CI-tronic Soft starters for Danfoss commercial compressor applications Type MCI 15C, MCI 25C, MCI 50CM-3 I-O

Similar documents
Data sheet. CI-tronic Soft start motor controller Type MCI 3, MCI 15, MCI 25, MCI 30 I-O, MCI 50 I-O 520B1443

CI-Tronic Soft start motor controller MCI 3, MCI 15, MCI 25, MCI 30 I-O, MCI 40-3D and MCI 50-3 I-O

CI-tronic Soft Start Motor Controller Type MCI 25B with Brake

Starting Torque Limiter Type TCI (Soft Start)

Design Guide. VLT Soft Start Controller MCD 100

MAKING MODERN LIVING POSSIBLE. Design Guide VLT MCD 100 Soft Starter the single speed drive

Application example of a motor controlled by MCD100 and protected by a circuit breaker

1 Phase electronic contactor (SC 1)

Contactors and Motor Starters. Smoother running. Longer lasting. Electronic contactors and motor controllers. Product overview and selection guide

DEVICE STATE/BYPASSED FAILURE OVERLOAD


MCD 200 Series Soft Starters

THE COMPLETE SOLUTION FOR STARTING AND STOPPING AC MOTORS. MCD 3000 Soft starter

RVS-AX Instruction Manual

Thermal overload relay TF140DU and TF140DU-V1000

Reduced Voltage Motor Starters

Electronic overload relays EF205 and EF370

Product Description. Application Description

Motor Starters. Reduced Voltage. Reduced Voltage Motor Starters Contents

Control Power V AC, 50/60 Hz 150-C30NBD 150-C30FHD

CI-TI Contactors and Motor Starters Type CI 6-50

Thermal overload relay TF65 and TF96

Electronic overload relay EF65, EF96 and EF146

Application Description

Soft Starter. Types RSBD. Product Description. Type Selection. Ordering Code RSB D E V 61 HP

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW

VEO. V2TF01 Art.Nr.: V2TF01P Art.Nr.: TECHNICAL DATA

RSC09 RSC16 RSC22 RSC38 RSC43 RSC63 RSC-AUX

300% Motor full load amps at 80 seconds, 400% Motor full load amps at 35 seconds

SOLSTART Instruction Manual

VLT Soft Starter MCD 100, MCD 201, MCD 202, MCD 3000

RE-PR1-F 1-Phase Din-Rail Mount 1.5, 3 & 6kW

1.1 Caution Statements

Performer scroll compressors. SM - SY - SZ R407C - R134a - R22-50 Hz QUICK REFERENCE MAKING MODERN LIVING POSSIBLE

Motor Controllers AC Semiconductor Motor Controller Type RSHP Flexy

Synergy EN product information

1.1. Reduced Voltage Motor Starters

High Capacity Valve Body, Type RA-G

AF series contactors (9 2650)

Index. Manual Motor Starters 1. Auxiliary Contact Blocks 1. Trip Alarm Auxiliary 1. Switch. Shunt Release 1. Under-voltage Release 2.

MAKING MODERN LIVING POSSIBLE. Performer scroll compressors. SM - SY - SZ R407C - R134a - R22-50 Hz. Quick reference

VLT Soft Starter. Remote operation. Serial communication 24 V AC/DC V AC. Constant effort to improve MCD 100, MCD 201, MCD 202, MCD 3000

300% Motor full load amps at 80 seconds, 400% Motor full load amps at 35 seconds

Assisted lift operated 2/2-way solenoid valves Type EV251B

Reduced Voltage Motor Starters

Reduced Voltage Motor Starters

BETA Switching Switches and Light Indicators

Thermal Overload Relays

When ordering, please state type and code number. Suitable sensor length. Max. Cap. range. tube adjust- see also Accessories. sensor. temp.

Motor Controllers AC Semiconductor Motor Controller Type RSHP Flexy

PCS compact soft starters

Protection and Connection Motorized and automatic transfer switches IEC Technical guide

Premounted Midi Shunts

AF series contactors (9 2650)

Dimensions WxHxD [mm] Weight [kg]

ATS22D88Q soft starter-ats22-control 220V-power 230V (22kW)/ V(45kW)

