MAKING MODERN LIVING POSSIBLE. Service Manual VLTp Soft Starter - MCD500 *MG17L402*

Similar documents
MCD 500 Service Manual. Functional Tests 5 Power Circuit Test 5 Start Performance Test 5 Run Performance Test 6 Trip Messages 6 General Faults 10

A problem with the motor windings. A phase loss on mains terminals L1, L2, or L3 during run mode. Parameter 2-3 Current Imbalance Delay.

Section 1.0. Section 2.0. Section 3.0. Section 4.0. MCD3000 Series. Contents. Warnings... 3

Operating Instructions. VLT Soft Starter - MCD 500. Phone: Fax: Web: -

USERS MANUAL MCD REMOTE OPERATOR

Operating Instructions VLT Soft Starter MCD 500

MCD 500 Operating Instruction. Safety 5 Warnings 5. Feature List 7 Type Code 8. Mechanical Installation 9 Dimensions and Weights 10

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

MAKING MODERN LIVING POSSIBLE. Operating Instructions. VLT Soft Starter - MCD500

Section 1.0 Warnings Section 2.0. Section 3.0. Section 4.0. MCD3000 Inside Delta Connection Kits. Contents

FLÄKTGROUP PM-MOTOR WITH INTEGRATED FC 106 FREQUENCY CONVERTER

TRIPS AND FAULT FINDING

Burden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM

THE COMPLETE SOLUTION FOR STARTING AND STOPPING AC MOTORS. MCD 3000 Soft starter

MAGNETIC MOTOR STARTERS

A. Danfoss VLT Soft Starter The single speed drive. For any soft start situation MAKING MODERN LIVING POSSIBLE

A. Danfoss VLT Soft Starter The single speed drive. For any soft start situation

SDS Enclosed Star-Delta Starter User Guide

1333 (SERIES B & C) TROUBLESHOOTING GUIDE

RVS-AX Instruction Manual

2.1 Warnings & Agency Approvals Electrical Connections - Specifications Standard Wiring Configurations...2 4

1.1 Caution Statements

Quick guide. Plug-in fans GPPM with FC101_106 August 2014

VLT Soft Starter MCD 100, MCD 201, MCD 202, MCD 3000

Operating Guide. VLT Soft Starter MCD 600

3 Internal Frequency Converter Operation 43

Design Guide. VLT Soft Start Controller MCD 100

LG Air Conditioning Universal & Multi Split Fault Codes Sheet. Universal and Multi Split Units

LG Air conditioning CAC and Multi Split unit Fault code sheet Universal and Multi Split Units

ARM V FDBK ENSURE MOTOR IS NOT ROTATING DURING POWER UP STILL FAULTS? YES ENSURE ARMATURE WIRING IS ISOLATED FROM ANY OTHER POWER LEADS STILL FAULTS?

Operating Guide VLT Soft Starter MCD 500

Application Engineering

MCD 200 Series Soft Starters

Table of Contents. Page. Introduction 2 Safety 2. Description of Operation 5 Sequence of Operation 9. Section One

Application Engineering

AC drive has detected too high a Check loading

Application example of a motor controlled by MCD100 and protected by a circuit breaker

MAKING MODERN LIVING POSSIBLE. Quick Setup VLT FCM 300 Series. Phone: Fax: Web: -

1332 TROUBLESHOOTING GUIDE. Remarks: If this function is not appropriate for the application, it can be eliminated by turning off DSWl, switch 3.

MAKING MODERN LIVING POSSIBLE. Design Guide VLT MCD 100 Soft Starter the single speed drive

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

VLT Soft Starter. Remote operation. Serial communication 24 V AC/DC V AC. Constant effort to improve MCD 100, MCD 201, MCD 202, MCD 3000

Open Chassis Star-Delta Starter User Guide

PowerOhm Installation Manual for BM R Series Braking Modules

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW

Axpert-CSS AMTECH DRIVES Axpert-CSS Amtech

Pocket Guide VLT Soft Starter the single speed drive

Direct On Line (DOL) Motor Starter. Direct Online Motor Starter

SB 2000 PUSH TO SEARCH NEXT STAG E. Aerotech, Inc. FORM: QM 1320

ICM325HN. Head Pressure Control with Optional Heat Pump Override. Installation, Operation & Application Guide

Operating Instructions. Drives Solutions.

Kelly HSR Series Motor Controller with Regen User s Manual V 3.3. Kelly HSR Opto-Isolated Series Motor Controller with Regen.

GLM SERIES CONTROL Users Manual Rev:

Matrix APAX. 380V-415V 50Hz TECHNICAL REFERENCE MANUAL

Instruction Manual. Q Series 2 Motor Control Modules - OEM

ACCESS Always replace the cover panel on the unit after gaining access to the electrical connections.

ICM 326HN/327HN Line Voltage Head Pressure Control Installation, Operation & Application Guide

KD LV Motor Protection Relay

620 Magnolia Avenue Suite B Ontario, CA (909) Diagnostic and Troubleshooting. Golf Cart. Revision: A Date:

CTi Automation - Phone: Fax: Web:

Table of Contents. Introduction. Section One. Section Two. Section Three. Section Four. Section Five. Section Six. Appendix 0-1

HIB Enclosed Inverter User Guide

ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL

2015 EDITION SUBMERSIBLE MOTORS AIM MANUAL. APPLICATION INSTALLATION MAINTENANCE 60 Hz, Single-Phase and Three-Phase Motors. franklinwater.

Cat. No. I526-E1-1 USER S MANUAL 3G3IV-PLKEB2 /4. Braking Resistor Units 3G3IV-PCDBR2 B/4 B. Braking Units

HPS2DB Serial Softstarter Operation Manual

Types of Motor Starters There are several types of motor starters. However, the two most basic types of these electrical devices are:

B-03 ELECTRICIAN TRAINING SKILL DEVELOPMENT GUIDE

SHORT-STOP. Electronic Motor Brake Type G. Instructions and Setup Manual

MAKING MODERN LIVING POSSIBLE. VLT Soft Starter MCD 100, MCD 201, MCD 202, MCD 500

EcoNet and Flash Codes

MODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM

High Frequency SineWave Guardian TM

SE-3SCR-LM MANUAL MOTOR LOAD MANAGER

Contents. MCD 200 Design Guide. Contents

Pocket Guide VLT Soft Starter the single speed drive

ADVANCED PID TROUBLESHOOTING

N1387 Series Troubleshooting Guide for N Alternators

ATOTH-G Series BLDC Motor Controller. User s Manual

Motor Protection With The MonitorPro

SECTION MOTOR CONTROL

HP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control

3 Phase Smart Controller

INSTALLATION INSTRUCTIONS FOR SYMCOM'S MODEL 777-HVR-SP ELECTRONIC OVERLOAD RELAY

9.1.4 Troubleshooting of Faults in LCD Screen

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL

OnCommand Troubleshooting Guide Hayward Industries

8 Troubleshooting and Maintenance

1.1. Reduced Voltage Motor Starters

5220 AUTOMATIC MAINS FAILURE MODULE OPERATING MANUAL

Installation, Operation and Maintenance Manual. EVC Controller (from February 2007)

