Inverter Testing at Sandia National Laboratories*

Similar documents
Distinctive Features: Bidirectional solar PCU Hybrid inverter (Solar/ Grid/BATT) Vector Modulated Inverter Control Multiple DSP control operation

Solar inverter From Wikipedia, the free encyclopedia

Solar inverter AX-series

RULE 21 GENERATING FACILITY INTERCONNECTION APPLICATION SMUD s Distribution System - (SMUD FORM 2655)

Distinctive Features: Bidirectional solar PCU Hybrid inverter (Solar/ Grid/BATT) Vector Modulated Inverter Control Multiple DSP control operation

Regenerative Utility Simulator for Grid-Tied Inverters

MERU Solar Off-Grid Inverters

Photovoltaics. MPI Hybrid Series

Application. Battery. Public Grid GS HYBRID INVERTER

A Study of Lead-Acid Battery Efficiency Near Top-of-Charge and the Impact on PV System Design

JOINT SERVICE POWER EXPO CLARY CORPORATION

K50. Technical Sheet

K10. Technical Sheet

Solar PCU/Inverter 1 KVA to 100 KVA

X600. Technical Sheet

Draft Guideline for the connection of smallscale inverter based distributed generation. EEA Asset Management Forum 22 June 2016 Dr Richard Strahan

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY

Hardware Testing of Photovoltaic Inverter Loss of Mains Protection Performance

Microgrid with Solar Power and Fuel Cell Technology

TECHNICAL SPECIFICATIONS OF 2 KVA POWER CONDITIONING UNIT

POWER+ PREMIUM CBS. BS-EN Emergency electrical installations Electric power systems Emergency lighting Escape lighting

Presented at the 2012 Aerospace Space Power Workshop Manhattan Beach, CA April 16-20, 2012

Using the Phoenix MultiPlus to reduce operating cost of a generator

Battery Evaluation for Plug-In Hybrid Electric Vehicles

APC Smart-UPS. GUIDE SPECIFICATIONS FOR 1000VA & 2000VA Smart-UPS 230VAC Uninterruptible Power Supply

E-15 Uninterruptible Power Systems (UPS)

UNC-Charlotte's Power Engineering Teaching lab

TECHNICAL DATA SHEET KVA UPS Systemss

Uninterruptible Power Systems

Is Your Factory Power Source Corrupting Your Product Testing? September 2015 Author: Steve Boegle Engineering Group Leader, Behlman Electronics

Development of Novel Connection Control Method for Small Scale Solar - Wind Hybrid Power Plant

Optimal and Modular Configuration of Wind Integrated Hybrid Power Plants for Off-Grid Systems

ANALYZING POWER LOSSES AND THEIR EFFECTS IN COMPLEX POWER SYSTEMS

INVERTER. MECHANICAL DATA Steel with powder paint Dimension (mm) 527 x 228 x 190 Net Weight (kgs) 18 STANDAR. Cont output power at 20ºC. Cos φ 0.

CENTAURI ENERGY SERVER TECHNICAL DATA kw POWER

Definitions. Scope. Customer Generation Interconnection Requirements

APPLICATION NOTE TESTING PV MICRO INVERTERS USING A FOUR QUADRANT CAPABLE PROGRAMMABLE AC POWER SOURCE FOR GRID SIMULATION. Abstract.

Hydro-Piezoelectricity: A Renewable Energy Source For Autonomous Underwater Vehicles

Using Inverter Input Modes for Smart Grid Management

Control System for a Diesel Generator and UPS

Wind Turbine Emulation Experiment

E-15 Uninterruptible Power Systems (UPS)

Technical Specifications of Solar PCUs

OFF-GRID PV INVERTERS EssenSolar & Expert series. 1kW-5kW. Solution on Unstable or Remote Area without Utility

Grid Management Voltage Control Distribution Grid Voltage Regulation with DER. Michael Sheehan, P.E. IREC Pacific Northwest Solar Partnership

Net Metering Interconnection Requirements

POWER+ CLASSIC 20/30 KVA, 3X208 VAC WITH INTERNAL BATTERIES. GAMATRONIC, A SolarEdge Division

POWER+ CLASSIC 20/30 KVA, 3X208 VAC WITH INTERNAL BATTERIES. GAMATRONIC, A SolarEdge Division

NET METERING PROGRAM. Technical Interconnection Requirements

Document Requirements for Engineering Review- PV Systems v1.1 12/6/2018

12-Batteries and Inverters. ECEGR 452 Renewable Energy Systems

Initial Project and Group Identification Document. Senior Design I EEL Off-Grid Clean Energy Power Generation

Using OutBack Inverters for 3-Phase 480V Applications

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase

2017 Southeastern Tri Regional SAME Training Symposium Microgrids What are they, lessons learned 8/30/2017 Dan Dorn Eaton Corp

Power Conversion Systems 2005/2006. Schaefer the Power to make it happen.

