EG1065X. Compatible with Barber Colman* Dyn1-1065X series * Use for reference purpose only and not a genuine Barber Colman product.

Similar documents
EG1069X. Generator Electronic Governor Controller Operation Manual

ESC2301. Universal Electronic Governor Controller Operation Manual

EG3000. Generator Electronic Governor Controller Operation Manual

EG3002. Electronic Engine Governor Controller User Manual

DYNA Power Control Manual For Plus 1, Plus 2, Plus 4 and Plus 6 Ft. Lb. Systems

DYNA 8000 DYNA 8200 DYNA

PRODUCT SERIES: DPG-2100

Application Information

ESD5500E Series Speed Control Unit

ENGINE GOVERNING SYSTEMS

ESD5550 / 5570 Series Speed Control Units

ESD5100 Series Speed Control Unit PART NUMBER ESD5120 ESD (127)

ESD-5550/5570 Series - Speed Control Unit

ESD-5500E Series - Speed Control Unit

ESD-5550/5570 Speed Control Unit. Manual

Product Manual (Revision E) Original Instructions. Min/Max Control Systems. Installation and Operation Manual

10V. the rack of the oil pump must be on the

Application Information

EDG6000 Electronic Digital Governor

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version

IGA225 Integrated Governor & Actuator

with discrete output (Overspeed) with auxiliary input (Synchronizer and Load Sharing)

Product Manual (Revision B) Original Instructions. EPG Electrically Powered Governor Models 501 and Installation and Operation Manual

EA07. Generator Automatic Voltage Regulator Operation Manual

2301A Load Sharing & Speed Control with Dual Dynamics. Product Manual (Revision NEW, 1990) Original Instructions

EDG5500 Electronic Digital Governor With Quikset Display

Product Manual (Revision D, 5/2015) Original Instructions. 2301A Speed Control. Installation and Operation Manual

Application Note. Controllers for Stanadyne Pumps Using DC Integrated Actuators. Calibration Instructions. Manual 36579

SPECIFICATIONS ATTENTION OPERATION DESCRIPTION

INSTRUCTION MANUAL FOR. VOLTAGE REGULATOR Model: APR Part Number:

INSTRUCTION MANUAL FOR VOLTAGE REGULATOR APR P/N

TRAC-3 TENSION READOUT AND CONTROL

ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER

5001TCP SPEED CONTROLLER

5001TCP SPEED CONTROLLER

UG-5.7, UG-8, UG10 Governor

ECU-02 Ver2.1 Automatic Engine Control Unit Operators Manual

GCU-10. Automatic Engine Control Unit Operators Manual

MX431 Generator Automatic Voltage Regulator Operation Manual

M9106-AGx-2N0x Series Electric Non-spring Return Actuators

DENISON HYDRAULICS Jupiter 500 Driver Card Series S

R81EAA-2 Economizer Circuit Board

PM300 VOLTAGE REGULATOR INSTRUCTION MANUAL

715B CONTROL SERIES. Instruction Manual Line Voltage DC Brushless Motor Control CONTROLS. Phone (317) Fax (317)

ES52. Auto Start Engine Controller. Full Version. Installation and User Manual for the ES52 Auto Start Engine Controller.

Troubleshooting Guide

Product Manual (Revision C) Original Instructions. EPG (Electric Powered Governor) with Position Feedback. Installation and Operation Manual

D-70, D-140, D-210, and D-280 Series Electric Non-Spring Return Actuators

AGELKOM CAP04 Plasma and Oxy Fuel Torch height control for sheet metal cutting machines Height Sensor & Controller

Controlled Ferroresonant Ballast (CFB) Generation #3. Manual

ECU. Speed Switch Manual. Contents. ECU is a registered trademark of Engineering Concepts Unlimited Inc.

PRODUCT INFORMATION BULLETIN

12 Series Linear Actuators. Operation & Maintenance Manual, Analog Positioner Installation

Series EA High Torque Actuators with Integrated Controller

INSTRUCTION MANUAL VIBRASWITCH MALFUNCTION DETECTOR MODEL 366

ES52 Auto Start Engine Controller Installation and User Manual for the ES52 Auto Start Engine Controller.

Troubleshooting Guide

GS10 Series MODELS: GS10 GS10-R NEMA 4X SCR MOTOR CONTROLS. User s Manual

EPG Electrically Powered Governor. Installation and Troubleshooting Manual. Models 1712/1724 and 512/524 without Position Feedback

4024 EPG (Electrically Powered Governor) Product Manual (Revision B, 3/2008) Original Instructions

MAXIGARD A2000 SPEED SWITCH. Introduction

Installation & Operation Manual

DO NOT INSTALL, REMOVE, OR REWIRE THIS EQUIPMENT WITH POWER APPLIED.