For Operation in the Control Cabinet

A. Danfoss VLT Soft Starter The single speed drive. For any soft start situation MAKING MODERN LIVING POSSIBLE

Softstarters. Softstarters Type SSM Medium voltage ,800V 1

Softstarter Intelligent Controllers

SonoSensor 30 Ultrasonic flow sensor

LH4 Modular Soft Start

ChangeOver6 and NovoCon ChangeOver6 - Motorized 6-port Ball Valves

3 - Protection components Motor circuit-breakers

Burden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM

Presentation Soft starters 0 Altistart 48 soft start - soft stop units

Data sheet. CI-TI TM Contactors and Motor Starters Circuit Breakers CTI B1427

KD LV Motor Protection Relay

Bulletin 193-T1 Bimetallic Overload Relays

MS General Information Extended Product Type: MS

USERS MANUAL MCD REMOTE OPERATOR

3RW Soft Starters. General data. 6/4 Siemens LV 1 T 2008

3RW Soft Starters. General data. 6/2 Siemens LV 1 N SIRIUS Soft Starters 01/2008. Siemens AG 2008

CI-TI Contactors and motor starters Types CI 61 - CI 98

Bulletin 825 SMM Smart Motor Manager

TeSys contactors. Use in category DC-1 (resistive loads; time constant L/R y 1 ms) Rated operational current Ie. to be wired in series

Essential equipment for all your requirements

1333 (SERIES B & C) TROUBLESHOOTING GUIDE

Motor Controllers Soft Starting/Soft Stopping Types RSC 4.../RSO 12.., RSC 60.../RSO 16..

Power Electronics. POWERSWITCH Semiconductor Relay / - Contactor With Load Circuit Monitoring PH 9270

Meta Solution. Contactors and Overload relays

Maneurop reciprocating compressors MT - MTZ - NTZ

RVS-DN Digital Reduced Voltage Motor Starter

ON/OFF zone valves AMZ 112, AMZ 113

Variable speed application guidelines

AF40... AF96 3-pole contactors Technical data

Page. Circuit-Breakers M4 2 for motor protection. Auxiliary contacts 3 Signalling switch Auxiliary releases

ATyS S - ATyS d S Remotely operated Transfer Switching Equipment from 40 to 125 A

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

A. Danfoss VLT Soft Starter The single speed drive. For any soft start situation

150 B180 N B D A 8L. Enclosure Type. Input Line Voltage Open Type V AC, 3-phase, 50 and 60 Hz V AC, 3-phase, 50 and 60 Hz

Manual motor starter MS116

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Standard Features

Manual motor starter MS116

For Operation in the Control Cabinet

D509E. Manual Motor - Starters

General technical data: CONTACTOR, AC-3, 11KW/400V, 1NO+1NC, AC110V 50HZ, 120V 60HZ 3-POLE, SZ S0 SCREW TERMINAL. product brand name

Technical Data Accessories MCBs Ex9B.

R134a R134a R13. 4a R134a R134a R134

NEW The new PROmax power supplies offer a wide range of robust solutions for demanding application requirements.

Transcription:

Data sheet CI-tronic Soft starters for Danfoss commercial compressor applications Type, MCI 25C, MCI 50CM-3 I-O The MCI compressor soft starters are designed for soft starting of 3 phase compressors. During start the MCI will gradually increase the voltage to the motor until it reaches full line voltage. The soft start ramp-up time and initial start torque is preset to ensure a fast start and allow easy and quick installation. MCI compressor soft starters are ideal for use on Danfoss Performer scroll and Maneurop Reciprocating compressors. The starting current can be reduced by up to 40% of the direct on line value. Features Universal control voltage: 24 480 V AC/DC Automatic detection of missing phases LED Status indication. Automatic adaptation to 50/60 Hz Easy and quick installation Up to 12 start/stop operations per hour Built in varistor protection IP20 Protection Compact modular design DIN rail mountable Ramp-time max. 0.5 s (factory set-up) EN 60947-4-2 IC.PD.C50.B3.02 1

Functional diagram Mains voltage, L1, L2, L3 Control voltage (A1, A2) Motor voltage (T1, T2, T3) LED 1 LED 2 SCR contact: 23-24 bypass (MCI 25C/MCI 50CM-3 I-O) Functional description Start During ramp-up the controller will gradually increase the voltage to the motor from the preset initial torque value until it reaches full line voltage. The actual ramp time is digitally calculated and will not be influenced by net frequency or load variations. Bypass mode (contact 23-24, only MCI 25C/ MCI 50CM-3 I-O) The auxiliary contacts are made possible by means of SCR technology and will only switch correctly on a.c. current. The contact is intended for operating an external bypass contactor. The contact will close when the controller is in steady state operation, see application example page 7. LED status indication LED 1 LED 2 Stand Ramp Full Line or by up on load error IC.PD.C50.B3.02 2

