOR HP. THREE-PHASE UPS from 100 to 800 kva GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

Uninterruptible Power System

Counter Rotating Fan San Ace 92 9CRA type

Technical data sheets

On Line UPS. LUC 1000E / LUC 2000E / LUC 3000E User Manual

POWER kva Nominal output power (Cos φ0,8) kva Nominal output power (Cos φ1,0) kw >88 Efficiency (AC AC)

Uninterruptible Power System

Development of the SANMOTION R1 100 sq. 1 kw -130 sq. 5 kw AC Servo Motor

Smart-UPS VT APC Smart-UPS VT 30kVA 208V w/4 Batt. Modules, Start-Up 5X8, Internal Maintenance Bypass

TECHNICAL DATA SHEET B8033FXS kva 3Ph(In) 3Ph(Out)

High Air Flow Fan San Ace 60 G Type

High-voltage Direct Inverter Applied to Induced Draft Fan Motor at Takehara Thermal Power Station No. 3 of Electric Power Development Co., Ltd.

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS

TECHNICAL DATA SHEET B8031 FXS kva 3Ph(In) 1Ph(Out)

Technology from the New Product SANUPS K for a Smart Grid Society

E-15 Uninterruptible Power Systems (UPS)

1.1 GENERAL CHARACTERISTICS

MKN-DSP SERIES - THREE PHASE

NB NB 1511 NB NB 4031 TRUE ON-LINE DOUBLE CONVERSION UPS

Technical Data Sheets

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase

ELEKTRA SERIES I.T GRADE ONLINE DOUBLE CONVERSION UPS 10KVA ~ 500KVA (3/3) Mission Critical & I.T Grade UPS

UPS Sentry HPS. power supply sources - isolation transformers and generators over less sophisticated power systems.

SmartOnline S3MX Series 3-Phase 380/400/415V 60kVA 54kW On-Line Double-Conversion UPS

D Series: UPS UPTO - 300KVA - Three / Three Phase

Standard 1000VA, 2000VA & 3000VA Universal Tower/Rack Mount LB Extended Models 900VA, 1700VA & 2500VA

Series 120/120VAC Universal Tower/Rack Mount

On-line, Single Phase, Double Conversion UPS

Development of Compact Cylinder Linear Servo Motor SANMOTION

True double-conversion online single-phase UPS. PowerValue 11 RT 1 10 kva Single-phase UPS for critical applications

USER S MANUAL CONTENTS. Uninterruptible Power Supply 1. INTRODUCTION SAFTY INSTRUCTION SYSTEM DESCRIPTION... 4

APC Smart-UPS. GUIDE SPECIFICATIONS FOR 1000VA & 2000VA Smart-UPS 230VAC Uninterruptible Power Supply

SmartOnline SUT Series 3-Phase 208/120V 220/127V 20kVA 20kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option

TECHNICAL SPECIFICATIONS

Technical Data Sheets

kVA. Liebert NX. Enterprise-Scale UPS Protection For Medium And Large Data Centers

Technical Data Sheets

ConceptpowerTM Modular kVA

EAST GROUP COMPANY PROFILE. Energy storage solutions. About us. Grid-connected PV systems. Our Products. Our Team. UPS solutions

Technical Data Sheets

BYD Distributed Energy Storage System (DESS) Integrated Type (European Version)

HAIRF UPS. X5 Series KVA

n Lower energy costs and carbon footprint n Cooler operation extends internal component life n High input power factor of 0.99

UPS Wizard User s Manual

Technical Specifications. Sentinel PRO 700 VA up to 3000 VA 1000 VA ER-2200 VA ER-3300 VA ER

3 Uninterruptible Power Systems

TLE Series UPS 400/500 kw With eboost Technology

TECHNICAL DATA SHEET INFINITY kva 3Ph(in) 3Ph(out)

Solar inverter AX-series

S2000 PRODUCT RANGE. Ultra compact

Technical Data Sheet. Uninterruptible Power Supply. Critical Power. imagination at work

FRENIC-Mega Series of High-performance Multi-function Inverters

Galaxy VM. From 160 kva to 1000 kva. Three-phase power protection. Galaxy VM trusted partner for your business continuity. schneider-electric.