UNIVERSAL VOLTAGE REGULATOR Manufactured in the USA by

Product Manual (Revision D, 3/2000) Original Instructions. UG-5.7, UG-8, UG10 Governor. Installation Manual

Electric Modulating Actuator Installation, Operation & Maintenance Manual

ELECTRONIC MANUAL VOLTAGE CONTROL Model: MVC 300. Part Number:

EEG6500 Enhanced Electronic Governor

Tension Control System MCS-166, MCS-203, MCS-204

Filtered PWM Speed Control for Permanent Magnet DC Motors

65E CONTROL SERIES CONTROLS. Instruction Manual. For DC Input Variable Speed Controls. P.0. Box W. 106th Street Zionsville, Indiana 46077

Q7130A, Q7230A, Q7330A Modutrol IV Interface Modules

CABINET REEL OPERATING INSTRUCTIONS

KT230 Series Caterpillar 3406 Governor System Installation Kit

CABINET REEL OPERATING INSTRUCTIONS

Instruction Manual for Barber-Colman Series EA Electric High Torque Actuators

MDC V, 30A Brushless Controller. User s Guide L East Orangefair Lane, Anaheim, CA

DUAL SWIVEL REEL OPERATING INSTRUCTIONS

ADVR-12. Hybrid Universal Analog Digital Voltage Regulator Operation Manual

USER MANUAL MODELS NRG02-D240AC-4Q NRG02-D240AC-4Q-PCM NRG05-D240AC-4Q NRG05-D240AC-4Q-PCM NRG10-115AC-4Q NRG10-115AC-4Q-PCM

INSTALLING, OPERATING AND MAINTAINING THE MODEL D1028 COMPUTER INPUT BI-DIRECTIONAL GENERATOR FIELD REGULATOR INSTRUCTION MANUAL # S-225

AGELKOM CAP04 Plasma and Oxy Fuel Torch height control for sheet metal cutting machines Height Sensor & Controller

Moniteur INSTALLATION & OPERATING INSTRUCTIONS. SERIES 40 Positioners. Installation and Operating Instructions Series 40 Positioners.

KT145 Series John Deere 6076 with Nippondenso Inj. Pump

Customizing the Basic Control Handle

VA-715x Electric Valve Actuator

CP-8301-xxx Series. Application. Features. Applicable Literature. 1 to 15 Vdc Input Electronic Actuator Drive General Instructions

Installation Instructions

SE-3SCR-LM MANUAL MOTOR LOAD MANAGER

Fincor Series 2230 MKII/2240

DC3R Regenerative DC Drive User Guide 1/4 to 2 HP, 115/230 VAC

WarninG TraDeMarkS Copyright 2013, 2018 Automationdirect.com Incorporated All Rights Reserved

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited.

Product Instruction. Door Control Board: Board 1Ø4 for PM/SSC (R3)

17429X.00 SERIES MODELS:

MDC Series

Electro-Pneumatic Positioner Series 830/831-WP/EX. Operation & Maintenance Manual

User s Manual. SCR, Adjustable Speed Drives for DC Brush Motors

Models: User s Manual. Pulse-Width Modulated, Adjustable Speed Drives for DC Brush Motors

RUS-L24-MOD Electric 24 Volt Modulating Control Damper & Louver Actuator

Transcription:

EG1065X Generator Electronic Governor Controller Operation Manual Compatible with Barber Colman* Dyn1-1065X series * Use for reference purpose only and not a genuine Barber Colman product. Headquarters : No.3, Lane 201, Chien Fu ST., Chyan Jenn Dist., Kaohsiung, TAIWAN Tel : + 886-7-8121771 Fax : + 886-7-8121775 URL : http://www.kutai.com.tw

