ATTACHMENT A PRINCE EDWARD COUNTY INVITATION FOR BIDS # MOBILE DIESEL PACKAGED ENGINE GENERATOR SPECIFICATIONS

Similar documents
Multi-Institutional Academic Health Science & Research Center Evansville, IN

DCA400SSI4F. WhisperWatt 400. MQ POWER Whisperwatt Series. Prime Rating 320 kw (400 kva) Standby Rating 336 kw (420 kva)

.3 Section Concrete Forms and Accessories: Installation of Anchor Devices, Setting Templates

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS

SECTION PACKAGED ENGINE GENERATOR SYSTEMS

SECTION GENERAL-SERVICE AIR COMPRESSOR PART 1 - GENERAL

Diesel generator set. QSB5 series engine Hz EPA Tier 3 emissions. Specification sheet. Description. Features

SECTION DOMESTIC-WATER PACKAGED BOOSTER PUMPS

Diesel generator set. 20 kw EPA emissions stationary Standby. Specification sheet. Description. Features

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

Diesel generator set. 50 kw - 60 kw EPA emissions stationary Standby. Specification sheet. Description. Features

SECTION STANDBY GENERATOR

Diesel generator set QSX15 series engine

IN2 Enclosed Switches and Circuit Breakers

Spark-ignited generator set

January 2015 Town of Surf City Standard Specifications

Diesel generator set QSK23 series engine

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:

REQUEST FOR QUOTATION

Diesel generator set 6BT5.9 series engine

Spark-ignited generator set

1. Division 26 Section "Elevator Shunt-Trip Fused Disconnect Switches".

Diesel generator set QSB7 series engine

Multi-Institutional Academic Health Science & Research Center Evansville, IN

Diesel generator set QSX15 series engine

Rental Power 800 kw. Specification sheet. Description. Features. Options

Rental Power QSB7 series engine

Magnum Mobile Generator MMG75 SS Specifications

SPECIAL SPECIFICATION 5066 Packaged Engine Generator System

Diesel generator set QSK23 series engine

Diesel generator set QSL9-G7 series engine

Magnum Mobile Generator MMG75 Specifications

SECTION AXIAL HVAC FANS

Diesel generator set 4BT3.3 series engine

SECTION ENCLOSED CONTROLLERS

Diesel generator set QSK60 series engine

Rental Power QSL9 series engine

SPECIAL SPECIFICATION 8334 Packaged Engine Generator

Magnum Mobile Generator MMG125 Specifications

30kW Standby / 27kW Prime Power Towable Generator

Magnum Mobile Generator MMG235 Specifications

EMERGENCY GENERATOR SET

Diesel Generator Set Model DFHB 60 Hz

Diesel generator set QSK50 series engine

Mobile Generator MMG130 Specifications

Diesel generator set QSK60 series engine

STANDBY EMERGENCY CNG/LPG GENERATOR

Spark-ignited generator set

13,000 Watt Diesel Generator AGi13P E

DIESEL GENERATOR SETS

Mobile Generator MMG25FHI Specifications

Diesel generator set QSK78 series engine

RENTAL DIESEL GENERATOR SET

DIESEL GENERATOR SET. 60 Hz FEATURES

Diesel generator set QSK78 series engine

Diesel generator set QSK95 series engine

10,000 Watt Diesel Generator AGi9P E

80kW Standby / 70kW Prime Power Towable Generator

Diesel Generator Set Model DFBF 60 Hz

Model DFHD 60 Hz EPA Emissions

Model DKAC 60 Hz EPA Emissions

Diesel generator set QSK60 series engine

60 Hz FEATURES. Exclusively from your Caterpillar dealer

Diesel generator set QST30 series engine

LINCOLN COUNTY STANDARD SPECIFICATIONS SECTION PACKAGED ENGINE GENERATORS, DIESEL

Rental Power 1500 kw. Specification sheet. Description. Features. Options

Diesel generator set QSK78 series engine 2750kVA kVA 50 Hz

Standby kw Prime kw

Model DFEH 60 Hz EPA Emissions

Diesel Generator Set Model DFCE 60 Hz

60 Hz FEATURES. Exclusively from your Caterpillar dealer

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.

