Polygyr -Compact Exhaust Air Temperature Controller

Similar documents
SAV Electronic Valve Actuator

SAX Electronic Valve Actuator

Air damper actuators

Use. Functions. OpenAir TM. Rotary version, modulating, with spring return, AC 24 V

Flowrite 599 Series SAX Electronic Valve Actuator Non-spring Return, 24 Vac, 3-Position Control

OpenAir Electric Damper Actuators GBB/GIB Series NSR Rotary 24 Vac - Modulating Control

SKD U Electronic Valve Actuator

SKD U Electronic Valve Actuator

Powermite 599 Series MZ Series SSB Electronic Valve Actuator 24 Vac Proportional Control

OpenAir GBB/GIB Series Electronic Damper Actuators Non-Spring Return, 24 Vac, Modulating Control

OpenAir Electric Damper Actuators GDE/GLB Series Non-spring Return Rotary 24 Vac - Modulating Control 0 to 10 Vdc

OpenAir GBB/GIB Series Electronic Damper Actuators Non-Spring Return, 24 Vac, Modulating Control

OpenAir Electric Damper Actuators GDE/GLB Series Non-spring Return Rotary 24 Vac - Modulating Control 0 to 10 Vdc

Powers TM Controls EA 338 Electronic Actuator

SAX Electronic Valve Actuator

Technical Instructions Flowrite 599 Series SKD6xU Electronic Valve Actuators 24 Vac Proportional Control Description Features Application

Electromotoric Actuators

Flowrite 599 Series SKB/C Electronic Valve Actuator 24 Vac, 3-Position (Floating) Control

Flowrite EA 599 Series SKB/C/D 62UA Series Electronic Valve Actuator 24 Vac Proportional Control Advanced Features

SKD62UA Series Electronic Valve Actuator, Advanced Features

Flowrite EA 599 Series SKD Electronic Valve Actuator 24 Vac Proportional Control

Flowrite EA 599 Series SKD Electronic Valve Actuator 24 Vac 3-Position (Floating) Control

Technical Instructions. SQV Series Electromotive Valve Actuators. Document No

GDB..3..1A GLB..3..1A

Flowrite EA 599 Series SKB/C/D 62UA Series Electronic Valve Actuator 24 Vac Proportional Control Advanced Features

OpenAir Electronic Damper Actuators GLB Series Enhanced Non-spring Return Rotary

Flowrite EA 599 Series SKB/C Electronic Valve Actuator 24 Vac, 3-Position (Floating) Control

Powermite 599 MT Series SSC Electronic Valve Actuator, 24 Vac Proportional Control

Flowrite EA 599 Series SKB/C/D 62UA Series Electronic Valve Actuator 24 Vac Proportional Control Advanced Features

Air damper actuators

Technical Instructions Document No EA GQD May 6, OpenAir GQD Series. Spring Return, 20 lb-in (2 Nm), Rotary Electronic Damper Actuators

Powermite 599 Series MZ Series SSB Electronic Valve Actuator 24 Vac Floating Control

OpenAir Electric Damper Actuators GDE/GLB Series Non-spring Return Rotary 24 Vac - Modulating Control 0 to 10 Vdc

SKP Series SKP25 U.. Pressure Regulating Gas Valve Actuator with Safety Shut-off Function

Powermite 599 MT Series SSC Electronic Valve Actuator, 24 Vac Proportional Control

Temperature Controller (Heat Pumps)

SKP Series SKP15 U.. Gas Valve Actuator with Safety Shutoff Function

Powers TM Controls RL 243 SW Switching Relay

Powers TM Controls Three-way Electro-pneumatic (EP) Valve Model 2

BACnet Lab and Pressurized Room Controllers with Off-board Air Modules

Powers TM Controls SW 141 Differential Static Airflow Switches

OpenAir GCA Series Spring Return 142 lb-in Electronic Damper Actuators

OpenAir Electric Damper Actuator GDE/GLB Series Non-spring Return Rotary 24 Vac 3-position Control