Service instructions. MAGNA Series 2000

team master medium voltage solid state starters

Design Guide. VLT MCD 200 Soft Starter. Phone: Fax: Web: -

Kelly KDHA High Voltage Series/PM Motor Controller User s Manual

CDBR-B. Dynamic Braking Unit Instruction Manual. April 2009 Part Number: R1 Copyright 2009 Electromotive Systems

Table of Contents. VLT 5000 Series Service Instructions. Introduction Product Overview Warnings and Cautions... 1

Table of Contents. Chapter 1: Introduction 1.1 General Description 1. Chapter 2 - Installation 2.1 Receiving and Unpacking.. 5

1B filter, RFI 1 B/LC filter. VLT 2800 Motorcoil, RFI

User s Manual: SMARTSTART Series. Models: 6R15 6R830 6V400 6V630

Transcription:

MAKING MODERN LIVING POSSIBLE www.danfoss.com/drives Service Manual VLTp Soft Starter - MCD500 175R0550 MG17L402 *MG17L402* Rev. 2010 11 05

Contents Contents 1 Warnings 3 2 Troubleshooting 4 2.1 Functional Tests 4 2.1.1 Power Circuit Test 4 2.1.2 Start Performance Test 4 2.1.3 Run Performance Test 4 2.1.4 After Repair Tests 5 2.1.5 Control Input Test 5 2.2 Trip Messages 6 2.3 General Faults 9 3 Service Instructions 11 3.1 Frame Sizes 11 3.1.1 MCD5-0021B - MCD5-0053B (G1B) 12 3.1.2 MCD5-0068B - MCD5-0105B (G1B) 13 3.1.3 MCD5-0131B - MCD5-0215B (G2B) 14 3.1.4 MCD5-0245C (G3C) 15 3.1.5 MCD5-0360C - MCD5-0927C (G4C) 16 3.1.6 MCD5-1200C - MCD5-1600C (G5C) 17 4 Spare Parts 18 4.1.1 Spare Parts 18 4.1 Main Control PCB 18 4.2 Model PCB 19 4.3 Backplane PCB 20 4.4 Bypass Driver PCB 21 4.5 SCRs and SCR Connections 22 4.6 Power Assemblies 23 4.7 Snubber Assemblies 24 4.8 Fans 24 4.9 Current Transformers 26 4.10 Bypass Contactors 27 4.11 Plastics 28 4.11.1 Complete Plastics 29 4.12 Bus Bars 30 4.13 Other Spare Parts 32 5 Avoiding Damage 33 5.1 SCRs 33 MG.17.L4.02 - VLT is a registered Danfoss trademark 1

Contents 5.1.1 Typical Causes of SCR Damage 33 5.1.2 Protecting SCRs 33 5.1.3 Semiconductor Fuses 33 5.1.4 Main Contactors 33 5.2 Output Relays 33 5.2.1 Using the Soft Starter to Switch a Contactor 34 5.3 Control Input 34 6 Appendix 35 6.1.1 Input/Output Busbars to SCRs 35 6.1.2 SCRs to Heatsink 36 6.1.3 Bypass Contactor Connections 36 6.1.4 Current Transformer Busbar Assembly 37 2 MG.17.L4.02 - VLT is a registered Danfoss trademark

Warnings 1 Warnings 1 1 When reading this manual you will come across different symbols that require special attention. The symbols used are the following: NOTE Indicates something to be noted by the reader CAUTION Indicates a general warning WARNING Indicates a high voltage warning The examples and diagrams in this manual are included solely for illustrative purposes. The information contained in this manual is subject to change at any time and without prior notice. In no event will responsibility or liability be accepted for direct, indirect or consequential damages resulting from the use or application of this equipment. NOTE Before changing any parameter settings, ensure that the current parameter set is saved to an internal file. Refer to MCD 500 Operating Instructions, MG.17.KX.YY, for more information. WARNING WARNING - ELECTRICAL SHOCK HAZARD MCD 500 soft starters contain dangerous voltages when connected to mains voltage. Only a competent electrician should carry out the electrical installation. Improper installation of the motor or the soft starter may cause equipment failure, serious injury or death. Follow this manual and local electrical safety codes. Models MCD5-0360C - MCD5-1600C: The bus bar and heatsink are live while the unit is operating (starting, running or stopping). If the starter is installed without a main contactor, the bus bar and heatsink are live whenever mains voltage is connected (including when the starter is ready or tripped). WARNING Disconnect the soft starter from mains voltage before carrying out repair work. It is the responsibility of the user or person installing the soft starter to provide proper grounding and branch circuit protection according to local electrical safety codes. Do not connect power factor correction capacitors to the output of MCD 500 soft starters. If static power factor correction is employed, it must be connected to the supply side of the soft starter. MCD5-0021B - MCD5-0105B: After transportation, mechanical shock or rough handling there is possibility that the bypass contactor may have latched into the on state. To prevent the possibility of the motor starting immediately, on first commissioning or operation after transportation, always ensure that the control supply is applied before the power, so that the contactor state is initialised. In Auto On mode, the motor can be stopped using digital or bus commands while the soft starter is connected to mains. CAUTION These stop functions are not sufficient to avoid unintended start. A motor that has been stopped may start if faults occur in the electronics of the soft starter, or a temporary fault in the supply mains or the motor connection ceases. CAUTION Use the auto-start feature with caution. Read all the notes related to auto-start before operation. Equipment containing electrical components may not be disposed of together with domestic waste. It must be collected separately as electrical and electronic waste according to local and currently valid legislation. MG.17.L4.02 - VLT is a registered Danfoss trademark 3

