GmbH Lufttechnik Dresden USER INFORMATION ROOF FANS SERIES VRV vertical outlet Issue 07/02
Roof fans made of plastic materials Series VRV with vertical outlet Usable in ventilation engineering of all branches of industry High chemical resistivity by encapsulated motors and use of plastic materials Low noise emission Volumetric flow Pressure increase up to 4,200 m³/h up to 700 Pa Explosion-proof versions according to European Directive 94/9/EG (ATEX) Installation accessories such as roof bases, noise absorption bases etc. Wide range of electrical accessories upper housing shell half motor cover motor cooling air pipe motor knee repair switch impeller lower housing half shell rain water outlet flange intake socket Data specified herein are subject to alteration without prior notice. They will not be valid without written confirmation by the manufacturers.
Roof fans of plastic materials Series VRV Technical explanation APPLICATION Good corrosion resistance makes the type VRV Roof fans with vertical outlet suitable preferably for process exhaust systems in the chemical and pharmaceutic industries, for ventilation of laboratories, battery rooms, pickling plants, laundries, galvanic and agricultural units etc. The medium to be conveyed is taken in axially and blown out vertically with high speed. This allows good mixing with the environment. Certain demands of environmental control, such as German standard DIN 1946, part 7 (Room ventilation systems for laboratories), can thus be met. Roof fan VRV with sound absorbing base SDS TECHNICAL DESCRIPTION The fans are made in five nominal sizes with four different housing sizes. All parts getting into contact with the medium conveyed are made of PP (other materials upon inquiry). Plastic covers protect steel components against corrosion. The impellers curved backward are balanced dynamically according to ISO 1940. The housing is split horizontally to facilitate maintenance and cleaning of the fan and the pipeline connected. The driving motor is encapsulated completely so that contact with the medium conveyed is ruled out. Cooling air is fed in separately from outside. The fan is connected to pipelines or the matched accessories by a stable flange (dimensions according to MIETZSCH factory standard MWS 3030). CONDITIONS OF USE permissible ambient temperature -30... +40 C permissible temperature of volume flow -30... +50 C Higher temperatures are speed-dependent and permissible after the manufacturers agreement. Aggressive gases and vapours can be conveyed. The plastic materials used lead to good resistance to acids, lyes, alcohols, benzines etc. Even dust-laden media can be conveyed. Consultation with the manufacturers is necessary in cases of doubt. Working range The fan always operates in stable regime and can be applied even outside the characteristic range specified. Permissible inclination of fan axis (slope of roof) ±10 ACCESSORIES Splinter guard, assembly plate, assembly plate with non-teturn flap, sound-absorbing base, base for corrugated roofs, motor protction switch, pole changer, fan controls, frequency inverter EXPLANATION OF TYPE DESIGNATIONS VRV 160 / 711 W 1450 P 1 radial fan, vertical outlet nominal size (impeller intake diameter/mm) impeller type direct drive nominal speed rpm (higher speed of pole-changing motors abbreviations for special designs E TS P1 P2 EX DD = single-phase drive = with thermal winding protection (PTC resistor) = speed halving (Dahlander) such as 1450 P1 = 1,450/710 rpm = changeover to next smaller speed such as 1450 P2 = 1,450/950 rpm = with explosion-proof motor = delta motor connection for inverter regime with 3 x 230 V 03
