Voltage Collapse Prevention in Doubly Fed Induction Generator Based Wind Farm Connected Power System

Similar documents
Wind Power Plants with VSC Based STATCOM in PSCAD/EMTDC Environment

Statcom Operation for Wind Power Generator with Improved Transient Stability

ENHANCEMENT OF ROTOR ANGLE STABILITY OF POWER SYSTEM BY CONTROLLING RSC OF DFIG

Voltage Sag Mitigation in IEEE 6 Bus System by using STATCOM and UPFC

EFFECT OF WIND TURBINE GENERATORS ON THE SMALL SIGNAL STABILITY OF POWER SYSTEMS. Kamel A. Shoush, Member, IEEE

COMPARISON BETWEEN ISOLATED AND GRID CONNECTED DFIG WIND TURBINE

Performance of Low Power Wind-Driven Wound Rotor Induction Generators using Matlab

Wind Farm Evaluation and Control

Comparative Analysis of Integrating WECS with PMSG and DFIG Models connected to Power Grid Pertaining to Different Faults

Combined Input Voltage and Slip Power Control of low power Wind-Driven WoundRotor Induction Generators

CONTROL AND PERFORMANCE OF A DOUBLY-FED INDUCTION MACHINE FOR WIND TURBINE SYSTEMS

VECTOR CONTROL AND DIRECT POWER CONTROL METHODS OF DFIG UNDER DISTORTED GRID VOLTAGE CONDITIONS

APPLICATION OF VARIABLE FREQUENCY TRANSFORMER (VFT) FOR INTEGRATION OF WIND ENERGY SYSTEM

POWER QUALITY IMPROVEMENT BASED UPQC FOR WIND POWER GENERATION

Effect of crowbar resistance on fault ride through capability of doubly fed induction generator

EE 742 Chap. 7: Wind Power Generation. Y. Baghzouz Fall 2011

VOLTAGE STABILITY IMPROVEMENT IN POWER SYSTEM BY USING STATCOM

Power Flow Simulation of a 6-Bus Wind Connected System and Voltage Stability Analysis by Using STATCOM

Coordinated Control of DFIG under Grid Fault Condition in Wind Energy Conversion System

Fuzzy based STATCOM Controller for Grid connected wind Farms with Fixed Speed Induction Generators

FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE

ECEN 667 Power System Stability Lecture 19: Load Models

APPLICATION OF STATCOM FOR STABILITY ENHANCEMENT OF FSIG BASED GRID CONNECTED WIND FARM

CHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM

Study of DFIG based Wind Turbine for Reactive Power Generation Capability

ASSESSING BEHAVOIR OF THE OUTER CROWBAR PROTECTION WITH THE DFIG DURING GRID FAULT

Journal of American Science 2015;11(11) Integration of wind Power Plant on Electrical grid based on PSS/E

CHAPTER 5 ACTIVE AND REACTIVE POWER CONTROL OF DOUBLY FED INDUCTION GENERATOR WITH BACK TO BACK CONVERTER USING DIRECT POWER CONTROL

DOUBLY-FED INDUCTION MACHINE IN WIND POWER GENERATION. Hector A. Pulgar-Painemal, Peter W. Sauer University of Illinois at Urbana-Champaign

EE 742 Chap. 7: Wind Power Generation. Y. Baghzouz

IMPROVEMENT IN DOUBLY FED INDUCTON GENERATOR UNDER FAULT USING INDUCTOR

Transient Stability Improvement of Squirrel Cage Induction Wind Turbine Generator using Plugging Mode

A Comparative Study of Constant Speed and Variable Speed Wind Energy Conversion Systems

TRANSMISSION LOSS MINIMIZATION USING ADVANCED UNIFIED POWER FLOW CONTROLLER (UPFC)

Battery Energy Storage System addressing the Power Quality Issue in Grid Connected Wind Energy Conversion System 9/15/2017 1

VECTOR CONTROL OF THREE-PHASE INDUCTION MOTOR USING ARTIFICIAL INTELLIGENT TECHNIQUE

Hamdy S. K. El-Goharey, Walid A. Omran, Adel T. M. Taha

Intensification of Transient Stability in Grid Connected Squirrel Cage Induction Generator Using Plugging Mode Operation

