Air-Cooled Liquid Chiller with integrated hydraulic module Cooling only: CGAN 200-250 - 300-400 - 450-490 - 500-600 - 700-800 - 900-925 Reversible: CXAN 200-250 - 300-400 - 450-490 - 500-600 - 700-800 - 900-925 CG-PRC010-E4
American Standard Inc. 2004 CG-PRC010-E4
Contents Features 4 General data 6 Application considerations 15 Cooling performance - Standard version 17 Cooling performance - Super Quiet version 29 Heating performance - Standard version and Super Quiet version 41 side performance 44 CG-PRC010-E4 3
Features Available in several configurations: - Standard or Super quiet - With or without hydraulic module - Hydraulic module with or without buffer tank 1 refrigerant circuit (sizes 200 to 490), 2 circuits (sizes 500 to 900) R407C operating charge Scroll compressors Stainless steel brazed plate heat exchanger Aluminium fin coil with copper tubes Filter drier Thermostatic expansion valves High and low pressure cut-outs 4-way valve (CXAN) Liquid receiver (CXAN) Low noise fans Disconnect switch flow switch Winter-freeze protection through pump activation if pump is controlled by unit Draining valve Frame in galvanized steel coated with powder polyester resin paint (RAL 9002) Threaded ISO R7 connection Control Microprocessor control module with Control of leaving water temperature. Control steps: - 2 steps for single circuit - 4 steps for double circuits Liquid crystal display indicating: - leaving water temperature. - main operating parameters - codes of any faults - unit status Control of operating parameters. Cold or hot water reset On/off Programming Anti-freeze protection of evaporator. Control of defrosting (CXAN). Dry contacts for remote signal of on/off and general fault. Inputs for external water setpoint reset, auxiliary setpoint, remote On/Off and Cooling/heating switch Options Hydraulic 5 versions available No hydraulic control With single pump contactors to control a remote pump With double pump contactors to control 2 remote double pumps With single pump integrated hydraulic module With double pump hydraulic module Hydraulic module Single or double pump Balancing valve Expansion vessel Pressure relief valve set to 3.5 bar strainer Shut-off valve Drainage valve Pressure ports for gauge connection pressure gauge Thermally insulated evaporator and liquid line to reduce water condensing or freezing Condensate collection and drainage (below pump) Pump winter freeze protection down to -18 C (the pump is activated under an ambient temperature setting) Buffer tank (only available with hydraulic module) As a unique design the water tank is located below the chiller which allow to keep the same footprint and increase the height of the unit of only 400 mm. The tank is fully insulated and is engineered for a continuous flow. Sizes 200 and 250 370 l. Sizes 300 to 490 410 l. Sizes 500 to 925 570 l. The purpose of such device is to increase the circuit inertia when necessary, for example with short water loops. A high circuit inertia reduces the compressors cycling to increase the compressors life span and also smoothes the water temperature for comfort or demanding processes. 4 CG-PRC010-E4
Features Condenser Fan control for low ambient operation in cooling mode: 1 speed fan (+10 C) 2 speeds fans (-10 C) Inverter fans (-18 C) Super quiet version, Unit with compressor sound insulated casing (-5dB(A) average) High External Static Pressure fans (not available in super quiet) 80 Pa for sizes 200, 250, 300, 500, 600, 700 60 Pa for sizes 400, 450, 490, 800, 900, 925 Condenser fins Aluminum fins and copper tubes (standard) Copper fins Aluminum fins with black epoxy fin protection Coil protection grille (not suitable for container shipment) Electrical Phase reversal protection Soft starter to reduce starting current (sizes 200 250 300 only not available with inverter fans) Antifreeze protection to protect the evaporator, hydraulic module and buffer tank down to -10 C For futher detail, refer to the official documentation LonWorks FTT-10A free topology transeiver user s guide and to the official LonWorks guidelines LonMark layer 1-6 interoperability guidelines version 3.0. These documents and additional information are available on the internet site www.lonmark.org The serial link uses the chiller controller profile reference 8040. The following orders can be sent to the chiller(s) : Modify the chilled or hot water temperature setpoint Start or stop the unit Switch from cooling to heating mode on heat pump The following information can be read : chilled or hot water temperature setpoint temperature at the inlet and outlet of the evaporator Ambient air temperature Chiller in operation Alarm description: Manual or auto reset fault Ckt1 or ckt2 fan fault Pump1 or pump 2 fault Compressor A1 or B1 or A2 or B2 fault Other HP and LP pressure gauges, pressure measurement can also be done through the controller (pressure transducers) Any other request please contact your local Trane Sales office LonTalk option Description The Lon interface uses an Echelon FTT-10 transceiver, which is approved to be used on the TP/FT-10 channel. This channel is characterized by the following main features: It consists of up to 64 nodes on a single network segment Data rate: 78 125 kbps Maximum distance: 1400 meters CG-PRC010-E4 5
General data Table 1 - CGAN cooling only - Standard version - R407C CGAN CGAN CGAN CGAN CGAN CGAN 200 250 300 400 450 490 Eurovent Performances (1) Net Cooling Capacity (kw) 50.7 62.5 76.2 102.8 121.8 132.3 Total Power input in cooling (kw) 19.1 24.4 28.8 38.7 43.6 50.5 pressure drop (kpa) 29 33 38 46 43 44 Pressure available (5) (kpa) 195 180 173 139 195 181 Main Power supply 400/3/50 Units Amps Nominal (4) (A) 47 57 69 89 102 111 Start-up Amps (A) 148 203 215 236 327 336 Short circuit unit capacity (ka) 10 10 10 10 10 10 Max supply cable size (mm 2 ) 16 35 35 95 95 95 Min supply cable size (mm 2 ) 10 16 16 50 50 50 Compressor Number 2 2 2 3 2 2 Scroll Model (10T+10T) (10T+15T) (15T+15T) (15T+15T+10T) (20T+25T) (25T+25T) Rated Amps (4) (A) 19+19 19+28.5 28.5+28.5 28.5+28.5+19 38+47 47+47 Locked rotor Amps (2) (A) 120 175 175 175 272 272 Motor RPM (rpm) 2900 2900 2900 2900 2900 2900 Power factor 0.84 0.85 0.85 0.85 0.87 0.87 Sump Heater (2) (W) 