PERFORMANCE p fa / Pa 200 150 100 VRV 100 / 711 2,900 rpm Design features - Impeller with vanes curved backward - Welded plastic housing - Various fastening versions by flange - Drive motor encapsulated completely - Repair switch with auxiliary contact fastened on fan 1,450 50 ρ = 1,2 kg/m³ 0 0 100 200 300 400 500 volumetric flow m³/h PRINCIPAL DIMENSIONS Performance sizes According to DIN 24 163, roof fans are specified by their pressure difference for free blowout: p fa = p bar - p ges S = p bar - p stats - r/2 * c S 2 In the desired working point, this pressure difference must be greater than the intake side pressure loss. Flange dimensions Ø 400 484 D L = 8 x 7 Ø 160 D LK = 200 MOTOR VERSIONS (other motors, such as single-phase or Ex, upon inquiry) nominal motor nominal motor weight fan type speed motor type power current with motor L A3m L WA rpm kw A kg db(a) db(a) VRV 100/711 1,450 0.12 0.42 11 45 62 W 1450 3 ~ VRV 100/711 2,900 400 V/50 Hz 0.18 0.51 12 51 68 W 2900 IP 55 VRV 100/711 2,900 3 ~ 0.20 0.58 13 51 68 W 2900 P1 1,450 polechanging 0.15 0.51 45 62 VRV 100/711 1,450 400 V/50 Hz 0.20 0.71 13 45 62 W 1450 P1 710 IP 55 0.05 0.30 33 50 L A3m = A - weighted sound pressure level at distance of 3 m L WA = A - weighted sound power level in duct 04
PERFORMANCE p fa / Pa 500 450 400 350 300 250 200 150 100 50 0 VRV 160 / 711 2,900 rpm 1,450 950 ρ = 1,2 kg/m³ 0 500 1000 1500 2000 volumetric flow m³/h PRINCIPAL DIMENSIONS Design features - Impeller with vanes curved backward - Welded plastic housing - Various fastening versions by flange - Drive motor encapsulated completely - Repair switch with auxiliary contact fastened on fan Performance sizes According to DIN 24 163, roof fans are specified by their pressure difference for free blowout: p fa = p bar - p ges S = p bar - p stats - r/2 * c S 2 In the desired working point, this pressure difference must be greater than the intake side pressure loss. Flange dimensions Ø 550 610 D L = 12 x 7 D LK = 290 Ø 250 MOTOR VERSIONS (other motors, such as single-phase or Ex, upon inquiry) nominal motor nominal motor weight fan type speed motor type power current with motor L A3m L WA rpm kw A kg db(a) db(a) VRV 160/711 950 0.09 0.44 14 34 48 W 950 3 ~ VRV 160/711 1,450 400 V/50 Hz 0.12 0.42 14 38 54 W 1450 IP 55 VRV 160/711 2,900 0.37 1.0 16 53 70 W2900 VRV 160/711 2,900 0.43 1.3 17 53 70 W 2900 P1 1,450 3 ~ 0.30 0.89 38 54 VRV 160/711 1,450 polechanging 0.20 0.71 16 38 54 W 1450 P1 710 400 V/50 Hz 0.05 0.30 30 46 VRV 160/711 1,450 IP 55 0.18 0.58 16 38 54 W 1450 P2 950 0.06 0.35 34 48 L A3m = A - weighted sound pressure level at distance of 3 m L WA = A - weighted sound power level in duct 05
PERFORMANCE p fa / Pa 700 600 500 400 300 VRV 200 / 712 2,900 rpm Design features - Impeller of PP, glass fibre-reinforced, with vanes curved backward - Welded plastic housing - Various fastening versions by flange - Drive motor encapsulated completely - Repair switch with auxiliary contact fastened on fan 200 1,450 100 950 710 ρ = 1,2 kg/m³ 0 0 500 1000 1500 2000 2500 3000 volumetric flow m³/h PRINCIPAL DIMENSIONS Performance sizes According to DIN 24 163, roof fans are specified by their pressure difference for free blowout: p fa = p bar - p ges S = p bar - p stats - r/2 * c S 2 In the desired working point, this pressure difference must be greater than the intake side pressure loss. Flange dimensions Ø 550 610 D L = 12 x 7 D LK = 290 Ø 250 MOTOR VERSIONS (other motors, such as single-phase or Ex, upon inquiry) nominal motor nominal motor weight fan type speed motor type power current with motor L A3m L WA rpm kw A kg db(a) db(a) VRV 200/712 710 0.09 0.36 15 34 51 W 710 VRV 200/712 950 3 ~ 0.18 0.62 15 35 52 W 950 400 V/50 Hz VRV 200/712 1,450 IP 55 0.25 0.76 15 42 59 W 1450 VRV 200/712 2,900 0.75 1.73 18 57 75 W2900 VRV 200/712 2,900 0.70 1.75 18 57 75 W 2900 P1 1,450 3 ~ 0.18 0.47 42 59 VRV 200/712 1,450 polechanging 0.20 0.71 16 42 59 W 1450 P1 710 400 V/50 Hz 0.05 0.30 34 51 VRV 200/712 1,450 IP 55 0.18 0.58 16 42 59 W 1450 P2 950 0.06 0.35 35 52 L A3m = A - weighted sound pressure level at distance of 3 m L WA = A - weighted sound power level in duct 06
PERFORMANCE p fa / Pa VRV 250 / 711 350 300 1,450 rpm 250 200 150 950 100 50 710 ρ = 1,2 kg/m³ 0 0 500 1000 1500 2000 2500 volumetric flow m³/h PRINCIPAL DIMENSIONS Design features - Impeller with vanes curved backward - Welded plastic housing - Various fastening versions by flange - Drive motor encapsulated completely - Repair switch with auxiliary contact fastened on fan Performance sizes According to DIN 24 163, roof fans are specified by their pressure difference for free blowout: p fa = p bar - p ges S = p bar - p stats - r/2 * c S 2 In the desired working point, this pressure difference must be greater than the intake side pressure loss. Flange dimensions Ø 750 790 D L = 12 x 9 D LK = 360 Ø 315 MOTOR VERSIONS (other motors, such as single-phase or Ex, upon inquiry) nominal motor nominal motor weight fan type speed motor type power current with motor L A3m L WA rpm kw A kg db(a) db(a) VRV 250/711 710 0.09 0.36 30 38 53 W 710 3 ~ VRV 250/711 950 400 V/50 Hz 0.18 0.62 31 41 56 W 950 IP 55 VRV 250/711 1,450 0.37 1.03 31 49 65 W 1450 VRV 250/711 1,450 0.50 1.28 31 49 65 W 1450 P1 710 3 ~ 0.10 0.57 38 53 VRV 250/711 1,450 polechanging 0.40 1.38 31 49 65 W 1450 P2 950 400 V/50 Hz 0.12 0.51 41 56 VRV 250/711 950 IP 55 41 56 W 950 P2 710 38 53 L A3m = A - weighted sound pressure level at distance of 3 m L WA = A - weighted sound power level in duct 07