Model Predictive Control of Back-to-Back Converter in PMSG Based Wind Energy System

Simulation and Analysis of a DFIG Wind Energy Conversion System with Genetic Fuzzy Controller

CHAPTER 6 DESIGN AND DEVELOPMENT OF DOUBLE WINDING INDUCTION GENERATOR

DYNAMIC BEHAVIOUR OF SINGLE-PHASE INDUCTION GENERATORS DURING DISCONNECTION AND RECONNECTION TO THE GRID

Enhancement of Power Quality in Transmission Line Using Flexible Ac Transmission System

Sliding Mode Control of a Variable Speed Wind Energy Conversion System based on DFIG

CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM

STABILITY ANALYSIS OF DISTRIBUTED GENERATION IN MESH DISTRIBUTION NETWORK IN FREE AND OPEN SOURCE SOFTWARE

Simulation Modeling and Control of Hybrid Ac/Dc Microgrid

Computer Aided Transient Stability Analysis

Experimental Resultsofa Wind Energy Conversion Systemwith STATCOM Using Fuzzy Logic Controller

Performance Analysis of Transmission Line system under Unsymmetrical Faults with UPFC

Dynamic Behaviour of Asynchronous Generator In Stand-Alone Mode Under Load Perturbation Using MATLAB/SIMULINK

Available online at ScienceDirect. Energy Procedia 42 (2013 ) Mediterranean Green Energy Forum MGEF-13

A Simple Position-Sensorless Algorithm for Rotor-Side Field-Oriented Control of Wound-Rotor Induction Machine

Reactive power support of smart distribution grids using optimal management of charging parking of PHEV

Keywords: DFIG wind turbine, MPPT, Voltage stability control, Power factor control, PSCAD simulation, Voltage oriented vector control.

Performance Analysis of 3-Ø Self-Excited Induction Generator with Rectifier Load

Implementation SVC and TCSC to Improvement the Efficacy of Diyala Electric Network (132 kv).

Control of Grid Voltage and Power of Doubly Fed Induction Generator wind turbines during grid faults

IJSER. 1. Introduction. 2. Power flow of Doubly fed Induction Generator (DFIG) K. Srinivasa Rao 1 G. Kamalaker 2

A Comprehensive Study on Speed Control of DC Motor with Field and Armature Control R.Soundara Rajan Dy. General Manager, Bharat Dynamics Limited

Modeling Of DFIG and Improving the LVRT Capability Of System Using Crowbar And Battery Energy Storage System

Simulation of Voltage Stability Analysis in Induction Machine

Matlab Modeling and Simulation of Grid Connected Wind Power Generation Using Doubly Fed Induction Generator

STUDY ON MAXIMUM POWER EXTRACTION CONTROL FOR PMSG BASED WIND ENERGY CONVERSION SYSTEM

Possibilities of Distributed Generation Simulations Using by MATLAB

Published by: PIONEER RESEARCH & DEVELOPMENT GROUP ( 201

Fault Rid Through Protection of DFIG Based Wind Generation System

Effect of prime mover speed on power factor of Grid Connected low capacity Induction Generator (GCIG)

ANN Peak Load Shaver.

Advance Electronic Load Controller for Micro Hydro Power Plant

Modelling and Simulation of DFIG with Fault Rid Through Protection

International Journal of Scientific & Engineering Research, Volume 6, Issue 10, October ISSN

PERFORMANCE ANALYSIS OF SQUIRREL CAGE INDUCTION GENERATOR USING STATCOM

Critical Clearing Time and Voltage Stability of DG Integration in Lebanon: A Simulation Using MATLAB/SIMULINK

Performance Analysis of DFIG Based Wind Power Generation under Unbalanced Conditions

Experience on Technical Solutions for Grid Integration of Offshore Windfarms

Asian Journal on Energy and Environment ISSN Available online at

Modeling of Active Crowbar Protection Scheme for Various Types of Fault in Wind Energy Conversion System using DFIG