SmartOnline SUT Series 3-Phase 208/120V 220/127V 30kVA 30kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option

SmartOnline 3-Phase In/Out 120/208V 20kVA 16kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, Tower, DB9 Serial, Hardwired

Green Power 2.0 MASTERYS GP

» Sophisticated» Reliable» Intelligent

Aurora Single Phase Emergency Lighting Inverters

Expanding Application of FRENIC-Lift Series for Elevators

Uninterruptible Power Supplies

Liebert NXC. 10kVA - 60kVA. Compact, Efficient, and Reliable Power Solution

MINUTEMAN UPS Endeavor Series Product Specifications 5,000VA 10,000VA Single-Phase Uninterruptible Power Supply 1.0 GENERAL

Uninterruptible Power System

MX1S Matrix Converter

Gree Photovoltaic Direct-driven Inverter Multi VRF System

SmartOnline 120V 2.2kVA 1.8kW Double-Conversion UPS, 2U, Extended Run, Network Card Slot, LCD, USB, DB9

POWERTRONIX QUASAR 5-40 KVA

User Manual 1KVA-5KVA INVERTER / CHARGER

TLE Series UPS 160/200/225/250 kw with eboost Technology

Galaxy VM. From 160 kva to 1000 kva Three-phase power protection. apc.com/products

U n i n t e r r u p t i b l e P o w e r S y s t e m

Transcription:

New Products Introduction Development of the SmallCapacity UPS SANUPS A11K Series Kazuya Yanagihara Shinichiro Yamagishi Yoshitsugu Kashiwagi Hiroshi Sakaba Hideaki Yoda Yasuhiko Ogihara Hidenori Takizawa Yuhei Shoyama Yuki Kurashina Shota Ozawa 1. Introduction In recent years advances of information and communications technology, the reliability of devices relating to network systems such as servers and routers and the maintenance management of stable operation are becoming extremely important. Also, as network systems increase in significance, the impact of the network system stop on society is increased. That is why there is a demand for the highly reliable uninterruptible supplies (hereinafter UPS ) that supply network systems with. Furthermore, the supplies are expected to have even higher efficiency because more people are concerned with natural protection, especially with CO2 reduction for the prevention of global warming. This document introduces the smallcapacity UPS SANUPS A11K that was developed to meet these demands. 3. Product Features For the SANUPS A11K we have prepared models with output capacities of 1 kva, 1.5 kva, 2 kva, 3 kva and 5 kva. Figures 1, 2 and 3 show the SANUPS A11K 1 kva, 3 kva and 5 kva, respectively. (1.5 kva and 2 kva differ to 1 kva only in depth.) Fig. 1: SANUPS A11K 1 kva 2. Background of the Development Sanyo Denki s conventional model, the SANUPS A11F adopts an online UPS system to supply high quality and has models of 1 kva to 3 kva in lineup, however the competition is extremely intense in this market and there is a need to enhance performance even further. Moreover, due to issues such as global warming, highly efficient products which are thoughtful of the environment are sought. In the 5 kva output capacity class, our conventional model SANUPS ASC is available, however the design is outdated and there was an urgent need to develop a successor model. This is the background of developing SANUPS A11K. Fig. 2: SANUPS A11K 3 kva Fig. 3: SANUPS A11K 5 kva 29 SANYO DENKI Technical Report No.40 November 2015

Development of the SmallCapacity UPS SANUPS A11K Series 3.1 High efficiency In the same way as the conventional models, these models adopt a 3arm continuous inverter supply system on their main circuits and achieve a maximum capacity of 92% or higher due to optimization of circuit components, artificial resonance of control circuits and so on. This efficiency enables the device to reduce running costs and contribute to energy conservation. Figure 4 shows the comparison data with conventional models. Efficiency (%) 93 92 91 90 89 88 87 86 85 84 90 92 92 A11F102 A11K102 ASC50S1 A11K502 (1 kva) (5 kva) Fig. 4: Comparison of efficiency with conventional models 87 range of conventional models is 0 C to 40 C) This makes it possible to use the device in a wide range of temperature environments. 3.4 Improved maintainability Through modularization of the inverter and battery sections, maintenance work such as the replacement of the inverter module has been simplified. Figure 5 shows a state with an inverter module and battery module installed. Maintenance bypass circuits are equipped on all models and it makes possible to supply from utility even during module replacement. Battery module module 3.2 Wide range input The allowable input voltage has a wide range of 20% to +20% rated voltage if the load factor exceeds 70% and 40% to +20% if the load factor is 70% or. The widerange input reduces the frequency of changing to battery feeding as well as minimizes battery wear and deterioration even in unstable environments. 3.3 Improved environment resistance characteristics The operating temperature range of 10 C to +55 C is wider than conventional models. (Operating temperature Fig. 5: module and battery module (1 kva) 3.5 Battery management function The new model features selfdiagnosis functions such as an automatic battery operation test and battery life management in order to be capable of performing reliable backup of load devices during outages. Furthermore, functions such as battery life warning, estimated battery operation time, battery charge percentage, and estimated backup time are included in order to improve reliability. Normal operation Start of operation confirmation Check battery supply Utility Rectifier Device Regular checks Utility Rectifier Device Battery Battery Return to normal operation * Returns to normal operation if the battery function deteriorates during an operation test. Fig. 6: Battery operation test SANYO DENKI Technical Report No.40 November 2015 30