1. SPECIFICATIONS 1.1 Electronic Specifications Operating Voltage 12 or 24 VDC ±20% Select by DIP Switch Output Current Quiescent: 80 ma, Stall: 15 A Power Input Voltage 12 or 24 VDC ±20% Current Temp. Stability Rated above maximum actuator stall current Better than ± 0.5% between -40 ~ 75 Speed Band ± 0.25 % at steady state Dimensions Weight 147mm L * 114mm W * 48.6mm H Remote Speed Adjustment 1. Connect 5KΩ potentiometer to terminal #9. Adjustable range is approximately 5% at 1800 RPM. 2. Connect 5KΩ potentiometer through resistor R to terminal #8 Reducing the value of R increases the remote adjustable speed range. Mechanical Vibration 1G @ 18 ~ 30 Hz, 2.5G @ 48 ~ 70 Hz Relative Humidity < 95% Operating Temperature -40 ~ 85 Storage Temperature -40 ~ 85 860g ± 2% 1.2 Compatible Products Barber Colman P/N DYN1-10652-000-0-12/24 DYN1-10653-000-0-12/24 DYN1-10654-000-0-12/24 DYN1-10656-000-0-12/24 Speed Input Signal Frequency* 250 ~ 1200 Hz 1200 ~ 2500 Hz 2500 ~ 5000 Hz 5000 ~ 9500 Hz *Speed Input Signal Frequency Speed Input Signal Frequency (Hz) = Engine RPM Number of Fly Wheel Gear Teeth 60 seconds Change Switch 4~7 for the correct Speed Input Signal Frequency range generated by the magnetic pickup at the maximum engine operated (RPM) speed. 2 EG1065X

2. FUNCTIONS 2.1 EG1065X Electronic Controller EG1065X is the information processing unit of the governor assembly. It contains electronic components which process the input signal from the magnetic pickup and control the engine to the desired speed / RPM set into EG1065X. Electronic adjustments are available on EG1065X for field adjusting the unit as necessary. The governor system receives its power from a battery or an AC to DC power supply supplying 12 or 24 VDC ±20% to match the governor voltage. The average operating current consumption is 2.5 to 3.5 amperes and the highest consumption is 14.75 amperes during engine start-up or during a large load change. 2.4 DROOP Operation Clockwise increases the droop. Droop operation is obtained by setting the droop potentiometer. A droop potentiometer setting of 10 o'clock will give about 4% droop, no load to full load when the pickup frequency is 4260 Hz and actuator shaft rotation is approximately 30 degrees from no load to full load. Lower pickup frequency or smaller shaft rotation results in less droop for the system. The amount of droop for a given setting depends on the magnetic pickup frequency and no load to full load actuator shaft rotation. No load Engine RPM Adjustadle Desired Engine RPM 2.2 Component Location 1. EG1065X, the controller, is off-mounted or installed in the engine control panel or cabinet. 2. The actuator of the governor assembly is mounted on the engine next to the fuel system. 3. The magnetic pickup is normally mounted in the flywheel housing in such a way that it can count the teeth on the starter ring gear. 2.3 Isochronous Operation Isochronous operation is obtained by setting droop potentiometer fully counterclockwise. EG1065X is all electric, and it is normally operated in the isochronous mode; i.e., engine RPM is constant (±0.25%) under steady state load conditions, up to the engine's maximum capability, regardless of load on the engine. Engine RPM lsochronous Operation Mode Engine Load Figure 1 Desired Engine RPM 100% 2.5 Remote Speed Adjustment A suitable remote speed selector can adjust engine RPM from up to 90 meters (300 ft.) from the engine. See Section 5, the potentiometer can be connected for a narrow (fine) or wide speed range control. 3. INSTALLATION 3.1 Mount EG1065X in the control panel. 3.2 Connect the wiring as shown in Section 5 or according to other particular wiring diagram. 3.3 Proper Procedures for Setting Switches SW1 and SW2. EG1065X has two response ranges for matching either the diesel or gas engine dynamics. Set SW1 to the OFF position for diesel engine applications. Set SW1 to the ON position for gas/gasoline engine applications. Set SW2 to OFF, this level is nominally 6.3 amperes for actuators with lower current level. Engine RPM % of Engine Load EG1065X 3 0% Figure 2 100%