A Variable Speed Wind Generation System Based on Doubly Fed Induction Generator

Power Quality Improvement Using Statcom in Ieee 30 Bus System

Faults Mitigation Control Design for Grid Integration of Offshore Wind Farms and Oil & Gas Installations Using VSC HVDC

Modeling and Simulation of Five Phase Inverter Fed Im Drive and Three Phase Inverter Fed Im Drive

International Conference on Advances in Energy and Environmental Science (ICAEES 2015)

Performance of FACTS Devices for Power System Stability

COMPARISON OF DIFFERENT METHODS FOR EXCITATION OF SYNCHRONOUS MACHINES

Control Scheme for Grid Connected WECS Using SEIG

Enhancement of Power System Stability Using Thyristor Controlled Series Compensator (TCSC)

Grid Connected DFIG With Efficient Rotor Power Flow Control Under Sub & Super Synchronous Modes of Operation

Squirrel cage induction generator based wind farm connected with a single power converter to a HVDC grid. Lluís Trilla PhD student

Abstract. Benefits and challenges of a grid coupled wound rotor synchronous generator in a wind turbine application

IEEE Transactions on Applied Superconductivity, 2012, v. 22 n. 3, p :1-5

STABILIZATION OF ISLANDING PEA MICRO GRID BY PEVS CHARGING CONTROL

Frequency Control of Isolated Network with Wind and Diesel Generators by Using Frequency Regulator

Dynamic Modeling of Doubly Fed Induction Generator Wind Turbines

RECENTLY, it has been shown that a grid-connected

Grid Stability Analysis for High Penetration Solar Photovoltaics

Design and Control of Lab-Scale Variable Speed Wind Turbine Simulator using DFIG. Seung-Ho Song, Ji-Hoon Im, Hyeong-Jin Choi, Tae-Hyeong Kim

Modeling and Neuro-Fuzzy Control of DFIG in Wind Power Systems for Grid Power Leveling

Islanding of 24-bus IEEE Reliability Test System

Paper ID: EE19 SIMULATION OF REAL AND REACTIVE POWER FLOW ASSESSMENT WITH FACTS CONNECTED TO A SINGLE TRANSMISSION LINE

Transcription:

INAE Lett (2016) 1:41 46 DOI 10.1007/s41403-016-0008-2 ORIGINAL ARTICLE Voltage Collapse Prevention in Doubly Fed Induction Generator Based Wind Farm Connected Power System Srayashi Konar 1 Dheeman Chatterjee 2 Received: 27 June 2016 / Accepted: 29 June 2016 / Published online: 16 July 2016 Indian National Academy of Engineering 2016 Abstract In this work, the doubly-fed induction generator (DFIG), rotor side converter (RSC) is controlled to regulate its reactive power output. A brief comparative study has been carried out between two different RSG control techniques, based on their ability to restore voltage stability of a power system. From this study the better DFIG RSC control strategy has been identified. The results are tested in IEEE-14 bus system and simulated in MATLAB. Keywords DFIG rotor side converter control Capacitive compensation Induction motor load Dynamic voltage stability Introduction The share of renewable energy integration to the modern power grid is increasing across the globe. Power generation from renewable sources being time variable, its effect on system stability is a matter of concern. This work emphasizes on the effects of wind power generation on dynamic voltage stability of a system. As evident in literature, that voltage instability occurs in a stressed system due to the presence of under load/on load tap changer (ULTC), generator over-excitation limiter (OXL) and loads (Cutsem and & Dheeman Chatterjee dheemanc@ee.iitkgp.ernet.in Srayashi Konar srayashi.konar@postgrad.curtin.edu.au 1 2 Electrical and Computer Engineering, Curtin University, Perth, Australia Electrical Engineering, Indian Institute of Technology Kharagpur, Kharagpur, West Bengal, India Vournas 1998). It is inevitable that in a wind farm integrated system, voltage stability will also be affected by the wind electrical system (Zheng and Kezunovic 2010; Kumar et al. 2014). The connection of doubly fed induction generator (DFIG) with a back to back converter in the rotor circuit allows a wide range of speed variation (Bhadra et al. 2005; Folly and Sheetekela 2009). As the converter is connected to the rotor circuit, only a fraction of the total power passes through the converter. Hence, the converter rating is less compared to the full power converter in a direct drive system (Devaraj and Jeevajyothi 2011). With the help of the converter controllers, DFIG can be made to operate in terminal voltage control mode or reactive power control mode, thus influencing the voltage stability of a system. However, the capacity of DFIG to control bus voltage is limited by the rating of the converters (Chi et al. 2006). It is also found that DFIG operating in voltage control mode can improve voltage stability margin of a system compared to its operation in constant power factor mode (Muñoz and Cañizares 2011). In this paper, a comprehensive comparative study has been carried out between efficiency of different RSC control schemes of DFIG on restoring voltage stability of a system. The efficacy of fixed capacitor to prevent voltage collapse is also observed and finally the most promising one among all these to restore stability of a system has been identified. The study also found that the selected RSC control scheme makes the reactive power injection through static shunt compensation redundant. System Description Wind Farm For simplicity of analysis, in this work the wind farm is represented by an aggregated equivalent wind-turbine-