100 160 160 160 150 150 Evaporator Number 1 1 1 1 1 1 Brazed plate volume (total) (L) 5.3 6.8 8.2 10.5 11.3 12.6 Antifreeze Heater (W) 115 115 115 115 115 115 Unit Connections Male ISO R7 Connections Diameter 2 2 2½ 2½ 2½ 2½ Coil Slit Fin Length (mm) 2489 2489 2896 2896 2896 2896 Height (mm) 1422 1422 1422 1626 1626 1626 Face Area (3) (m 2 ) 3.54 3.54 4.12 4.71 4.71 4.71 Rows 2 3 3 3 4 4 Fins per foot (fpf) 204 180 180 180 168 168 Fan Propeller Number 2 2 3 3 3 3 Diameter (mm) 710 710 710 800 800 800 Drive type Direct drive Air flow (m 3 /h) 20200 19100 26300 37300 37100 37100 Number of motors 2 2 3 3 3 3 Motor HP (2) (kw) 0.6 0.6 0.6 1.05 1.05 1.05 Rated Amps (2) (A) 1.5 1.5 1.5 2.4 2.4 2.4 Motor RPM (rpm) 700 700 700 680 680 680 Dimensions Height (6) (mm) 1897 1897 1897 2074 2074 2074 Length (mm) 2800 2800 3200 3200 3200 3200 Width (mm) 1100 1100 1100 1100 1100 1100 Operating Weight (kg) 748 842 968 1143 1267 1292 Shipping Weight (kg) 743 834 954 1124 1260 1284 System Data Number of refrigerant circuits 1 1 1 1 1 1 Capacity steps 2 2 2 2 2 2 Minimum capacity () 50 40/60 50 37/63 37/63 37/63 Refrigerant Charge (3) Circuit A (kg) 13 18 21 24 28 28 Circuit B (kg) - - - - - - (1) at Eurovent Conditions (Evap 12 C/7 C - Air. 35 C) (2) per motor (3) per circuit (4) Max rated conditions. (5) Dual Pump Option (6) For units with HESP option, contact your local sales office 6 CG-PRC010-E4
General data Table 1 cont CGAN CGAN CGAN CGAN CGAN CGAN 500 600 700 800 900 925 Eurovent Performances (1) Net Cooling Capacity (kw) 128.9 157.1 182.8 214.2 241.3 267.0 Total Power input in cooling (kw) 49.1 57.9 68.4 77.9 88.3 102.4 pressure drop (kpa) 30 36 30 35 35 41 Pressure available (5) (kpa) 206 185 196 174 137 124 Main Power supply 400/3/50 Units Amps Nominal (4) (A) 113 136 153 188 208 225 Start-up Amps (A) 259 282 300 334 354 450 Short circuit unit capacity (ka) 10 10 10 10 10 10 Max supply cable size (mm 2 ) 95 95 150 150 150 150 Min supply cable size (mm 2 ) 50 50 95 95 95 95 Compressor Number 4 4 6 6 6 4 Scroll Model (10T+15T) (15T+15T) (10T+10T+15T) (15T+15T+10T) (15T+15T+15T) (25T+25T) Rated Amps (4) (A) 2x(19+28.5) 2x(28.5+28.5) 2x(19+19+28.5) 2x(28.5+28.5+19) 2x(28.5+28.5+28.5) 2x(47+47) Locked rotor Amps (2) (A) 175 175 175 175 175 272 Motor RPM (rpm) 2900 2900 2900 2900 2900 2900 Power factor 0.85 0.85 0.85 0.85 0.85 0.87 Sump Heater (2) (W) 160 160 160 160 160 150 Evaporator Number 1 1 1 1 1 1 Brazed plate volume (total) (L) 17.2 19.8 25.6 29.0 35.7 35.7 Antifreeze Heater (W) 180 180 180 180 180 180 Unit Connections Male ISO R7 Connections Diameter 2 ½ 2 ½ 3 3 3 3 Coil Slit Fin Length (mm) 2489 2896 2896 2896 2896 2896 Height (mm) 1422 1422 1626 1626 1626 1626 Face Area (3) (m 2 ) 3.54 4.12 4.71 4.71 4.71 4.71 Rows 3 3 3 3 4 4 Fins per foot (fpf) 180 180 180 180 180 168 Fan Propeller Number 4 6 6 6 6 6 Diameter (mm) 710 710 710 800 800 800 Drive type Direct drive Air flow (m 3 /h) 38300 52700 55400 86300 83000 79300 Number of motors 4 6 6 6 6 6 Motor HP (2) (kw) 0.57 0.57 0.57 1.4 1.4 1.4 Rated Amps (2) (A) 1.5 1.5 1.5 4 4 4 Motor RPM (rpm) 700 700 700 680 680 680 Dimensions Height (6) (mm) 1897 1897 2100 2100 2100 2100 Length (mm) 3400 3400 3400 3400 3400 3400 Width (mm) 2300 2300 2300 2300 2300 2300 Operating Weight (kg) 1623 1818 2087 2245 2423 2456 Shipping Weight (kg) 1588 1778 2030 2181 2344 2377 System Data Number of refrigerant circuits 2 2 2 2 2 2 Capacity steps 4 4 4 4 4 4 Minimum capacity () 20/30 25 22/29 19/32 17/33 17/33 Refrigerant Charge (3) Circuit A (kg) 19 22 27 27 34 31 Circuit B (kg) 19 22 27 27 34 31 (1) at Eurovent Conditions (Evap 12 C/7 C - Air. 35 C) (2) per motor (3) per circuit (4) Max rated conditions. (5) Dual Pump Option (6) For units with HESP option, contact your local sales office CG-PRC010-E4 7
General data Table 2 CGAN cooling only - Super Quiet version - R407C CGAN CGAN CGAN CGAN CGAN CGAN 200 250 300 400 450 490 Eurovent Performances (1) Net Cooling Capacity (kw) 50.5 62.2 75.7 101.9 121.8 132.3 Total Power input in cooling (kw) 18.8 24.2 28.4 36.4 43.6 50.5 pressure drop (kpa) 29 32 37 45 43 44 Pressure available (5) (kpa) 195 180 174 141 195 181 Main Power supply 400/3/50 Units Amps Nominal (4) (A) 46 55 66 90 102 111 Start-up Amps (A) 147 202 213 236 327 336 Short circuit unit capacity (ka) 10 10 10 10 10 10 Max supply cable size (mm 2 ) 16 35 35 95 95 95 Min supply cable size (mm 2 ) 10 16 16 50 50 50 Compressor Number 2 2 2 3 2 2 Scroll Model (10T+10T) (10T+15T) (15T+15T) (15T+15T+10T) (20T+25T) (25T+25T) Rated Amps (2)(4) (A) 19+19 19+28.5 28.5+28.5 28.5+28.5+19 38+47 47+47 Locked rotor Amps (2) (A) 120 175 175 175 272 272 Motor RPM (rpm) 2900 2900 2900 2900 2900 2900 Power factor 0.84 0.85 0.85 0.85 0.87 0.87 Sump Heater (2) (W) 100 160 160 160 150 150 Evaporator Number 1 1 1 1 1 1 Brazed plate volume (total) (L) 5.3 6.8 8.2 10.5 11.3 12.6 Antifreeze Heater (W) 115 115 115 115 115 115 Unit Connections Male ISO R7 Connections Diameter 2 2 2 ½ 2 ½ 2 ½ 2 ½ Coil Slit Fin Length (mm) 2489 2489 2896 2896 2896 2896 Height (mm) 1422 1422 1422 1626 1626 1626 Face Area (3) (m 2 ) 3.54 3.54 4.12 4.71 4.71 4.71 Rows 2 3 3 3 4 4 Fins per foot (fpf) 204 180 180 180 168 168 Fan Propeller Number 2 2 3 3 3 3 Diameter (mm) 710 710 710 800 800 800 Drive type Direct drive Air flow (m 3 /h) 20200 19100 26300 37300 37100 37100 Number of motors 2 2 3 3 3 3 Motor HP (2) (kw) 0.57 0.57 0.57 1.05 1.05 1.05 Rated Amps (2) (A) 1.5 1.5 1.5 2.4 2.4 2.4 Motor RPM (rpm) 700 700 700 680 680 680 Dimensions Height (6) (mm) 1897 1897 1897 2048 2048 2048 Length (mm) 2800 2800 3200 3200 3200 3200 Width (mm) 1100 1100 1100 1100 1100 1100 Operating Weight (kg) 778 872 1010 1155 1279 1304 Shipping Weight (kg) 773 864 996 1136 1272 1296 System Data Number of refrigerant circuits 1 1 1 1 1 1 Capacity steps 2 2 2 2 2 2 Minimum capacity () 50 40/60 50 37/63 37/63 37/63 Refrigerant Charge (3) Circuit A (kg) 13 18 21 24 28 28 Circuit B (kg) - - - - - - (1) at Eurovent Conditions (Evap 12 C/7 C - Air. 35 C) (2) per motor (3) per circuit (4) Max rated conditions. (5) Dual Pump Option (6) For units with HESP option, contact your local sales office 8 CG-PRC010-E4