MF Series MS Series

VE VVG Series Electronic Two-way Valves Normally Closed

OpenAir Electric Damper Actuator GDE/GLB Series Non-spring Return, 24 Vac Floating Control, Rotary

Electromotoric Actuators

Electromotoric actuators

Electromotoric Actuators

Electric actuators for small valves

Actuators for small valves

MVF461H Series Modulating Control Valves with Magnetic Actuators, Positioning Control and Position Feedback for Hot Water and Steam

Technical Instructions Document No P25 EA GMA January 19, OpenAir. GMA Series Spring Return Rotary Electronic Damper Actuators

Technical Instructions Document No P25 EA GMA May 19, OpenAir. GMA Series, Spring Return, 62 lb-in, Rotary, Electronic Damper Actuators

Powermite 599 MT Series SQS Electronic Valve Actuator, 24 Vac, Floating Control (3-position)

DuraDrive MF /MS Series Non-spring Return Rotary Electronic Damper Actuators 24 Vac Three-position/Modulating

ML7420A/ML7425A,B. Honeywell. Electric Linear Valve Actuator FEATURES SPECIFICATIONS GENERAL SPECIFICATION DATA

We reserve the right to alter data according to improvements made. Previous documents become invalid with the issue of this document.

M9116, M9124, and M9132 Series Electric Non-spring Return Actuators

POWERS CONTROL RC 195 Multiple Input Receiver- Controller

Mount directly to 1.05 jackshafts. (new ZG-120 bracket shown) EFB24-S N4, EFX24-S N4(H) EFB24-S, EFX24-S (p. 21)

POWERS Controls. Technical Instructions Document No P25 AP December 3, No. 6 Pneumatic Damper Actuator.

VVP45 and VXP45 Series Two-port and Three-port Seat Valves ANSI Class 250 Short-stroke Valves

Flowrite EA 599 Series SQX Electronic Valve Actuator 24 Vac, 3-Position Control

Special voltages: Voltage >500 V AC are only permissible with external control box. 3-phase AC Voltages/frequencies. 1-phase AC Voltages/frequencies

Owner s Manual. DC-DC Step Down Converter

SQL35.00 SQL85.00 SQK angle of rotation

MF /MS Series

POWERS TM CONTROLS SW 786 Selector Switch

OpenAir. Technical Instructions. GCA Series Spring Return 160 lb-in Electronic Damper Actuators. Document No P25 EA GCA-1.

S10010 / S SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS 10/20 Nm (88/177 lb-in) FOR MODULATING AND FLOATING CONTROL SPECIFICATIONS GENERAL

Pressure Independent Control Series 2-Way Valves and Electronic Valve Actuators

Powers TM Controls SW 134 Pressure Electric Switch (Adjustable Differential)

Differential pressure sensor

LF Series Spring Return Direct Coupled Actuator

EL5600 Series Electric Actuators for DN15 to DN100 Valves

S1024-2POS / S POS S2024-2POS / S POS

Powermite 599 MT Series SSC Electronic Valve Actuator, 24 Vac Floating Control

Electromotoric Actuators

Damper Actuators Non-Spring Return

Powermite 599 MT Series Terminal Unit Valve and Actuator Assembly Selection

Laboratory Room Controller

Flowrite AP 599 Series

MS Application. Features. Proportional Valve Actuator General Instructions

Metasys Zoning Package Installation

Laboratory Exhaust Air Terminal

Powers Controls TT 184 Temperature Transmitters

POWERS Controls No. 4 Pneumatic Damper Actuator

POWERS TM CONTROLS LC Pneumatic Damper Actuator

Series 71, 72, and 76 Modutrol IV Motors

MagSpring. Courtesy of Steven Engineering, Inc. - (800)

TAC DuraDrive Product Guide Direct Coupled Actuators

SmartX MF and MS

Powers Controls No. 6 Damper Actuators Tandem Mounting

Powers Controls No. 6 Pneumatic Damper Actuator

2-position electric actuators with Ball valves VBZ ½...11/4

Commercial Actuator Selection Chart Non-Spring Return

Model Number Structure

Powers Controls RL 147 Positioning Relay

OpenAir Electric Damper Actuator GDE/GLB Series Non-spring Return, 24 Vac Floating Control, Rotary

