Fire/smoke damper EKO-JBG2

Similar documents
Fire/smoke damper EKO-SRBG1

Smoke damper EKO-SRB1

Fire/combustion gas damper EKO-JBG

Fire/combustion gas damper EKO-JBL

Combustion gas damper EKO-SRB

Combustion gas damper EKO-JB

Bevent Rasch BSK Fire /04/2017

Bevent Rasch BSK6. - Fire /04/2017

Fire damper ETPR. Specifications. Product code example Fire damper ETPR

(L=500) L=300 (L=500) PL /E... electric actuator version. Table standard dimensions, L = 300 mm.

ETPR-E-1 FIRE DAMPER» TECHNICAL CATALOGUE

FDR - Fire Damper for Rectangular and Circular Ducts. Halton FDR. Fire Damper for Rectangular and Circular Ducts

Fire damper FK120/FK90 TECHNICAL DATA

7/S1 FIRE DAMPER PPZEN. v 2.5 (en)

Fire dampers ETCE and ETCS TECHNICAL DATA

PKIR3G, PKIS, PKIS3G and PKIS3GA

KSOF Fire damper valve

FIRE DAMPERS, FIRE PROTECTION VALVES, SMOKE DAMPERS

WGA Long throw nozzle grille

7/S6 FIRE DAMPER FDC40. v 2.9 (en)

Ceiling swirl diffusers

Ceiling swirl diffusers

JVR CONTENTS. Page Introduction 2 Models and dimensions 3 Technical data. Selection tables 4 Technical data. Selection charts 5 Product codes 6

Fire Dampers. Types FKA FRL FRK 4/1/EN/1

7/S5 FIRE DAMPER FD40. v 2.9 (en)

DKISMA. Systemair multicompartment rectangular smoke control dampers. Ordering codes. Description. Design. Fire safety products 1 / 8.

CRP. Commissioning damper, Ductwork Leakage Class 0 QUICK FACTS. Perforated damper blade for better damper characteristic

PKI-C Cartridge Fire Dampers

series RVV Variable flow rate controllers

Krantz. Floor displacement outlet Q-B-DN 200. Air distribution systems

M A D E L. FOK-EIS-180 Fire dampers CE

ESAS Smoke control damper

UTK/UTT - Multi-blade Damper. Halton UTK, UTT. Multi-blade Damper

EAGLE Wall. Wall air diffusers with discs for supply air and flush mounting QUICK FACTS

CAV controllers. Type VFL. Volume flow limiter for insertion into ducting PD VFL 1

Rectangular fire damper TFER 30. pag. C-10

TPM 075/09. Valid from 1/2/2016 EN 15650: FIRE DAMPER FDMB

DCV-CF DCV-CF. DCV-CF Pressure control with airflow measuring CFL Version B03. Pressure controlwith airflow measuring. Product description

Heights up to 1000 mm Fire resistance period up to 120 minutes

Smoke control damper RKI-90 Test certificate Z

Type VDL FOR HIGH ROOMS, WITH ADJUSTABLE AIR CONTROL BLADES. Homepage > Products > Air Diffusers > Swirl diffusers > Type VDL

BSB SINGLE INLET CENTRIFUGAL FAN with Backward Wheels

Standard Installation Fire Damper Models: 319, 319(SS), D39

THB - Perforated Ceiling Diffuser. Halton THB. Perforated Ceiling Diffuser

BSB. SINGLE INLET CENTRIFUGAL FAN with Backward Wheels

TPM 075/09-DK VALID FROM: 15/1/2012 FIRE DAMPER AND FIRE DAMPER-SMOKE FDMB, FDMB-SRD

KAT. DOUBLE INLET CENTRIFUGAL FAN with Forward Wheels

NEO. Fire Damper. air handling intelligence FIRE SAFETY FUNCTION

FlowBar High Capacity Slot Diffuser

Regulation and shut-off damper SPB and SPC

CornerAir. CornerAir. Active chilled beam

1/3/EN/4. Ventilation Grilles Types TRS-K TRS-R TRSE-R

ETPS-EI Fire Damper EI 60 S / EI 120 S Instructions for Installation, Operation and Maintenance

FALCON Ceiling. Circular ceiling air diffuser for supply air QUICK FACTS

DFB - Conical Ceiling Diffuser. Halton DFB. Conical Ceiling Diffuser

Wall air diffusers with discs for supply air and flush mounting. Quick guide COLIBRI WALL