General data Table 2 cont CGAN CGAN CGAN CGAN CGAN CGAN 500 600 700 800 900 925 Eurovent Performances (1) Net Cooling Capacity (kw) 128.1 156.1 181.5 212.1 238.0 264.9 Total Power input in cooling (kw) 48.8 57.2 68.0 73.4 85.0 102.1 pressure drop (kpa) 29 36 29 34 34 40 Pressure available (5) (kpa) 207 186 197 176 139 126 Main Power supply 400/3/50 Units Amps Nominal (4) (A) 110 131 150 178 200 216 Start-up Amps (A) 256 278 295 324 344 441 Short circuit unit capacity (ka) 10 10 10 10 10 10 Max supply cable size (mm 2 ) 95 95 150 150 150 150 Min supply cable size (mm 2 ) 50 50 95 95 95 95 Compressor Number 4 4 6 6 6 4 Scroll Model (10T+15T) (15T+15T) (10T+10T+15T) (15T+15T+10T) (15T+15T+15T) (25T+25T) Rated Amps (2)(4) (A) 2x(19+28.5) 2x(28.5+28.5) 2x(19+19+28.5) 2x(28.5+28.5+19) 2x(28.5+28.5+28.5) 2x(47+47) Locked rotor Amps (2) (A) 175 175 175 175 175 272 Motor RPM (rpm) 2900 2900 2900 2900 2900 2900 Power factor 0.85 0.85 0.85 0.85 0.85 0.87 Sump Heater (2) (W) 160 160 160 160 160 150 Evaporator Number 1 1 1 1 1 1 Brazed plate volume (total) (L) 17.2 19.8 25.6 29.0 35.7 35.7 Antifreeze Heater (W) 180 180 180 180 180 180 Unit Connections Male ISO R7 Connections Diameter 2 ½ 2 ½ 3 3 3 3 Coil Slit Fin Length (mm) 2489 2896 2896 2896 2896 2896 Height (mm) 1422 1422 1626 1626 1626 1626 Face Area (3) (m 2 ) 3.54 4.12 4.71 4.71 4.71 4.71 Rows 3 3 3 3 4 4 Fins per foot (fpf) 180 180 180 180 180 168 Fan Propeller Number 4 6 6 6 6 6 Diameter (mm) 710 710 710 800 800 800 Drive type Direct drive Air flow (m 3 /h) 38300 52700 55400 74700 71400 74300 Number of motors 4 6 6 6 6 6 Motor HP (2) (kw) 0.57 0.57 0.57 1.05 1.05 1.05 Rated Amps (2) (A) 1.5 1.5 1.5 2.4 2.4 2.4 Motor RPM (rpm) 700 700 700 680 680 680 Dimensions Height (6) (mm) 1897 1897 2100 2074 2074 2074 Length (mm) 3400 3400 3400 3400 3400 3400 Width (mm) 2300 2300 2300 2300 2300 2300 Operating Weight (kg) 1685 1900 2171 2335 2513 2546 Shipping Weight (kg) 1650 1860 2114 2271 2434 2467 System Data Number of refrigerant circuits 2 2 2 2 2 2 Capacity steps 4 4 4 4 4 4 Minimum capacity () 20/30 25 22/29 19/32 17/33 17/33 Refrigerant Charge (3) Circuit A (kg) 19 22 27 27 34 31 Circuit B (kg) 19 22 27 27 34 31 (1) at Eurovent Conditions (Evap 12 C/7 C - Air. 35 C) (2) per motor (3) per circuit (4) Max rated conditions. (5) Dual Pump Option (6) For units with HESP option, contact your local sales office CG-PRC010-E4 9
General data Table 3 - CXAN reversible - Standard version - R407C CXAN CXAN CXAN CXAN CXAN CXAN 200 250 300 400 450 490 Eurovent Performances (1) Net Cooling Capacity (kw) 49.2 60.8 73.6 94.5 116.4 124.8 Total Power input in cooling (kw) 20.3 25.4 30.1 40.0 42.8 49.7 pressure drop in cooling (kpa) 28 31 35 39 40 39 Pressure available in cooling (5) (kpa) 198 183 177 156 201 190 Net Heating Capacity (kw) 48.1 59.6 72.7 99.2 112.3 120.3 Power input in heating (kw) 20.3 24.9 30.4 43.0 45.7 48.7 Pressure drop in heating (kpa) 26 30 35 43 37 36 Pressure available in heating (5) (kpa) 200 185 179 146 205 195 Main Power supply 400/3/50 Units Amps Nominal (4) (A) 47 57 69 89 89 89 Start-up Amps (A) 148 203 215 236 236 236 Short circuit unit capacity (ka) 10 10 10 10 10 10 Max supply cable size (mm 2 ) 16 35 35 95 95 95 Min supply cable size (mm 2 ) 10 16 16 50 50 50 Compressor Number 2 2 2 3 3 3 Scroll Model (10T+10T) (10T+15T) (15T+15T) (15T+15T+10T) (15T+15T+10T) (15T+15T+10T) Rated Amps (2)(4) (A) 19+19 19+28.5 28.5+28.5 28.5+28.5+18.5 28.5+28.5+18.6 28.5+28.5+18.7 Locked rotor Amps (2) (A) 120 175 175 175 176 177 Motor RPM (rpm) 2900 2900 2900 2900 2900 2900 Power factor 0.84 0.85 0.85 0.85 0.87 0.87 Sump Heater (2) (W) 100 160 160 50 50 50 Evaporator Number 1 1 1 1 1 1 Brazed plate volume (total) (L) 5.3 6.8 8.2 10.5 10.5 10.5 Antifreeze Heater (W) 115 115 115 115 115 115 Unit Connections Male ISO R7 Connections Diameter 2 2 2 ½ 2 ½ 2 ½ 2 ½ Coil Plate Fin Length (mm) 2489 2489 2896 2896 2896 2896 Height (mm) 1422 1422 1422 1626 1626 1626 Face Area (3) (m 2 ) 3.54 3.54 4.12 4.71 4.71 4.71 Rows 2 3 3 3 4 4 Fins per inch (fpf) 204 204 204 204 168 168 Fan Propeller Number 2 2 3 3 3 3 Diameter (mm) 710 710 710 800 800 800 Drive type Direct drive Number of speeds 1 Air flow (m 3 /h) 20200 19100 26300 37300 37100 37300 Number of motors 2 2 3 3 3 3 Motor HP (2) (kw) 0.57 0.57 0.57 1.05 1.05 1.05 Rated Amps (2) (A) 1.5 1.5 1.5 2.4 2.4 2.4 Motor RPM (rpm) 700 700 700 680 680 680 Dimensions Height (6) (mm) 1897 1897 1897 2048 2048 2048 Length (mm) 2800 2800 3200 3200 3200 3200 Width (mm) 1100 1100 1100 1100 1100 1100 Operating Weight (kg) 776 870 996 1182 1302 1331 Shipping Weight (kg) 771 862 982 1163 1295 1323 System Data Number of refrigerant circuits 1 1 1 1 1 1 Capacity steps 2 2 2 2 2 2 Minimum capacity () 50 40/60 50 37/63 37/64 37/65 Refrigerant Charge (3) Circuit A (kg) 13 18 21 24 40 40 Circuit B (kg) - - - - - - (1) at Eurovent Conditions (Cooling : 12 C/7 C - Air. 35 C // Heating : 40 C/45 C - Air. DB7 C / WB6 C) (2) per motor (3) per circuit (4) Max rated conditions. (5) Dual Pump Option (6) For units with HESP option, contact your local sales office 10 CG-PRC010-E4
General data Table 3 cont CXAN CXAN CXAN CXAN CXAN CXAN 500 600 700 800 900 925 Eurovent Performances (1) Net Cooling Capacity (kw) 125.9 153.1 167.4 195.1 220.7 251.9 Total Power input in cooling (kw) 51.1 60.7 69.8 78.2 90.1 102.0 pressure drop in cooling (kpa) 28 35 25 29 29 36 Pressure available in cooling (5) (kpa) 209 189 208 191 148 134 Net Heating Capacity (kw) 119.2 145.3 171.8 198.4 220.0 251.6 Power input in heating (kw) 49.5 60.4 69.6 84.5 92.6 101.1 Pressure drop in heating (kpa) 25 31 26 30 29 36 Pressure available in heating (5) (kpa) 214 197 205 188 149 134 Main Power supply 400/3/50 Units Amps Nominal (4) (A) 113 136 153 188 208 225 Start-up Amps (A) 259 282 300 334 354 450 Short circuit unit capacity (ka) 10 10 10 10 10 10 Max supply cable size (mm 2 ) 95 95 150 150 150 150 Min supply cable size (mm 2 ) 50 50 95 95 95 95 Compressor Number 4 4 6 6 6 4 Scroll Model (10T+15T) (15T+15T) (10T+10T+15T) (15T+15T+10T) (15T+15T+15T) (25T+25T) Rated Amps (2)(4) (A) 2x(19+28.5) 2x(28.5+28.5) 2x(19+19+28.5) 2x(28.5+28.5+19) 2x(28.5+28.5+28.5) 2x(47+47) Locked rotor Amps (2) (A) 175 175 175 175 175 272 Motor RPM (rpm) 2900 2900 2900 2900 2900 2900 Power factor 0.85 0.85 0.85 0.85 0.85 0.87 Sump