Troubleshooting 2 2 Troubleshooting When a protection condition is detected, the MCD 500 will write this to the event log and may also trip or issue a warning. The soft starter's response to some protections may depend on the Protection Action settings (parameter group 16). If the MCD 500 trips you will need to reset the soft starter before restarting. If the MCD 500 has issued a warning, the soft starter will reset itself once the cause of the warning has been resolved. Some protections cause a fatal trip. This response is predefined and cannot be overridden. These protection mechanisms are designed to protect the soft starter, or can be caused by a fault within the soft starter. 2.1 Functional Tests Use the tests in this section to identify the cause of problems with the soft starter. 2.1.1 Power Circuit Test This procedure tests the soft starter's power circuit, including the SCR, Interface PCB and Main Control PCB. Use a 500V DC insulation tester on the 200Ω scale or a standard multimeter (voltmeter). 1. Isolate the soft starter from the incoming mains supply and remove the control voltage. 2. Disconnect the motor cables and any external bypass contactor cables from the soft starter. 3. Allow the soft starter to cool to room ambient temperature. 4. Using a meter, check the resistance across each phase of the soft starter in both directions. L1 to T1, T1 to L1, L2 to T2, T2 to L2, L3 to T3 and T3 to L3. 5. If any reading is less than 200Ω, the SCR or internal bypass relay has failed short circuit and must be replaced. NOTE There is no need to replace the Main Control PCB or the Backplane PCB just because an SCR has been damaged. Consider replacing these parts only after first replace the damaged SCR(s) and checking for correct operation. 6. Investigate the likely cause of SCR damage to prevent a repeat SCR failure. The modern SCRs used in MCD 500 soft starters are extremely reliable and it is extremely unlikely that they will fail due to faulty manufacture. SCR damage is almost always caused by external influences. Often these influences can be identified but in other cases the identification may prove difficult or impossible because the damaging event was temporary in nature. See Avoiding Damage for information on typical causes of SCR damage. 2.1.2 Start Performance Test This procedure tests that the MCD 500 soft starts correctly. This test is performed using an AC voltmeter. During Start mode, the On LED on the LCP should flash. 1. Connect the MCD 500 to mains voltage, control voltage and to a motor. 2. Measure the voltage across each phase (L1-T1, L2- T2, L3-T3). This should be close to the nominal mains voltage (phase voltage for in-line connection and line voltage for inside delta connection). If the voltage is zero, the SCR on that phase may have failed. If the voltage is not equivalent to the nominal mains voltage, the bypass contactor may be damaged and should be replaced (models MCD5-0021B - MCD5-0215B only). 3. Command the MCD 500 to start. While the MCD 500 is starting, measure the voltage across each phase. The voltage should fall to less than 2 VAC just before the soft starter reaches Run mode. If the voltage remains near nominal mains voltage, the SCR is not firing correctly. Check the connections between the Main Control PCB and SCRs. If the voltage starts near nominal mains voltage then falls to less than 2V AC just before the MCD 500 reaches Run mode, the MCD 500 is operating correctly and the cause of the starting problem is not the soft starter. 2.1.3 Run Performance Test Models MCD5-0021B - MCD5-0215B incorporate internal bypass contactors. If the internal bypass contactor does not operate, the SCRs will eventually fail due to thermal stress. This procedure tests the operation of the internal bypass contactors. Use this test if the starter trips with "Bypass Fail" or "Time Overcurrent". 4 MG.17.L4.02 - VLT is a registered Danfoss trademark

Troubleshooting This test is performed using either an AC voltmeter. 1. Connect the MCD 500 to mains voltage, control voltage and to a motor. 2. Measure the voltage across each phase (L1-T1, L2- T2, L3-T3). This should be close to the nominal mains voltage (phase voltage for in-line connection and line voltage for inside delta connection). If the voltage is zero, the SCR on that phase may have failed. If the voltage is not equivalent to the nominal mains voltage, the bypass contactor may be damaged and should be replaced. 3. Command the soft starter to start. After a successful start, you should hear the bypass contactors close. If the bypass contactors do not close, the bypass contactor, Main Control PCB, Model PCB or Bypass Driver PCB (models MCD5-0131B - MCD5-0215B only) may be faulty or there may be a faulty connection between these components. 4. When the soft starter is running, measure the voltage across each phase. This should be less than 0.5 VAC. 5. Command the soft starter to stop and listen for the bypass contactor to open. NOTE The bypass contactors used in the MCD 5-0021B ~ MCD5-0105B are latching. The MCD 500 control circuits are designed to open the bypass contactors even in the event of removal or loss of control voltage. However it is still possible that the bypass contactor may be closed when there is no control supply to the soft starter. The bypass contactors will open when control voltage is next applied. 2.1.4 After Repair Tests NOTE The servicing technician is responsible for ensuring that all electrical safety tests have been completed in accordance with local regulations. To test the operation of the soft starter with a small motor (ie a motor with a current rating which is much lower than that of the soft starter) 1. Use the tools menu to load the Factory Default parameter file for the soft starter. 2. Disable 2-4 Undercurrent Trip. 3. Connect a small motor to the output terminals of the soft starter. Test that the soft starter functions as expected. NOTE Ensure that 2-4 Undercurrent Trip is reset to its default value after conducting tests. 2.1.5 Control Input Test This procedure tests the condition of the soft starter control inputs. This test is performed using a wire link. 1. Disconnect all external wiring from the soft starter's control inputs. 2. Control voltage must still be connected to the soft starter. 3. Connect a wire link between each input. If the corresponding LED lights up then the input is operating correctly If the LED does not light up, the control input is damaged. Replace the Main Control PCB 2 2 To test that the soft starter functions correctly after reassembly 1. Apply control power only to the soft starter. 2. Ensure that the welcome screen displays the correct Control/Mode/HMI firmware versions. 3. Perform a Run Simulation test using both the LCP and remote switches. 4. Connect mains supply and motor. Test that the soft starter functions as expected. MG.17.L4.02 - VLT is a registered Danfoss trademark 5

