USER MANUAL. Power GUARD UPS. Uninterruptible Power System

Similar documents
Uninterruptible Power System

USER MANUAL. Blazer Vista 1000/1400/2000. Uninterruptible Power System

1. INTRODUCTION. Features:

800VA/ 1000VA/ 1200VA/ 1500VA 2200VA/ 3000VA USER S MANUAL

Liebert PSI XR 1000/1500/2200/3000, 120VAC. User Manual

BRAVER UPS. (Uninterruptible Power System) User s Manual

Liebert PowerSure PSI

Uninterruptible Power System

LINE INTERACTIVE LONG BACKUP TIME UPS EN-1000 / EN-2000 USER S MANUAL

Series VA 230V. USER MANUAL English

User Manual Digital Energy Uninterruptible Power Supply ML Series UPS VA GE Digital Energy Power Quality

Uninterruptible Power System

USER S MANUAL ENDURE 500VA ENDURE 750VA ENDURE 1000VA ENDURE 2000VA

UPS USER MANUAL F-11 LINE INTERACTIVE UPS GENERAL PURPOSE UPS 650VA/1200VA/2200VA

Liebert PowerSure PSI UPS

Sola 3000 Guide Specifications

User Manual. Digital Energy Uninterruptible Power Supply ML Series UPS VA. GE Digital Energy Power Quality. GE imagination at work

AC Power For Business-Critical Continuity. Liebert PSI XR. User Manual 1000/1500/2200/3000VA, 50/60Hz, 230VAC

USER S MANUAL CONTENTS. Uninterruptible Power Supply 1. INTRODUCTION SAFTY INSTRUCTION SYSTEM DESCRIPTION... 4

Sola/Hevi-Duty S3K Series Mini-Tower UPS

Informer Compact Series

General Precautions. Personnel Precautions

USER MANUAL. PowerMust 1400/2000 LCD. Uninterruptible Power System

User Manual. NetGuard IMPORTANT. PSD 650/1200/1600 Line Interactive UPS Uninterruptible Power Supply System. UPS Monitoring Software

Uninterruptible Power System

UPStation GXT. 6 & 10 kva 208V & 240V. USER MANUAL English

Uninterruptible Power Supply

Uninterruptible Power System. Line Interactive Network Protection Pure Sine Wave Output UPS. Rack Mount Models 1000VA/ 1500VA/ 2000VA/ 3000VA

Uninterruptible Power Supply ERA LCD 0.65 ERA LCD 0.85 ERA LCD 1.1. User s manual

Match 19" GE Digital Energy. Uninterruptible Power Supply VA. Technology for the Digital World. Match 19" UPS.

User Manual V1.1 OptiFlex 1100 / OptiFlex 2000

On Line UPS. LUC 1000E / LUC 2000E / LUC 3000E User Manual

USER MANUAL ONLINE UPS 6000L(XL)/10000L(XL) Uninterruptible Power Supply

Uninterruptible Power Supply USER MANUAL Version 1.4. Always On UPS Systems Inc. GES-801L, GES-102L, GES-152L, GES-202L, GES-302L

Limousin II User Manual

USER S MANUAL CONTENTS. Uninterruptible Power Supply 1. INTRODUCTION SAFTY INSTRUCTION CABLE CONNECTION... 4

User Manual Easy UPS BV Series 500VA, 650VA, 800VA, 1000VA Safety and General Information

CONTENTS 1. INTRODUCTION SAFTY INSTRUCTION CABLE CONNECTION SYSTEM DESCRIPTION INVERTER OPERATION...

OPERATIONAL MANUAL .TYPE - ONLINE UNINTTERRUPTIBLE POWER SUPPLY

USER MANUAL. Uninterruptible Power Supply Line-interactive VCL Series UPS VA

USER MANUAL. IPS home inverters with UPS function. IPS home inverter manual

Users Manual. Defender 1 8.0KW to 14.0KW Online Emergency Lighting Inverter. Technical Manual # Revision B

User Manual Back-UPS BX650CI-MS 230 Vac with AVR

Liebert GXT3 UPS 230V 700VA-3000VA

CP900EPFCLCD User s Manual K

Users Manual. Cobra Plus Stand-By Emergency Lighting Inverter. Technical Manual # Revision B

LIFT 1500 VA UNINTERRUPTIBLE POWER SUPPLY UPS USER MANUAL

Installation and Operation Back-UPS BX550CI-CN

SmartPro Medical-Grade UPS, Line Interactive, Lithium Battery, 6 Outlets - 230V, 1kVA, 750W, Full Isolation