Volume Flow Limiters Type VFL

ASA. SINGLE INLET CENTRIFUGAL FAN with Airfoil Wheels

Systemair Fire Dampers

Registers for spiral ducts

Slot diffusers, Round duct diffusers. IMP Klima

CAV controllers. Type RN-Ex. For the precise control of constant volume flows in potentially explosive atmospheres (ATEX) PD RN-Ex 1

Circular Silencer. Rigid and flexible construction Type CA CB CF CS. TROX GmbH Telephone +49/28 45/ Telefax +49/28 45/

ADAPTTM. Extract. Extract air diffuser for the WISE system. Quick Selection

Circular silencers. Type CA. For the reduction of noise in circular ducts, galvanised sheet steel construction. 02/2017 DE/en PD CA 1

TRB - Conical Ceiling Diffuser. Halton TRB. Conical Ceiling Diffuser

ROOFMASTER STEF-HT ROOF FAN

CAV controllers. Type RN. For the precise control of constant volume flow rates PD RN 1

CAV controllers. Type VFL. Volume flow limiter for insertion into ducting K

Accessories. Front vane panel Coupling sleeve with gasket Galvanised steel Gasket of rubber compound

ROOFMASTER STEF-HT ROOF FAN

PART MATERIAL FINISHING. Frame Carbon steel Painted or galvanised

Technical documentation

COLIBRI Ceiling QUICK FACTS. Square ceiling diffuser with discs for supply air

CRP. Commissioning damper, Ductwork Leakage Class 0

CONSTANTFLOW Volume Flow Controllers

DCV-LC DCV-LC. DCV-LC Lab climate control unit. Lab climate control SMART DAMPERS & MEASURING UNITS. Product description. Occupancy AIN AOUT DCV-LC

THL - Conical Ceiling Diffuser. Halton THL. Conical Ceiling Diffuser

PK-I-Ex. Fire resistance class Circular: EI60S, EI90S, EI120S Square: EI90S, EI120S. Systemair Fire Dampers for Explosive Areas.

THT/HATCH THT/HATCH. Order code THT/HATCH 40 2T 1 N 1 G

Ventilation grilles for installation into walls, sills or rectangular

Wall and Ceiling Grille

DKR - Multi-nozzle Ceiling Diffuser. Halton DKR. Multi-nozzle Ceiling Diffuser

DCV-RC DCV-RC. DCV-RC Room climate control unit. Room climate control SMART DAMPERS & MEASURING UNITS. Product description.

lindab we simplify construction LindabSmoke control system single compartment Duct and fittings, Smoke control dampers Mounting instruction

Additional operating instructions according to ATEX 94/9/EC Volumetric flow controller VM-PRO-Ex

The Straight Way. Rectangular Cabinet Fan. Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains and heating Products Tunnel Fans

Systemair Fire Dampers

PELICAN Ceiling HF. Square extract air diffuser QUICK FACTS

BX-1H. Fire Valve FIRE SAFETY FUNCTION APPLICATION DESCRIPTION. in libraries of

EX C E L L E N C E ISO 9001 CERTIFIED COMPANY LINEAR BAR GRILLES.

CAV controllers. Type EN-Ex. For the precise control of normal and high constant volume flows in potentially explosive atmospheres (ATEX)

Ceiling diffusers. Type VDR. For large temperature differences in heating mode, high penetration of air, with adjustable air control blades

technical data air conditioning systems Round Flow Cassette FXFQ-P9VEB

Round duct grille Model KG-RR

Type DCS FOR HORIZONTAL SWIRLING SUPPLY AIR DISCHARGE CREATING HIGH INDUCTION LEVELS, WITH FIXED AIR CONTROL BLADES

ROOF FAN ROOFMASTER STEC NON-INSULATED VERSION TECHNICAL CATALOGUE

HIGH-POWERED VENTILATORS

series FSD-FLD Fire and smoke dampers UL Approval

BRC

Transcription:

Fire/smoke damper EKO-JBG2 Description The EKO-JBG2 fire/smoke damper is a CE-approved damper intended for fire compartmentation or protection against the spread of fire and smoke in ventilation installations. The damper is designed in compliance with current regulations. The damper is intended for in-wall installation in fire-containment sections conforming to fire-technical class up to EI 120. The ventilation duct can be left without any fire insulation whatever. A wire mesh grille should always be fitted when the damper is not connected to the ducting. CE-approval The EKO-JBG2 fire/smoke damper has been tested by SP and approved by SP Certifiering, CE-marking 0402-CPR SC0400-13. Design The EKO-JBG2 fire/smoke damper is available with guide or flange connections as standard. The damper has a factory-mounted electrical motor with spring return, end position contacts and thermal sensor. Since the damper has two inspection hatches it is reversible and there is no need to select a particular motor side. The standard EKO-JBG2 is manufactured of galvanized sheet steel (C2) with damper blades and casing of fire-resistant material. Alternatively, the damper can be made of aluzinc (C4) or stainless steel for a higher corrosivity class. The damper is fitted with a gasket to seal the air side. There is also a sealing strip on the damper that expands and seals if the damper is exposed to heat. The pivot shaft must nevertheless always be mounted horizontally. Temperature Since the EKO-JBG2 damper frame is fitted with sealing strips that expand to seal off in the event of fire, the operating temperature must not exceed 70 C. Sizes The EKO-JBG2 fire/smoke damper is manufactured in a large number of standard sizes from 200 x 200 to 1200 x 1000 mm. Product data EKO-JBG2 Sizes 200 x 200 to 1200 x 1000 mm. Supplied with guide or flange connections. Material of manufacture: galvanized, aluzinc coated or stainless sheet steel. Fire-technical class in compliance with SS-EN 15650:2010 EI 120 (ve ho i < > o) SC 20000 Testing and classification in compliance with EN 1366-2 and EN 13501-3. CE-marking 0402-CPR-SC0400-13 The damper conforms to air tightness class 2 and the casing conforms to air tightness class B according to EN 1751:1998. The damper conforms to air tightness class 2 and pressure class A according to AMA VVS & Kyl 12. The differential pressure over a closed damper can be 1000 Pa, corresponding to pressure class A. Conforms to environmental class C2. AMA VVS code QJC.2 Fire/smoke damper EKO-JBG2. EI 120 S 1 1 (8)

Motors The EKO-JBG2 is supplied with a 24 V or 230 V electrical safety motor supplemented with a thermal sensor and test button for manual testing of functioning in situ. If the temperature exceeds 70 C inside or outside the damper, the sensor cuts off the power to the motor and the fire damper is closed. The same thing happens in the event of a power cut. A 24 V motor is always used together with the monitoring units EKO-KE 2-16 and EKOTME/TSE. A 230 V motor is used for the EKO-MKE/SKE monitoring unit. Note that the damper must always be delivered with a factory-mounted safety motor if P-certification is to be valid. Maintenance External and internal inspection Check electricity cables to the motor, smoke detectors and thermal sensor to ensure that they are not damaged. Check the damper casing, the motor attachment, damper blades and sealing strip to ensure that no damage has occurred. Function control Check that the damper is fully open when operating, closes and opens fully when tested, and closes completely when power is cut off. Otherwise follow the instructions for the EKO MKE/SKE/KE/TME/ TSE control and monitoring system. The air conditioning equipment must be switched off during the function control. Cleaning We recommend preventive maintenance of the damper according to the needs of the installation. Damper blades and body (interior) should be cleaned by brushing, vacuum cleaning or wiping down. NOTE! No water or other liquid may be used. Note After inspection the fire damper should be left in normal working position. Installation Installation must always be done in accordance with the supplied installation instructions. An installation device for attaching the damper to a wall and angle brackets for ducts are included in the damper delivery. Other components, such as couplings and fire collars, must be ordered separately. The size of the hole is always the dimension of the damper + 140 mm. Accessories EKO-ANS Connection adapter for spiral ducting. EKO-FLS Extension adapter for walls or beams thicker than 310 mm or damper height over 550 mm and in combination with connection adapter EKO-ANS or wire mesh grille EKO-N, EKO-NR. EKO-KER Fire sealing kit for wall. EKO-KPB Junction box. EKO-RKB Control unit. EKO-RE Smoke detector (duct). EKO-RET Smoke detector (ceiling). EKO-KE Control and monitoring system. EKO-MKE/SKE Control and monitoring system. EKO-TK Test button. EKO-TME/TSE Control and monitoring system. EKO-MFL Counter flange. EKO-INR Wall frame. EKO-N Wire mesh grille. EKO-NR Wire mesh grille. 2 2 (8)

