Achieving the Highest Power Density in the Smallest Footprint

Similar documents
Simply Reliable Solutions for Continuous, High Quality Power Tradition. Technology. Innovation.

Experience and History

VYCON Direct Connect (VDC ) Kinetic Energy Storage Systems

ULTRACAPACITORS FOR UNINTERRUPTIBLE POWER SUPPLY (UPS)

Theory of Operation: Low Speed Flywheel

Power Conditioning of Microgrids and Co-Generation Systems

MORE EFFICIENT DIESEL ELECTRIC POWER PLANT FOR DREDGES

Machine, Panel, and Plant Level Solutions

SDC,Inc. SCR-Regenerative Ac Drive

VYCON Direct Connect (VDC ) Kinetic Energy Storage Systems

Expect More From An Energy Storage Solution BATTERY FREE DC ENERGY STORAGE FOR UPS BILL WOLFE NORTHEAST REGIONAL MANAGER

Electric Power Delivery To Big Cities

400/230 Volt 60Hz UPS Power

POWER. ANYTIME. ANYWHERE. YOU GOT THE POWER. AIRPORT TECHNOLOGIES GROUND POWER UNITS

Flywheel Energy Storage

GE Critical Power. The Retrofit Case for Upgrading Legacy Power Systems at Telecom Central Offices

Bridge Time UPS Batteries: A Scalable Alternative to Flywheels by

ABB UPS 3. November 2014

A Comparison of Typical UPS Designs in Today s Markets

Flywheel UPS Systems, kva

kw. Introducing the Power Xpert 9395P UPS. Setting the standard. 9395P Power rating. Can be paralled up to 7 units. The energy to innovate

Flexible and Reliable Power Supply Solution Intelligent Control. Secure Power

CONTINUOUS POWER IN YOUR CONTROL KEM5

ULTIMA U75 U HP OIL-FREE TWO-STAGE VARIABLE SPEED ROTARY SCREW COMPRESSOR. Ultima

Liebert NXC. 10kVA - 60kVA. Compact, Efficient, and Reliable Power Solution

CT430 - Soft Starters on Motor Applications

Power Quality. Power Factor Wiring and Service. Background. Introduction. bchydro.com

Microgrid solutions Delivering resilient power anywhere at any time

BATTERY FREE DC ENERGY STORAGE FOR UPS. Yorba Linda CA (714)

Development and Operational Advantages of a Solid State Circuit Breaker with Current Limiting

Hawai'i Island Planning and Operations MEASURES TO IMPROVE RELIABILITY WITH HIGH DER

SitePro UPS 400Vac / CE. GE Consumer & Industrial August 2004

One Solution for Ideal Power Quality

SmartOnline S3MX Series 3-Phase 380/400/415V 60kVA 54kW On-Line Double-Conversion UPS

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS

MGE TM Galaxy TM 7000

Batteries and Flywheels and their application in UPS systems

3ph UPS NS3000 series kVA

MTU ONSITE ENERGY DIESEL GENERATOR SETS 50 Hz: 30-3,730 kva 60 Hz: 30-3,250 kwe

NorthStar Battery (NSB) Telecom Application Manual

Power Safety. Protect 8. Industrial UPS. Protect 8.31 Single Phase output 10 kva 120 kva. Protect 8.33 Three Phase output 10 kva 120 kva

PowerWAVE (60 kva/kw) Paralellable up to 5 MVA/MW

One Solution for Ideal Power Quality

White Paper. Application of Resistive/Reactive Load Banks for kva Testing

UNIT 6: BATTERIES, UPS AND CABLES

NO-BREAK KS. Dynamic UPS system PRESENTATION

Power Protection Discrete Automation & Motion South Africa

SS SyStem SyStemy free UPS tter ba UPS

UNINTERRUPTIBLE CHILLED WATER SUPPORT STANDARD DESIGN AND WHITE PAPER

MGE TM Galaxy TM 7000 GFC

High-voltage Direct Inverter Applied to Induced Draft Fan Motor at Takehara Thermal Power Station No. 3 of Electric Power Development Co., Ltd.

Don t Discriminate: The importance of selective coordination in electrical installations

Application Note CTAN #127

Basics of Paralleling

Power Conversion System for ESS 100 kw to 30 MW Bi-directional Inverters

Ampd Silo. Energy Storage System. Maintenance-free Li-ion energy storage for mission critical backup. Power to Empower

200 kva* Noise level (Generator online) Fuel tank size (approx. 5.5 hours autonomy) 1400 liters 308 gallons /370 US gallons

Uptime. All the time.

Benefits of VFD for single to three phase conversion

Flybrid mechanical kinetic energy

Electric Power Marketing Spec Sheet Continuous Power Module CPM250

WELCOME! Today we d like to Introduce you to your North American Rotary UPS Solutions Partner!