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS

3000VA 120/208/230VAC

UTILITY INPUT MAINS OUTLET

Installation and Operation Manual Back-UPS BX1100CI-CN

CONTENTS 1. INTRODUCTION SAFTY INSTRUCTION CABLE CONNECTION SYSTEM DESCRIPTION OPERATION... 9

Power Inverter. User s Manual. Diamond Series CPD1200EILCD

USER MANUAL. Uninterruptible power supply MODEL: 53965,

Liebert GXT2-6000RTL630

USER MANUAL MPS 1-5KW SERIES

1. INTRODUCTION SYSTEM DESCRIPTION Front Panel CONNECTION AND OPERATION TROUBLESHOOTING...8

POWER TROLLEY 8 INSTRUCTION MANUAL POWER TROLLEY 8. Model: SINE Instruction Manual for: Self-Contained Sinewave Mobile Power Backup System

U P S. Uninterruptible Power System Unterbrechungsfreie Stromversorgung

MM-AVR UPS Series User s Manual

Eclipse Plus VA UPS and Surge Suppressor User s Manual

Liebert GXT3 230V, ,000VA

Installation and Operation Manual Back-UPS BR800/1100CI-IN

Back-UPS 650 VA 230 V with AVR (BX650CI-ZA)

USER MANUAL. Line Interactive UPS. Uninterruptible Power System

Industrial On-Line UPS V, 700 VA VA. S4KC Series. Instruction Manual

PR1000ELCD / PR1500ELCD User s Manual

661-SK [1]I:\USV_TEAM\USV_MANUAL\Roline\LineSecureII\661-SK [1].d oc U P S. Uninterruptible Power System

USER MANUAL English / Español

Installation Guide Smart-UPS On-Line SRT1000/SRT1500 XLA Tower/Rack-Mount

User Manual V1.0 MaxiFlex 3000

PowerSure POWER PROTECTION USER S MANUAL. Uninterruptible Power System 250 VA 600 VA 115 V PS250-60S 250 VA PS400-60S 400 VA PS600-60S 600 VA.

User Manual 1KVA-5KVA INVERTER / CHARGER

02/15/01. Powerware User s Guide VA.

Installation and Operation Manual Back-UPS BX800CI-ZA/BX1100CI-ZA

CX-SERIES ADVANCED BATTERY CHARGER

Thank you for choosing EATON products. Safety information and operating instructions are included in this manual. Do not attempt to operate the UPS

User manual. Solar Hybrid 1-5KVA. Uninterruptible Power Supply / Charger

U n i n t e r r u p t i b l e P o w e r S y s t e m

USER MANUAL ONLINE UPS

Liebert PSA VA. Installer/User Guide

UPStation GX 1000 VA to 3000 VA

NB NB 1511 NB NB 4031 TRUE ON-LINE DOUBLE CONVERSION UPS

Line Interactive UPS 1000/1400/2000VA Uninterruptible Power System

Liebert GXT4. User Manual 700VA ~ 3000VA (230V)

User Manual. English. APC Smart-UPS. 750/1000/1500 VA 100/120/230 Vac 2U Rack-Mount Uninterruptible Power Supply

OPERATING INSTRUCTION UPS PROTECT A. PROTECT A PROTECT A. 1400

Centurion 1000/1500/2000/3000 Tower/Rackmount On Line UPS User s manual

User Manual Rittal PMC UPS 6kVA

User Manual Back-UPS BC500-RS, BC650-RS 650 VA 230 V

USER MANUAL DN / DN

Liebert GXT VA RT230 Rack-Tower model GUIDE SPECIFICATIONS 1.0 GENERAL

1KVA/ 2KVA/ 3KVA/ 4KVA/ 5KVA MS, LV MPPT INVERTER / CHARGER. User Manual. Version: 2.3

SmartOnline SUT Series 3-Phase 208/120V 220/127V 30kVA 30kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option

Sine Wave Solar UPS. Owner s Manual. Thank you for choosing the intelligent NON STOP Solar UPS with state of art technology.

Whad 0.8, 1, 1.5 kva. Manuel d installation Installation manual. Part. LE05733AA-07/12-01 GF

Solar Hybrid Power Generating System CPS1200EOH12SC CPS2200EOH24SC CPS3000EOH24SC. User s Manual K01-C

Transcription:

USER MANUAL Power GUARD UPS Uninterruptible Power System

IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for Power GUARD that should be followed during installation and maintenance of the UPS and batteries. Read all safety and operating instructions before operating the UPS. Adhere to all warnings on the unit and in this manual. Follow all operating and user instruction.

