W Datasheet: Residual current circuit breaker, series PRIORI, 10kA, Typ B W SCHRACK-INFO All-current sensitive RCCB ( type B, B+ and Bfq) B+ types also meet the requirements of superior fire-protection systems No monthly test required Residual current indicator with 3 LED Warning before the RCD trips in case of leakage currents with an integrated auxiliary contact 4-pole types can also be used as 2-pole devices for photovoltaic applications Real contact position indicator Fault current tripping indicator Automatic re-setting possible W Technical datas Standards Types B and Bfq acc. to IEC/EN 61008, IEC/EN 62423 Type B+ acc. to VDE 0664-400 Type G/B and G/B+ additional acc. to ÖVE E 8601 Poles 4-pole Type B, B+, Bfq Sensitivity Alternating, pulsed and direct currents Rated current I n 25A, 40A, 63A Rated voltage U n 240/415 VAC, 50 Hz PAGE 1/11
Operation voltage electronic 50 456 VAC Voltage range test circuit 30mA 196-264V AC Rated tripping current I Δn 300mA 196-456V AC 30mA, 300mA Tripping time Type G IΔn 10ms and 300ms No tripping residual current I Δno Rated insulation voltage U i Rated impulse withstand voltage U imp Rated short circuit capacity I cn 2 xiδn 10ms and 150ms 5 x IΔn 10ms and 40ms Type S IΔn 130ms and 500ms 2 xiδn 60ms and 200ms 5 x IΔn 50ms and 150ms 0,5 IΔn 440V 4kV (1.2/50µs) 10kA Bemessungsschaltvermögen I m 25A - type 500A 40A - type 500A 63A - type 630A Bemessungsfehlerschaltvermögen I m 25A - type 500A Peak withstand current 40A - type 63A - type Type G/B, G/B+ and G/Bfq Type S/B, S/B+ and S/Bfq 500A 630A 3kA (8/20µs) surge current proof typ. 5kA (8/20µs) selective + surge current proof Electrical isolation > 4mm contact space Maximum back-up fuse short circuit protection I n = 25A 63A gg/gl I n = 40A 63A gg/gl I n = 63A 63A gg/gl Maximum back-up fuse overload protection I n = 25A 63A gg/gl Power loss I n = 40A I n = 63A 63A gg/gl 63A gg/gl according to the following diagram PAGE 2/11
Prevents nuisance tripping caused by switching electronic light: delayed G,S 30mA delayed G,S 100mA with commercially available ballast according to the manufacturer max. 30 EVG each phase, max. 90 each RCCB delayed G,S with commercially available ballast according to the manufacturer max. 90 EVG each phase Endurance electrical components > 4,000 operating cycles mechanical components > 20,000 operating cycles Tripping temperature Storage- and transport temperature Resistance to climatic conditions Dimensions Frame size 45mm Mounting Device height Device width Polution degree 2 Degree of protection Upper and lower terminals Terminal protection Terminal capacity Terminal screw Terminal torque Busbar thickness Terminal capacity warning contact Contact position indicator Tripping indicator -25 C to +40 C -35 C to +60 C 25-55 C/90-95% relative humidity acc. to IEC 60068-2 80mm 70mm (4MW) quick fastening with 2 lock-in positions on DIN rail IEC/EN 60715 IP20 built-in IP40 open mouthed/lift terminals finger and hand touch safe, BGV A3, ÖVE- EN 6 1.5-35mm² single wire 2 x 16mm² multi wire M5 (Pozidriv PZ2) 2-2.4Nm 0.8-2mm 0.25-1.5 mm2 (plug in terminals) red / green white / blue PAGE 3/11
W Tripping diagram PAGE 4/11
W Power loss Order no. Pole I N I Δn Type Power loss BC822103-- 4-pole 25 A 30 ma G/B 4,6 W BC822130-- 4-pole 25 A 300 ma G/B 4,6 W BC824103-- 4-pole 40 A 30 ma G/B 6,2 W BC824130-- 4-pole 40 A 300 ma G/B 6,2 W BC826103-- 4-pole 63 A 30 ma G/B 10 W BC826130-- 4-pole 63 A 300 ma G/B 10 W BC832103-- 4-pole 25 A 30 ma G/B+ 4,6 W BC832130-- 4-pole 25 A 300 ma G/B+ 4,6 W BC834103-- 4-pole 40 A 30 ma G/B+ 6,2 W BC834130-- 4-pole 40 A 300 ma G/B+ 6,2 W BC836103-- 4-pole 63 A 30 ma G/B+ 10 W BC836130-- 4-pole 63 A 300 ma G/B+ 10 W BC852130-- 4-pole 25 A 300 ma S/B 4,6 W BC854130-- 4-pole 40 A 300 ma S/B 6,2 W BC856130-- 4-pole 63 A 300 ma S/B 10 W BC862130-- 4-pole 25 A 300 ma S/Bfq 4,6 W BC864130-- 4-pole 40 A 300 ma S/Bfq 6,2 W BC866130-- 4-pole 63 A 300 ma S/Bfq 10 W BC872103-- 4-pole 25 A 30 ma G/Bfq 5 W BC872130-- 4-pole 25 A 300 ma G/Bfq 4,6 W BC874103-- 4-pole 40 A 30 ma G/Bfq 7 W BC874130-- 4-pole 40 A 300 ma G/Bfq 6,2 W BC876103-- 4-pole 63 A 30 ma G/Bfq 11 W BC876130-- 4-pole 63 A 300 ma G/Bfq 10 W BC882130-- 4-pole 25 A 300 ma S/B+ 4,6 W BC884130-- 4-pole 40 A 300 ma S/B+ 6,2 W BC886130-- 4-pole 63 A 300 ma S/B+ 10 W PAGE 5/11