XQ175 RENTAL. 60 Hz FEATURES EPA TIER 3 AND CARB CERTIFIED FOR NON-ROAD MOBILE APPLICATIONS

Diesel generator set QSK60 series engine

Diesel Generator Set Model DFJD 60 Hz

University of Houston Master Construction Specifications Insert Project Name

APS150A SOUND ATTENUATED DUAL VOLTAGE/60HZ

STANDBY 200 ekw 250 kva

Diesel generator set QSL9 series engine

Ice Rink Renovation & New Clubhouse

RENTAL XQ400 SOUND ATTENUATED. 50/60 Hz FEATURES

1510 GENERATOR AND TRANSFER SWITCHES

Spark-Ignited Generator Set Model GGLA 60 Hz

Diesel Generator set QSK50 series engine 1135 kw-1500 kw 60 Hz EPA emissions

Spark-Ignited Generator Set Model GGKD 60 Hz

Mobile Generator MMG75D Specifications

Diesel Generator Set Model DGDB 60 Hz

Model DSHAE 60 Hz EPA Emissions

Diesel generator set QSK78 series engine 2750kVA kVA 50 Hz Data Center Continuous

Spark-Ignited Generator Set Model GGKC 60 Hz

Diesel Generator Set Model DSHAD 60 Hz EPA Emissions

Diesel Generator set QSK95 series engine

MMG45IF4. Mobile Generator. Engine. Generators. System Output. System Controls MMG45IF4

Industrial Diesel Generator Set KD1100-F 50 Hz Fuel Consumption Optimized

Tier4 certified diesel generator set QSK50 series engine

MDG75DF4 4.5L 75 kva MOBILE DIESEL GENERATOR SET. Power When and Where You Need It

STANDBY 80 ekw 100 kva PRIME 72 ekw 90 kva

Diesel Generator set QSK95 series engine

AGi20P 2.2 L 20 kw Perkins Powered Diesel Generator AURORA GENERATORS INCORPORATED AURORA STANDARD FEATURES STANDBY POWER RATING 20 KW, 20 KVA, 60 HZ.

100 KW(NG) / 100 KW(LP) LIQUID COOLED POWERED by

Transcription:

PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section. 1.2 SUMMARY A. This Section includes packaged engine-generator sets for emergency power supply with the following features: 1. Diesel Engine with Trailer. 2. 1 Year / Unlimited Hours Warranty. 3. Unit-mounted cooling system. 4. Unit-mounted control and monitoring. 5. Sound Attenuated Weatherproof enclosure with 23hr at 100% Load Sub-Base Diesel Tank. 6. Generator Rating 80kW Prime Rating, 100kW Standby Rating, Multiple Voltage a. Must be EPA Tier 4i Emissions Certified for Mobile Use b. UL2200 Listed Package c. NFPA110 Upgraded 1.3 SUBMITTALS A. Product Data: For each type of packaged engine generator indicated. Include rated capacities, operating characteristics, and furnished specialties and accessories. In addition, include the following: 1. Thermal damage curve for generator. 2. Time-current characteristic curves for generator protective device. B. Shop Drawings: Detail equipment assemblies and indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection. 1. Dimensioned outline plan and elevation drawings of engine-generator set and other components specified. 2. Wiring Diagrams: Power, signal, and control wiring. C. Field quality-control test reports. D. Operation and Maintenance Data: For packaged engine generators to include in emergency, operation, and maintenance manuals. Include the following: 1. List of tools and replacement items recommended to be stored at Project for ready access. Include part and drawing numbers, current unit prices, and source of supply. E. Warranty: Special warranty specified in this Section. A-1 of 8