CONTENTS 1. Introduction 1 2. Safety CAUTION! 1-3 3. System Concept 3-5 4. System Description 6-10 5. Installation 10-11 6. Operation 11-12 7 Trouble Shooting 13-15 8. Specification 15-16

1. Introduction This series are Line Interactive Sinewave UPS series and provide conditioned power to microcomputer and other sensitive electronic equipment. Upon generation, AC power is clean and stable. However, during transmission it may be subject to voltage sags, spikes, or complete power failure which may interrupt computer operations, cause data loss, or even damage equipment. This series protects equipment from these disturbances. This series UPS is a compact, and Line Interactive UPS. A Line Interactive UPS continuously conditions and regulates its output voltage, whether the mains power is present or not. It supplies connected equipment with clean sinewave power, to simulate as much as possible, the power generated by the mains. Sensitive electronic equipment operates best from sinewave power. For ease of use, this series contain a light emitting diode (LED) bar display to indicate either load percentage or battery capacity depending upon the mode of operation. It also provides self diagnostics and two levels of alarms when the unit is operating on battery. This series have an interface port for communications between the UPS and a LAN server or other computer system. This port provides detailed operating information including voltages, currents, and alarm status to the host system when used in conjunction with C-eyes software. 2. Safety CAUTION WARNING: Do not attempt to service this product yourself except to replace the battery. Opening or removing the cover may expose you to dangerous voltages, even when the AC cord is disconnected from the electrical outlet. Refer all servicing to qualified service personnel. 1. This product is designed for Commercial/Industrial use only. It is not intended for use with life support and other designated critical devices. 1

Maximum load must not exceed that shown on the UPS rating label. If uncertain, consult your dealer. See Limited Warranty. 2. When replacing the batteries, use the appropriate replacement battery kit. Proper disposal of batteries is required. Refer to your local laws and regulations for disposal requirements. 3. Always turn off the UPS and unplug it before starting the battery replacement procedure. To replace batteries, refer to the battery replacement procedure. If you feel unqualified to replace the batteries, do not open the battery door. Refer all servicing to qualified service personnel. 4. CAUTION: Do not open or mutilate the batteries. Released electrolyte is harmful to skin and eyes and may be toxic. 5. The mains supply socket or means of isolation must be within 2 meters of the equipment and accessible to the operator. The UPS is designed for data processing equipment. 6. The UPS comes with two output power leads with molded connectors. Do not modify the output power leads. Consult dealer if connector does not match the load socket. UPS must be earthed at all times while in use. Turn UPS off before unplugging it, or the safety earth will be removed. 7. The UPS output supply sockets may electrically live whenever the input power lead is plugged into the mains supply socket. Turning the UPS off does not electrically isolate the internal parts. To isolate the UPS, turn the UPS off and then isolate it from the mains supply. CAUTION: The UPS and connected load total earth leakage current must not exceed 3.5 milliamperes If the connected load earth leakage current is likely to exceed 2.5 milliamperes or you are unsure, then convert the input lead attachment to either a fixed wiring installation or an industrial plug/socket (e.g. CEE 17 connector). This task should be carried out by a competent electrical engineer who is conversant with local electrical codes/regulations. 2

8. Operate UPS only from a properly earth, 50Hz or 60Hz, 220-240 VAC mains supply. Models are available from 100-127VAC supply voltages. 9. Route power supply leads so they are not walked on or pinched. 10. Never block or insert any object into the ventilation holes or other openings. Maintain a minimum clearance of 100mm (4 inches) all around the UPS for proper airflow and cooling. 11. Operate the UPS in an indoor environment only, with an ambient temperature range of 0 C to 40 C (32 F to 104 F). Install it in a clean environment, free from moisture, flammable liquids, gasses, or corrosive substances. 12. Storing magnetic media on top of the UPS may result in data loss or corruption. 13. Turn the UPS off and unplug the UPS before cleaning. Use only a soft cloth, never liquid or aerosol cleaners. 14. This equipment can be operated by individuals without previous training. 3. System Concept 3-1 UPS Operation Line Mode: When input AC is normal, I/P voltage delivers directly to O/P without draining battery energy. They include normal, buck and boost modes. The O/P voltage is almost the same as I/P voltage in normal mode. The O/P voltage is almost 1.15/1.12 (1.12) times of I/P voltage in boost mode for 120V / 220V (230V/240V) models and 0.88 / 0.90 (0.90) times of I/P voltage in buck mode for 120V / 220V (230V/240V) models. Refer to Figures 1, 2, and 3. Fig. 1 UPS in Normal Mode 3