42 INAE Lett (2016) 1:41 46 Fig. 2 DFIG rotor side converter reactive power control loop Fig. 1 DFIG connection to the load bus generator. The DFIG stator and rotor dynamics are considered (Mei 2008; Pal and Mei 2008; Mei and Pal 2005) for this study. The corresponding state variables are the rotor speed, the d-axis and the q-axis components of the stator current (i ds,i qs ) and rotor current (i dr,i qr ). The wind turbine and the DFIG rotating mass is represented by the single-mass model (Mei 2008). Wind turbine generator specifications are as per (Mei 2008; Pal and Mei 2008). DFIG is connected to a load bus of the IEEE-14 bus system through a double circuit line and a transformer (Donnelly et al. 1996) asshownin Fig. 1. Throughout this study it has been assumed that the wind farm is operating at its rated wind speed with a capacity of 100 MW. DFIG Rotor Side and Grid Side Converter Controllers (Pal and Mei 2008; Mei and Pal 2005) The rotor side converter (RSC) and grid side converter (GSC) of the DFIG allow bi-directional power flow in the rotor circuit. As a result, a wide range of speed variation becomes possible. The RSC controller consists of two decoupled loops, shown in Figs. 2 and 3. The slower outer loop achieves electrical torque (T e ) and reactive power (Q tot ) control and produces the reference current for the faster inner current control loop. Q tot is the stator reactive power. Subscript ref stands for the reference point. K x and T x are the proportional gains and the integral time constants, respectively. This control scheme has been referred to as T e - Q tot control, in the rest of the paper. In this work, for minimum converter rating the power sharing is neglected and it is assumed that the reactive power supplied by the DFIG comes from the stator side. Due to the faster dynamics of the GSC and the DC-link, the grid side converter dynamics and DC link dynamics has been neglected and the GSC is represented as a current source. The current source magnitude is set such that the active power supply to the grid, i.e., P GSC, in Fig. 1 matches the power supplied by DFIG in the rotor circuit, i.e. P R at unity power factor. Fig. 3 DFIG rotor side converter electromagnetic torque control loop Synchronous Machine and Network Model The synchronous generators of the system are represented by the flux decay model (Sauer and Pai 2002). The state variables are angular position of rotor (d), per unit speed deviation of rotor (Dx) and q-axis component of the voltage behind the transient reactance (E 0 q). A static exciter is considered which is represented by one gain and one time constant. The corresponding state variable is the exciter voltage (E fd ). The network dynamics is neglected. Network is represented using algebraic equations. The algebraic variables are bus voltage magnitude (V i ) and angle (hk i ). OXL and ULTC (Cutsem and Vournas 1998) Each synchronous generator is equipped with an over excitation limiter (OXL) to keep the generator field current within its limit. In this study, the pre-disturbed field current value is taken as the reference field current of the OXL. OXL starts operating with an initial delay (t oxl ). The system is equipped with ULTC transformers which regulate the load end voltage by changing its tap positions. For simplicity of study it is considered that, the initial mechanical delay (t ultc ) and intermediate delay (delay between consecutive tap movements, t int ) of all the ULTC transformers present in the system are same. IEEE-14 bus system, as shown in Fig. 4 consists of two synchronous generators and three condensers. All are equipped with OXLs. The 2 winding transformer connected between buses 4 and 9 is modelled as ULTC transformer. Load Modelling Wind farm integrated multi-machine system has been studied using constant power (CP) and induction motor