X400. Technical Sheet

SmartOnline S3MX Series 3-Phase 380/400/415V 60kVA 54kW On-Line Double-Conversion UPS

ABB n.v Power Quality in LV installations

TECHNICAL DATA SHEET INFINITY kva 3Ph(in) 3Ph(out)

Power Electronics & Drives [Simulink, Hardware-Open & Closed Loop]

Copyright 2003 Advanced Power Technologies, Inc.

Power+ CLASSIC. 20/30 kva, 3x208 Vac

Residential Smart-Grid Distributed Resources

EFFEKTA Power Supplies

Magellan Stand Alone Power System (3P) Magellan Renewables Range

Customer and Utility Energy Management Fundamentals 101

User Manual 1KVA-5KVA INVERTER / CHARGER

OPTIMIZING COMMERCIAL SOLAR

ILLUMINATOR LV. Emergency Lighting Inverter System 175VA through 750VA. Illuminator Series LV Single Phase

Grid Stability Analysis for High Penetration Solar Photovoltaics

White Paper. Application of Resistive/Reactive Load Banks for kva Testing

BATTERY CHARGERS.

SAE E-motor Symposium 2012 Advanced Motor and Drive Testing. D & V Electronics Ltd.

How To AC Couple Grid Tied Inverters with OutBack Frequency Shifting Inverters

Configuration Diagrams

TERMS AND CONDITIONS

User Manual 1KVA-5KVA INVERTER / CHARGER

Magellan Stand Alone Power System (1P) Magellan Renewables Range

Glossary. * Credit for glossary starter: Florida Solar Energy Center. August 2015 PV Installer's Course: Glossary 1

DER Commissioning Guidelines Community Scale PV Generation Interconnected Using Xcel Energy s Minnesota Section 10 Tariff Version 1.

Technologies for ToT & Power Electronics Test Facility. under NaMPET-II CDAC, Thiruvananthapuram

There are two leading power conversion technologies used in formation charging rectifiers

Code Calculations. for an Off-Grid PV System

3 Uninterruptible Power Systems

off-grid Solutions Security of supply Basics: Off-grid energy supply

14 October 09 Vas Kandiah AOQ SSMBB

3 Uninterruptible Power Systems

3 Uninterruptible Power Systems

Uninterruptible Power Systems

VFD Best Practices: Getting the Most from Your VFD Investment

HQST 500W (12V) HQST 1000W (12V) Modified Sine Wave Inverter. User Manual

Solar Inverter Manual

400W / 600W / 1000W / 1500W DIY Wind Turbine

Energy 142 NABCEP (North American Board of Certified Energy Practitioners) Entry Level Test Review. System Components

Illuminator Series CM. GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION. 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System

DRAFT. Guidelines on Power quality & safety issues in usage of roof-top solar pv system CENTRAL ELECTRICITY AUTHORITY

Net Metering Interconnection Requirements. Customer Generation Capacity Not Exceeding 100 kw. Date: Version: 1

Solar Hybrid Inverter SP Efecto Series

Questions Section: Do you have questions that aren't covered? Please contact us!

Transcription:

Inverter Testing at Sandia National Laboratories* Jerry W. Ginn Russell H. Bonn Greg Sittler Photovoltaic System Components Department Sandia National Laboratories PO Box 5800 Albuquerque, NM 87185-0752 Abstract. Inverters are key building blocks of photovoltaic (PV) systems that produce ac power. The balance of systems (BOS) portion of a PV system can account for up to 50% of the system cost, and its reliable operation is essential for a successful PV system. As part of its BOS program, Sandia National Laboratories (SNL) maintains a laboratory wherein accurate electrical measurements of power systems can be made under a variety of conditions. This paper outlines the work that is done in that laboratory. TESTING ACTIVITIES Inverter testing at SNL thus far has fallen into one or more of the following three categories. Benchmark Testing Tests have been designed and performed to benchmark the performance of inverters. The primary goal of benchmark testing is to provide information on inverter performance over a standardized set of tests. This is important because * This work was supported by the United States Department of Energy under Contract DE-AC04-94AL85000. Sandia is a multi-program laboratory operated by Sandia Corporation, a Lockheed Martin Company, for the United States Department of Energy.