Troubleshooting 2 2.2 Trip Messages This table lists soft starter's protection mechanisms and the probable cause of the trip. Some of these can be adjusted using parameter group 2 Protection and parameter group 16 Protection Action, other settings are built-in system protections and cannot be set or adjusted. Display Battery/Clock Current Imbalance Possible cause/suggested solution A verification error has occurred on the real time clock, or the backup battery voltage is low. If the battery is low and the power is off, date/time settings will be lost. Reprogram the date and time. Related Pars.: 16-12 Current imbalance can be caused by problems with the motor, the environment or the installation, such as: - An imbalance in the incoming mains voltage - A problem with the motor windings - A light load on the motor Excess Start Time FLC Too High Frequency Heatsink Overtemp Current imbalance can also be caused by incorrect cabling between the external bypass contactor and the soft starter or an internal problem with the soft starter, particularly an SCR that has failed open circuit. A failed SCR can only be definitely diagnosed by replacing the SCR and checking the starter's performance. Related Pars.: 2-2, 2-3, 16-2 Excess start time trip can occur in the following conditions: 1-1 Motor Full Load Current is not appropriate for the motor 1-4 Current Limit 1-6 Start Ramp Time has been set greater than the setting for 1-9 Excess Start Time Setting 1-6 Start Ramp Time is set too short for a high inertia load when using Adaptive Acceleration Control Related Pars.: 1-1, 1-6, 1-4, 1-9, 7-9, 7-1, 7-6, 7-4, 16-7 The MCD 500 can support higher motor FLC values when connected to the motor using inside delta configuration rather than in-line connection. If the soft starter is connected in-line but the programmed setting for 1-1 Motor Full Load Current is above the in-line maximum, the soft starter will trip at start. Related Pars.: 1-1, 7-1 The mains frequency has gone beyond the specified range. Check for other equipment in the area that could be affecting the mains supply (particularly variable speed drives). If the MCD 500 is connected to a generator set supply, the generator may be too small or could have a speed regulation problem. Related Pars.: 2-8, 2-9, 2-10, 16-5 Check if cooling fans are operating. If mounted in an enclosure, check if ventilation is adequate. Fans operate during Start, Run and for 10 minutes after the starter exits the Stop state. NOTE Models MCD5-0021B to MCD4-0053B and MCD5-0141B do not have a cooling fan. Models with fans will operate the cooling fans from a Start until 10 minutes after a Stop. Input A Trip Inst Overcurrent Internal Fault X Related Pars.: 16-6 Identify and resolve the condition which caused Input A to activate. Related Pars.: 3-3, 3-4, 3-5, 3-6, 3-7, 16-8 The motor has experienced a sharp rise in motor current, probably caused by a locked rotor condition (shearpin) while running. This may indicate a jammed load. Related Pars.: 2-6, 2-7, 16-4 The MCD 500 has tripped on an internal fault. Contact your local supplier with the fault code (X). Related Pars.: None 6 MG.17.L4.02 - VLT is a registered Danfoss trademark

Troubleshooting Display L1 Phase Loss L2 Phase Loss L3 Phase Loss L1-T1 Shorted L2-T2 Shorted L3-T3 Shorted Low Control Volts Motor Overload/ Motor 2 Overlaod Motor Connection Motor Thermistor Possible cause/suggested solution During prestart checks the starter has detected a phase loss as indicated. In run state, the starter has detected that the current on the affected phase has dropped below 3.3% of the programmed motor FLC for more than 1 second, indicating that either the incoming phase or connection to the motor has been lost. Check the supply and the input and output connections at the starter and at the motor end. Phase loss can also be caused by a failed SCR, particularly an SCR that has failed open circuit. A failed SCR can only be definitely diagnosed by replacing the SCR and checking the starter's performance. Related Pars.: None During prestart checks the starter has detected a shorted SCR or a short within the bypass contactor as indicated. Related Pars.: none The internal 24 VDC rail has dropped below 19V. This may have been caused by a fluctuation of the control supply. Reset the trip. If the problem persists: The 24 V supply in the main control PCB may be faulty; or the bypass driver PCB may be faulty (internally bypassed models only). These trips cannot be reset. Contact your local supplier for advice. Related Pars: None The motor has reached its maximum thermal capacity. Overload can be caused by: - The soft starter protection settings not matching the motor thermal capacity. - Excessive starts per hour - Excessive throughput - Damage to the motor windings. Resolve the cause of the overload and allow the motor to cool. Related Pars.: 1-1, 1-2, 1-3, 1-4, 7-1, 7-2, 7-3, 7-4, 16-1 The motor is not connected correctly to the soft starter for inline or inside delta use. - Check individual motor connections to the soft starter for power circuit continuity. - Check connections at the motor terminal box. Related Pars.: 15-7 The motor thermistor input has been enabled and: - The resistance at the thermistor input has exceeded 3.6 kω for more than one second. - The motor winding has overheated. Identify the cause of the overheating and allow the motor to cool before restarting. - The motor thermistor input has been open. NOTE If a valid motor thermistor is no longer used, a 1.2 kω resistor must be fitted across terminals 05, 06. 2 2 Related Pars.: 16-9 Network Comms The network master has sent a trip command to the starter, or there may be a network communication problem. Check the network for causes of communication inactivity. Related Pars.: 16-11 Parameter out of Range - A parameter value is outside the valid range. Phase Sequence The starter will load the default value for all affected parameters. Press MAIN MENU to go to the first invalid parameter and adjust the setting. Related Pars.: None The phase sequence on the soft starter's input terminals (L1, L2, L3) is not valid. Check the phase sequence on L1, L2, L3 and ensure the setting in Par. 2-1 is suitable for the installation. Related Pars.: 2-1 MG.17.L4.02 - VLT is a registered Danfoss trademark 7

Troubleshooting 2 Display Possible cause/suggested solution Power Loss The starter is not receiving mains supply on one or more phases when a Start Command is given. Check that the main contactor closes when a start command is given, and remains closed until the end of a soft stop. Related Pars.: 15-5 Starter/Comms - There is a problem with the connection between the soft starter and the optional communications module. Remove and reinstall the module. If the problem persists, contact your local distributor. - There is an internal communications error within the soft starter. Contact your local distributor. Thermistor Cct Related Pars.: 16-10 The thermistor input has been enabled and: - The resistance at the input has fallen below 20 Ω (the cold resistance of most thermistors will be over this value) or - A short circuit has occurred. Check and resolve this condition. Time - Overcurrent Undercurrent Unsupported Option Check that a PT100 (RTD) is not connected to 05, 06. Related Pars.: None. The MCD 500 is internally bypassed and has drawn high current during running. (The 10A protection curve trip has been reached or the motor current has risen to 600% of the motor FLC setting.) Related Pars.: None The motor has experienced a sharp drop in current, caused by loss of load. Causes can include broken components (shafts, belts or couplings), or a pump running dry. Related Pars.: 2-4, 2-5, 16-3 The selected function is not available (e.g. jog is not supported in inside delta configuration). Related Pars.: None 8 MG.17.L4.02 - VLT is a registered Danfoss trademark