Mellivora: A Battery Experiment

GE Transportation. 7FDS Medium-Speed Diesel Generators High efficiency reciprocating engines with low life-cycle costs

ELG4125: Flexible AC Transmission Systems (FACTS)

n Lower energy costs and carbon footprint n Cooler operation extends internal component life n High input power factor of 0.99

High- or Medium-Speed Generator Sets: Which Is Right for Your Application?

INTEGRATED POWER SYSTEMS FOR MANUFACTURING AND INDUSTRIAL FACILITIES

Uninterruptible Power System

APC Smart-UPS. GUIDE SPECIFICATIONS FOR 1000VA & 2000VA Smart-UPS 230VAC Uninterruptible Power Supply

JOINT SERVICE POWER EXPO CLARY CORPORATION

Pump ED 101. Power Factor (Part 2) - - Electricity Behaving Better

Liebert FS Flywheel DC Energy Storage System

Abstract. Benefits and challenges of a grid coupled wound rotor synchronous generator in a wind turbine application

MASTERYS IP+ 10 to 80 kva

Power Quality and Power Interruption Enhancement by Universal Power Quality Conditioning System with Storage Device

ELECTRIC SHIP TECHNOLOGY SYMPOSIUM EXPERIMENTAL TESTBED TO DE-RISK THE NAVY ADVANCED DEVELOPMENT MODEL

S C ELECTRIC EUROPE LTD. Excellence Through Innovation. Harnessing the Wind. November 2011 Descriptive Bulletin E

off-grid Solutions Security of supply Basics: Off-grid energy supply

SmartOnline SVTX Series 3-Phase 380/400/415V 20kVA 18kW On-Line Double-Conversion UPS, Tower, Extended Run, SNMP Option

Shaft Grounding and Sliding Electrical Contacts

Multi-megawatt power protection at medium voltage

Network Powering Strategies and Alternatives

Development of Small-capacity OFF-LINE UPS

High Effective Availability Decentralized UPS HEAD-UPS (c) 3.0 High Effective Availability Decentralized UPS-HEAD-UPS(c)

Diesel UPS/CPS systems Continuous power

Lithium-ion battery systems for ABB UPS solutions Reliable, lightweight and compact UPS energy storage for critical applications

Development of Emergency Train Travel Function Provided by Stationary Energy Storage System

GE Energy. Variable Frequency Transformers Grid Inter-tie

ASHRAE - Variable Speed Drives. By Dan Watkins, LEED BD+C Bornquist, Inc.

TECHNICAL SPECIFICATION FOR A 10 TO 50 KVA THREE PHASE, UNINTERRUPTIBLE POWER SYSTEM WaveRider III

UPS Ratings-Not so Apparent

Liebert. FP 50Z kva

Hydro Plant Risk Assessment Guide

G V Series UNINTERRUPTIBLE POWER SYSTEMS. Phone: Fax: Web:

Three-phase UPS system. DPA UPScale ST kw Best-in-class modular UPS for maximum availability

Solar Freedom Package - Starter Kit Grid-Interconnected Solar System with Battery Storage

Symmetra PX 250/500. Scalable from 100 kva kw to 500 kw, parallel capable up to 2,000 kw

PARALLELING SWITCHGEAR

Outdoor Distribution (15 kv through 25 kv) S&C Fault Tamer Fuse Limiter

Transcription:

Achieving the Highest Power Density in the Smallest Footprint White Paper Summary For many years, mission critical applications have required high quality power conditioning and uninterruptable power to ensure business continuity. In recent years however, new efficiency matrixes have dominated the market and real estate has become more valuable, highlighting the need for high efficiency, low footprint solutions. The Diesel Rotary UPS (DRUPS) is no exception and in fact, with several innovations, has become increasingly viable for both small and large applications, while providing the lowest footprint of any UPS. This whitepaper examines the advantages of the Diesel Rotary UPS solution and explains how it can maximize on power density with the smallest footprint. Whitepaper HitzWP001 Date May 17 th 2016 Author Ben Jones, CEO and President at Hitzinger USA, LLC.

Introduction Critical loads demand exacting standards and innovative application of proven systems to assure the infrastructure integrity. Hitzinger diesel rotary systems provide proven reliability and offer many advantages over the battery backed UPS and Standby diesel generator including; maximizing available plant room space, minimizing running costs, eliminating UPS air conditioning requirements and addressing some of the technical issues presented by large static UPS installations such as harmonic filtration, poor input power factor, no inherent fault clearing capability and maintaining a controlled battery environment. Despite the many salient benefits provided by the DRUPS to mission critical applications; there is one huge advantage that is consistently over looked, yet is arguably one of the most significant benefits of the Rotary solution. We are referring to footprint, the ability to achieve the highest density in the smallest footprint to be exact. With the market applying constant pressure to UPS manufacturers to meet larger density power, top quality solutions, superior load handling and higher efficiency (>96.8%), the DRUPS solution is fast becoming the preferred choice for electrical supply critical installations. UPS Comparisons A. Battery Backed with Additional Standby Diesel Generator Operation For any application requiring a long-term backup of the consumer, a diesel engine and alternator (otherwise referred to as a Diesel Generator) is required. The use of a Diesel Generator can supply the load for prolonged outages, but on average can take anything between 5-30seconds before it can supply power to the consumer. In mission critical applications, this short interruption in power can be catastrophic, however, a UPS system can be installed to bridge the time required for the Diesel Generator to supply power. One way to bridge this gap is to use a static UPS, which uses a DC battery backup to support the load until the Diesel Generator upstream can get to speed. For these DC batteries to keep charge the static UPS requires a rectifier and inverter; which converts the mains utility supply from AC to DC, providing a DC power to float charge the battery bank. In stand-by operation, the Inverter will supply AC output, albeit with an artificial sine wave, to the consumer. See figure 1 below, demonstrating the normal power flow to the consumer in stand-by operation.