of the variations in the manner in which inverters have been rated and specified by the manufacturers. For example, inverter efficiency is often reported as a single number without regard for load characteristics which affect efficiency significantly. These tests are intended to provide information which is useful to PV system integrators in selecting an inverter for a specific application and in anticipating its performance under a variety of conditions. Development Testing The purpose of development testing is to assist inverter manufacturers in their development of a technological innovation or refinement of their product. Consequently, the manufacturers are the primary customers for development test results. This service can be significant because creating, equipping, maintaining, and operating a test facility is, in many cases, prohibitively expensive. Key elements of the facility which can be useful include a variety of loads, dc and ac sources, and diagnostic equipment. Acceptance Testing In a few cases, inverters have been tested to verify that their laboratory performance meets government contractual requirements. The customers in this case are the end users of the equipment. Since some of the capabilities of the inverter may be new, acceptance testing has typically followed a preliminary period of development testing. Two examples of acceptance testing are a 250- kva Kenetech hybrid inverter for the Dangling Rope Marina at Lake Powell, Utah, and a 300-kVA Abacus Controls, Inc. hybrid inverter for the U.S. Navy s Superior Valley installation at China Lake, California. APPLICATION CATEGORIES Inverter hardware can be grouped into the following four categories. Stand-Alone Inverters operating in a stand-alone mode provide ac power from a dc battery. They range in power capability from hundreds of watts to a few kilowatts. Because their market is relatively substantial, including recreational vehicles, boats, off-grid homes, and any application requiring remote operation of ac equipment, many thousands of these units have been manufactured. Consequently, the technology involved in stand-alone inverters is relatively

mature. SNL purchases these inverters for bench-mark testing. Issues of interest include load compatibility, power quality, and safety of operation. Small Grid-Tied Grid-tied inverters take dc power either from a battery or directly from a PV array and provide ac power to the utility grid. The only grid-tied inverters that have been produced in quantity have had a capacity of a few kilowatts. Typically, they have been produced in response to projects that are least partially subsidized by a utility and/or by the government. The total number that have been manufactured is certainly less than the number of stand-alone inverters, but still in the hundreds. The technology associated with grid-tied inverters is relatively mature. SNL purchases these inverters for bench-mark testing. Issues of interest are those required to provide confidence on the part of potential utility customers, including power quality, safety of operation, islanding protection, and overall reliability. Small Hybrid Small hybrids have evolved from small stand-alone inverters. They typically have single-phase ac outputs with power ratings of a few kilowatts. They can operate in a stand-alone mode but also have the capability to interact with a secondary ac source, such as the utility grid or a backup generator. The secondary source is requested by the inverter controls to recharge the battery and/or to power loads when necessary. Variations in control schemes are possible. The manufacturer typically provides the inverter to SNL for evaluation. Issues of interest include load compatibility, voltage regulation, power quality, site control, and safety. Large Hybrid Large hybrid inverters can range in size from tens to hundreds of kilowatts and generally have three-phase outputs. Applications for these units are remote military installations and remote village power. Because only a few have been produced, the technology is still under development. The inverter is normally purchased by the end-user. Testing at SNL assists in the final development and may serve as a partial functional acceptance test prior to a final field acceptance test. Issues include load compatibility, voltage regulation, power quality, site control, and safety. Of these, the most challenging has been the control issue.

SANDIA POWER-CONDITIONING SYSTEMS TEST FACILITY Data Acquisition System Sandia maintains a laboratory capable of measuring performance of powerconditioning equipment ranging in size from a few hundred watts to hundreds of kw. Voltages and currents are acquired on both ac and dc sides of the equipment and are analyzed to evaluate key parameters including efficiency, distortion, output regulation, and load compatibility. Data is acquired in both averaging and high-speed waveform-acquisition modes. The data-acquisition system uses a 16-bit, 100 khz digitizer controlled by a National Instruments Labview program. Data is plotted in Microsoft Excel format. Backup instruments for independent corroboration of data include: oscilloscopes, digital multimeters, dynamic signal analyzers, spectrum analyzers, and audio analyzers. Additional quantities which can be evaluated include conducted and radiated radio-frequency emissions, and audible noise. Hardware Loads Programmable resistive bank: 150 kw, 480 V, 3-phase Programmable inductive bank: 225 kvar, 480 V, 3-phase Manual resistive bank: 360 kw, 480 V, 3-phase Nonlinear bank: 50 kva, 277 V Motors: 3-phase to 10 hp, 1-phase to ¾ hp with dynamometer and computer control AC Sources Main power grid: 500 kva, 480 V Separately-derived power grid: 50 kva, 120/240 V Permanent onsite diesel generator: 92.5 kva, 480 V with remote-start panel Temporary generator: wiring and switchgear provision for up to 500-kVA ac motor-generator: 150 kva, 480 V