Soft starter selection guide Performer scroll compressors Motor voltage code 4, 400 V - 3 phase - 50 Hz / 460 V - 3 phase - 60 Hz Compressor model Ambient temp. max. 40 C Ambient temp. max. 55 C SM/SZ 084 SM/SZ 090 SM/SZ 100 MCI 25C SM/SZ 110 SM/SZ 115-125 SM/SZ 120 SM/SZ 160 SM/SZ 148-161 SM/SZ 175-185 SY/SZ 240 MCI 25C MCI 25C 1 ) SY/SZ 300 MCI 50CM-3 I-O 1 ) MCI 50CM-3 I-O 1 ) SZ 380 MCI 50CM-3 I-O 1 ) MCI 50CM-3 I-O 1 ) 1) The controller must be by-passed in steady state mode. See application example page 7 Maneurop compressors Motor voltage code 4, 400 V - 3 phase - 50 Hz / 460 V - 3 phase - 60 Hz Compressor model MT/MTZ 18-22 MT/MTZ 28 MT/MTZ 32 MT/MTZ 36 MT/MTZ 40 MT/MTZ 44-50 MT/MTZ 45-51 MT/MTZ 56 MT/MTZ 57-65 MT/MTZ 64 MT/MTZ 72-73-80-81 MT/MTZ 100 MT/MTZ 125 MT/MTZ 144 MT/MTZ 160 Ambient temp. max. 40 C 1) The controller must be by-passed in steady state mode. See application example page 7 Ambient temp. max. 55 C MCI 25C MCI 25C MCI 25C 1 ) MCI C Soft Starter selection Type Operational voltage Module dimensions [V AC] [mm] Code no. 380 480 45 037N0076 MCI 25C 380 480 90 037N0077 MCI 50CM-3 I-O 380 480 180 037N0401 IC.PD.C50.B3.02 3

Technical data Output specifications MCI 25C MCI 50CM-3 I-O Operational voltage V AC 380 480 380 480 380 480 Operational current (AC-3, AC-53a, AC-53b) max. 15 A 25 A / 30 A 35 A / 50 A Ramp up time (preset) max. 0.4 s 0.4 s 0.5 s Leakage current max. 5 ma 5 ma 5 ma Operational current min. 50 ma 50 ma 50 ma Overload relay trip class Class 10 Class 10 Class 10 Semiconductor protection fusing: Type 1 1 ) co-ordination 50 A gl/gg 100 A gl/gg 125 A gl/gg Type 2 2 ) co-ordination I 2 t(t=10 ms) 1800 A 2 S 6300 A 2 S 25300 A 2 S Rating index: AC-53a Asynchronous motors 3 ) 15A: AC-53a: 8-3: 100-3000 AC-53b Asynchronous motors with bypass - 25A: AC-53a: 8-3: 100-3000 30A: AC-53b: 6-3: 30 35A: AC-53a: 6-6: 100-120 50A: AC-53b: 6-3: 30 1 ) Type 1 coordination require that, under short-circuit conditions, the device shall cause no danger to persons or installation and may not be suitable for further use without repair and replacement of parts 2 ) Type 2 coordination require that, under short-circuit conditions, the device shall cause no danger to persons or installation and shall be suitable for further use 3 ) 15A: AC-53a: 8-3:100-3000 means max. load 8x15A for 3 seconds. 100% ON-load factor or 3000 operations per hour Control circuit specifications Control voltage range 24 480 V AC/DC Pick-up voltage max. 20.4 V AC/DC Drop-out voltage min. 5 V AC/DC Control current for no operation max. 1 ma Control current / power max. 15 ma / 2 VA Response time max. 70 ms SCR by-pass contact, optional Voltage / current (AC-14, AC-15) max. 24 240 V / 0.5A 24 240 V / 0.5A 24 240 V / 1.0A Fuse max. 10 A gl/gg, I 2 t max. 72 A 2 s EMC immunity Meets requirements of EN 50082-1 and EN 500082-2 Insulation Rated insulation voltage U i Rated impulse withstand voltage U imp Installation category 660 V AC 4 kv III Thermal specification Cooling method Natural convection Mounting Vertical +/- 30 Storage temperature range -20 C 80 C Enclosure degree / pollution degree IP20 / 3 IP20 / 3 IP10 / 3 Power dissipation, continuous duty max. 2 W/A 2 W/A 3 W/A Power dissipation, intermittent duty max. 2 W/A duty cycle 2 W/A duty cycle 3 W/A duty cycle Materials Housing self extinguishing Heatsink aluminium Base PPO UL94V1 Black anodized Electroplated steel IC.PD.C50.B3.02 4