How to order the EKO-JBG2 Designation: Fire/smoke damper EKO-JBG2-A-B-C-D A B C D SIZE MATERIAL CONNECTION MOTOR (Width x Height) 1 = Galvanized (C2) 5 = Flange 10 = Motor 24 V 2 = Aluzinc (C4) 6 = Guide 11 = Motor 230 V 3 = Stainless EN 1.4301 7 = Round duct 4 = Stainless EN 1.4404 8 = Flange/Round duct 9 = Guide/Round duct Example: 1 Fire/smoke damper EKO-JBG2-400x200-1-6-10 Technical data EKO-JBG2 Dimensions Ø 25x10 Interval = 200 C 20 D 500 D B 45 Motor C Interval = 200 C Guide connection Ø 12 19 A 40 135 230 135 45 Inspection hatches Electrical data Dimensioning effect VA Max running time s EKO-JBG2 Damper motor Safety class ** 24 V AC/DC 230 V Motor Spring All BF 10 12,5 140 16 IP54 Other data see separate product information. ** Applies only when cable bushing is installed downward. Circuit diagram 3 3 (8)

Standard sizes A or B C Number of intervals 200 120 0 0 250 145 0 0 300 170 0 0 350 195 0 0 400 120 1 0 450 145 1 0 500 170 1 0 550 195 1 20 600 120 2 45 650 145 2 70 700 170 2 95 750 195 2 120 800 120 3 145 850 145 3 170 900 170 3 195 950 195 3 220 1000 120 4 245 1050 145 4 1100 170 4 1150 195 4 1200 120 5 D Weight of standard sizes* A B 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 200 13 14 15 16 18 19 21 22 23 24 26 27 28 29 31 32 33 250 14 15 16 18 20 21 22 23 25 26 27 29 30 31 32 34 35 300 15 16 18 19 21 22 24 25 26 27 29 30 31 33 34 35 37 350 16 18 19 20 22 24 25 26 28 29 30 32 33 35 36 37 39 400 18 19 20 22 24 25 26 28 29 31 32 33 35 36 38 39 40 450 19 20 22 23 25 27 28 29 31 32 34 35 37 38 39 41 42 500 20 21 23 24 27 28 29 31 32 34 35 37 38 40 41 43 44 550 21 23 24 26 28 29 31 32 34 35 37 38 40 41 43 44 46 600 23 24 26 27 29 31 32 34 35 37 38 40 42 43 45 46 48 650 24 25 27 28 31 32 34 35 37 39 40 42 43 45 46 48 50 700 25 27 28 30 32 34 35 37 38 40 42 43 45 47 48 50 51 750 26 28 30 31 33 35 37 38 40 42 43 45 47 48 50 52 53 800 28 29 31 33 35 37 38 40 42 43 45 47 48 50 52 53 55 850 29 30 32 34 36 38 40 41 43 45 47 48 50 52 53 55 57 900 30 32 33 35 38 39 41 43 45 46 48 50 52 53 55 57 59 950 31 33 35 37 39 41 43 44 46 48 50 52 53 55 57 59 61 1000 32 34 36 38 40 42 44 46 48 50 51 53 55 57 59 61 62 1050 34 36 37 39 42 44 46 47 49 51 53 55 57 59 60 62 64 1100 35 37 39 41 43 45 47 49 51 53 55 57 58 60 62 64 66 1150 36 38 40 42 45 47 48 50 52 54 56 58 60 62 64 66 68 1200 37 39 41 43 46 48 50 52 54 56 58 60 62 64 66 68 70 * Weight in kg, including motor. 4 4 (8)

Dimensioning diagram Total pressure drop Pa 100 50 30 20 10 Sound power level, L WA (dba) 30 35 40 45 50 55 60 5 3 2 (1) (2) (3) 1 1 2 3 4 5 10 20 Air velocity m/s (damper area) (1) Damper height B = 200 mm (2) Damper height B = 350 mm (3) Damper height B 500 mm Correction of sound power level L WAKORR for different sizes used as per curves (1), (2), (3) in accordance with L WAK1 = L WA +K 1 1 EKO-JBG2 Width B (mm) 250 350 500 800 1000 1200 Damper height B (mm) Damper area (m 2 ) 200 acc. to (1) 0.05 0.07 0.1 0.16 0.2 0.24 350 acc. to (2) 0.09 0.12 0.18 0.28 0.35 0.42 500 acc. to (3)* 0.13 0.18 0.25 0.4 0.5 0.6 K 1 (db) -3-2 0 2 3 4 *) For damper height above 500 mm use the actual area. Example: Width 500 mm and height 1000 mm, A = 0.5 m 2, which gives K 1 = 3. Correction of sound power level in octave bands. L WAOK = L WA + K OK 90 EKO-JBG2 Centre frequency (Hz) Octave band 63 125 250 500 1k 2k 4k 8k Correction, K OK 90 1 3 0-3 -6-7 -12-19 Tolerance ± db 4 4 2 2 4 4 4 Sound power levels, pressure drop and air flow measured on a fire/smoke damper according to ISO 5135. Standard deviation (tolerance) in accordance with EN ISO 3741:2010. 5 5 (8)