3.6 Downsizing Compared with conventional models, the new model is downsized by up to 30% as a result of efforts such as making the battery charging/discharging circuit common and using surfacemounted devices. In addition, output and battery backup time have been increased. Table 1 shows a comparison with conventional models. Table 1: Comparison with conventional models Moreover, in addition to the conventional RS232C communication interface, the model is standard equipped with a USB connector and can be connected with a PC via a commerciallysold USB, making it possible to use UPS management software. 4. Circuit Configuration Figure 7 shows the UPS circuit block diagram. Output capacity 1 kva 1.5 kva 2 kva 3 kva 5 kva Device model no. A11K102 (New A11F102 A11K152 (New A11F152 A11K202 (New A11F202 A11K302 (New A11F302 A11K502 (New ASC50S1 Output 800 W 700 W 1,200 W 1,050 W 1,600 W 1,400 W 2,400 W 2,100 W 4,000 W 3,500 W Backup time 13 min 700 W) 9 min 700 W) 12 min 1,050 W) 7 min 1,050 W) 1,400 W) 1,400 W) 2,100 W) 2,100 W) 3,500 W) 3,500 W) Volume comparison 1.1% 12.3% 30.0% 26.4% 28.4% 4.1 Main circuit configuration This UPS is configured from a rectifier, inverter, DC/DC convertor, bypass circuit, battery and so on. (1) Improved motor efficiency through the adoption of a 3arm continuous inverter supply system. (2) Reduced number of components and achieved downsizing through the adoption of a DC/DC convertor which makes the battery charging/discharging circuit common. 4.2 Control circuit configuration This UPS has successfully reduced the mounting surface by designing the control circuit components to be surfacemounted. Moreover, the hardware of this model is slimmed down by integrating the sequence control, converter control, inverter control and battery charging/discharging control on one CPU. High efficiency of the control circuit is achieved by adopting the artificial resonance RCC system. Moreover, by featuring an auxiliary control circuit it has become possible to continue supplying from utility circuit by using the bypass circuit even if an error occurs in the control. 3.7 Improvement of functionality User operability and visibility have been improved by implementing an LCD panel on the operation area. By modularization of the operation area, it is possible to change the direction to one which enables easy operations depending on whether the device is stored vertically or horizontally. 31 SANYO DENKI Technical Report No.40 November 2015

Development of the SmallCapacity UPS SANUPS A11K Series Maintenance bypass circuit Bypass circuit BYPASS OC 15 A Electronic switch Relay AC output NEMA 515R AC input NEMA 515P Filter Fuse Flow rectifier Filter Relay DC/DC converter Fuse Remote module Control circuit Interface PC I/F (D sub 9P) PC I/F USB TYPE B CARD I/F AUX OUTPUT External battery Battery (battery module) LAN I/F (Option) Contact I/F (Option) Fig. 7: Circuit block diagram (1 kva) 4.3 Electrical characteristics Table 2 shows the general specifications for the UPS. Item Units Rating or characteristic Remarks Model A11K102 A11K152 A11K202 A11K302 A11K502 Rated output capacity kva/kw 1/0.8 1.5/1.2 2/1.6 3/2.4 5/4 System AC input Charging system Online UPS Cooling system Forced air cooling INV system High frequency PWM Number of phases Singlephase, twowire Apparent /effective Utilitysynchronous online UPS system Rated voltage V 100, 110, 120 Same as output voltage Rated voltage within 20 With a load factor of 70% or more Voltage range % Rated voltage within 40, +20 With a load factor of than 70% Return voltage of 20% or more Rated frequency Hz 50 or 60 Frequency range % Rated frequency 1, 3, 5, 7 Required capacity Table 2: SANUPS A11K Series specifications kva 1.1 or 1.5 or 2.0 or 3.0 or Power factor 0.95 or higher 0.97 or higher 5.3 or Automatic frequency discrimination (Note 1) (Fluctuation range is identical to the output frequency accuracy selection) Max. capacity during battery recovery When input voltage distortion is within 1% SANYO DENKI Technical Report No.40 November 2015 32