Dimensions MCI 25C MCI 50CM-3 I-O Mounting instructions The controller is designed for vertical mounting. If the controller is mounted horizontally the load current must be reduced by 50%. The controller needs no side clearance. Clearance between two vertical mounted controller must be minimum 80 mm (3.15 ). Clearance between controller and top and bottom walls must be minimum 30 mm (1.2 ). IC.PD.C50.B3.02 5

Overload and short circuit protection Overload and short circuit protection is easily achieved by installing a circuit breaker on the line side of the motor controller. Select the circuit breaker from the table below. Be aware of the maximum prospective short circuit current breaking capacity. For further information please refer to the data sheet on the circuit breaker. Performer scroll compressors Compressor type Motor voltage code 4 / 400 V - 3ph - 50 Hz / 460 V - 3ph - 60 Hz Compressor max. current Danfoss CTI [A] Type Code no. SM/SZ 084 17 CTI 25M 047B3150 SM/SZ 090 17 CTI 25M 047B3150 SM/SZ 100 19 CTI 25M 047B3151 SM/SZ 110 20 CTI 25M 047B3151 SM/SZ 115 25 CTI 25M 047B3152 SM/SZ 120 29 CTI 25M 047B3152 SM/SZ 125 25 CTI 25M 047B3152 SM/SZ 148 32 CTI 45MB 047B3164 SM/SZ 161 32 CTI 45MB 047B3164 SM/SZ 160 29 CTI 25M 047B3152 SM/SZ 175 35 CTI 45MB 047B3164 SM/SZ 185 35 CTI 45MB 047B3164 SY/SZ 240 50 CTI 45MB 047B3165 Maneurop reciprocating compressors Motor voltage code 4 / 400 V - 3ph - 50 Hz / 460 V - 3ph - 60 Hz Compressor type Compressor max. current Danfoss CTI [A] Type Code no. MT/MTZ 18 5 CTI 25M 047B3147 MT/MTZ 22 6 CTI 25M 047B3148 MT/MTZ 28 7.5 CTI 25M 047B3148 MT/MTZ 32 8 CTI 25M 047B3149 MT/MTZ 36 9 CTI 25M 047B3149 MT/MTZ 40 10 CTI 25M 047B3149 MT/MTZ 44 9.5 CTI 25M 047B3149 MT/MTZ 45 9.5 CTI 25M 047B3149 MT/MTZ 50 12 CTI 25M 047B3150 MT/MTZ 51 11.5 CTI 25M 047B3149 MT/MTZ 56 12 CTI 25M 047B3150 MT/MTZ 57 12 CTI 25M 047B3150 MT/MTZ 64 15 CTI 25M 047B3150 MT/MTZ 65 14 CTI 25M 047B3150 MT/MTZ 72 15.5 CTI 25M 047B3150 MT/MTZ 73 17 CTI 25M 047B3150 MT/MTZ 80 18 CTI 25M 047B3151 MT/MTZ 81 19 CTI 25M 047B3151 MT/MTZ 100 22 CTI 25M 047B3151 MT/MTZ 125 27 CTI 25M 047B3152 MT/MTZ 144 30 CTI 45MB 047B3164 MT/MTZ 160 36 CTI 45MB 047B3164 Overheat protection If required, the controller can be protected against overheating by inserting a thermostat in the slot on the right-hand side of the controller. Order: UP 62 thermostat, code no. 037N0050 For wiring connections see application examples below. IC.PD.C50.B3.02 6

Application examples Overheat protection The thermostat is connected in series with the control circuit of the main contactor. When the temp. of the heat sink exceeds 90 C the main contactor will be switched OFF. This circuit requires manual reset to restart the motor. Line controlled soft start When the contactor K1 is switched to the ONstate, the soft starter will start the motor, according to the settings of the ramp-up time and initial torque adjustments. When the contactor K1 is switched to the OFF-state the motor will be switched off instantaneously. In this application the contactor will have no load during opertion. The contactor will carry and break the nominal motor current. Danfoss 37N51 MCI 25 with bypass contactor By means of the built-in auxiliary contact the bypass function is easily achieved, see wiring diagram from the side. No heat is generated from the MCI. As the contactor always switches in no-load condition it can be selected on the basis of the thermal current (AC-1). (13-14 contact not applicable with MCI 25C and MCI 50CM-3 I-O). Input controlled soft start When the control voltage is applied to A1 - A2, the MCI soft starter will start the motor, according to the settings of the Ramp-up time and Initial torque adjustments. When the control voltage is switched OFF, the motor will switch off instantaneously. Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary eady agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved. IC.PD.C50.B3.02 7