INAE Lett (2016) 1:41 46 43 Fig. 5 Variation of bus voltages (a) and induction motor (IM) slips (b) Fig. 4 IEEE 14-bus system (Power System Toolbox, Version 3.0 2008) load (IM). The approximate load compositions are as follows L s ¼ CP ð1þ L d ¼ 0:4 IM þ 0:6 CP ð2þ Voltage Collapse Prevention in Wind Farm Connected System In this section the voltage stability of IEEE-14 bus system, followed by line outage contingency has been studied. The DFIG RSC is controlled by the T e Q tot control strategy discussed in DFIG Rotor Side and Grid Side Converter Controllers (Pal and Mei 2008; Mei and Pal 2005). The fatal cases from this study are evaluated twice, once with capacitive compensation and next with no compensation but a modified RSG control strategy. Voltage Collapse in a Wind Farm Connected System In this study, DFIG is operating with T e Q tot control mode and the reactive power output of the DFIG, i.e., Q totref in Fig. 2 is maintained constant at one-tenth of its rated active power. IEEE-14 bus system being a small and steady system, double line outage contingency is simulated to induce voltage instability. Figure 5 shows a voltage collapse case. This case is simulated with a wind farm connected to bus 13 and the system load is L d type. An outage of line 1 2 takes place at 30 s. ULTC and OXL start operating at 40 s (i.e., with an initial delay t ultc = t oxl = 10 s). After this, the tap positions keep changing (if required) with an intermediate delay, t int = 5 s. Outage of a second line (4 5) takes place at t = 55 s. The variations of the voltages of bus 9 (ULTC regulated bus) and bus 13 (DFIG connected bus) are shown in Fig. 5a with dotted line and solid line, respectively. The variation in the slips of the induction motors connected to the buses numbered 6, 13 and 14 are shown in Fig. 5b. It can be observed from Fig. 5a, b that with fall in voltages, motor slips increase and eventually start stalling. Voltages of the two buses fall below 0.7 pu. The low bus voltage level and the stalling of induction motors connected to the system indicate voltage instability. Figure 6 shows the change in the relative rotor angles of generator 2 and 3, i.e., generators connected to bus 2 and 3, respectively, with respect to the generator connected to bus1. The damped oscillation in the relative rotor angles indicates the above instability is not an angular instability. System Stability Restoration with Capacitive Compensation The voltage collapse case observed in Voltage Collapse in a Wind Farm Connected System, is studied again with a capacitive compensation, keeping other system conditions unchanged. A shunt capacitor bank is switched at the regulated side of the ULTC transformer (Taylor 1994), i.e., bus 9, when voltage of its regulated end falls below a threshold value. The size of the capacitor is kept nearly equal to the reactive load of the bus, to which it is connected (Taylor 1994). Hence, the capacitor size is about 20 MVAR. The capacitor bank is switched in, as soon as the bus 9 voltage falls below 0.85 pu. The bus voltages and slips of induction motors are shown in Fig. 7a, b, respectively. It is evident from Fig. 7