Troubleshooting 2.3 General Faults This table describes situations where the soft starter does not operate as expected but does not trip or give a warning. Symptom Probable Cause 2 2 Soft starter does not respond to commands. - If the soft starter does not respond to the RESET button on the LCP: The soft starter may be in Auto On mode and will only accept commands from the remote control inputs. In Auto On mode, the Auto On LED on the LCP is illuminated. Press the Hand On or Off button to enable control via the LCP (this will also send a start or stop command to the MCD 500). - If the soft starter does not respond to commands from the control inputs: The soft starter may be in Hand On mode and will only accept commands from the LCP. When the soft starter is in Hand On control mode, the Off or Hand On LED on the LCP is active. To change to Auto On mode, press the Auto On button once. The control wiring may be incorrect. Check that the remote start, stop and reset inputs are configured correctly (see Control Wiring for details). The signals to the remote inputs may be incorrect. Test the signalling by activating each input signal in turn. The appropriate remote control input LED should activate on the LCP. The soft starter will only execute a start command from the remote inputs if the remote stop input is inactive and the remote reset input is activated (the Reset LED on the starter will be on). - If the soft starter does not respond to a start command from either the local or remote controls: The soft starter does not control the motor correctly during starting. The soft starter may be waiting for the restart delay to elapse. The length of the restart delay is controlled by Par. 2-11 Restart Delay. The motor may be too hot to permit a start. If Par. 2-12 Motor Temperature Check is set to Check, the soft starter will only permit a start when it calculates that the motor has sufficient thermal capacity to complete the start successfully. Wait for the motor to cool before attempting another start. The emergency stop function may be active. If Par. 3-3 is set to Emergency Stop and there is an open circuit on the corresponding input, the MCD 500 will not start. If the emergency stop situation has been resolved, close the circuit on the input. - Start performance may be unstable when using a low Motor Full Load Current setting Par. 1-1). This can affect use on a small test motor with full load current between 5 A and 50 A. - Power factor correction (PFC) capacitors must be installed on the supply side of the soft starter. To control a dedicated PFC capacitor contactor, connect the contactor to run relay terminals. Motor does not reach full speed. - If the start current is too low, the motor will not produce enough torque to accelerate to full speed. The soft starter may trip on excess start time. NOTE Make sure the motor starting parameters are appropriate for the application and that you are using the intended motor starting profile. If Par. 3-3 is set to Motor Set Select, check that the corresponding input is in the expected state. - The load may be jammed. Check the load for severe overloading or a locked rotor situation. Erratic motor operation. - The SCRs in the MCD 500 require at least 5 A of current to latch. If you are testing the soft starter on a motor with full load current less than 5 A, the SCRs may not latch correctly. Soft stop ends too quickly. - The soft stop settings may not be appropriate for the motor and load. Review the settings of Pars. 1-10, 1-11, 7-10 and 7-11. - If the motor is very lightly loaded, soft stop will have limited effect. MG.17.L4.02 - VLT is a registered Danfoss trademark 9

Troubleshooting Symptom Probable Cause 2 AAC adaptive acceleration control, DC brake and Jog functions not working A reset does not occur after an Auto-Reset, when using a remote 2-wire control. Remote start/stop command is overriding Auto Start/Stop settings when using remote 2-wire control. After selecting AAC the motor used an ordinary start and/or the second start was different to the first. Non-resettable THERMISTOR CCT trip, when there is a link between Thermistor input 05, 06 or when the motor thermistor connected between 05, 06 is permanently removed. - These features are only available with in-line installation. If the MCD 500 is installed inside delta, these features will not operate. - The remote 2-wire start signal must be removed and reapplied for a re-start. - Auto Start/Stop function should only be used in HAND ON mode or in tandem with HAND OFF mode, 3 and 4-wire control. - The first AAC start is current limit so that the starter can learn from the motor characteristics. Subsequent starts use AAC. - The thermistor input is enabled once a link is fitted and short circuit protection has activated. Remove the link then load the default parameter set. This will disable the thermistor input and clear the trip. Place a 1k2 Ω resistor across the thermistor input. Turn thermistor protection to 'Log only' (Par. 16-9). Parameter settings cannot be stored. - Make sure you are saving the new value by pressing the OK button after adjusting a parameter setting. If you press BACK, the change will not be saved. - Check that the adjustment lock (Par. 15-2) is set to Read/Write. If the adjustment lock is on, settings can be viewed but not changed. You need to know the security access code to change the adjustment lock setting. - The EEPROM may be faulty on the Main Control PCB. A faulty EEPROM will also trip the soft starter, and the LCP will display the message Par. Out of Range. Contact your local supplier for advice. 10 MG.17.L4.02 - VLT is a registered Danfoss trademark

Service Instructions 3 Service Instructions 3.1 Frame Sizes The physical layout and spare parts for MCD 500 vary according to the size of the starter. MCD 500 starters can be grouped into five classes ("frame sizes") as follows: 3 3 Class G1B G2B G3C G4C G5C MCD 500 Models MCD5-0021B MCD5-0037B MCD5-0043B MCD5-0053B MCD5-0068B MCD5-0084B MCD5-0089B MCD5-0105B MCD5-0131B MCD5-0141B MCD5-0195B MCD5-0215B MCD5-0245C MCD5-0360C MCD5-0380C MCD5-0428C MCD5-0595C MCD5-0619C MCD5-0790C MCD5-0927C MCD5-1200C MCD5-1410C MCD5-1600C MG.17.L4.02 - VLT is a registered Danfoss trademark 11

Service Instructions 3.1.1 MCD5-0021B - MCD5-0053B (G1B) 8 9 10 11 3 1 2 3 4 5 6 7 177HA536.10 1 Cover 7 Current transformers 2 Cable guide 8 Mounting posts 3 Main plastic 9 Backplane PCB 4 Terminal blocks 10 SCRs 5 LCP and Main Control PCB 11 Side plastic 6 Model PCB 12 MG.17.L4.02 - VLT is a registered Danfoss trademark

3 3 Service Instructions 3.1.2 MCD5-0068B - MCD5-0105B (G1B) 8 9 10 11 12 13 1 2 3 4 5 6 7 177HA537.10 1 Cover 8 Mounting posts 2 Cable guide 9 Bypass contactors 3 Main plastic 10 Backplane PCB 4 Terminal blocks 11 SCRs 5 LCP and Main Control PCB 12 Side plastic 6 Model PCB 13 Fan 7 Current transformers MG.17.L4.02 - VLT is a registered Danfoss trademark 13

Service Instructions 3.1.3 MCD5-0131B - MCD5-0215B (G2B) 7 8 9 10 11 12 13 3 1 2 3 4 5 6 177HA538.10 1 Cover 8 Model PCB 2 Main plastic 9 Current transformers 3 Cable guide 10 Bypass contactors 4 Terminal blocks 11 SCRs 5 LCP and Main Control PCB 12 Main body 6 Bypass Driver PCB 13 Fan and bracket 7 Support plastic 14 MG.17.L4.02 - VLT is a registered Danfoss trademark