Heater (2) (W) 160 160 160 160 160 150 Evaporator Number 1 1 1 1 1 1 Brazed plate volume (total) (L) 17.2 19.8 25.6 29.0 35.7 35.7 Antifreeze Heater (W) 180 180 180 180 180 180 Unit Connections Male ISO R7 Connections Diameter 2½ 2½ 3" 3" 3" 3" Coil Plate Fin Length (mm) 2489 2896 2896 2896 2896 2896 Height (mm) 1422 1422 1626 1626 1626 1626 Face Area (3) (m 2 ) 3.54 4.12 4.71 4.71 4.71 4.71 Rows 3 3 3 3 4 4 Fins per inch (fpf) 204 204 204 204 180 168 Fan Propeller Number 4 6 6 6 6 6 Diameter (mm) 710 710 710 800 800 800 Drive type Direct drive Number of speeds 1 Air flow (m 3 /h) 38300 52700 55400 86300 83000 79300 Number of motors 4 6 6 6 6 6 Motor HP (2) (kw) 0.57 0.57 0.57 1.4 1.4 1.4 Rated Amps (2) (A) 1.5 1.5 1.5 4 4 4 Motor RPM (rpm) 700 700 700 680 680 680 Dimensions Height (6) (mm) 1897 1897 2100 2100 2100 2100 Length (mm) 3400 3400 3400 3400 3400 3400 Width (mm) 2300 2300 2300 2300 2300 2300 Operating Weight (kg) 1677 1872 2166 2324 2502 2535 Shipping Weight (kg) 1642 1832 2109 2260 2423 2456 System Data Number of refrigerant circuits 2 2 2 2 2 2 Capacity steps 4 4 4 4 4 4 Minimum capacity () 20/30 25 22/29 19/32 17/33 17/33 Refrigerant Charge (3) Circuit A (kg) 21 24 29 30 37 41 Circuit B (kg) 21 24 29 30 37 41 (1) at Eurovent Conditions (Cooling : 12 C/7 C - Air. 35 C // Heating : 40 C/45 C - Air. DB7 C / WB6 C) (2) per motor (3) per circuit (4) Max rated conditions. (5) Dual Pump Option (6) For units with HESP option, contact your local sales office CG-PRC010-E4 11
General data Table 4 - CXAN reversible - Super Quiet version - R407C CXAN CXAN CXAN CXAN CXAN CXAN 200 250 300 400 450 490 Eurovent Performances (1) Net Cooling Capacity (kw) 49.1 60.4 73.1 93.6 116.4 124.8 Total Power input in cooling (kw) 19.9 25.2 29.8 37.6 42.8 49.7 pressure drop in cooling (kpa) 27 31 35 38 40 39 Pressure available in cooling (5) (kpa) 198 183 178 158 201 190 Net Heating Capacity (kw) 48.1 59.6 72.7 99.2 112.3 120.3 Power input in heating (kw) 19.6 24.2 29.3 39.8 45.7 48.7 Pressure drop in heating (kpa) 26 30 35 43 37 36 Pressure available in heating (5) (kpa) 200 185 179 146 205 195 Main Power supply 400/3/50 Units Amps Nominal (4) (A) 46 55 66 90 102 111 Start-up Amps (A) 147 202 213 236 327 336 Short circuit unit capacity (ka) 10 10 10 10 10 10 Max supply cable size (mm 2 ) 16 35 35 95 95 95 Min supply cable size (mm 2 ) 10 16 16 50 50 50 Compressor Number 2 2 2 3 2 2 Scroll Model (10T+10T) (10T+15T) (15T+15T) (15T+15T+10T) (20T+25T) (25T+25T) Rated Amps (2)(4) (A) 19+19 19+28.5 28.5+28.5 28.5+28.5+19 38+47 47+47 Locked rotor Amps (2) (A) 120 175 175 175 272 272 Motor RPM (rpm) 2900 2900 2900 2900 2900 2900 Power factor 0.84 0.85 0.85 0.85 0.87 0.87 Sump Heater (2) (W) 100 160 160 160 150 150 Evaporator Number 1 1 1 1 1 1 Brazed plate volume (total) (L) 5.3 6.8 8.2 10.5 11.3 12.6 Antifreeze Heater (W) 115 115 115 115 115 115 Unit Connections Male ISO R7 Connections Diameter 2 2 2 ½ 2 ½ 2 ½ 2 ½ " Coil Plate Fin Length (mm) 2489 2489 2896 2896 2896 2896 Height (mm) 1422 1422 1422 1626 1626 1626 Face Area (3) (m 2 ) 3.54 3.54 4.12 4.71 4.71 4.71 Rows 2 3 3 3 4 4 Fins per inch (fpf) 204 204 204 204 168 168 Fan Propeller Number 2 2 3 3 3 3 Diameter (mm) 710 710 710 800 800 800 Drive type Direct drive Number of speeds 1 Air flow (m 3 /h) 20200 19100 26300 37300 37100 37100 Number of motors 2 2 3 3 3 3 Motor HP (2) (kw) 0.57 0.57 0.57 1.05 1.05 1.05 Rated Amps (2) (A) 1.5 1.5 1.5 2.4 2.4 2.4 Motor RPM (rpm) 700 700 700 680 680 680 Dimensions Height (6) (mm) 1897 1897 1897 2048 2048 2048 Length (mm) 2800 2800 3200 3200 3200 3200 Width (mm) 1100 1100 1100 1100 1100 1100 Operating Weight (kg) 806 900 1038 1194 1314 1343 Shipping Weight (kg) 801 892 1024 1175 1307 1335 System Data Number of refrigerant circuits 1 1 1 1 1 1 Capacity steps 2 2 2 2 2 2 Minimum capacity () 50 40/60 50 37/63 37/63 37/63 Refrigerant Charge (3) Circuit A (kg) 13 18 21 24 40 40 Circuit B (kg) - - - - - - (1) at Eurovent Conditions (Cooling : 12 C/7 C - Air. 35 C // Heating : 40 C/45 C - Air. DB7 C / WB6 C) (2) per motor (3) per circuit (4) Max rated conditions. (5) Dual Pump Option (6) For units with HESP option, contact your local sales office 12 CG-PRC010-E4
General data Table 4 cont CXAN CXAN CXAN CXAN CXAN CXAN 500 600 700 800 900 925 Eurovent Performances (1) Net Cooling Capacity (kw) 125.5 152.5 166.8 194.1 219.2 250.0 Total Power input in cooling (kw) 50.9 60.3 69.6 75.9 88.3 101.5 pressure drop in cooling (kpa) 28 34 25 29 29 36 Pressure available in cooling (5) (kpa) 209 190 209 192 149 135 Net Heating Capacity (kw) 119.2 145.3 171.8 198.4 220.0 251.6 Power input in heating (kw) 48.5 59.0 68.2 79.5 87.6 97.4 Pressure drop in heating (kpa) 25 31 26 30 29 36 Pressure available in heating (5) (kpa) 214 197 205 188 149 134 Main Power supply 400/3/50 Units Amps Nominal (4) (A) 110 131 150 178 200 216 Start-up Amps (A) 256 278 295 324 344 441 Short circuit unit capacity (ka) 10 10 10 10 10 10 Max supply cable size (mm 2 ) 95 95 150 150 150 150 Min supply cable size (mm 2 ) 50 50 95 95 95 95 Compressor Number 4 4 6 6 6 4 Scroll Model (10T+15T) (15T+15T) (10T+10T+15T) (15T+15T+10T) (15T+15T+15T) (25T+25T) Rated Amps (2)(4) (A) 2x(19+28.5) 2x(28.5+28.5) 2x(19+19+28.5) 2x(28.5+28.5+19) 2x(28.5+28.5+28.5) 2x(47+47) Locked rotor Amps (2) (A) 175 175 175 175 175 272 Motor RPM (rpm) 2900 2900 2900 2900 2900 2900 Power factor 0.85 0.85 0.85 0.85 0.85 0.87 Sump Heater (2) (W) 160 160 160 160 160 150 Evaporator Number 1 1 1 1 1 1 Brazed plate volume (total) (L) 17.2 19.8 25.6 29.0 35.7 35.7 Antifreeze Heater (W) 180 180 180 180 180 180 Unit Connections Male ISO R7 Connections Diameter 2 ½ 2 ½ 3 3 3 3" Coil Plate Fin Length (mm) 2489 2896 2896 2896 2896 2896 Height (mm) 1422 1422 1626 1626 1626 1626 Face Area (3) (m 2 ) 3.54 4.12 4.71 4.71 4.71 4.71 Rows 3 3 3 3 4 4 Fins per inch (fpf) 204 204 204 204 180 168 Fan Propeller Number 4 6 6 6 6 6 Diameter (mm) 710 710 710 800 800 800 Drive type Direct drive Number of speeds 1 Air flow (m 3 /h) 38300 52700 55400 74700 71400 74300 Number of motors 4 6 6 6 6 6 Motor HP (2) (kw) 0.57 0.57 0.57 1.05 1.05 1.05 Rated Amps (2) (A) 1.5 1.5 1.5 2.4 2.4 2.4 Motor RPM (rpm) 700 700 700 680 680 680 Dimensions Height (6) (mm) 1897 1897 2100 2074 2074 2074 Length (mm) 3400 3400 3400 3400 3400 3400 Width (mm) 2300 2300 2300 2300 2300 2300 Operating Weight (kg) 1739 1954 2250 2414 2592 2625 Shipping Weight (kg) 1704 1914 2193 2350 2513 2546 System Data Number of refrigerant circuits 2 2 2 2 2 2 Capacity steps 4 4 4 4 4 4 Minimum capacity () 20/30 25 22/29 19/32 17/33 17/33 Refrigerant Charge (3) Circuit A (kg) 21 24 29 30 37 41 Circuit B (kg) 21 24 29 30 37 41 (1) at Eurovent Conditions (Cooling : 12 C/7 C - Air. 35 C // Heating : 40 C/45 C - Air. DB7 C / WB6 C) (2) per motor (3) per circuit (4) Max rated conditions. (5) Dual Pump Option (6) For units with HESP option, contact your local sales office CG-PRC010-E4 13