1.4 QUALITY ASSURANCE A. Manufacturer Qualifications: A qualified manufacturer who manufactures the engine and controls for the generator. Maintain, within 100 miles of Project site, a service center capable of providing training, parts, and emergency maintenance repairs. B. Source Limitations: Obtain packaged generator sets and auxiliary components through one source from a single manufacturer. C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use. D. Comply with ASME B15.1. E. Comply with NFPA 37. F. Comply with NFPA 70. G. Comply with NFPA 110 requirements for Level 2 emergency power supply system. H. Comply with UL 2200. I. Engine Exhaust Emissions: Comply with applicable EPA state and local government requirements. 1.5 PROJECT CONDITIONS A. Environmental Conditions: Engine-generator system shall withstand the following environmental conditions without mechanical or electrical damage or degradation of performance capability: 1. Ambient Temperature: Minus 15 to plus 40 deg C. 2. Relative Humidity: 0 to 95 percent. 3. Altitude: Sea level to 1000 feet. 1.6 WARRANTY A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components of packaged engine generators and associated auxiliary components that fail in materials or workmanship within specified warranty period. 1. Warranty Period: One (1) Year Unlimited Hours, or Two (2) Year / 2000 Hour to commence after unit has been Started up by Generator Technician 1.7 MANUFACTURERS A. Manufacturers: Subject to compliance with requirements, provide products by one of the following only: 1. Basis of Design MQ DCA125SSJE2 (MultiQuip) 2. Cummins Power Generation; Industrial Business Group. 3. Kohler. A-2 of 8

1.8 ENGINE-GENERATOR SET A. Factory-assembled and -tested, engine-generator set. B. Mounting Frame: Maintain alignment of mounted components without depending on concrete foundation; and have lifting attachments. C. Capacities and Characteristics: 1. Output Connections: Three-phase, four wire. 2. Nameplates: For each major system component to identify manufacturer's name and address, and model and serial number of component. D. Generator-Set Performance: 1. Steady-State Voltage Operational Bandwidth: 3 percent of rated output voltage from no load to full load. 2. Transient Voltage Performance: Not more than 20 percent variation for 50 percent stepload increase or decrease. Voltage shall recover and remain within the steady-state operating band within three seconds. 3. Steady-State Frequency Operational Bandwidth: 0.25 percent of rated frequency from no load to full load. 4. Steady-State Frequency Stability: When system is operating at any constant load within the rated load, there shall be no random speed variations outside the steady-state operational band and no hunting or surging of speed. 5. Transient Frequency Performance: Less than 5 percent variation for 50 percent stepload increase or decrease. Frequency shall recover and remain within the steady-state operating band within five seconds. 6. Output Waveform: At no load, harmonic content measured line to line or line to neutral shall not exceed 5 percent total and 3 percent for single harmonics. Telephone influence factor, determined according to NEMA MG 1, shall not exceed 50 percent. 7. BRUSHLESS with AVR 1.9 ENGINE A. Fuel: Fuel oil, Grade DF-2. B. Rated Engine Speed: 1800 rpm. C. Maximum Piston Speed for Four-Cycle Engines: 2250 fpm. D. Lubrication System: The following items are mounted on engine or skid: 1. Filter and Strainer: Rated to remove 90 percent of particles 5 micrometers and smaller while passing full flow. 2. Thermostatic Control Valve: Control flow in system to maintain optimum oil temperature. Unit shall be capable of full flow and is designed to be fail-safe. 3. Crankcase Drain: Arranged for complete gravity drainage to an easily removable container with no disassembly and without use of pumps, siphons, special tools, or appliances. E. Engine Fuel System: A-3 of 8

1. Main Fuel Pump: Mounted on engine. Pump ensures adequate primary fuel flow under starting and load conditions. 2. Relief-Bypass Valve: Automatically regulates pressure in fuel line and returns excess fuel to source. 3. Fuel/Water Separator F. Coolant Jacket Heater: Electric-immersion type, factory installed in coolant jacket system, 120V or 240V, single-phase operation. G. Governor: Electronic H. Cooling System: Closed loop, liquid cooled, with radiator factory mounted on engine-generatorset mounting frame and integral engine-driven coolant pump. 1. Coolant: Solution of 50 percent ethylene-glycol-based antifreeze and 50 percent water, with anticorrosion additives as recommended by engine manufacturer. 2. Size of Radiator: Adequate to contain expansion of total system coolant from cold start to 110 percent load condition. 3. Temperature Control: Self-contained, thermostatic-control valve modulates coolant flow automatically to maintain optimum constant coolant temperature as recommended by engine manufacturer. 4. Coolant Hose: Flexible assembly with inside surface of nonporous rubber and outer covering of aging-, ultraviolet-, and abrasion-resistant fabric. a. Rating: 50-psig maximum working pressure with coolant at 180 deg F, and noncollapsible under vacuum. b. End Fittings: Flanges or steel pipe nipples with clamps to suit piping and equipment connections. I. Muffler/Silencer: Sized as recommended by engine manufacturer and selected with exhaust piping system to not exceed engine manufacturer's engine backpressure requirements. For aesthetics, the Silencer shall be internal to the enclosure. J. Air-Intake Filter: Heavy-duty, engine-mounted air cleaner with replaceable dry-filter element and "blocked filter" indicator. K. Starting System: 12-V electric, with negative ground. 1. Components: Sized so they will not be damaged during a full engine-cranking cycle with ambient temperature at maximum specified in Part 1 "Project Conditions" Article. 2. Cranking Motor: Heavy-duty unit that automatically engages and releases from engine flywheel without binding. 3. Cranking Cycle: 60 seconds. 4. Battery: Adequate capacity within ambient temperature range specified in Part 1 "Project Conditions" Article to provide specified cranking cycle at least three times without recharging. 5. Battery Cable: Size as recommended by engine manufacturer. Include required interconnecting conductors and connection accessories. 6. Battery-Charging Alternator: Factory mounted on engine with solid-state voltage regulation and 35-A minimum continuous rating. 7. Unit shall include a Battery Charger to be used while genset is in storage. A-4 of 8