3 3 Service Instructions 3.1.4 MCD5-0245C (G3C) 7 8 9 10 11 1 2 3 4 5 6 177HA539.10 1 Cover 7 Support plastic 2 Cable guide 8 Model PCB 3 Main plastic 9 Current transformers 4 Terminal blocks 10 SCRs 5 LCP and Main Control PCB 11 Main body 6 Fan assembly MG.17.L4.02 - VLT is a registered Danfoss trademark 15

Service Instructions 3.1.5 MCD5-0360C - MCD5-0927C (G4C) 7 8 9 10 3 177HA540.10 1 2 3 4 5 6 11 12 1 Cover 8 Snubber assembly 2 Main plastic 9 Module mount and spacer plastic 3 Cable guide 10 Fan assembly 4 Support plastic 11 Power assembly 5 Model PCB 12 Current transformer assembly 6 Module mount and spacer plastic 13 Main body 7 Magnetic bypass plate (models <0595>C ~ 0927C) 16 MG.17.L4.02 - VLT is a registered Danfoss trademark

3 3 Service Instructions 3.1.6 MCD5-1200C - MCD5-1600C (G5C) 1 2 3 4 6 7 9 10 11 177HA541.11 5 8 12 13 1 Cover 8 Snubber assembly 2 Main plastic 9 Magnetic bypass plate 3 Cable guide 10 Power assembly 4 LCP and Main Control PCB 11 Fan assembly 5 Bypass driver PCB 12 Current transformer assembly 6 Support plastic 13 Main body 7 Model PCB MG.17.L4.02 - VLT is a registered Danfoss trademark 17

Spare Parts 4 Spare Parts 4.1.1 Spare Parts 4 NOTE Unless otherwise indicated, spare part kits contain only one of each item. All images in this section are indicative. 4.1 Main Control PCB Each soft starter requires one Main Control PCB. MCD5-0021B MCD5-0037B MCD5-0043B MCD5-0053B MCD5-0068B MCD5-0084B MCD5-0089B MCD5-0105B MCD5-0131B MCD5-0141B MCD5-0195B MCD5-0215B MCD5-0245C MCD5-0360C MCD5-0380C MCD5-0428C MCD5-0595C MCD5-0619C MCD5-0790C MCD5-0927C MCD5-1200C MCD5-1410C MCD5-1600C CV1 CV2 T5 T7 T5 T7 175G5603 175G5604 175G5601 175G5602 175G5607 175G5608 175G5605 175G5606 175G5601-175G5604 175G5605-175G5608 18 MG.17.L4.02 - VLT is a registered Danfoss trademark

Spare Parts 4.2 Model PCB Each soft starter requires one Model PCB. MCD5-0021B 175G5609 MCD5-0245C 175G5621 MCD5-0037B 175G5610 MCD5-0360C 175G5622 MCD5-0043B 175G5611 MCD5-0380C 175G5623 MCD5-0053B 175G5612 MCD5-0428C 175G5624 MCD5-0068B 175G5613 MCD5-0595C 175G5625 MCD5-0084B 175G5614 MCD5-0619C 175G5626 MCD5-0089B 175G5615 MCD5-0790C 175G5627 MCD5-0105B 175G5616 MCD5-0927C 175G5628 MCD5-0131B 175G5617 MCD5-1200C 175G5629 MCD5-0141B 175G5618 MCD5-1410C 175G5630 MCD5-0195B 175G5619 MCD5-1600C 175G5631 MCD5-0215B 175G5620 4 4 175G5609-175G5612 175G5613-175G5616 175G5617-175G5631 MG.17.L4.02 - VLT is a registered Danfoss trademark 19

Spare Parts 4.3 Backplane PCB Models MCD5-0021B - MCD5-0105B require one Backplane PCB. 4 MCD5-0021B MCD5-0037B MCD5-0043B MCD5-0053B MCD5-0068B MCD5-0084B MCD5-0089B MCD5-0105B MCD5-0131B MCD5-0141B MCD5-0195B MCD5-0215B MCD5-0245C MCD5-0360C MCD5-0380C MCD5-0428C MCD5-0595C MCD5-0619C MCD5-0790C MCD5-0927C MCD5-1200C MCD5-1410C MCD5-1600C 175G5632 Not required 175G5632 20 MG.17.L4.02 - VLT is a registered Danfoss trademark

Spare Parts 4.4 Bypass Driver PCB Models MCD5-0131B - MCD5-0215B require one Bypass Driver PCB. MCD5-0021B MCD5-0037B MCD5-0043B MCD5-0053B MCD5-0068B MCD5-0084B MCD5-0089B MCD5-0105B MCD5-0131B MCD5-0141B MCD5-0195B MCD5-0215B MCD5-0245C MCD5-0360C MCD5-0380C MCD5-0428C MCD5-0595C MCD5-0619C MCD5-0790C MCD5-0927C MCD5-1200C MCD5-1410C MCD5-1600C Not required 175G5633 175G5698 1 Not required 4 4 177HA595.10 175G5633 175G5698 1 Bypass contactor upgrade- Refer to Product Note PN04 MCD 500 Bypass Contactor Upgrade for more information. MG.17.L4.02 - VLT is a registered Danfoss trademark 21

Spare Parts 4.5 SCRs and SCR Connections Models MCD5-0021B - MCD5-0245C use SCRs. Each soft starter requires three SCRs. 4 MCD5-0021B MCD5-0037B MCD5-0043B MCD5-0053B MCD5-0068B MCD5-0084B MCD5-0089B MCD5-0105B MCD5-0131B MCD5-0141B MCD5-0195B MCD5-0215B MCD5-0245C 175G5119 175G5120 175G5121 175G5122 175G5123 175G5124 175G5634 175G5635 175G5126 175G5127 175G5119-175G5122 175G5123, 175G5124, 175G5634 175G5635, 175G5126, 175G5127 NOTE Spare part kits may onclude either Semikron or Eupec SRCs. These SCRs are fully interchangeable in MCD 500 units and can be mixed within the same soft starter. Model 0021-0068 Red Black White Yellow Red Black White Yellow 7 6 5 4 SEMIKRON 7 6 5 4 EUPEC 177HA600.10 22 MG.17.L4.02 - VLT is a registered Danfoss trademark