PERFORMANCE p fa / Pa 600 500 400 300 200 100 0 VRV 315 / 712 1,450 rpm 950 710 ρ = 1,2 kg/m³ 0 1000 2000 3000 4000 5000 volumetric flow m³/h PRINCIPAL DIMENSIONS Design features - Impeller of PP, glass fibre-reinforced, with vanes curved backward - Welded plastic housing - Various fastening versions by flange - Drive motor encapsulated completely - Repair switch with auxiliary contact fastened on fan Performance sizes According to DIN 24 163, roof fans are specified by their pressure difference for free blowout: p fa = p bar - p ges S = p bar - p stats - r/2 * c S 2 In the desired working point, this pressure difference must be greater than the intake side pressure loss. Flange dimensions Ø 750 800 D L = 12 x 9 D LK = 444 Ø 400 MOTOR VERSIONS (other motors, such as single-phase or Ex, upon inquiry) nominal motor nominal motor weight fan type speed motor type power current with motor L A3m L WA rpm kw A kg db(a) db(a) VRV 315/712 710 0.18 0.75 39 48 65 W 710 3 ~ VRV 315/712 950 400 V/50 Hz 0.37 1.2 39 50 68 W 950 IP 55 VRV 315/712 1,450 0.75 1.86 40 61 78 W 1450 VRV 315/712 1,450 0.70 1.76 41 61 78 W 1450 P1 710 3 ~ 0.15 0.77 48 65 VRV 315/712 1,450 polechanging 0.80 2.10 42 61 78 W 1450 P2 950 400 V/50 Hz 0.25 1.05 50 68 VRV 315/712 950 IP 55 50 68 W 950 P2 710 48 65 L A3m = A - weighted sound pressure level at distance of 3 m L WA = A - weighted sound power level in duct 08
Roof fans of plastic materials Series VRV Accessories Assembly plate MPL - VRV The assembly plate MPL-VRV is used for fastening the VRV Roof fans on flat roofs and foundations. The flange with nominal diameter DN is employed for fan fastening. Fastening elements and a seal are in the range of delivery. Diameter D1 on the connection side is smooth. The plate should be supported on its entire face. Careful sealing toward the roof is important. Special designs: with non-return flap with rain water edge base height H = 300 mm pipe connection (with welded socket) design for pitched roof. optional with non-return flap optional with rain water edge Special dimensions and variants for particular roof designs and foundations upon inquiry. Material: PPs (PVC) Designation: MPL - VRV D N - D 1 fan type type of D N D 1 a H L assembly plate mm mm mm mm mm VRV 100/711 MPL-VRV 160-160 160 160 500 60 300 MPL-VRV 160-110 160 110 500 60 300 VRV 160/711 MPL-VRV 250-250 250 250 560 60 300 MPL-VRV 250-160 250 160 560 60 300 VRV 200/712 MPL-VRV 250-250 250 250 560 60 300 MPL-VRV 250-200 250 200 560 60 300 VRV 250/711 MPL-VRV 315-315 315 315 800 60 500 MPL-VRV 315-250 315 250 800 60 500 VRV 315/712 MPL-VRV 400-400 400 400 800 60 500 MPL-VRV 400-315 400 315 800 60 500 Sound-absorbing base SDS - VRV The sound-absorbing base is used for damping the sound power in the suction line. The absorber material is incombustible according to DIN 4102 and covered with glass wool and perforated plates. The flange with nominal diameter DN is employed for fan fastening. Fastening elements and a seal are in the range of delivery. Connecting diameter D1 is designed as a socket. The base should be supported on its entire face. Careful sealing toward the roof is important. Special designs: with non-return flap with rain water edge with sealing plate or rain water collar with cable bushing design for pitched roof. Special dimensions and variants for particular roof designs and foundations upon inquiry. optional with sealing plate (for roof insulation) socket (welded on) optional with rain collar (for roof insulation) Material: PPs (PVC) Designation: SDS - VRV D N - D 1 fan type base type DN D1 Da a H De mm mm mm mm mm db VRV 100/711 SDS-VRV 160-160 160 160 400 650 500 13 SDS-VRV 160-110 160 110 400 650 500 27 VRV 160/711 SDS-VRV 250-250 250 250 500 750 500 10 SDS-VRV 250-160 250 160 500 750 500 19 VRV 200/712 SDS-VRV 250-250 250 250 500 750 500 10 SDS-VRV 250-200 250 200 500 750 500 14 VRV 250/711 SDS-VRV 315-315 315 315 560 810 1000 16 SDS-VRV 315-250 315 250 560 810 1000 24 VRV 315/712 SDS-VRV 400-400 400 400 750 900 1000 15 SDS-VRV 400-315 400 315 750 900 1000 19 09