Transcription:

Document No. CM1N3405E-P25 Polygyr -Compact Exhaust Air Temperature Controller Features Two outputs for heating and cooling Continuous control signal Application P control Electronic 24 Vac The RCM61.21 is used for controlling exhaust air temperature in smaller ventilating and air conditioning installations (by heating and cooling). Application examples: Individual installations, (restaurants, conference rooms, storage rooms, etc.) Parts of larger installations (ancillary air handling units used in conjunction with central air handling equipment). The following units can be controlled: Heating and cooling valve actuator Air damper actuator Step controller or current valve for electric air heater battery Signal converter The temperature controlled by the RCM61.21 can be shifted by: the outdoor temperature to obtain summer/winter compensation. a building automation system to obtain set point adjustment (fixed value shift). It is also possible to provide low limiting of discharge air temperature. Product Number Ordering RCM61.21 When ordering, specify quantity, product number and description.

Polygyr-Compact Exhaust Air Temperature Controller Function The RCM61.21 provides P control. The P band can be adjusted. The controller compares the actual value with the set point and generates a proportional control signal when a deviation occurs. The control signal is continuous and has a range of 0-10 Vdc. When the control signal changes from 0 10 Vdc, the correcting variable changes from 0-100%, i.e., there is a proportional relationship between the correcting variable and the control signal. The adjusted Xp (proportional band refers to heating (). The P band for cooling ()is half as wide, making it possible to obtain the same control quality for both heating and cooling, although the control conditions are different (nearly the same plant gain with different correcting spans). Between the two outputs there is a fixed dead zone. The proportional offset is zero when the load is zero (actual value = set point). Each control output generates a control signal of 0 10 Vdc. The outputs are switch in sequence and their mode of operation is opposed: One output for heating and one for cooling. Y 10V SASC0009R1 Xp 0 Xdz X - W W X Xdz Xp Y Set point Actual value Dead Zone P band Signal voltage Heating Cooling Figure 1. Compensation The reference value is fed to the controller, which shifts the set point. There are two possibilities: Universal compensation over the whole setting range or over any part of the setting range with the help of the RZF61.100 universal shift controller, or from a building automation system. Set point adjustment within ± 10% of the setting range; this is generally made from a building automation system. For more information on compensation, see Application Notes. Low Limiting of Discharge Air Temperature Design Features The RCM61.12 discharge air temperature controller serves as a limiter. Its control signal is fed to the exhaust air temperature controller, preventing the discharge air temperature from falling below the selected low limit value. See Technical Instructions CM1N3406E-P25. The RCM61.21 is a small, electronic controller that combines controller, setting unit and sensing element into one unit. The casing is plastic with a removable cover, fully active flexible sensing element, and removable mounting flange with adjustable positions. All setting devices and connecting terminals are contained in the housing and accessible only when the cover is removed. Page 2

Polygyr-Compact Exhaust Air Temperature Controller Technical Instructions Design Features, Continued 1 Connecting terminals 2 Slider for setting the desired value 3 Setting scale 4 Selector switch for mode of operation 5 Setting potentiometer for Pband 6 Mounting flange 7 Flexible sensing element Figure 2. The scale and slider for setting the desired temperature can be seen through a window in the cover. Knock-out holes (Pg11) provide entry for the cables. After fitting the mounting flange to the duct wall, the controller can be installed in seven different positions so that, with layers of insulation up to 2.76 inches, the controller housing will not be insulated. The sensing element can be bent and adapted to the shape of the duct. It senses the average temperature in the duct because the measuring element (Ni wire) extends over the total length of the flexible sensing element. Unit Combinations The RCM61.21 can control various units with the following characteristics: Remote Setting Units Type of control 10 Vdc Operating voltage 24 Vac The FZA21.11 remote setting unit is used for remote setting of the desired value. Specifications Operating voltage 24 Vac ± 20% Frequency 50 60 Hz Power consumption 1 VA Control signal: Voltage 0 10 Vdc, continuous Current 1 ma Measuring element LG-Ni 1000 Ω 15 32 F (0 C) Time constant 30 s at 6.5 ft/s Setting ranges Set point 32 122 F (0 50 C) Proportional band Xp 1.8 9 F Dead zone Approx. 2.7 F Permissible ambient temperature: Operation 14 122 F (-10 50 C) Transport and storage -13 149 F (-25 65 C) Cable entry fitting Pg11 Connecting terminals for 2 x 14 AWG or 1 x 12 AWG Weight 0.55 lb. Page 3