1.10 TRAILER and FUEL TANK A. 11,000 lb GVWR Rated Tandem Axle Trailer, Torsion Type Suspension B. Must meet all National Highway Traffic safety Administration regulations. C. Include DOT Lighting Package, Tongue Swivel Jack, Safety Chains, DOT Steel Brake Lines D. Replaceable, Bolt-on Hydraulic Brake Actuator, Surge Hydraulic Drum Brakes (all axles), Steel Fenders, Powder-Coated Frame. E. Adjustable 2-5/16 Ball Coupler, Spare Tire with Locking Mount F. Tongue Mounted Utility Storage Box G. Fuel Tank shall be minimum 168-Gallon, 23+ hours at 100% load and be mounted under genset. Direct reading fuel gauges. H. 123% Spill Containment for all fluids. 1.11 GENERATOR OUTPUT PANEL A. Generator must produce simultaneous 3-Phase and 1-Phase Power. B. Three Phase Voltages Required: 208Y/120, 240Y/139, 480Y/277, 220Y120 C. Single Phase Voltage Required: 240/120 D. Required: Two (2) 120v, 20 amp GFCI Receptacles. Three (3) CS-6369 Twist Lock Receptacles, 240v/120v, 50 Amps. Circuit breakers for each GFCI and CS-6369 receptacle. E. Panel must be Microprocessor based with remote 2-wire start/stop control. LCD Display with heated screen and alphanumeric readout. F. Modbus interface required. Automatic Safety Shutdowns for water temp, engile oil pressure, low coolant, overspeed and overcrank. Warning Lights to indicate abnormal condition. G. Analog Instrumentation including AC Ammeter, AC Voltmeter, frequency meter, ammeter phase selector switch. H. Control Panel must be fully covered, with panel viewing window. I. Generator must be fitted with CAM-LOK Connectors for quick hookup to Load Cables. 1.12 GENERATOR OVERCURRENT AND FAULT PROTECTION A. Generator Circuit Breaker: 300 Amp, Molded-case, thermal-magnetic type complying with NEMA AB 1 and UL 489. 1. Tripping Characteristic: Designed specifically for generator protection. 2. Trip Rating: Matched to generator rating. A-5 of 8