W Wiring diagram W LED signal and auxiliary contact PAGE 6/11
W Test Circuit W Instruction RCCB must be tested by PUSHING the TEST BUTTON 1x yearly. A test is further needed if red and yellow LED are on together. The switch must trip immediately. The testing is the responsibility of the user! The yearly test interval is only valid for residential and similar applications. Under all other conditions (e.g. damply or dusty environment), it is recommended to test in shorter intervals. PAGE 7/11
W Possible connections PAGE 8/11
W Dimensions W Articles Residual current circuit breaker, series PRIORI, 10kA, Typ B, G, 30mA Residual current circuit breaker 25A, 4-p, 30mA, type B, G Residual current circuit breaker 40A, 4-p, 30mA, type B, G Residual current circuit breaker 63A, 4-p, 30mA, type B, G BC822103-- BC824103-- BC826103-- Residual current circuit breaker, series PRIORI, 10kA, Typ B, G, 300mA Residual current circuit breaker 25A, 4-p, 300mA, type B, G Residual current circuit breaker 40A, 4-p, 300mA, type B, G Residual current circuit breaker 63A, 4-p, 300mA, type B, G BC822130-- BC824130-- BC826130-- PAGE 9/11
Residual current circuit breaker, series PRIORI, 10kA, Typ B, S, 300mA Residual current circuit breaker 25A, 4-p, 300mA, type B, S Residual current circuit breaker 40A, 4-p, 300mA, type B, S Residual current circuit breaker 63A, 4-p, 300mA, type B, S BC852130-- BC854130-- BC856130-- Residual current circuit breaker, series PRIORI, 10kA, Typ B+, G, 30mA Residual current circuit breaker 25A, 4-p, 30mA, type B+, G Residual current circuit breaker 40A, 4-p, 30mA, type B+, G Residual current circuit breaker 63A, 4-p, 30mA, type B+, G BC832103-- BC834103-- BC836103-- Residual current circuit breaker, series PRIORI, 10kA, Typ B+, G, 300mA Residual current circuit breaker 25A, 4-p, 300mA, type B+, G Residual current circuit breaker 40A, 4-p, 300mA, type B+, G Residual current circuit breaker 63A, 4-p, 300mA, type B+, G BC832130-- BC834130-- BC836130-- Residual current circuit breaker, series PRIORI, 10kA, Typ B+, S, 300mA Residual current circuit breaker 25A, 4-p, 300mA, type B+, S Residual current circuit breaker 40A, 4-p, 300mA, type B+, S Residual current circuit breaker 63A, 4-p, 300mA, type B+, S BC882130-- BC884130-- BC886130-- Residual current circuit breaker, series PRIORI, 10kA, Typ B-fq B for frequncy converters, G, 30mA Residual current circuit breaker 25A, 4-p, 30mA,type B-fq,G Residual current circuit breaker 40A, 4-p, 30mA,type B-fq,G Residual current circuit breaker 63A, 4-p, 30mA,type B-fq,G BC872103-- BC874103-- BC876103-- PAGE 10/11
Residual current circuit breaker, series PRIORI, 10kA, Typ B-fq B for frequncy converters, G, 300mA Residual current circuit breaker 25A, 4-p, 300mA,type B-fq,G Residual current circuit breaker 40A, 4-p, 300mA,type B-fq,G Residual current circuit breaker 63A, 4-p, 300mA,type B-fq,G BC872130-- BC874130-- BC876130-- Residual current circuit breaker, series PRIORI, 10kA, Typ B-fq B for frequncy converters, S, 300mA Residual current circuit breaker 25A, 4-p, 300mA,type B-fq,S Residual current circuit breaker 40A, 4-p, 300mA,type B-fq,S Residual current circuit breaker 63A, 4-p, 300mA,type B-fq,S BC862130-- BC864130-- BC866130-- PAGE 11/11