General data Table 5 - Hydraulic module and buffer tank CGAN CGAN CGAN CGAN CGAN CGAN CGAN CGAN CGAN CGAN CGAN CGAN CXAN CXAN CXAN CXAN CXAN CXAN CXAN CXAN CXAN CXAN CXAN CXAN 200 250 300 400 450 490 500 600 700 800 900 925 Motor (2) (kw) 2.2 2.2 2.2 2.2 4.0 2.2 4.0 4.0 4.0 4.0 5.5 5.5 Rated Amps (2) (A) 4.9 4.9 4.9 4.9 7.5 7.5 7.5 7.5 7.5 7.5 11.1 11.1 Motor RPM (rpm) 2900 strainer Ø 2 2 2 ½ 2 ½ 2 ½ 2 ½ 2 ½ 2 ½ 3 3 3 3 Expansion tank volume (L) 25 25 25 25 25 25 35 35 35 35 35 35 User volume expansion capacity (1) (L) 1000 1000 1000 1000 1000 1000 1400 1400 1400 1400 1400 1400 Antifreeze heater (W) 150 Piping Steel Hydraulic Module Weight (kg) 103 103 108 108 108 108 110 110 114 114 189 189 tank volume (Option) (L) 370 370 410 410 410 410 570 570 570 570 570 570 tank additionnal shipping height (mm) 400 tank additionnal shipping weight (kg) 396 396 437 436 436 436 644 644 644 644 644 644 (1) Hydrostatic pressure 3 bar at 45 C with -12 C mini (2) Dual Pump Option 14 CG-PRC010-E4
Application considerations Optimum performance of CGAN and CXAN units will be achieved only if proper application guidelines are followed. Where the application varies from the guidelines presented, it should be reviewed with your local Trane sales engineer. Unit sizing Unit capacities are listed in the Performance Data section. Intentionally oversizing a unit to assure adequate capacity is not recommended. Erratic system operation and excessive compressor cycling are often a direct result of an oversized unit. In addition, an oversized unit is usually more expensive to purchase, install and operate. If oversizing is desired, consider using two units. drainage Insure there is adequate drainage to drain away water from the unit in the event of shutdown or repair. Vertical clearance Vertical condenser air discharge must be unobstructed. While it is difficult to predict the degree of warm air recirculation, a unit installed as shown in Figure 1 would have its capacity and efficiency significantly reduced possibly to the degree of nuisance high head pressure tripouts. Performance data is based on free air discharge. Figure 1 Unit placement Foundation A base or foundation is not required if the selected unit location is level and strong enough to support the unit operating weight. Isolation and sound emission Structurally transmitted sound is reduced by using rubber pads isolators provided as standard. They have to be installed between the unit and the ground. 4 or 6 rubber pads are provided to avoid contact between the unit and the ground. Sound emission or structural vibration can be reduced by using other rubber pad isolators between the unit and the ground. An acoustical engineer should always be consulted on critical applications. Table 6 - Standard Operating Limits CGAN - CXAN Cooling CXAN Heating Low ambient operating Standard 2 Speed Fan Speed inverter Min. outdoor air temperature +10 C -10 C -18 C -10 C (1) Max. outdoor air temperature +42 C +42 C +42 C +20 C Min. leaving water temperature -12 C -12 C -12 C +25 C Max. leaving water temperature +12 C +12 C +12 C +50 C (2) (1) For a maximum of 35 C leaving water (2) For a minimum of 0 C outdoor air temperature CG-PRC010-E4 15
Application considerations Lateral clearance The condenser coil inlet must not be obstructed. A unit installed closer than the minimum recommended distance to a wall or other vertical riser may experience a combination of coil starvation and warm air recirculation, resulting in unit capacity and efficiency reductions and possible excessive head pressures. The recommended lateral clearances are given in the certified drawings for multiple chiller installation up to 3 units. For more than 3 chillers applications, check with the local Trane sales engineer. Walled enclosure installations When the unit is placed in an enclosure or small depression, the top of the fans should be no lower than the top of the enclosure or depression. If they are, consideration should be given to ducting the top of the unit. Ducting individual fans, however, is not recommended. Such applications should always be reviewed with the local Trane sales engineer. Parameters which influence the water temperature stability - Number of capacity step. - Minimum time between two starts of a compressor. - loop volume. - Load fluctuations. Minimum water volume for a comfort application For comfort application we can allow water temperature fluctuation at part load. The parameter to take into account is the minimum operating time of the compressor. In order to avoid lubrication problem on a scroll compressor it must run at least 2 minutes (120 seconds) before it stops. It is important to check that the total water loop volume is at least equal to the value indicated in Table 7. For specific applications or for additional information, refer to the chiller IOM or contact your local sales office. Minimal installation water content The water volume is an important parameter because it allows a stable chilled water temperature and avoids short cycle operation of the compressors. Table 7 - Minimum water loop volume for comfort application CGAN CGAN CGAN CGAN CGAN CGAN CGAN CGAN CGAN CGAN CGAN CGAN CXAN CXAN CXAN CXAN CXAN CXAN CXAN CXAN CXAN CXAN CXAN CXAN 200 250 300 400 450 490 500 600 700 800 900 925 volume (l) 250 360 360 610 640 620 370 370 500 650 760 630 At Eurovent conditions 16 CG-PRC010-E4