44 INAE Lett (2016) 1:41 46 Fig. 6 Generators 2 and 3 relative rotor angle during voltage instability Fig. 8 DFIG q-axis control loop (Chi et al. 2006) Fig. 7 Dynamics of bus voltages (a) and induction motor slips (b) over time that with the capacitive compensation induction motors continue to operate stably, following line outages. Voltages of bus 9 and bus 13 remained above 0.8 pu. Therefore, from this study it can be concluded that the stability of the system is improved with switching a capacitor at ULTC regulated bus. System Stability Restoration with Modified Control of DFIG RSC The increase in the reactive power output of the DFIG may also help to prevent collapse. To verify this presumption, the voltage collapse case observed in Voltage Collapse in a Wind Farm Connected System is studied with a modified DFIG RSC control, as shown in Fig. 8. Unlike the RSC q-axis control loop or reactive power control loop as discussed in DFIG Rotor Side and Grid Side Converter Controllers (Pal and Mei 2008; Mei and Pal 2005), this modified RSC controller can control both voltage and reactive power. As shown in Fig. 2 the DFIG RSG controller is augmented by including the option of using DFIG terminal Fig. 9 Dynamics of bus voltages (a) and induction motor slips (b) with DFIG T e Q tot /V s control technique voltage (V s ) as a control variable for the cases where V s falls below a predefined threshold (V sref ). Otherwise (when V s [ V sref ), the reactive power of DFIG continues to be the control variable. The error signal generated from outer loop of the RSC generates the reference q-axis rotor current for the inner current control loop. Here, V qrref is the reference for the q-axis voltage of the rotor. This control technique is referred in this paper as (T e Q tot /V s ) control. The study described in Voltage Collapse in a Wind Farm Connected System is repeated in this section with (T e Q tot /V s ) control technique of DFIG. During this study system is without any capacitive compensation. Objective of this study is to observe the effect of (T e Q tot /V s ) control scheme on voltage stability of the system. Variations in the bus voltages and slip of induction motors are shown in Fig. 9a, b, respectively. From the variation in the induction motor slip it can be stated that, motors remained in their stable operating regions, following the disturbances. Voltages of bus 9 and 13 are above 0.8 pu. Hence, from this study it can be inferred that, with (T e Q tot /V s ) control technique of DFIG RSC, system stability can be improved.

INAE Lett (2016) 1:41 46 45 Table 1 Comparative study in 14-bus system with L S type load Contingency (line outage) (DFIG at bus 13) RSC controlling RSC controlling T e Q tot, T e Q tot a capacitor is switched RSC controlling both T e Q tot /V s (1 2) and (5 6) Voltage collapse Voltage collapse Voltage collapse (5 6) and (11 5) Voltage collapse Voltage collapse Stable (6 8) and (5 6) Voltage collapse Stable Stable (11 5) and (5 6) Voltage collapse Voltage collapse Stable (2 3) and (1 2) Voltage collapse Voltage collapse Voltage collapse (13 5) and (1 2) Voltage collapse Voltage collapse Stable Table 2 Comparative study in 14 bus system Line outage RSC controlling T e Q tot, a capacitor is switched RSC controlling both T e Q tot /V s (6 8) and (5 6) Stable; V rmax = 0.2973; I rmax = 1.162 Stable; V rmax = 0.2908; I rmax = 1.126 (11 5) and (5 6) Unstable Stable; V rmax = 0.291; I rmax = 1.183 (13 5) and (1 2) Unstable Stable; V max = 0.2802; I rmax = 1.122 A Comprehensive Comparison Between Capacitive Compensation and (T e Q tot /V s ) Control In System Stability Restoration with Capacitive Compensation and System Stability Restoration with Modified Control of DFIG RSC, we have studied two different methods for restoring voltage stability of a stressed system. Unstable cases of Voltage Collapse in a Wind Farm Connected System, with DFIG RSC T e Q tot control scheme are listed in Table 1. All these catastrophic collapse cases are simulated with capacitive compensation, as illustrated in System Stability Restoration with Capacitive Compensation and the modified DFIG RSG control scheme as described in System Stability Restoration with Modified Control of DFIG RSC. The system conditions are also enlisted in Table 1. It is evident from Table 1, that the collapse cases observed with DFIG, RSC T e Q tot control scheme can be prevented in a very nominal number of cases with capacitive compensation. However, a lion s share of the collapse scenarios can be restored with DFIG, RSC T e Q tot /V s control scheme. So, it can be inferred from this study that DFIG, RSC T e Q tot /V s control scheme improves voltage stability of a system considerably. Moreover, with this control scheme, there is no need to put a capacitor at the regulated end of the ULTC transformer to restore stability. Effect of the DFIG RSC T e Q tot /V s Control Scheme on the RSC Ratings Accordingto Voltage Collapse Prevention in Wind Farm Connected System, the use of capacitor to prevent voltage collapse can be avoided with a simple modification in the RSC control scheme by using DFIG terminal voltage as the control variable under certain conditions. However, it is important to check the effect of this modification on the rotor current and voltage, as the converter rating depends on these values. For this work, the limits used for DFIG RSC voltage and current are, respectively, ±10 % of the pre-disturbance rotor current and ±30 % of the pre-disturbance rotor voltage. These values of DFIG, in IEEE-14 bus system are V rmax = 0.298 pu; V rmin = 0.1604 pu; I rmax = 1.2249 - pu; I rmin = 0.6596 pu. The maximum rotor current and rotor voltage for the cases listed in Table 1 are enlisted in Table 2. It can be concluded from Table 2 that with this T e Q tot /V s control of DFIG RSC there is no need to change the converter rating. Keeping the RSC current and voltage within its limit, the T e Q tot /V s control scheme can prevent voltage instability. Conclusion This paper discusses about two schemes to prevent voltage instability of a system. After doing a comparative study between the two techniques, (1) DFIG rotor side converter T e Q tot control along with switching on a fixed capacitor and (2) DFIG rotor side converter T e Q tot /V s control, it can be concluded that the (T e Q tot /V s ) control is more efficient in improving the voltage stability conditions of a system. This modification of the DFIG rotor side converter control does not require any change in the RSC rating. Moreover, this study also concludes that the DFIG (T e Q tot /V s ) control eliminates the need of connecting a capacitor at the regulated end of the ULTC transformer.