DC Sources Photovoltaic arrays: 30 kw configurable (2 each) Photovoltaic simulators: 64 kw and 11 kw Power supplies: 350 V, 35 A (3 each) and 55 V, 180 A (2 each) dc motor-generator: 115 kw, 700 V Battery Storage 720 kwh bank of 288 cells with 1250 AH capacity, configurable to 576 Vdc in 24-V increments 52.8 kwh bank of 24 cells with 1100 AH capacity, configurable to 48 Vdc in 6-V increments Lightning Simulator Voltage and current surge generator: Velonix Model 587 TESTING EXAMPLES Stand-Alone Example: Trace DR1524 Benchmark Test The standardized set of tests for evaluation of stand-alone inverters results in a two-page test report. The report associated with the 1.5-kW quasi-sine wave Trace DR1524, is shown in the appendix. Efficiency is plotted for various loads. For all inverters, efficiency is not a single value, but is a function of load type and magnitude. Voltage and frequency regulation and voltage distortion are tabulated for a variety of loads. Regulation is very good, whereas distortion is extremely high due to the quasi-sinusoidal waveform. If battery charging is a capability of the inverter, it is characterized in a table. Overloads are applied and the results are tabulated and compared to the manufacturer s specifications. Copies of the test reports for five different stand-alone inverters are available on Sandia s PV website: http://www.sandia.gov/renewable_energy/photovoltaic/pv.html

Large Hybrid Example: Kenetech Development/Acceptance Test The standardized set of tests for evaluation of hybrid inverters results in a fourpage test report. Tests of the inverter (dc-to-ac) mode of operation are analogous to those for stand-alone inverters. In addition, a series of tests summarizes interactions with the generator. Copies of the test reports for two different large hybrid inverters are available on the web site, one of which is that for the 250-kW Kenetech unit developed for Dangling Rope Marina. Development testing was especially useful in this case, since this was a new product for Kenetech. Their company had extensive experience with windpowered, grid-tied applications, but little with PV and none with batteries. As a result, their factory testing concentrated on verifying sub-system functionality. Compromises in their factory testing resulted from the lack of a generator, batteries, PV, or realistic nonlinear loads, all of which SNL was able to provide. Tracking of the maximum-power point was refined and tuned, the battery charge algorithm was updated, and a number of inverter/generator transfer issues were uncovered in a relatively short period of time. This testing served as the laboratory portion of the contract acceptance tests. The inverter met all specifications; however, the voltage imbalance among phases was significant for severe load imbalances. This is shown in Figure 1. Kenetech was apprised of this result and was confident that by deriving feedback from the load side of the output transformer and changing the control algorithm, the voltage imbalance could be acceptably reduced in future products. Grid-Tied: Development of Benchmark Test A test plan for grid-tied inverters has been developed and is available for review at Sandia s PV web site. Parameters of interest include efficiency, distortion, radio-frequency interference, maximum power tracking effectiveness, dc and ac operating ranges, acoustic noise, control features, anti-islanding effectiveness, and restart following utility outage.

70000 60000 Unbalanced resistive loads 300 290 50000 280 Power 40000 30000 20000 Pla Plb Plc Vla Vlb Vlc 270 260 250 Voltage 10000 240 0 230 9:41 9:42 9:43 9:44 9:45 9:46 9:47 9:48 9:49 Time FIGURE 1. Unbalanced voltages resulting from unbalanced loads (Phase A varied in 10 kw steps with a fixed resistive load on phases B and C) temperature. Test results will be provided to manufacturers to assist their product development. Another goal of long-term testing is to obtain a statistically significant quantity of data for use in developing IEEE Standard 929, IEEE Recommended Practice for Utility Interface of Residential and Intermediate Photovoltaic Systems. This data and IEEE 929 will help utilities assess reliability and any potential negative impact on their systems. Grid-tied inverters to be characterized fall into two groups, both of which will be treated identically in the test. The first group includes inverters similar to those that have been installed by the Sacramento Municipal Utility District (SMUD), the Environmental Protection Agency (EPA) PV project and others. These include the 4-kW Omnion 2400, 3-kW Pacific Inverter PI-3000, 4-kW Trace 4024, 5-kW Abacus Sunverter, and a 2.2-kW inverter by Sanrex, a Japanese manufacturer. The second group includes module-scale inverters, which are mounted permanently as an integral part of a PV module. The two manufacturers that have developed hardware of this type for the PV Mat initiative are Ascension Technologies and Solar Design Associates, which uses an AES inverter. Module-scale inverters manufactured by Trace Engineering and Evergreen are also planned to be included.