Installation accessories EKO-JBG2 Connections 45 A x B ØD A x B ØD A + 90, B + 90 61 500 61 ØD 100-500 mm No extension adapter required 61 100 200 500 100 200 61 250 250 ØD 630-1000 mm 2 extension adapters required Connection adapter Connection sleeve Connection adapte EKO-ANS Extension adapter Extension adapter Extension adapter EKO-FLS Mounting plate EKO-MOP* * Included in the EKO-JBG2 delivery 100 ØD A x B 61 100 200 250 25 80 Duct dimension + 100 6 6 (8)

Mounting instructions EKO-JBG2 Structural element wall of plasterboard or equivalent in fire-technical class EI 60/EI 120. Damper mounted with mounting plate EKO-MOP flush with wall Slot min 25 mm Mounting plate EKO-MOP A+140 B+140 EKO- JBG2 Wire mesh grille EKO-N Screw Fill with EKO-KER or similar fire sealant and seal with fire protection sealant 230 Important! The fire/smoke damper should always be installed with the pivot shaft horizontal. 1. Add horizontal studs and where necessary also vertical studs so that a suitable opening in the wall is obtained equivalent to the nominal dimensions of the damper + 140 mm. 2. Attach the EKO-MOP mounting plates to the damper with screws so that the damper blade is placed within the wall when mounted. 3. Centre the damper in the opening and screw the mounting plates to the wall studs. Ensure that the diagonal dimensions of the duct are equal. 4. Fill the gap between the duct and the wall with fire sealant EKO-KER or similar and seal with fire protection sealant. 6. In cases where the damper is mounted as a transfer air device or end plate, an EKO-N wire mesh grille must be fitted. 7. The following minimum dimensions must be observed when mounting: Minimum distance between dampers: 200 mm. Minimum distance to wall/floor: 75 mm. NOTE! On dampers with a height exceeding 550 mm the extension adapter EKO-FLS with wire mesh grille must be used since the damper blade protrudes beyond the damper adapter in open position. 5. The suspension devices for the damper and ducting must meet the requirements for the firetechnical class of the aperture. 7 7 (8)

Mounting instructions EKO-JBG2 Load-bearing structural element wall or floor of concrete, brick or aerated concrete of fire-technical class EI 60/EI 120. Damper mounted with mounting plate EKO-MOP flush with wall Slot min 25 mm A+140 B+140 EKO- JBG2 Wire mesh grille EKO-N Mounting plate EKO-MOP Fill with EKO-KER or similar fire sealant and seal with fire protection sealant For wall thicknesses over 310 mm the damper must be fitted with extension adapter EKO-FLS Important! The fire/smoke damper should always be installed with the pivot shaft horizontal. 1. Make an opening in the wall equivalent to the nominal dimensions of the damper + 140 mm. 2. Attach the EKO-MOP mounting plates to the damper with screws so that the damper blade is placed within the wall when mounted. 3. Centre the damper in the opening and screw the mounting plates to the wall studs. Ensure that the diagonal dimensions of the duct are equal. 4. Fill the gap between the duct and the wall with fire sealant EKO-KER or similar and seal with fire protection sealant. 6. In cases where the damper is mounted as a transfer air device or end plate, an EKO-N wire mesh grille must be fitted. 7. The following minimum dimensions must be observed when mounting: Minimum distance between dampers: 200 mm. Minimum distance to wall/floor: 75 mm. NOTE! On dampers with a height exceeding 550 mm the extension adapter EKO-FLS with wire mesh grille must be used since the damper blade protrudes beyond the damper adapter in open position. 5. The suspension devices for the damper and ducting must meet the requirements for the firetechnical class of the aperture. 8 8 (8)