Spare Parts Model 0084-0131 Black Red White Yellow Red Black Yellow White 6 7 5 4 7 6 4 5 4 4 177HA603.10 SEMIKRON EUPEC Model 0141-0245 Red Black Yellow White Red Black Yellow White 7 6 5 4 7 6 5 4 SEMIKRON EUPEC 177HA606.10 4.6 Power Assemblies Models MCD5-0360C - MCD5-1600C use power assemblies. Each soft starter requires two power assemblies. MCD5-0360C MCD5-0380C MCD5-0428C MCD5-0595C MCD5-0619C MCD5-0790C MCD5-0927C MCD5-1200C MCD5-1410C MCD5-1600C 175G5636 175G5637 175G5638 175G5639 175G5640 175G5641 175G5642 175G5643 175G5644 175G5645 177HA550.11 175G5636-175G5642 175G5643-175G5645 MG.17.L4.02 - VLT is a registered Danfoss trademark 23

Spare Parts 4.7 Snubber Assemblies Each snubber kit includes three snubber assemblies. T7 (AC input) models MCD5-0360C ~ MCD5-1600C use snubber assemblies. Each soft starter requires three snubber assemblies. 4 MCD5-0360C MCD5-0380C MCD5-0428C MCD5-0595C MCD5-0619C MCD5-0790C MCD5-0927C MCD5-1200C MCD5-1410C MCD5-1600C 175G5699 175G5700 175G5699 175G5700 4.8 Fans Certain models include a fan. The number of fans required differs between units and is shown in the table below. 24 MG.17.L4.02 - VLT is a registered Danfoss trademark

Spare Parts Part number Quantity MCD5-0021B MCD5-0037B MCD5-0043B Not required MCD5-0053B MCD5-0068B MCD5-0084B MCD5-0089B MCD5-0105B MCD5-0131B MCD5-0141B 175G5646 Not required 1 MCD5-0195B MCD5-0215B 175G5646 1 MCD5-0245C MCD5-0360C MCD5-0380C MCD5-0428C MCD5-0595C MCD5-0619C 175G5137 3 MCD5-0790C MCD5-0927C MCD5-1200C 175G5138 2 MCD5-1410C MCD5-1600C 175G5138 3 4 4 175G5646, 175G5647 175G5648 MG.17.L4.02 - VLT is a registered Danfoss trademark 25

Spare Parts 4.9 Current Transformers Each soft starter requires three current transformers. 4 MCD5-0021B MCD5-0037B MCD5-0043B MCD5-0053B MCD5-0068B MCD5-0084B MCD5-0089B MCD5-0105B MCD5-0131B MCD5-0141B MCD5-0195B MCD5-0215B MCD5-0245C MCD5-0360C MCD5-0380C MCD5-0428C MCD5-0595C MCD5-0619C MCD5-0790C MCD5-0927C MCD5-1200C MCD5-1410C MCD5-1600C 175G9046 175G9048 175G5652 175G5653 175G5654 175G5655 175G5656 175G5657 175G5658 175G5659 175G9046-175G9048 175G5652-175G5659 26 MG.17.L4.02 - VLT is a registered Danfoss trademark

Spare Parts 4.10 Bypass Contactors Models MCD5-0021B - MCD5-0215B are internally bypassed. The bypass contactor for models MCD5-0021B - MCD5-0053B is included in the Model PCB. The bypass contactors for models MCD5-0068B - MCD5-0215B are shown below. Each soft starter requires three bypass contactors. MCD5-0021B MCD5-0037B MCD5-0043B MCD5-0053B MCD5-0068B MCD5-0084B MCD5-0089B MCD5-0105B MCD5-0131B MCD5-0141B MCD5-0195B MCD5-0215B MCD5-0245C MCD5-0360C MCD5-0380C MCD5-0428C MCD5-0595C MCD5-0619C MCD5-0790C MCD5-0927C MCD5-1200C MCD5-1410C MCD5-1600C Not required 175G5660 175G5661 175G5697 1 Not required 4 4 175G5660 175G5661/175G5697 1 Bypass contactor upgrade. Refer to Product Note PN04 MCD 500 Bypass Contactor Upgrade for more information. MG.17.L4.02 - VLT is a registered Danfoss trademark 27

Spare Parts 4.11 Plastics The following body plastic components are available for MCD-500. 4 MCD5-0021B MCD5-0037B MCD5-0043B MCD5-0053B MCD5-0068B MCD5-0084B MCD5-0089B MCD5-0105B MCD5-0131B MCD5-0141B MCD5-0195B MCD5-0215B MCD5-0245C MCD5-0360C MCD5-0380C MCD5-0428C MCD5-0595C MCD5-0619C MCD5-0790C MCD5-0927C MCD5-1200C MCD5-1410C MCD5-1600C Cover Main plastic Cable guide Mounting posts 175G5667 175G5671 175G5670 (set of 3) 175G5668 175G5669 175G5672 Not required Not required 175G5667, 175G5668 175G5671, 175G5672 175G5669 175G5670 28 MG.17.L4.02 - VLT is a registered Danfoss trademark

Spare Parts 4.11.1 Complete Plastics The complete plastics kit contains the following items: 175G5673: 175G5667, 175G5671, 175G5669, 175G5670, side plastic, plastic base 175G5674: 175G5668, 175G5672, 175G5669, support plastic 175G5675: 175G5672, 175G5669, support plastic MCD5-0021B MCD5-0037B MCD5-0043B MCD5-0053B MCD5-0068B MCD5-0084B MCD5-0089B MCD5-0105B MCD5-0131B MCD5-0141B MCD5-0195B MCD5-0215B MCD5-0245C MCD5-0360C MCD5-0380C MCD5-0428C MCD5-0595C MCD5-0619C MCD5-0790C MCD5-0927C MCD5-1200C MCD5-1410C MCD5-1600C Complete plastics 175G5673 175G5674 175G5675 4 4 MG.17.L4.02 - VLT is a registered Danfoss trademark 29

Spare Parts 4.12 Bus Bars Each soft starter requires a total of six bus bars (three input and three output). Each kit contains three bus bars (unless otherwise stated) and fixing accessories if applicable. 4 Input Output MCD5-0021B MCD5-0037B MCD5-0043B MCD5-0053B MCD5-0068B 175G5677 175G5679 175G5678 175G5680 MCD5-0084B MCD5-0089B MCD5-0105B MCD5-0131B 175G5681 175G5696 174G5682 175G5683 MCD5-0141B MCD5-0195B MCD5-0215B MCD5-0245C 175G5684 175G5686 175G5685 175G5687 (set of 6) MCD5-0360C MCD5-0380C MCD5-0428C MCD5-0595C MCD5-0619C MCD5-0790C MCD5-0927C 175G5688 175G5690 175G5689 175G5691 MCD5-1200C MCD5-1410C 175G5692 175G5693 MCD5-1600C 175G5694 175G5695 175G5677 175G5679, 175G5681 175G5678, 175G5680, 175G5682 175G5696, 175G5684 175G5683, 175G5685 30 MG.17.L4.02 - VLT is a registered Danfoss trademark