Cooling performance - Standard version R407C Table 8 - Cooling capacities CGAN 200 Standard version 37-12 C 27.4 11.9 13.4 1.9 26.1 13.3 15.3 1.9 24.6 15.0 17.5 1.9 23.0 16.9 20.0 2.0 33-8 C 32.6 12.2 13.8 2.4 31.0 13.7 15.8 2.4 29.2 15.4 18.0 2.4 27.3 17.4 20.5 2.4 27-4 C 38.3 12.6 14.4 2.9 36.4 14.1 16.4 2.9 34.3 15.9 18.6 2.9 32.1 17.9 21.1 2.9 29.7 20.3 23.8 2.9 29.2 20.8 20 0 C 44.4 13.0 14.9 3.4 42.3 14.6 17.0 3.4 39.9 16.4 19.3 3.4 37.4 18.5 21.8 3.5 34.7 20.9 24.5 3.5 34.1 21.4 33.5 21.9 10 4 C 51.0 13.5 15.6 4.0 48.6 15.1 17.7 4.0 45.9 16.9 20.0 4.0 43.1 19.1 22.5 4.0 40.0 21.5 25.3 4.1 39.4 22.1 0 5 C 52.9 13.6 15.8 4.1 50.4 15.2 17.9 4.2 47.7 17.1 20.2 4.2 44.7 19.3 22.7 4.2 41.5 21.7 25.5 4.3 0 6 C 54.6 13.7 16.0 4.3 52.0 15.3 18.1 4.3 49.2 17.2 20.4 4.3 46.1 19.4 22.9 4.4 42.9 21.9 25.7 4.4 0 7 C 56.3 13.8 16.2 4.4 53.6 15.5 18.3 4.5 50.7 17.4 20.6 4.5 47.6 19.6 23.1 4.5 44.3 22.0 25.9 4.6 0 8 C 58.0 14.0 16.3 4.6 55.2 15.6 18.5 4.6 52.2 17.5 20.7 4.6 49.0 19.7 23.3 4.7 0 9 C 59.7 14.1 16.5 4.7 56.8 15.7 18.6 4.8 53.8 17.7 20.9 4.8 50.5 19.9 23.5 4.8 0 10 C 61.4 14.2 16.7 4.9 58.5 15.9 18.8 4.9 55.3 17.8 21.1 5.0 52.0 20.0 23.7 5.0 0 11 C 63.1 14.3 16.9 5.1 60.1 16.0 19.0 5.1 56.9 18.0 21.3 5.1 53.5 20.2 23.9 5.2 0 12 C 64.8 14.5 17.0 5.2 61.7 16.2 19.2 5.2 58.5 18.1 21.5 5.3 54.9 20.4 24.1 5.3 Table 9 - Cooling capacities CGAN 250 Standard version 37-12 C 34.3 15.1 13.5 1.9 32.6 16.8 15.5 1.9 30.8 18.9 17.7 1.9 33-8 C 40.7 15.6 14.0 2.4 38.6 17.4 16.0 2.4 36.5 19.6 18.3 2.4 34.1 22.1 20.9 2.4 27-4 C 47.7 16.1 14.6 2.9 45.3 18.0 16.7 2.9 42.8 20.3 19.0 2.9 40.1 22.9 21.6 2.9 37.2 25.8 24.4 2.9 20 0 C 55.2 16.7 15.2 3.4 52.5 18.7 17.4 3.4 49.6 21.0 19.7 3.4 46.5 23.7 22.3 3.4 43.1 26.7 25.2 3.5 42.4 27.3 10 4 C 63.2 17.4 15.9 4.0 60.2 19.5 18.1 4.0 56.8 21.9 20.5 4.0 53.3 24.6 23.2 4.0 0 5 C 65.5 17.6 16.2 4.1 62.3 19.7 18.4 4.1 58.9 22.1 20.8 4.2 55.2 24.9 23.4 4.2 0 6 C 67.5 17.7 16.3 4.3 64.2 19.9 18.6 4.3 60.7 22.3 21.0 4.3 56.9 25.1 23.6 4.4 0 7 C 69.6 17.9 16.5 4.4 66.2 20.1 18.7 4.4 62.5 22.5 21.2 4.5 58.6 25.3 23.9 4.5 0 8 C 71.6 18.1 16.7 4.6 68.1 20.3 18.9 4.6 64.4 22.7 21.4 4.6 60.3 25.5 24.1 4.7 0 9 C 73.6 18.3 16.9 4.7 70.0 20.5 19.1 4.8 66.2 23.0 21.6 4.8 62.1 25.8 24.3 4.8 0 10 C 75.7 18.5 17.1 4.9 72.0 20.7 19.4 4.9 68.0 23.2 21.8 4.9 63.8 26.0 24.6 5.0 0 11 C 77.7 18.6 17.3 5.0 73.9 20.9 19.6 5.1 69.9 23.4 22.1 5.1 65.5 26.3 24.8 5.1 0 12 C 79.8 18.8 17.5 5.2 75.9 21.1 19.8 5.2 71.7 23.6 22.3 5.3 67.3 26.5 25.0 5.3 HP = High Pressure gauge LP = Low Pressure gauge flow (l/s) = Cap/(4.18 x t), With t = Entering - Temperature ( C) and Cap (kw) CG-PRC010-E4 17
Cooling performance - Standard version R407C Table 10 - Cooling capacities CGAN 300 Standard version 37-12 C 41.4 17.9 13.2 1.9 39.3 19.9 15.2 1.9 37.2 22.3 17.4 1.9 35.0 25.1 19.8 1.9 33-8 C 49.1 18.4 13.7 2.3 46.7 20.5 15.7 2.4 44.2 23.0 17.9 2.4 41.5 25.8 20.3 2.4 27-4 C 57.6 19.1 14.2 2.8 54.8 21.2 16.2 2.8 51.9 23.8 18.5 2.9 48.8 26.7 21.0 2.9 45.5 30.0 23.7 2.9 44.9 30.7 44.2 31.4 20 0 C 66.7 19.7 14.8 3.4 63.6 22.0 16.9 3.4 60.2 24.6 19.1 3.4 56.7 27.6 21.6 3.4 52.9 30.9 24.4 3.4 52.1 31.6 51.3 32.4 10 4 C 76.6 20.5 15.4 3.9 73.0 22.8 17.5 3.9 69.2 25.5 19.9 4.0 65.1 28.6 22.4 4.0 60.7 32.0 25.2 4.0 59.8 32.7 0 5 C 79.4 20.7 15.6 4.1 75.7 23.1 17.7 4.1 71.7 25.8 20.1 4.1 67.5 28.8 22.6 4.2 63.0 32.3 25.4 4.2 62.0 33.0 0 6 C 81.8 20.9 15.8 4.2 78.0 23.3 17.9 4.3 73.9 26.0 20.2 4.3 69.6 29.1 22.8 4.3 64.9 32.5 25.6 4.3 0 7 C 84.3 21.1 16.0 4.4 80.4 23.5 18.1 4.4 76.2 26.2 20.4 4.4 71.7 29.3 23.0 4.5 66.9 32.8 25.8 4.5 0 8 C 86.8 21.3 16.2 4.5 82.7 23.7 18.3 4.6 78.4 26.5 20.6 4.6 73.8 29.6 23.2 4.6 0 9 C 89.3 21.5 16.3 4.7 85.1 23.9 18.5 4.7 80.7 26.7 20.8 4.7 76.0 29.9 23.4 4.8 0 10 C 91.8 21.7 16.5 4.8 87.5 24.2 18.7 4.9 83.0 27.0 21.0 4.9 78.1 30.1 23.6 4.9 0 11 C 94.3 21.9 16.7 5.0 89.9 24.4 18.8 5.0 85.2 27.2 21.2 5.0 80.2 30.4 23.8 5.1 0 12 C 96.8 22.1 16.9 5.1 92.3 24.6 19.0 5.2 87.5 27.5 21.4 5.2 82.4 30.6 24.0 5.2 Table 11 - Cooling capacities CGAN 400 Standard version 37-12 C 55.6 23.8 13.2 1.9 52.8 26.5 15.2 1.9 49.9 29.7 17.3 1.9 46.9 33.4 19.8 1.9 33-8 C 65.9 24.5 13.7 2.4 62.7 27.3 15.7 2.4 59.3 30.6 17.8 2.4 55.7 34.4 20.3 2.4 27-4 C 77.3 25.3 14.2 2.9 73.5 28.2 16.2 2.9 69.6 31.6 18.4 2.9 65.4 35.5 20.9 2.9 60.9 39.9 23.6 2.9 60.0 40.8 20 0 C 89.5 26.2 14.8 3.4 85.3 29.2 16.8 3.4 80.7 32.6 19.1 3.4 75.9 36.6 21.5 3.4 70.8 41.1 24.3 3.5 69.7 42.1 68.6 43.1 10 4 C 102.6 27.2 15.4 3.9 97.7 30.2 17.5 4.0 92.6 33.8 19.8 4.0 87.1 37.8 22.3 4.0 81.3 42.4 25.0 4.0 80.0 43.4 0 5 C 106.3 27.4 15.6 4.1 101.3 30.5 17.7 4.1 96.0 34.1 20.0 4.1 90.3 38.2 22.5 4.2 84.2 42.8 25.3 4.2 82.9 43.8 0 6 C 109.5 27.7 15.8 4.2 104.4 30.8 17.8 4.3 98.9 34.4 20.1 4.3 93.1 38.5 22.7 4.3 86.8 43.1 25.4 4.3 0 7 C 112.7 27.9 15.9 4.4 107.5 31.1 18.0 4.4 101.9 34.7 20.3 4.4 95.8 38.8 22.8 4.5 89.4 43.5 25.6 4.5 0 8 C 116.0 28.2 16.1 4.5 110.6 31.3 18.2 4.6 104.8 35.0 20.5 4.6 98.6 39.1 23.0 4.6 92.0 43.8 25.8 4.6 0 9 C 119.3 28.4 16.3 4.7 113.7 31.6 18.4 4.7 107.8 35.3 20.7 4.7 101.4 39.5 23.2 4.8 0 10 C 122.5 28.7 16.5 4.8 116.8 31.9 18.6 4.8 110.7 35.6 20.9 4.9 104.2 39.8 23.4 4.9 0 11 C 125.8 28.9 16.6 5.0 119.9 32.2 18.7 5.0 113.6 35.9 21.1 5.0 107.0 40.1 23.6 5.1 0 12 C 129.0 29.2 16.8 5.1 123.0 32.4 18.9 5.1 116.6 36.2 21.2 5.2 109.7 40.4 23.8 5.2 HP = High Pressure gauge LP = Low Pressure gauge flow (l/s) = Cap/(4.18 x t), With t = Entering - Temperature ( C) and Cap (kw) 18 CG-PRC010-E4
Cooling performance - Standard version R407C Table 12 - Cooling capacities CGAN 450 Standard version 37-12 C 61.2 26.1 14.0 2.9 58.1 29.1 15.9 2.9 54.8 32.8 18.1 2.9 33-8 C 72.4 26.9 14.4 3.3 68.4 29.9 16.4 3.3 64.2 33.7 18.6 3.3 59.8 38.1 21.0 3.3 27-4 C 88.0 28.0 15.0 3.9 82.9 31.2 17.0 3.9 77.6 35.0 19.2 3.9 72.0 39.5 21.7 3.9 66.1 44.6 24.4 3.9 20 0 C 105.4 29.4 15.7 4.6 99.6 32.7 17.8 4.6 93.3 36.6 20.0 4.6 86.8 41.2 22.5 4.6 79.8 46.3 25.3 4.6 78.4 47.4 10 4 C 123.2 30.8 16.5 5.4 116.7 34.4 18.6 5.4 109.7 38.5 20.9 5.4 102.4 43.1 23.4 5.4 0 5 C 128.0 31.3 16.7 5.6 121.3 34.9 18.8 5.6 114.2 39.0 21.1 5.6 106.7 43.6 23.7 5.6 0 6 C 132.1 31.6 16.9 5.7 125.2 35.3 19.0 5.8 118.0 39.4 21.4 5.8 110.4 44.1 23.9 5.8 0 7 C 136.3 32.0 17.1 5.9 129.2 35.7 19.2 5.9 121.8 39.9 21.6 5.9 114.0 44.5 24.1 6.0 0 8 C 140.4 32.4 17.3 6.1 133.2 36.2 19.4 6.1 125.6 40.4 21.8 6.1 117.7 45.0 24.4 6.1 0 9 C 144.6 32.8 17.5 6.3 137.2 36.6 19.6 6.3 129.5 40.8 22.0 6.3 121.4 