SUMMARY The goal and future direction for the three types of SNL inverter testing are as follows. Benchmark testing will: 1. result in a standardized method for evaluating inverters 2. influence government specifications 3. provide useful information to system integrators 4. reassure utilities that PV inverters will not interfere with their operation Development testing will: 1. support PVMat, SNL R&D in reliability, and inverter manufacturers 2. be coordinated with system requirements to ensure best possible design Laboratory acceptance testing will: 1. reduce field down time by early detection of problems 2. provide useful information on system performance 3. support users with potentially significant market impact All SNL testing is under continuous development. Suggestions are actively solicited.

Appendix: Stand-Alone Inverter Test Report of the Trace DR1524 1.5-kW Quasi-Sine-Wave Inverter manufacturer s specifications Model Evaluated DR1524 Output voltage 120 Vac Rated Power 1500 W Distortion N/A Rated volt-amps not specified dc disconnect voltage 22 Vdc Surge power 4500 W dc float voltage N/A Efficiency 94% (maximum) Max charge rate N/A dc evaluation using 200 A-H battery (Trojan T-105) Parameter Quantity Inverter Mode battery disconnect voltage 21.2 Vdc Charge Mode dc ripple voltage peak (float) 1.1 V dc ripple current peak (float) 28 A at 2.3A float battery float voltage 26.6 Vdc charging efficiency 91% average 95 efficiency 105 90 90 85 efficiency 75 % Efficiency 80 75 dc current 60 45 dc Current 70 30 65 15 Efficiency for a resistive load 60 0 0 250 500 750 1000 1250 1500 1750 volt-amps

95 90 85 pf = 1 % Efficiency 80 75 70 pf =.72 pf =.53 65 Efficiency for an RL Load pf =.32 60 0 250 500 750 1000 1250 1500 1750 volt-amps 95 90 85 % Efficiency 80 75 resistive load only 430 watts (840 VA) of NL load 1 70 65 Efficiency for a R load in parallel with a nonlinear load 60 0 250 500 750 1000 1250 1500 1750 volt-amps 95 90 Resistive load only 85 % Efficiency 80 75 430 watts (840 VA) of NL load 1 plus inductive load 70 pf = 0.5 no NL load 65 Efficiency for a complex load 60 0 250 500 750 1000 1250 1500 1750 volt-amps

voltage and frequency regulation, and distortion Note: Regulation is referenced to no-load values of 118.7 Vac and of 60.00 Hz. Test Configuration % voltage % frequency % voltage regulation regulation distortion % full load (PF = 1.0) no load 0 0 42 20% full load 2.4 0.0 37 50% full load 3.0 0.0 27 90% full load 2.9 0.0 28 100% full load 2.1 0.0 31 full load reactive PF =.5 1.2 0.0 31 PF =.72 1.1 0.0 32 non-linear loads in parallel with R NL = 56% of rated VA (VA @ 75%) 3.6 0.0 27 NL = 56% of rated VA (VA @ 100%) 3.5 0.0 33 motor loads motor only 2 motor plus R = 100% full load 2 inverter overload Test Configuration Planned Load Duration Measured Load Duration Manufacturer s Specification Measured Power Level full load 5 hours 5 hours 1500 W 1550 W full load + 20% 15 minutes 15 minutes not specified 1600 W 3 full load + 50% 1 minute 1 minute not specified 1690 W 3 full load + 100% 30 seconds 30 seconds not specified 1830 W 3 motor starting SNL line motor only initial ac voltage (rms) 117 voltage sag 9% voltage regulation 1% surge current (peak amps) 85 time to steady state (seconds) 0.13 steady-state voltage (rms) 117 steady-state current (rms) 12 inverter inverter fully motor only loaded Comments 1 Nonlinear load drew 430 W (840 VA) when connected to grid and 390 W (520 VA) when connected to inverter 2 inverter would not start ¾-hp motor load 3 ac output voltage was reduced; target power levels of 1800 W, 2250 W, and 3000 W could not be achieved