Fig. 2. UPS in Buck Mode Fig. 3. UPS in Boost Mode Battery Mode: When input AC source (utility) is abnormal, O/P is supplied by batteries. Its output waveform is sine wave. Fig. 4. UPS in Battery Mode 3-2 Transient voltage surge suppression (TVSS) and EMI/RFI filters These UPS components provide surge protection and filter electromagnetic interference (EMI) and radio frequency interference (RFI). They minimize any surges or interference present in the mains line and keep the sensitive equipment protected. 4

3-3 Automatic voltage regulator In normal operation, the automatic voltage regulator (AVR) passes mains AC power to the connected load. When mains power voltage is outside acceptable limits, the AVR activates. It raises undervoltage power and lowers overvoltage power. This keeps the UPS output voltage within the connected equipment s tolerances and allows wide mains voltage fluctuations without utilizing battery power. 3-4 Bi-Directional converter In normal operation, the bi-directional converter converts mains AC power into regulated DC power to float charge the battery system. Upon a mains power failure, the bi-directional converter receives its required energy from the battery and inverts it into precise, regulated sinewave AC power. Charging takes place whenever the UPS is plugged into the wall outlet and mains power is within acceptable limits. 3-5 Battery This series utilizes valve regulated, nonspillable, lead acid batteries. At typical room temperatures and with the UPS float charging, the battery system will last many years. For battery run times, refer to Typical Battery Discharge Curves. 5

4. System Description Front Panel 1KVA/1.25KVA 1KVA/1.25KVA 2KVA/2.5KVA 2KVA/2.5KVA/3KVA/3.5KVA 3KVA/3.5KVA Tower Rack 6

1. Power Switch: The power switch controls output power to connected loads. CAUTION: Pressing the power switch when AC mains is not present will cause the UPS to begin operating from battery. This should not be performed unless the UPS input is connected to a properly earthed socket. 2. Alarm Silence/ Battery Test Button The Alarm Silence/Battery Test Button serves a dual purpose. During normal mode operation, press button for at least one half second to test capacity of the battery system. The UPS will operate in battery mode for approximately 15 seconds. The illuminated LED indicators in Load/Battery Level determine battery mode capacity in 25% increments. During battery mode operation or active alarm condition, this button functions as the alarm silence feature. Pressing this button for at least one half second will silence the alarm. After the alarm is silenced, the UPS will reactivate the alarm system to alert of additional problems. The low battery alarm is the single alarm that cannot be silenced. During a Battery Test, if the top two LEDs do not illuminate, allow the UPS to recharge the batteries for 24 hours. After 24 hours, retest the batteries. If the batteries have been retested and the top two LEDs still do not illuminate, contact your dealer for a battery replacement kit. 3. Mains/Battery Status Indicator (Green LED) An illuminated LED indicates the power button is on and mains power is available. Green LED flashing 5 times along with an alarm signifies mains voltage is out of specification and UPS is operating in battery mode. 4. Boost and Buck AVR Indicator (Yellow LED) An illuminated LED indicates the UPS is correcting mains power, due to a mains overvoltage or undervoltage condition. 5. Load/Battery Level Indicators (All Green LEDs) The Load/Battery Level Indicators have dual functions. During normal mode operation, LED indicators display electrical load placed upon the UPS; and during battery mode operation, LED indicators display battery 6. Fault Indicator (Green LED) The Fault Indicator is the second bottommost LED (contained in load/battery level indicators). A flashing LED indicates the UPS has detected a problem. An alarm sounds to alert that the UPS requires attention. Refer to Trouble Shooting Guide. 7

Audible Alarm Condition Condition Alarm One short beep every 10 Battery Mode seconds; more than 2 minutes (Power Failure) of run time remaining Two short beeps every 5 Low Battery seconds; less than 2 minutes of run time remaining Battery Replacement 2-second beep every minute Overload One short beep every second UPS fault Continuously Sounding Back Panel for Tower Case 1KVA/1.25KVA 2KVA/2.5KVA 8