45.5 24.6 6.3 0 10 C 148.8 33.2 17.7 6.5 141.3 37.1 19.9 6.5 133.4 41.3 22.2 6.5 125.2 46.0 24.9 6.5 0 11 C 153.0 33.7 17.9 6.7 145.3 37.5 20.1 6.7 137.3 41.8 22.5 6.7 128.9 46.5 25.1 6.7 0 12 C 157.3 34.1 18.1 6.8 149.4 38.0 20.3 6.9 141.3 42.3 22.7 6.9 132.8 47.0 25.4 6.9 Table 13 - Cooling capacities CGAN 490 Standard version 37-12 C 67.1 30.7 13.3 1.9 63.9 34.3 15.3 1.9 60.2 38.7 17.5 1.9 33-8 C 79.3 31.8 13.8 2.3 75.1 35.5 15.8 2.3 70.5 39.9 18.0 2.3 65.4 45.3 20.5 2.3 27-4 C 96.2 33.4 14.4 2.9 90.8 37.2 16.5 2.9 84.9 41.7 18.8 2.9 78.6 47.0 21.3 2.9 20 0 C 115.2 35.2 15.2 3.6 108.7 39.1 17.3 3.6 101.8 43.8 19.7 3.6 94.4 49.0 22.2 3.6 86.5 54.9 25.0 3.6 84.9 56.2 10 4 C 134.4 37.1 16.1 4.4 127.1 41.3 18.3 4.4 119.4 46.0 20.6 4.4 111.2 51.3 23.2 4.4 0 5 C 139.6 37.7 16.3 4.6 132.1 41.9 18.5 4.6 124.2 46.6 20.9 4.6 115.9 51.9 23.5 4.6 0 6 C 144.0 38.1 16.5 4.7 136.3 42.4 18.7 4.7 128.2 47.2 21.1 4.8 119.7 52.4 23.7 4.8 0 7 C 148.4 38.6 16.7 4.9 140.6 42.9 18.9 4.9 132.3 47.7 21.3 4.9 123.6 53.0 24.0 5.0 0 8 C 152.9 39.1 16.9 5.1 144.8 43.5 19.2 5.1 136.4 48.3 21.6 5.1 127.6 53.5 24.2 5.1 0 9 C 157.3 39.6 17.2 5.3 149.1 44.0 19.4 5.3 140.5 48.8 21.8 5.3 131.6 54.1 24.5 5.3 0 10 C 161.8 40.2 17.4 5.5 153.5 44.6 19.6 5.5 144.7 49.4 22.1 5.5 135.6 54.6 24.8 5.5 0 11 C 166.4 40.7 17.6 5.7 157.8 45.1 19.9 5.7 148.9 50.0 22.3 5.7 139.6 55.2 25.0 5.7 0 12 C 170.9 41.2 17.8 5.8 162.2 45.7 20.1 5.9 153.1 50.5 22.6 5.9 143.7 55.7 25.3 5.9 HP = High Pressure gauge LP = Low Pressure gauge flow (l/s) = Cap/(4.18 x t), With t = Entering - Temperature ( C) and Cap (kw) CG-PRC010-E4 19
Cooling performance - Standard version R407C Table 14 - Cooling capacities CGAN 500 Standard version 37-12 C 70.5 30.2 13.5 2.0 66.9 33.8 15.6 2.0 63.0 38.0 17.8 2.0 33-8 C 83.5 31.3 14.1 2.4 79.3 35.0 16.1 2.4 74.8 39.3 18.4 2.5 70.0 44.4 21.0 2.5 27-4 C 97.9 32.4 14.7 2.9 93.0 36.3 16.8 3.0 87.7 40.8 19.1 3.0 82.1 46.0 21.7 3.0 76.1 51.9 24.5 3.0 20 0 C 113.4 33.7 15.3 3.5 107.8 37.7 17.5 3.5 101.8 42.3 19.9 3.5 95.3 47.7 22.5 3.5 88.4 53.7 25.4 3.6 86.9 55.0 10 4 C 130.2 35.1 16.1 4.1 123.8 39.3 18.3 4.1 116.9 44.1 20.7 4.1 109.5 49.6 23.4 4.2 0 5 C 135.0 35.5 16.3 4.3 128.4 39.7 18.5 4.3 121.3 44.6 21.0 4.3 113.6 50.1 23.6 4.3 0 6 C 139.3 35.8 16.5 4.4 132.4 40.1 18.7 4.4 125.1 45.0 21.2 4.5 117.2 50.6 23.9 4.5 0 7 C 143.6 36.2 16.7 4.6 136.5 40.5 19.0 4.6 128.9 45.5 21.4 4.6 120.8 51.1 24.1 4.7 0 8 C 147.9 36.6 16.9 4.7 140.6 41.0 19.2 4.8 132.8 46.0 21.6 4.8 124.5 51.6 24.3 4.8 0 9 C 152.3 37.0 17.1 4.9 144.8 41.4 19.4 4.9 136.8 46.5 21.9 5.0 128.2 52.1 24.6 5.0 0 10 C 156.7 37.4 17.4 5.1 149.0 41.9 19.6 5.1 140.7 46.9 22.1 5.1 131.9 52.6 24.8 5.2 0 11 C 161.2 37.8 17.6 5.3 153.2 42.3 19.9 5.3 144.7 47.4 22.4 5.3 135.7 53.1 25.1 5.4 0 12 C 165.6 38.2 17.8 5.4 157.5 42.8 20.1 5.5 148.8 47.9 22.6 5.5 139.4 53.7 25.4 5.5 Table 15 - Cooling capacities CGAN 600 Standard version 37-12 C 85.0 35.9 13.3 2.0 80.7 40.0 15.3 2.0 76.3 44.8 17.4 2.0 71.7 50.4 19.9 2.0 33-8 C 100.7 37.1 13.8 2.4 95.8 41.3 15.8 2.4 90.6 46.2 18.0 2.4 85.1 51.9 20.4 2.4 79.4 58.4 23.2 2.5 27-4 C 118.1 38.3 14.3 2.9 112.4 42.7 16.3 2.9 106.4 47.8 18.6 2.9 100.1 53.6 21.1 3.0 93.3 60.2 23.8 3.0 91.9 61.6 90.5 63.1 20 0 C 137.0 39.8 14.9 3.5 130.6 44.3 17.0 3.5 123.7 49.5 19.3 3.5 116.3 55.5 21.8 3.5 108.4 62.2 24.5 3.5 106.8 63.6 105.1 65.1 10 4 C 157.6 41.3 15.6 4.1 150.2 46.0 17.7 4.1 142.3 51.4 20.0 4.1 133.8 57.6 22.6 4.1 124.8 64.4 25.3 4.1 122.9 65.8 0 5 C 163.5 41.8 15.8 4.2 155.8 46.5 17.9 4.2 147.6 52.0 20.2 4.3 138.9 58.1 22.8 4.3 129.5 65.0 25.6 4.3 0 6 C 168.7 42.2 16.0 4.4 160.8 47.0 18.1 4.4 152.3 52.5 20.4 4.4 143.3 58.7 23.0 4.5 133.6 65.6 25.8 4.5 0 7 C 173.9 42.6 16.2 4.5 165.8 47.5 18.3 4.6 157.1 53.0 20.6 4.6 147.8 59.2 23.2 4.6 0 8 C 179.2 43.1 16.4 4.7 170.9 47.9 18.5 4.7 161.9 53.5 20.8 4.8 152.3 59.8 23.4 4.8 0 9 C 184.6 43.5 16.5 4.9 176.0 48.4 18.7 4.9 166.8 54.0 21.1 4.9 156.9 60.3 23.6 5.0 0 10 C 190.0 44.0 16.7 5.0 181.2 48.9 18.9 5.1 171.7 54.5 21.3 5.1 161.5 60.9 23.9 5.1 0 11 C 195.5 44.4 16.9 5.2 186.4 49.4 19.1 5.2 176.6 55.1 21.5 5.3 166.2 61.4 24.1 5.3 0 12 C 201.1 44.9 17.2 5.4 191.7 49.9 19.3 5.4 181.6 55.6 21.7 5.4 170.9 62.0 24.3 5.5 HP = High Pressure gauge LP = Low Pressure gauge flow (l/s) = Cap/(4.18 x t), With t = Entering - Temperature ( C) and Cap (kw) 20 CG-PRC010-E4
Cooling performance - Standard version R407C Table 16 - Cooling capacities CGAN 700 Standard version 37-12 C 99.4 42.3 13.5 2.0 94.3 47.2 15.5 2.0 88.9 53.1 17.8 2.0 83.1 60.0 20.3 2.0 33-8 C 117.9 43.7 14.1 2.5 111.9 48.8 16.1 2.5 105.5 54.9 18.4 2.5 98.6 62.0 20.9 2.5 27-4 C 138.4 45.2 14.7 3.0 131.4 50.6 16.7 3.0 124.0 56.8 19.0 3.0 115.9 64.1 21.6 3.0 107.3 72.4 24.4 3.0 105.5 74.1 20 0 C 160.6 47.0 15.3 3.5 152.6 52.5 17.4 3.5 144.0 59.0 19.8 3.5 134.8 66.5 22.4 3.6 124.9 74.9 25.2 3.6 122.8 76.7 10 4 C 184.6 48.9 16.1 4.1 175.4 54.7 18.3 4.1 165.6 61.4 20.6 4.2 155.1 69.0 23.3 4.2 0 5 C 191.5 49.5 16.3 4.3 182.0 55.3 18.5 4.3 171.8 62.1 20.9 4.3 160.9 69.8 23.5 4.4 0 6 C 197.5 50.0 16.5 4.5 187.7 55.9 18.7 4.5 177.3 62.7 21.1 4.5 166.0 70.5 23.7 4.5 0 7 C 203.7 50.5 16.7 4.6 193.6 56.5 18.9 4.6 182.8 63.3 21.3 4.7 171.2 71.1 24.0 4.7 0 8 C 209.9 51.0 16.9 4.8 199.5 57.1 19.1 4.8 188.4 64.0 21.6 4.8 176.5 71.8 24.2 4.9 0 9 C 216.2 51.6 17.2 5.0 205.5 57.7 19.4 5.0 194.1 64.6 21.8 5.0 181.8 72.5 24.5 5.0 0 10 C 222.5 52.1 17.4 5.1 211.5 58.3 19.6 5.1 199.8 65.3 22.0 5.2 187.2 73.2 24.7 5.2 0 11 C 228.9 52.7 17.6 5.3 217.6 58.9 19.8 5.3 205.5 66.0 22.3 5.4 192.6 74.0 25.0 5.4 0 12 C 235.4 53.3 17.8 5.5 223.8 59.6 20.1 5.5 211.3 66.7 22.5 5.5 198.0 74.7 25.2 5.6 Table 17 - Cooling capacities CGAN 800 Standard version 37-12 C 114.4 47.3 13.1 2.0 108.7 52.6 15.0 2.0 102.7 58.9 17.2 2.0 96.4 66.2 19.5 2.0 33-8 C 135.9 48.7 13.5 2.4 129.2 54.1 15.5 2.5 122.2 60.5 17.6 2.5 114.8 68.0 20.0 2.5 27-4 C 159.7 50.2 14.0 3.0 152.1 55.8 16.0 3.0 144.0 62.4 18.2 3.0 135.3 69.9 20.6 3.0 126.1 78.6 23.2 3.0 124.2 80.4 122.3 82.3 20 0 C 185.7 51.9 14.6 3.5 177.0 57.6 16.6 3.5 167.7 64.3 18.7 3.5 157.8 72.1 21.2 3.5 147.2 80.8 23.9 3.6 145.0 82.7 142.7 84.6 10 4 C 214.1 53.7 15.2 4.1 204.1 59.6 17.2 4.1 193.5 66.5 19.4 4.1 182.2 74.4 21.9 4.2 170.1 83.3 24.6 4.2 167.6 85.2 165.0 87.2 0 5 C 222.2 54.2 15.4 