Figure 1 Static UPS Power Flow in Stand-by Operation The above diagram is a simplistic overview of a typical static UPS, however, to ensure top quality power conditioning some static UPS systems may require additional Power Factor Correction and harmonic suppression equipment (not shown). In addition, static UPS systems require costly air conditioning in the battery rooms to ensure maximum life. In the event of mains failure, the DC battery bank will support the load via the inverter and provide adequate time for the diesel generator upstream to supply power. Figure 2 Static UPS Power Flow in Battery Operation.

Figure 3 Diesel Generator Supplying the Load In conclusion, to bridge just 30-seconds of power, the static UPS requires an extremely large footprint as well as high operational costs and costly battery overhauls. B. Diesel Rotary UPS systems (DRUPS) An alternative to battery backed UPS are Diesel Rotary UPS systems (DRUPS) that significantly reduce the footprint by mechanically combining the UPS and Diesel Generator. Unlike the static UPS that require a battery bank to support the load during mains failure, a DRUPS uses a kinetic energy storage module mounted at the end of the alternator shaft. This simple mechanical storage means that the DRUPS solution is only 2-4.5ft longer than the equivalent generator (Depending on size 150>3000kVA), but provides the same uninterruptable power in a significantly reduced footprint. In normal operation, the engine of the DRUPS system is off and clutch is open, thus separating it from the alternator. The alternator and Kinetic storage module are both spinning 365days/year 24hrs/day, acting like a synchronous motor on the mains. This motor, in connection with an inline choke (Inductor), provide conditioning of the mains supply. In normal operation, the outer rotor of the Kinetic storage module spins approximately twice as fast (3000rpm) as the alternator rotor (1800rpm synchronous speed). In the event of mains failure, the faster outer rotor slows down in order to maintain the speed of the alternator shaft at 1800rpm. At the same time, the diesel engine receives a signal to start and becomes the prime mover of the alternator within 5-7seconds.

Hitzinger Solution Highest Power Density with the Lowest Footprint The Hitzinger Diesel Rotary UPS uses a simple mechanical coupling to join a flywheel onto the Diesel Generator thus mitigating the need for the Static UPS components including; Rectifier, Inverter, Batteries including DC breakers and DC Bus, power factor correction capacitors, harmonic suppression and Air Conditioning. In total, a Diesel Rotary UPS will save between 40-60% footprint (dependent on the total load). Figure 4 Hitzinger Diesel Rotary UPS System Hitzinger DRUPS solution - providing vital space saving technology with 40-60% more efficient results to better serve your business.

Please consider this: A diesel generator (Engine and Alternator) is required for both systems, as the long-term back-up of the mains. The additional flywheel for the DRUPS only adds approximately 4.5ft for the largest system (3000kVA) and takes full advantage of a standard diesel generator installation, including both internal and containerized solutions. No additional equipment is required to fully support the application and no costly air conditioning is required. The larger the system, the higher percentage of footprint savings is created. In addition, the DRUPS can provide a medium voltage solution using a direct generation alternator (>15kV), providing simplistic distribution solutions. The simple design of a DRUPS system provides top quality conditioned power within an extremely reliable compact solution. Conclusion The Hitzinger solution provides significant advantages, both commercial and technical. Our system benefits from over 70-yrs of turnkey power solution experience and provides the lowest maintenance, including overhaul, of any UPS. Coupling the Kinetic storage module to the Diesel generator means that costly battery overhauls can be avoided and with high efficiencies of >96.6%, the Hitzinger solution can help reduce running costs of UPS to a minimum.

About the Author Ben Jones is the CEO and President of Hitzinger USA. He graduated from London Southbank with a Bachelor of Science with Honors and a holds a Master s Degree from Greenwich University. He has worked with Hitzinger since 2005 where his tenure began in the UK, and has extensive experience with design and installation of turnkey power solutions. Other Whitepapers are available upon request, please email benjones@hitzinger.us and receive a full list of whitepapers currently available. Hitzinger USA LLC. 11764 Marco Beach Drive, Suite 4-6 Jacksonville, Florida 32224 Tel: (904) 518-9635