3. Mounting: Adjacent to or integrated with control and monitoring panel. 1.13 GENERATOR, EXCITER, AND VOLTAGE REGULATOR A. Comply with NEMA MG 1. B. Drive: Generator shaft shall be directly connected to engine shaft. Exciter shall be brushless, self-excited. OPEN DELTA ALTERNATOR DESIGN. C. Electrical Insulation: Class F. D. Stator-Winding Leads: Brought out to terminal box to permit future reconnection for other voltages if required. E. Construction shall prevent mechanical, electrical, and thermal damage due to vibration, over speed up to 125 percent of rating, and heat during operation at 110 percent of rated capacity. F. Enclosure: Drip-proof. G. Instrument Transformers: Mounted within generator enclosure. H. Voltage Regulator: Solid-state type, separate from exciter, providing performance as specified. 1. Adjusting rheostat on control and monitoring panel shall provide plus or minus 5 percent adjustment of output-voltage operating band. I. Sub transient Reactance: 12 percent, maximum. 1.14 OUTDOOR GENERATOR-SET ENCLOSURE -70dBA at 23 under full load. A. Description: Vandal-resistant, weatherproof steel housing and wind resistant up to 100 mph. Multiple panels shall be lockable and provide adequate access to components requiring maintenance. Panels shall be removable by one person without tools. Instruments and control shall be mounted within enclosure. 1. Silencer to be mounted inside the enclosure. B. Engine Cooling Airflow through Enclosure: Maintain temperature rise of system components within required limits when unit operates at 110 percent of rated load for 2 hours with ambient temperature at top of range specified in system service conditions. 1. Louvers: Fixed-engine, cooling-air inlet and discharge. Storm-proof and drainable louvers prevent entry of rain and snow. C. Include a Panel Viewing Window 1.15 VIBRATION ISOLATION DEVICES A. Manufacturers recommended Isolation Pads between Component Mounts and Frame. A-6 of 8

1.16 FINISHES A. Indoor and Outdoor Enclosures and Components: Manufacturer's standard finish over corrosion-resistant pretreatment and compatible primer. 1.17 LOAD CABLES: A. Provide Five (5) 50 Lengths of Load Cable (1) per phase. And one (1) each for Ground and Neutral) Color of each cable shall be different and based on 208v voltage use. B. 2000V, 400 amp rated to NEC Table 400.5 (B), UL and C-UL listed. Dual Layer Jacket, MSHA Approved. C. Each end shall have a CAM-LOK Connection to connect to Docking Station and Cam-Lok Connections on Genset. 1.18 SOURCE QUALITY CONTROL A. Prototype Testing: Factory test engine-generator set using same engine model, constructed of identical or equivalent components and equipped with identical or equivalent accessories. PART 2 - EXECUTION 2.1 IDENTIFICATION A. Identify system components according to Division 26 Section "Common Work Results for Electrical." 2.2 FIELD QUALITY CONTROL A. Perform tests and inspections and prepare test reports. 1. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect components, assemblies, and equipment installations, including connections, and to assist in testing. B. Tests and Inspections: 1. Perform tests using available Site Loads. 2. Battery Tests: Equalize charging of battery cells according to manufacturer's written instructions. Record individual cell voltages. a. Measure charging voltage and voltages between available battery terminals for full-charging and float-charging conditions. Check electrolyte level and specific gravity under both conditions. b. Test for contact integrity of all connectors. Perform an integrity load test and a capacity load test for the battery. c. Verify acceptance of charge for each element of the battery after discharge. d. Verify that measurements are within manufacturer's specifications. 3. Battery-Charger Tests: Verify specified rates of charge for both equalizing and floatcharging conditions. A-7 of 8

4. System Integrity Tests: Methodically verify proper installation, connection, and integrity of each element of engine-generator system before and during system operation. Check for air, exhaust, and fluid leaks. 5. Voltage and Frequency Transient Stability Tests: Use recording oscilloscope to measure voltage and frequency transients for 50 and 100 percent step-load increases and decreases, and verify that performance is as specified. C. Coordinate tests with tests for transfer switches and run them concurrently. D. Test instruments shall have been calibrated within the last 12 months, traceable to standards of NIST, and adequate for making positive observation of test results. Make calibration records available for examination on request. E. Leak Test: After installation, charge system and test for leaks. Repair leaks and retest until no leaks exist. F. Operational Test: After electrical circuitry has been energized, start units to confirm proper motor rotation and unit operation. G. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment. H. Remove and replace malfunctioning units and retest / re-inspect as specified above. I. Retest: Correct deficiencies identified by tests and observations and retest until specified requirements are met. J. Report results of tests and inspections in writing. Record adjustable relay settings and measured insulation resistances, time delays, and other values and observations. Attach a label or tag to each tested component indicating satisfactory completion of tests. 2.3 DEMONSTRATION A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain packaged engine generators. B. Coordinate training with that required for automatic transfer switch. C. Provided (1/2 hour) of training for generator at the Time of Startup. 2.4 FUELING - by Customer END OF ATTACHMENT A A-8 of 8