4.3 211.9 60.2 17.4 4.3 200.9 67.2 19.6 4.3 189.2 75.1 22.1 4.3 176.7 84.0 24.8 4.4 174.0 85.9 171.4 87.9 0 6 C 229.4 54.7 15.6 4.4 218.8 60.8 17.6 4.5 207.5 67.7 19.8 4.5 195.4 75.7 22.3 4.5 182.5 84.7 25.0 4.5 179.8 86.6 0 7 C 236.7 55.2 15.7 4.6 225.8 61.3 17.7 4.6 214.2 68.3 20.0 4.6 201.7 76.3 22.4 4.7 188.4 85.3 25.1 4.7 185.7 87.2 0 8 C 244.2 55.7 15.9 4.8 232.9 61.8 17.9 4.8 220.9 68.9 20.2 4.8 208.1 77.0 22.6 4.8 194.5 86.0 25.3 4.9 191.6 87.9 0 9 C 251.7 56.2 16.1 4.9 240.1 62.4 18.1 4.9 227.8 69.5 20.4 5.0 214.6 77.6 22.8 5.0 200.6 86.6 25.5 5.0 0 10 C 259.3 56.8 16.3 5.1 247.4 63.0 18.3 5.1 234.7 70.1 20.5 5.1 221.2 78.2 23.0 5.2 206.7 87.3 25.7 5.2 0 11 C 266.9 57.3 16.4 5.3 254.7 63.5 18.5 5.3 241.7 70.8 20.7 5.3 227.8 78.9 23.2 5.3 212.9 88.0 25.9 5.4 0 12 C 274.7 57.8 16.6 5.4 262.1 64.1 18.7 5.5 248.7 71.4 20.9 5.5 234.4 79.6 23.4 5.5 HP = High Pressure gauge LP = Low Pressure gauge flow (l/s) = Cap/(4.18 x t), With t = Entering - Temperature ( C) and Cap (kw) CG-PRC010-E4 21
Cooling performance - Standard version R407C Table 18 - Cooling capacities CGAN 900 Standard version 37-12 C 130.0 53.7 13.2 2.0 123.3 59.7 15.2 2.0 116.5 66.9 17.3 2.0 109.4 75.2 19.8 2.0 33-8 C 154.2 55.4 13.7 2.5 146.6 61.6 15.7 2.5 138.6 69.0 17.9 2.5 130.2 77.4 20.3 2.5 121.3 87.0 23.0 2.5 27-4 C 181.1 57.3 14.2 3.0 172.3 63.7 16.2 3.0 163.1 71.3 18.4 3.0 153.2 79.9 20.9 3.0 142.8 89.7 23.6 3.0 140.6 91.8 138.4 93.9 20 0 C 210.4 59.3 14.8 3.5 200.3 66.0 16.9 3.5 189.7 73.8 19.1 3.6 178.3 82.7 21.6 3.6 166.2 92.6 24.3 3.6 163.7 94.7 161.1 96.9 10 4 C 242.1 61.6 15.5 4.1 230.6 68.6 17.6 4.2 218.4 76.6 19.8 4.2 205.4 85.6 22.4 4.2 191.5 95.8 25.1 4.2 188.6 97.9 0 5 C 251.1 62.3 15.7 4.3 239.3 69.3 17.8 4.3 226.6 77.4 20.1 4.4 213.1 86.5 22.6 4.4 198.7 96.7 25.3 4.4 195.7 98.8 0 6 C 259.2 62.9 15.9 4.5 247.0 70.0 17.9 4.5 233.9 78.1 20.2 4.5 220.0 87.3 22.8 4.5 205.1 97.5 25.5 4.6 0 7 C 267.3 63.5 16.0 4.6 254.7 70.7 18.1 4.7 241.3 78.8 20.4 4.7 227.0 88.0 23.0 4.7 211.7 98.3 25.8 4.7 0 8 C 275.6 64.2 16.2 4.8 262.6 71.4 18.3 4.8 248.8 79.6 20.6 4.9 234.0 88.8 23.2 4.9 218.3 99.1 26.0 4.9 0 9 C 283.9 64.8 16.4 5.0 270.6 72.1 18.5 5.0 256.3 80.3 20.9 5.0 241.2 89.6 23.4 5.0 0 10 C 292.4 65.5 16.6 5.1 278.6 72.8 18.7 5.2 264.0 81.1 21.1 5.2 248.4 90.5 23.6 5.2 0 11 C 300.9 66.1 16.8 5.3 286.8 73.5 18.9 5.3 271.7 81.9 21.3 5.4 255.6 91.3 23.8 5.4 0 12 C 309.5 66.8 17.0 5.5 295.0 74.2 19.1 5.5 279.5 82.7 21.5 5.5 263.0 92.1 24.1 5.6 Table 19 - Cooling capacities CGAN 925 Standard version 37-12 C 147.6 63.0 13.3 2.1 139.6 70.1 15.3 2.1 130.7 78.9 17.5 2.1 33-8 C 174.7 65.4 13.8 2.6 165.2 72.7 15.8 2.6 154.8 81.6 18.0 2.6 143.4 92.1 20.5 2.6 27-4 C 204.6 68.0 14.3 3.2 193.5 75.6 16.4 3.2 181.4 84.7 18.6 3.2 168.4 95.2 21.1 3.2 20 0 C 237.1 70.9 15.0 3.8 224.2 78.9 17.1 3.8 210.4 88.1 19.4 3.8 195.7 98.6 21.9 3.8 180.1 110.4 24.6 3.8 176.9 112.9 10 4 C 272.2 74.3 15.7 4.5 257.4 82.6 17.8 4.5 241.9 92.0 20.2 4.5 225.5 102.5 22.7 4.5 208.3 114.1 25.5 4.5 0 5 C 282.1 75.3 15.9 4.7 266.8 83.7 18.0 4.7 250.8 93.1 20.4 4.7 233.9 103.6 23.0 4.7 216.3 115.1 25.8 4.7 0 6 C 291.0 76.2 16.1 4.9 275.3 84.7 18.2 4.9 258.9 94.2 20.6 4.9 241.6 104.6 23.2 4.9 223.6 116.0 26.0 4.9 0 7 C 300.1 77.2 16.3 5.0 283.9 85.7 18.5 5.0 267.1 95.2 20.8 5.1 249.5 105.6 23.4 5.1 0 8 C 309.3 78.2 16.5 5.2 292.7 86.8 18.7 5.2 275.4 96.3 21.0 5.2 257.4 106.7 23.6 5.3 0 9 C 318.6 79.2 16.7 5.4 301.5 87.8 18.9 5.4 283.8 97.4 21.2 5.4 265.5 107.7 23.9 5.5 0 10 C 328.0 80.2 16.9 5.6 310.5 88.9 19.1 5.6 292.4 98.5 21.5 5.6 273.6 108.8 24.1 5.7 0 11 C 337.6 81.3 17.1 5.8 319.6 90.1 19.3 5.8 301.1 99.6 21.7 5.8 282.0 109.9 24.4 5.9 0 12 C 347.2 82.4 17.3 6.0 328.8 91.2 19.5 6.0 309.9 100.8 22.0 6.1 290.4 111.0 24.6 6.1 HP = High Pressure gauge LP = Low Pressure gauge flow (l/s) = Cap/(4.18 x t), With t = Entering - Temperature ( C) and Cap (kw) 22 CG-PRC010-E4
Cooling performance - Standard version R407C Table 20 - Cooling capacities CXAN 200 Standard version 37-12 26.9 12.3 14.0 1.9 25.6 13.7 15.9 1.9 24.1 15.4 18.1 1.9 33-8 31.9 12.8 14.6 2.3 30.3 14.2 16.5 2.4 28.5 16.0 18.7 2.4 26.6 18.0 21.2 2.4 27-4 37.4 13.3 15.3 2.8 35.5 14.8 17.3 2.8 33.5 16.6 19.5 2.9 31.3 18.7 22.0 2.9 20 0 43.4 13.8 16.0 3.4 41.2 15.4 18.1 3.4 38.9 17.2 20.3 3.4 36.3 19.4 22.8 3.4 33.6 21.8 25.5 3.5 10 4 49.8 14.5 16.9 3.9 47.3 16.1 18.9 4.0 44.7 18.0 21.2 4.0 41.8 20.1 23.7 4.0 0 5 51.6 14.6 17.1 4.1 49.1 16.3 19.2 4.1 46.3 18.2 21.5 4.2 43.4 20.4 24.0 4.2 0 6 53.2 14.8 17.4 4.3 50.6 16.4 19.4 4.3 47.8 18.4 21.7 4.3 44.7 20.6 24.2 4.3 0 7 54.8 15.0 17.6 4.4 52.1 16.6 19.7 4.4 49.2 18.6 21.9 4.5 46.1 20.8 24.4 4.5 0 8 56.5 15.1 17.8 4.6 53.7 16.8 19.9 4.6 50.7 18.7 22.2 4.6 47.5 21.0 24.7 4.6 0 9 58.1 15.3 18.1 4.7 55.3 17.0 20.1 4.7 52.2 18.9 22.4 4.8 48.9 21.2 24.9 4.8 0 10 59.8 15.5 18.3 4.9 56.8 17.2 20.4 4.9 53.7 19.1 22.7 4.9 50.4 21.4 25.2 5.0 0 11 61.4 15.7 18.5 5.0 58.4 17.4 20.6 5.0 55.2 19.3 22.9 5.1 51.8 21.6 25.5 5.1 0 12 63.1 15.8 18.8 5.2 60.0 17.5 20.9 5.2 56.7 19.5 23.2 5.2 53.2 21.8 25.7 5.3 Table 21 - Cooling capacities CXAN 250 Standard version 37-12 33.6 15.4 13.9 1.9 31.9 17.2 15.9 1.9 30.0 19.3 18.1 1.9 33-8 39.7 16.0 14.5 2.3 37.7 17.8 16.5 2.3 35.6 20.0 18.8 2.3 33.3 22.5 21.3 2.4 27-4 46.5 16.6 15.2 2.8 44.2 18.6 17.2 2.8 41.6 20.8 19.6 2.8 39.0 23.4 22.1 2.8 20 0 53.8 17.4 15.9 3.3 51.1 19.4 18.1 3.3 48.2 21.7 20.4 3.4 45.1 24.4 23.0 3.4 41.8 27.4 25.9 3.4 10 4 61.6 18.2 16.8 3.9 58.5 20.3 19.0 3.9 55.3 22.7 21.4 3.9 51.7 25.4 24.0 4.0 0 5 63.8 18.4 17.1 4.1 60.6 20.5 19.2 4.1 57.2 23.0 21.6 4.1 53.6 25.7 24.3 4.1 0 6 65.8 18.6 17.3 4.2 62.5 20.8 19.5 4.2 59.0 23.2 21.9 4.3 55.2 26.0 24.5 4.3 0 7 67.7 18.9 17.5 4.4 64.3 21.0 19.7 4.4 60.8 23.5 22.1 4.4 56.9 26.2 24.8 4.4 0 8 69.7 19.1 17.7 4.5 66.2 21.2 20.0 4.5 62.5 23.7 22.3 4.6 58.5 26.5 25.0 4.6 0 9 71.6 19.3 18.0 4.7 68.1 21.5 20.2 4.7 64.3 24.0 22.6 4.7 60.2 26.8 25.3 4.8 0 10 73.6 19.5 18.2 4.8 70.0 21.7 20.4 4.8 66.1 24.2 22.8 4.9 61.9 27.1 25.5 4.9 0 11 75.6 19.8 18.4 5.0 71.9 22.0 20.7 5.0 67.8 24.5 23.1 5.0 63.6 27.3 25.8 5.1 0 12 77.6 20.0 18.7 5.1 73.7 22.2 20.9 5.2 69.6 24.8 23.4 5.2 HP = High Pressure gauge LP = Low Pressure gauge flow (l/s) = Cap/(4.18 x t), With t = Entering - Temperature ( C) and Cap (kw) CG-PRC010-E4 23