AC output Item Units Rating or characteristic Remarks Number of phases Singlephase, twowire Rated voltage V 100,110,120 Default, voltage waveform: Sine wave Voltage setting precision % Rated voltage within 2 During rated operations Rated frequency Hz 50 or 60 Same as input frequency Frequency precision % Voltage wave form distortion factor Sudden variation of load Power outage/ recovery Battery Transient voltage fluctuation Sudden variation of input voltage Rated frequency within 1, 3, 5, 7 (Default 3) % 3 or / 7 or % Frequency accuracy settings are adjustable ( 1,3,5,7%) 0.5% or during battery operation (Note 1) Linear load/wave rectifier load during rated operations 0 100% change, during output changeover % During rated operations Rated voltage within 5 % Change 10% Response time Max. 5 cycles Load factor 0.8 (slow) Overcurrent protection % 105 or higher Overload endurance Acoustic noise Operating environment Fluctuation range 0.7 (delay) to 1.0 Automatic switching to bypass circuit (Note 1) 105 or higher 200 ms % Bypass 200 / 800 30 seconds / 2 cycles Type Smallsized valve regulated leadacid battery Backup Ambient temperature 25 C, Minute 10 10 Time during rated output, default 1 m from device front, 40 or 45 or A characteristic ambient temperature is db 40 C or ) 1 m from device front, 50 or 55 or A characteristic ambient temperature exceeds 40 C) Ambient temperature C 10 to +55 (Note 3) Relative humidity % 10 to 90 No condensation Note 1: When the AC input frequency has a range of 3% (selectable between 1%, 3%, 5%, or 7%) the rated frequency and the AC input voltage has a range of 20% the rated voltage load factor is 70% or, the range is 40% to +20%), the inverter operated synchronous with the AC input and nobreak transfers to the bypass circuit are possible. If the AC input frequency exceeds the setting range, operation switches to battery operations. Note 2: When the load factor is 0.7 (2 kva: 1.4 kw, 3 kva: 2.1 kw, 5 kva: 3.5 kw). 8 min when the load factor is 0.8. Note 3: Battery charging stops when ambient temperature exceeds 40 C. 33 SANYO DENKI Technical Report No.40 November 2015

Development of the SmallCapacity UPS SANUPS A11K Series 5. Benefits for Our Customers By achieving a high conversion efficiency of 92% or more, this UPS can help to reduce our customers running costs and conserve energy. Moreover, by a wideranging of input voltage, battery replacement costs have been reduced by minimizing battery wear and deterioration even in unstable environments. Kazuya Yanagihara Joined Sanyo Denki in 2013. Shinichiro Yamagishi Joined Sanyo Denki in 1991. 6. Conclusion As information communication technology becomes more sophisticated, its social importance will continue to grow. Moreover, the UPS demand will be more diversified to use in a variety environments. We will continue to quickly develop products to meet these market demands and provide devices that fulfill our customers needs. We sincerely thank the many people involved in the development and realization of this UPS product for their advice and support. Reference Yoshitsugu Kashiwagi and Others: Development of SmallCapacity UPS SANUPS A11F SANYO DENKI Technical Report No.19 Yoshitsugu Kashiwagi Joined Sanyo Denki in 1989. Hiroshi Sakaba Joined Sanyo Denki in 1990. Hideaki Yoda Joined Sanyo Denki in 1991. Yasuhiko Ogihara Joined Sanyo Denki in 1991. Worked on the structural design of UPS. Hidenori Takizawa Joined Sanyo Denki in 1999. Worked on the structural design of UPS. Yuhei Shoyama Joined Sanyo Denki in 2009. Yuki Kurashina Joined Sanyo Denki in 2010. Shota Ozawa Joined Sanyo Denki in 2014. SANYO DENKI Technical Report No.40 November 2015 34