Set SW2 to ON, this level is nominally 7.3 amperes for actuators with lower current level. O N O F F Top View 1 2 The drawings above should clarify any confusion about switch settings. The easiest way to set the switches is to apply pressure with a small pointed object until the switch clicks into position. SW1 in the above drawing is in ON position, and SW2 in the above drawing is in OFF position. CAUTION!! As a safety measure, the engine should be equipped with and independent overspeed shutdown device in the event of failure which may render the governor inoperative. NOTE : For some diesel engines, better operation may be obtained by placing SW1 in ON position. If difficulty experience in OFF position, try SW1 ON and recalibrate. 4. CALIBRATION OF DYN1-1065X 4.1 Connection Information 1. When using an ILS unit, the remote speed potentiometer may be left connected to the controller as shown in Section 5. 2. When an ILS unit is used, connect 3-wire shielded cable to terminals 6, 7 and 8. Connect drain shield wire to terminal 10 at EG1065X only. Other end of drain shield wire is to be cut off and taped. 4.2 Calibrations and Adjustments 1. See Section 5 for a reference guide before making any adjustments of the potentiometers, DROOP, I, GAIN and SPEED. 2. Power OFF - engine not operating. 3. Initial potentiometer settings: ON OFF ON OFF Side View "on" Side View "off " Set the I adjustment three divisions from zero and the GAIN at the second division from zero. For isochronous operation, set DROOP counterclockwise to minimum position as shown in paragraphs 3.5 and 3.6. For DROOP operation, set DROOP potentiometer clockwise to obtain desired amount of DROOP from no-load to full load. Turning potentiometer clockwise increases DROOP. NOTE : If the full 35 rotation of the actuator shaft is used and the linkage adjusted to use only the active fuel range, the maximum obtainable DROOP would be approximately 12% at full load. 4. If a remote speed potentiometer is used for narrow range, set it to mid-range. If the remote speed potentiometer is connected to terminals 6, 7 and 9, a resistor "R" in the wiper is not needed. This will provide approximately a 5% adjustable speed range. 5. Start the engine. Adjust the controller speed potentiometer until the engine is operating at the desired engine RPM. Clockwise increases engine RPM. If the governor system is unstable, slightly reduce the GAIN setting. NOTE : Except for the speed adjustment, the potentiometers have internal stops at the 0 and 100% positions. 6. With the engine unloaded, finalize the settings, I and GAIN adjustments as follows: (1) Turn the GAIN adjustment clockwise slowly until the actuator lever oscillates. (One may need to disturb the actuator lever to cause oscillation.) (2) Reduce the GAIN adjustment slowly counterclockwise until the lever is stable. Upset the lever by hand.. (3) If the lever oscillates 3 to 5 diminishing oscillations and stops, the setting is correct (4) If system performance to load changes is satisfactory, omit step (5), (6) & (7) (5) Reduce the GAIN setting counterclockwise one division. Next, turn the I adjustment fully clockwise while observing the actuator lever. (6) If the lever does not become unstable, upset it by hand. When the lever slowly oscillates, turn the adjustment counterclockwise slowly until the lever is stable. (7) Upset the lever again; it should oscillate 3 to 5 times and then become stable for optimum response. 4 EG1065X

5. TYPICAL WIRING DIAGRAM & CONTROLLER INSTALLATION DIMENSIONS KUTAI ELECTRONICS SW1-OFF-DIESEL SW1-ON -GAS SW2-OFF-8000 ACT SW2-ON -8200,8400 ACT SW3-ON -12V OFF-24V SW4-ON -10652 1 2 3 4 5 6 7 SW DROOP I SW5-ON -10653 SW6-ON -10654 GAIN SW7-ON -10656 REMOTE SPEED POT 4 INC 23 56 1 7 _ SPEED _ TP1 TP2 8V 4V ILS ~ SW ACT 1 2 3 4 5 6 7 8 9 10 MPU 11 + Cadle C + Red Black _ Red Black Red Black Wnite Cable A Cable B DC Power R Magnetic Pickup Cadle C CCW 5K CW Actuator Failsafe TP1 TP2 1 2 3 4 5 6 7 8 9 10 11 Battery Actuator +8V +4V Chassls Gnd Screw *The 5K remote speed potentiometer can be wired two different ways: 1. Connect 5KΩ potentiometer to terminal #9. Adjustable range is approximately 5% at 1800 RPM. 2. Connect 5KΩ potentiometer through resistor R to terminal #8 Reducing the value of R increases the remote adjustable speed range. **Cable A, B, C -- should purchase a cable with a wrapped mylar supported aluminum foil shield with a drain wire. ILS Exterral Speed Adjust Chassls Gnd Screw Bik Wht Magnenic Pick-up DIP Switch Description SW1 OFF for Diesel Engine ON for Gas Engine *** Remote speed potentiometer and 499K ohm resistor is B-C P/N (DYNS-10000) SW2 OFF for DYNA8000 actuator ON for DYNA8200 / 8400 actuator SW3 OFF for 24V I/O, ON for 12V I/O SW4 ON* compatible with DYN1-10652 SW5 ON* compatible with DYN1-10653 SW6 ON* compatible with DYN1-10654 SW7 ON* compatible with DYN1-10656 *When one of the SW4~7 is ON, set others of SW4~7 OFF DROOP GAIN Governor Controls Droop rate Adjustment MPU Output Gain Adjustment EG1065X 5 I SPEED Engine Stability Adjustment Engine Speed Adjustment