4 4 Spare Parts 175G5686 175G5687 175G5688, 175G5690, 175G5692, 175G5694 175G5689, 175G5691, 175G5693, 175G5695 MG.17.L4.02 - VLT is a registered Danfoss trademark 31

Spare Parts 4.13 Other Spare Parts The following spare parts are also available. 4 MCD5-0021B MCD5-0037B MCD5-0043B MCD5-0053B MCD5-0068B MCD5-0084B MCD5-0089B MCD5-0105B MCD5-0131B MCD5-0141B MCD5-0195B MCD5-0215B MCD5-0245C MCD5-0360C MCD5-0380C MCD5-0428C MCD5-0595C MCD5-0619C MCD5-0790C MCD5-0927C MCD5-1200C MCD5-1410C MCD5-1600C Cage Clamps 175G5666 (set of 3) Not required Connector Plugs 175G5676 (set of 3) 175G5666 175G5676 32 MG.17.L4.02 - VLT is a registered Danfoss trademark

Avoiding Damage 5 Avoiding Damage 5.1 SCRs 5.1.1 Typical Causes of SCR Damage SCR damage is generally caused by overcurrent, overvoltage or overtemperature. To prevent future damage, check that the soft starter has been installed properly. Common causes of SCR problems include: Overcurrent: cable fault on soft starter output motor fault start current and/or start time exceeds the soft starter's rating starts per hour exceed the soft starter rating Overvoltage: power supply transient or surge lightning strike (direct or indirect) on power supply motor fault loose connection in power circuit, before or after the starter power factor correction connected to the output of the soft starter over-corrected bulk power factor correction on a lightly loaded system causing severe ringing voltages Overtemperature: blocked heatsinks or restricted ventilation inadequate ventilation excessive ambient temperatures bypass relay fails to close during running (internally bypassed starters only) 5.1.2 Protecting SCRs 5.1.4 Main Contactors SCRs are most vulnerable to overvoltage damage when voltage is applied to their input terminal while they are off. In this condition the SCR is blocking the full line voltage. Using a main contactor to remove voltage from the SCR input when the starter is off eliminates the risk of SCR damage due to overvoltage. 5.2 Output Relays MCD 500 soft starters have three programmable output relays. These relays are often used to control external contactors. The electronic contactor coils used in many contactors have a high initial inrush current, which can damage the soft starter's internal relays if the contactor coil is switched directly. 5 5 Modern SCRs are generally rugged and reliable. However, the risk of SCR damage can be reduced by using semiconductor fuses and/or a main contactor. 5.1.3 Semiconductor Fuses Semiconductor fuses reduce the potential for SCR damage caused by short circuits on the output of the starter. Protection systems such as circuit breakers or HRC fuses do not operate quickly enough to protect SCRs from short circuits. MG.17.L4.02 - VLT is a registered Danfoss trademark 33

Avoiding Damage 5.2.1 Using the Soft Starter to Switch a Contactor 5 Before using the soft starter's output relay to switch an electronic contactor coil, consult the contactor manufacturer. Some contactor manufacturers (eg Klockner- Moeller) state that you cannot use PCB mount relays for direct switching of their electronic contactor coils. If this is the case, there are two solutions: 1. Use the soft starter's output relay to control a slave relay. This slave relay can then be used to directly switch the electronic contactor coil circuit. A10 A1 1 2 A11 A2 177HA338.11 1 KA1 1. Soft starter output relay 2. Contactor coil 5.3 Control Input MCD 500 soft starters can be operated by external two wire or three wire control signals. External switches are configured and wired into control input terminals 01, 02. 2 KA1 1. Soft starter output relay 2. Slave relay coil 3. Contactor coil KM1 A1 A2 3 177HA337.11 External switches operating the control inputs must be rated for the control voltage being used and a continuous current of 100 ma. Incorrect configuration and wiring of the external contacts/switches to the control input terminals may cause damage. If long cable runs are used, wiring must be twisted pair or shielded cable and must be separated from AC power cables by at least 300 mm. 34 MG.17.L4.02 - VLT is a registered Danfoss trademark

Appendix 6 Appendix When assembling soft starter components, each bolt should be tightened using a calibrated torque driver set to the appropriate assembly torque. The following tables indicate 6.1.1 Input/Output Busbars to SCRs the different types of bolts and bolt tightening torques for each assembly. Model Bolt size Torque (Nm) MCD5-0021B MCD5-0037B MCD5-0043B MCD5-0053B MCD5-0068B MCD5-0084B MCD5-0089B MCD5-0105B MCD5-0131B M5x12 M6x16 4 4 MCD5-0141B MCD5-0195B MCD5-0215B MCD5-0245C MCD5-0360C M8x20 8 MCD5-0380C MCD5-0428C MCD5-0595C MCD5-0619C MCD5-0790C MCD5-0927C MCD5-1200C M8x16 12 MCD5-1410C MCD5-1600C M10x35 20 6 6 MG.17.L4.02 - VLT is a registered Danfoss trademark 35

Appendix 6.1.2 SCRs to Heatsink 6 Model Bolt size Torque (Nm) MCD5-0021B MCD5-0037B MCD5-0043B MCD5-0053B MCD5-0068B MCD5-0084B MCD5-0089B MCD5-0105B MCD5-0131B M5x16 4 MCD5-0141B MCD5-0195B MCD5-0215B MCD5-0245C M5x20 M5x20 4 4 MCD5-0360C MCD5-0380C MCD5-0428C MCD5-0595C MCD5-0619C Not required Not required MCD5-0790C MCD5-0927C MCD5-1200C MCD5-1410C MCD5-1600C 6.1.3 Bypass Contactor Connections Model Bolt size Torque (Nm) MCD5-0021B MCD5-0037B MCD5-0043B MCD5-0053B MCD5-0068B M5x12 4 MCD5-0084B MCD5-0089B MCD5-0105B MCD5-0131B M6x12 4 MCD5-0141B MCD5-0195B MCD5-0215B MCD5-0245C M5x12 M8x20 4 8 MCD5-0360C MCD5-0380C MCD5-0428C MCD5-0595C MCD5-0619C MCD5-0790C MCD5-0927C MCD5-1200C MCD5-1410C MCD5-1600C Not required Not required 36 MG.17.L4.02 - VLT is a registered Danfoss trademark

6 6 Appendix 6.1.4 Current Transformer Busbar Assembly Model Bolt size Torque (Nm) MCD5-0245C M6x16 4 MG.17.L4.02 - VLT is a registered Danfoss trademark 37