3KVA/3.5KVA (For 110V only) Back Panel for Rack Case 1KVA/1.25KVA 2KVA/2.5KVA 9

(For 110V only) 3KVA/3.5KVA 1. Input Socket / Input Power cord 2. Output Socket 3. RS-232 4. Output Socket (large circuit)(for 110v only) 5. Input Circuit Breaker 6. Output Circuit Breaker 7. RJ-45 (Network / FAX / Modem / surge Protection) 8. Site Wiring Fault LED 9. Fan 5. Installation 1. Inspection Unpack the UPS carefully and note the packing method. Retain the box and packing material for possible future shipment. Visually inspect the UPS for freight damage. Report damage to the carrier and your dealer. CAUTION: The UPS is heavy (see specification). Take proper precautions when lifting or moving it. 2. Placement Locate the UPS where it cannot be accidentally disconnected. Locate it in an area with unrestricted airflow, away from water, flammable liquids, gases, or corrosives. Maintain a minimum of 100mm (4 inches) clearance around the UPS. Maintain an ambient temperature range of 0 C to 40 C (32 F to 104 F) 10

3. Before Connection Shutdown load equipment, turn off mains supply and unplug load equipment s power input cable from mains supply socket. As the color of the wires in the mains lead may not correspond with the 4. Load Connection Connect the supplied IEC320-10 output cable between the load equipment input socket and one of the UPS AC output socket. Connect all load equipment to the UPS in the same way. 5. Turn on Turn on the UPS by pressing the power switch for at least 0.5 second; then turn on the connected load equipment. The UPS is ready for normal operation. 6. Operation 1. Normal Mode Operation During normal operation, mains power provides energy to the UPS. The filters and the power conditioning circuit process this power to provide computer grade power to connected loads. The UPS maintains the batteries in a fully charged state. The front panel displays the percentage of load on the UPS output. The figure below indicates approximately 51%-75% loading. 2. Mains High/Low Mode Operation If high or low voltage conditions occur, the UPS will automatically correct the mains voltage by either lowering or raising the input voltage condition. The UPS will continue to correct these conditions indefinitely, without draining battery power. The figure below indicates approximately 51-57% loading while automatically correcting the mains voltage. 11

3. Battery Mode Operation Battery mode occurs in event of extreme input voltage condition or complete mains failure. The battery system along with the bi-directional converter generates power for the connected load. During battery mode an alarm sounds every 10 seconds. This will change to 2 beeps every 5 seconds when battery runs low (approximately 2 minutes remaining). Each load/battery level indicator represents a 25% capacity level. As capacity decreases, fewer indicators remain illuminated. Mains LED will flash every second indicating the UPS is operating from battery mode. Battery mode supports a full rated load for approximately 5 minutes before it shuts down. To increase this time, turn off non-essential pieces of equipment (such as idle computers and monitors) WARNING: Turning off the UPS while in battery mode will result in loss of output power. The figure below displays approximately 51-57% battery capacity remaining. 4. Battery Charge Mode The UPS resumes normal operation once mains power is restored, whether the UPS is ON or OFF. At this time, the bi-directional converter begins recharging the battery. 12

7. Trouble Shooting The information below indicates various symptoms a user may encounter in the event the UPS develops a problem. Use this information to determine whether external factors cause the problem and how to remedy the situation. 1. The fault indicator will flash every second to indicate the UPS detected a problem. 2. An alarm will sound to alert that the UPS requires attention. 3. One or more additional load/battery level LED segments will be illuminated to provide a diagnostic aid to the operator, as described below: A. UPS fault (fan failure, battery overcharge) NOTE: The internal fan operates intermittently as needed B. UPS failed battery test D. UPS shutdown due to output overload time-out A.&B. UPS shutdown due to main input relay failure/output short circuit A.&D. UPS shutdown due to over temperature condition B.&D. UPS shutdown due to command from communication ports (remote shutdown or SNMP) The fault indicators will be illuminated indefinitely while battery charger is operational, or for a maximum of 5 minutes while battery charger is not operational. If a problem persists, consult your dealer immediately. Trouble Shooting Guide Problem Cause Solution UPS fails to start when UPS output short circuited Ensure Ups is off. On/Off button is pressed. or overloaded. Disconnect all loads and ensure nothing is lodged in output receptacles. Ensure loads are not detective or shorted internally. Internal fuse is blown, indicating internal fault. Do not attempt to open or service the Ups. Contact your dealer. 13