Series VRV Outlet silencer ASD Dimensions / Noise absorption The circular silencer welded on the upper housing half shell leads to noise absorption on the outlet side which is 7 db better than the standard design. fan type D N H ges D e mm mm db VRV 100/711 - ASD VRV 160/711 - ASD 250 1000 7 VRV 200/712 - ASD 250 1000 7 VRV 250/711 - ASD 315 1190 7 VRV 315/712 - ASD 400 1300 7 Material: PPs (PVC) Example how to order: Roof fan VRV 160 and 1,450 rpm with outlet silencer: VRV 160 / 711 W 1450 - ASD 10
No. Quantity Designition Individual price EUR Overall price EUR Roof fan of plastic material vertical outlet Mietzsch Lufttechnik - series VRV radial impeller with vanes curved backward of PPs (PVC) or glass fibre-reinforced PP, balancing quality G 6.3 according to ISO 1940, fly-mounted on motor shaft split conical housing with vertical inlet and outlet, made of PPs (PVC), intake nozzle shaped aerodynamically fastening with assembly plate MPL or sound-absorbing base SDS with flange direct drive by standard motor encapsulated against flowing medium, version for single-phase AC or three-phase current, two-, four-, six- or eight-pole, polechanging optionally motor optionally with thermal winding protection (PTC resistor) repair switch with auxiliary contact, fastened on fan safety requirements according to VDMA 24 167 VRV _ / 71 _ W - - nominal size impeller type nominal speed special design material volumetric flow : m 3 /h pressure increase free outlet : Pa temperature of medium conveyed : C motor power : kw voltage / frequency : V Hz nominal currant : A power input : kw fan speed : rpm noise level L A3m : db(a) weight : kg connection diameter : mm Accessories and special equipment 1) Assembly plate MPL - VRV Assembly plate MPL-VRV with non-return flap Sound-absorbing base SDS - VRV Outlet silencer ASD Motor protection switch Other elements 1) delete as applicable 07/02
Our program of products and services Radial fans of plastic material Direct and belt drive up to about 80 000 m³/h and 3 500 Pa Explosion-proof fans according to ATEX for zone 1 and zone 2 Roof fans of all-plastic design with many assembly accessories Special fans Duct built-in devices, mobile radial fans Systems for central ventilation in housing construction, special-purpose fans, exhaust elements, controlling and regulating devices Complete plants of plastic materials for industry and craft, laboratory and process exhaust systems, air cleaning plants Ventilation components of plastic material Pipes, ducts, fittings, flaps, gas-tight shutoff flaps, exhaust air heads, deflector hoods, exhaust hoods, filter cases, volume flow controller etc. Droplet eliminators and moisteners Gas washers for separation of gaseous dangerous substances, dust/gas separators Heat exchangers for recovery of heat from moist and aggressive exhaust air Containers of PVC, PP, PE for liquids endangering water, according to water resources regulations, containers of composite design PVC/GFRP, PP/GFRP Controlling and regulating elements and systems Switches, motor protection devices, speed controllers, frequency inverter, fan controls, flow supervision Special designs of plastic materials Devices, linings etc. Engineering performances Planning, calculation, and design, ventilation measurement on standardized test stands, low and high temperature test in company-own climatic test chambers Rectangular and cylindrical silencers, silencing casings in corrosion-proof design Großenhain Moritzburg Dresden-Neustadt exit BERLIN COTTBUS BAUTZEN Dresden-Hellerau exit Dresden-Wilder Mann exit Hubertusplatz FRANKFURT A.M. CHEMNITZ LEIPZIG DRESDEN 51 05 06 N 13 43 32 O Trachenberger Platz Dresden-city center GmbH Lufttechnik Dresden Großenhainer Straße 137 01129 Dresden Telefon: (0351) 8433 0 FAX: (0351) 8433 160 e-mail mietzsch@mietzsch.de Internet http://www.mietzsch.de