Polygyr-Compact Exhaust Air Temperature Controller Application When the unit is switched off or the power supply interrupted (Terminal G), the regulating unit is automatically run to the closed or no-load position. A transformer is required to generate the operating voltage of 24 Vac. When several units are connected, the size of the transformer is determined by adding up the power consumption of the individual units. See Wiring Diagrams for connecting terminal designations. The RCM61.21 can control up to 10 units (actuators, converters, etc.) in parallel operation. If a compensation input is used, attention must be paid to the input signal. Terminal Z1: Terminal Z3: Input for universal compensation. The signal + 5V ± 10V corresponds to ± 100% of the theoretical setting range. Input for set point adjustment (fixed value shift) from a building automation system. The signal + 5V ± 5V corresponds to ± 10% of the theoretical setting range. Mounting Mounting location: In the exhaust air duct as close as possible to the room, or in the main air duct if there are several air outlets; always in front of the exhaust air fan. The flexible sensing element should be positioned diagonally in the duct, but must not come in contact with the duct wall. Installation Instructions are supplied with the unit. Commissioning The correct operation of the regulating unit can be checked by setting the slider to its limit positions. The factory-set P band Xp normally gives good control results. If readjustment is required, the following must be noted: In case of instability: Xp must be increased. In case of excess stability: Xp must be decreased. If auxiliary control functions (e.g., limitation, compensation) are fed to the controller, the controlled value must first be adjusted, with no influence from the auxiliary control functions. To do this, the terminals for auxiliary units must be disconnected. The auxiliary values are adjusted only after the controlled value is adjusted. If a remote setting unit is used, the slider for setting the desired temperature must be set to ext. Page 4

Polygyr-Compact Exhaust Air Temperature Controller Technical Instructions Wiring Diagrams The following wiring diagrams only show the fundamental layout. They do not contain the switch off functions and other switching functions which can vary from one installation to another according to the operating conditions. SP R M R1 24V~ RM Z1 Z3 G Z9 N1 SASC0011R1 SN Figure 3. Exhaust Air Temperature Control with Remote Setting Unit. SP R M R1 24V~ RM Z1 Z3 G Z9 N1 Z1 Z3 R M G N2 SASC0012R1 SN N1 N2 R1 RCM61.21 Exhaust Air Temperature Controller RCM61.12 Discharge Air Temperature Controller FZA21.11 Remote Setting Unit Actuator for (heating) Actuator for (cooling) Figure 4. Exhaust Air Temperature Control with Low Limiting of Discharge Air Temperature. Terminal Layout SASC0010R1 G Z1 Z3 Z9 R Figure 5. Terminal Layout. M G, Operating voltage 24 Vac G System potential (SP) System neutral (SN) M Measuring neutral R Set point signal Control signal 0 10 Vdc for heating Control signal 0 10 Vdc for cooling Z1 Reference signal + 5V ± 10V Z3 Reference signal + 5V ± 5V Z9 Limiting signal 0 10 Vdc Page 5

Polygyr-Compact Exhaust Air Temperature Controller Dimensions 2.76 4.33 0.24 min. 1.57 max. 3.94 min. 2.76 max. 0.39 4.02 0.75 0.79 1.97 16.73 0.08 4.02 2.36 3.15 0.24 SASC0008R1 ~0.91 2.13 Pg.11 1.02 1.02 Figure 6. Dimensions in Inches. Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. Polygyr is a trademark of 2000 Landis & Staefa Division 1000 Deerfield Parkway Buffalo Grove, IL 60089-4513 U.S.A. Document No. CM1N3405E-P25 Printed in the U.S.A. Page 6