Mains indicator flashing UPS not plugged in. UPS is operating in battery mode. Make sure that UPS is securely plugged into the wall receptacle. UPS has reduced battery time. UPS input protection has UPS is operating in battery opened. mode. Save data and close applications. Replace UPS input fuse or reset input beaker, then restart UPS. Mains voltage out of UPS UPS is operating in battery input range. mode. Save data and close applications. Ensure mains supply voltage is within acceptable limits for UPS. Battery not charged Keep UPS plugged in continuously at least 24 hours to recharge batteries. UPS is overloaded. Check load level display and remove non-essential loads. Batteries may not be able Replace batteries. to hold a full charge due to age. Fault indicator and UPS fan failure or battery UPS requires service. diagnostic LED A are overcharge. Contact your dealer. illuminated. Fault indicator and UPS failed the battery test. Replace batteries. diagnostic LED B are illuminated. UPS shut down. Fault indicator and diagnostic LED D are illuminated. UPS overloaded or load equipment is faulty. Check load level display and remove non-essential loads. Recalculate load VA and reduce number of loads connected to Ups. Check load equipment for faults. 14

UPS shut down with the UPS shutdown due to UPS requires service. Fault indicator and internal failure. Contact your dealer. diagnostic LEDs A and B are illuminated. UPS shuts down with the Fault indicator and diagnostic LEDs A and D are illuminated. UPS shutdown due to an internal over temperature condition. Ensure UPS is not overloaded, ventilation openings not blocked, or room ambient temperature not excessive. Wait 30 minutes to allow UPS to cool, then restart UPS. If it does not restart, contact your dealer. UPS shuts down with the Fault indicator and diagnostic LEDs B and D are illuminated. UPS shutdown due to a command from the communication port. Your UPS has received a signal or command from the attached computer. If this was inadvertent, ensure the communication cable used is correct for your system. For assistance, contact your dealer. 8. Specification MODEL Tower type 1K/1.25K 2K/2.5K 3K/3.5K CAPACITY INPUT OUTPUT Rack mount type 1K/1.25K 2K/2.5K 3K/3.5K VA/W 1KVA/600W 2KVA/1200W 3KVA/1800W 1.25KVA/750W 2.5KVA/1500W 3.5KVA/2100W Voltage 110VAC / 230VAC Acceptable Voltage Range 89-129VAC / 178-260VAC Line Low Transfer 82VAC ± 4% / 168VAC ± 4% Voltage Line Low Comeback 89VAC ± 4% / 178VAC ± 4% Range Line High Transfer 136VAC ± 4% / 272VAC ± 4% Line High Comeback 129VAC ± 4% / 260VAC ± 4% Voltage 110VAC / 230VAC Voltage Regulation (Batt. Mode) 7% Frequency Frequency Regulation (Batt. Mode) Waveform 50Hz or 60Hz ±0.5Hz Pure Sinewave TRANSFER TIME Typical 4-6ms 15

BATTERY INDICATORS AUDIBLE ALARM PHYSICAL Tower Battery Type* 12V/7.2Ah 12V/7.2Ah 12V/5Ah Rack 12V/8Ah 12V/8Ah 12V/5Ah Tower Rack Battery Type* 2 pcs 4 pcs 8 pcs Backup Time (at full load) 5-10 minutes (Typical) Recharge Time 4 hours to 95% after discharged AC Mode Green LED lighting Backup Mode Green LED flashing Boost/Buck Yellow LED lighting It represents Load Level in AC Mode and Battery Level in Backup Mode. 4-segment LED bar- Load/Battery Level 0-25% : 4th LED lighting 26%-50% : 3rd and 4th LEDs lighting 51%-75% : 2nd, 3rd, and 4th LEDs lighting 76%-100% : 4 LEDs in a row all lighting Low Battery The bottom LED in a row of Load/Battery LEDs flashing every 2 seconds Backup Mode Sounding every 10 seconds Low Battery Sounding every 5 seconds UPS Fault Continuously Sounding Overload Sounding every 0.5 second Battery Replacement Sounding 2 seconds every 60 seconds Tower Dimension (DxWxH) mm 390x125x190 420x200x290 460x200x290 Case Net weight (kgs) 15 / 16 25 / 26 35 / 36 Rack Dimension (DxWxH) mm 375x482x85 445x482x130 445x482x172** Case Net weight (kgs) 16 / 17 27 / 28 35 / 36 ENVIRONMENT Operating Environment 0-40 C, 0-90 % relative humidity (non-condensing) Noise Level Less than 45dB INTERFACE RS-232 Support Windows 95/98/NT/2000/XP, Novell, and Linux 16