46 INAE Lett (2016) 1:41 46 Acknowledgments The authors thank Department of Science and Technology, New Delhi, India for financially assisting this work through the project numbered, SR/S3/EECE/0043/2009. References Bhadra SN, Kastha D, Banerjee S (2005) Wind electrical systems. Oxford University Press, New Delhi, India Chi Y, Liu Y, Wang W, Dai H (2006) Voltage stability analysis of wind farm integration into transmission network. In: International conference on power system technology Devaraj D, Jeevajyothi R (2011) Impact of wind turbine systems on power system voltage stability. In: International conference on computer, communication and electrical technology, March 2011 Donnelly MK, Dagley JE, Trudnowski DJ, Rogers GJ (1996) Impacts of the distributed utility on transmission system stability. IEEE Trans Power Syst 11(2):741 746. doi:10.1109/59.496148 Folly KA, Sheetekela SPN (2009) Impact of fixed and variable speed wind generators on the transient stability of a power system network. In: Power systems conference and exposition, March 2009 Kumar VSS, Reddy KK, Thukaram D (2014) Coordination of reactive power in grid-connected wind farms for voltage stability enhancement. IEEE Trans Power Syst 29(5):2381 2390 Mei F (2008) Small signal modelling and analysis of doubly-fed induction generators in wind power applications. PhD thesis, Department of Electrical and Electronic engineering, Imperial College London Mei F, Pal B (2005) Modal Analysis of grid-connected doubly fed induction generators. IEEE Trans Energy Convers 22(3):728 736 Muñoz JC, Cañizares CA (2011) Comparative stability analysis of DFIG-based wind farms and conventional synchronous generators. In: 2011 IEEE/PES power systems conference and exposition (PSCE), Phoenix, AZ, p 1 7. doi:10.1109/psce.2011. 5772545 Pal BC, Mei F (2008) Modelling adequacy of the doubly fed induction generator for small signal stability studies in power system. IET Renew Power Gen 2(3):181 190 Power System Toolbox, Version 3.0 (2008) Cherry Tree Scientific Software Sauer PW, Pai MA (2002) Power system dynamics and stability. Pearson Education Singapore Pte. Ltd. (First Indian Reprint) Taylor CW (1994) Power system voltage stability. McGraw-Hill Ryerson, Limited Van Cutsem T, Vournas C (1998) Voltage stability of electric power system. Springer Zheng C, Kezunovic M (2010) Distribution system voltage stability analysis with wind farms integration. In: North American power symposium (NAPS), 2010, Arlington, TX, pp 1 6