6. TROUBLESHOOTING 6.1 Problem: Governor Is Completely Dead And Actuator Lever Stays At Minimum Position When Power Is Applied To Governor. 6.1.1 Check battery voltage at terminals 1 and 2 on controller. Terminal 1 is positive. Check battery connections and contacts for turning power ON to the controller. 6.1.2 Check for proper linkage setup. Correct and free linkage. 6.1.3 Magnetic pickup signal absent or too low. Measure AC voltage across terminals 10 and 11 while cranking the engine. Voltage should be min. 2.5 VAC. NOTE : The voltmeter should have an impedance of 5000 ohms/volts or higher. Check pole tip gap over gear tooth. Should be 0.037 mm / 0.127 mm (0.015" / 0.005"). 6.1.4 Measure the resistance of the magnetic pickup coil. This should be above 150 ohms. If there is an open or shorted coil, replace the magnetic pickup. 6.1.5 Measure the resistance of each pin to the metal case of the magnetic pickup. No continuity should be evident. If there is continuity to case, replace the magnetic pickup. 6.1.6 DC SUPPLY OFF. Place an insulated jumper between terminals 2 and 3 (TP1 & TP2). With DC ON, the actuator should go to full stroke. DC voltage at terminals 4 and 5 should be within 3volts of the supply. If the actuator still does not move to full stroke, continue with steps below. 6.1.7 Measure actuator coil resistance: If actuator coil is open or shorted to case, replace actuator. If governor still does not operate, continue with steps below. 6.1.8 Measuring the resistance of each coil lead to the actuator case should indicate an open circuit on a low scale of the ohm meter. If continuity is detected, replace the actuator. 6.1.9 With the DC to the governor ON and the engine OFF, measure the DC voltage from terminal 6 (+) to terminal 2 ( ). This should be approx. 8 VDC. If 8 VDC is not present, replace the controller. 6.1.10 Between terminal 7 (+) to terminal 2 ( ), the voltage should be approx. 4 VDC. If 4 VDC is not present, replace the controller. 6.2 Problem: Actuator Goes To Full Stroke When Dc Power Is Turned On (Engine Is Not Operating). 6.2.1 Check magnetic pickup leads for proper shielded wire or open shield. Verify and correct wiring as necessary. 6.2.2 Be sure there is no jumper between terminals 2 and 3. Verify and correct wiring as necessary. 6.2.3 Failsafe circuit in the controller may be damaged or defective. Replace EG1065X. 6.2.4 With DC power OFF remove leads at actuator. Check continuity of each terminal to case. There should be no continuity between any terminal and case of EG1065X. If continuity is detected, replace the controller. 6.2.5 If remote speed potentiometer has been connected to terminals 6, 7 and 9 of the controller, DISCONNECT THESE LEADS. Turn DC power ON to the governor if the actuator is now normal. Proceed to step 6.3.1 6 EG1065X

6.3 Problem: Improper Operation From Remote Speed Potentiometer 6.3.1 Investigate wiring to remote speed potentiometer for open or shorted circuits. Check wiring. 6.3.2 If the leads at terminals 6 and 7 to the remote speed potentiometer are reversed, speed control by the remote speed potentiometer will be reversed. Correct wiring. 6.3.3 Lead wire to remote speed setting potentiometer should be 3-wire shielded cable. Verify that the drain shield wire is isolated from ground at the potentiometer. 6.3.4 If terminal 7 lead to the remote speed potentiometer is open, engine speed will go high. Correct the wiring. 6.3.5 If lead 9 (wiper lead to remote potentiometer) is open, there will be no control by the remote speed potentiometer. Verify and correct wiring. 6.3.6 If lead 6 to the clockwise terminal of the remote speed potentiometer is open, speed will remain at the value set in EG1065X. 6.4 Problem: Erratic Governor Operation 6.4.1 Measure DC voltage at 1 and 2 on controller terminal strip. Normal battery voltage should be indicated. If nominal voltage is present, wiring is correct. 6.4.2 Low battery voltage 20% below rated can cause erratic operation. Check battery and charging system. 6.4.3 RFI noise due to incorrect shielding. Correct wiring. 6.4.4 RFI noise fed through power supply leads. Connect power leads directly to the battery. 6.5 Problem: Slow, Small Amplitude Hunting Of Speed Or Frequency 6.5.1 Sticking or very loose linkage. Correct Linkage. 6.6 Problem: Fast Oscillation Of Governor Linkage 6.6.1 Verify calibration settings of the controller. Readjust settings as necessary. 6.7 Problem: Engine Will Not Start -- Actuator Goes To Full Fuel During Cranking 6.7.1 Make sure fuel is available. Check fuel to engine. Check for correct wiring to the automatic shutdown circuits. 6.7.2 Air may be trapped in fuel line. Check fuel lines for leaks. 6.7.3 Try to operate engine manually. EG1065X 7