GENSET CONTROL MODULE LEVEL 0 A120A. User selectable time delays for engine start and engine stop (cool down).

Similar documents
GENSET CONTROL MODULE A121H / A241H. User selectable time delays for engine start and engine stop (cool down).

GENSET CONTROL MODULE A121A / A241A

GENSET CONTROL MODULE LEVEL 1 A121CM / A241CM. Special logic to re-establish cranking following a false start.

Flight Systems. Replacement for KASSEC DESCRIPTION

1. AC VOLTS: Displays generator output in voltage. 2. AC FREQUENCY: Displays the speed of the generator set in Hertz.

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version

HGM72 Automatic Generator Module OPERATING MANUAL Smartgen Electronic

ENGEN -100/ENGEN -200 ENGINE GENERATOR CONTROLLER

60 Series Engine Controls

DEEP SEA ELECTRONICS PLC

DEEP SEA ELECTRONICS PLC

HGM1780 AUTOMATIC GENERATOR MODULE CONTENT 1. SUMMARY PERFORMANCE AND CHARACTERISTICS SPECIFICATION OPERATION...

HGM72 Automatic Generator Module OPERATING MANUAL Smartgen Electronic

ANALOG CONTROL PANEL

MODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM

Deep Sea Electronics Plc

HGM1770 Automatic Generator Control Module OPERATING MANUAL Smartgen Electronic

Cascade CD101 Auto-Start Controller. Installation and Operations Manual Sections 40 & 75

702 AUTOMATIC START MODULE OPERATING INSTRUCTIONS

DKG-114 MANUAL AND REMOTE START UNIT

5220 AUTOMATIC MAINS FAILURE MODULE OPERATING MANUAL

ES52 Auto Start Engine Controller Installation and User Manual for the ES52 Auto Start Engine Controller.

HGM1780. Automatic Genset Controller USER MANUAL. Smartgen Technology

GSC300 Auto Start Engine Controller

Generator Start Control Module

DEEP SEA ELECTRONICS PLC

DEEP SEA ELECTRONICS PLC

GCU-10. Automatic Engine Control Unit Operators Manual

Generator Start Control Module

HGM6410/6420 AUTOMATIC GENERATOR MODULE WITH J1939 INTERFACE SOFTWARE MANUAL

DEEP SEA ELECTRONICS PLC

Cat/DCG-6D1I/07-08/03/Ver 1 Page 2/10

ECU-02 Ver2.1 Automatic Engine Control Unit Operators Manual

DEEP SEA ELECTRONICS PLC

GSC300. Auto Start Engine Controller. Installation and User Manual for the GSC300 Auto Start Engine Controller. Full Version

PSM72H Push-Button Start Module

PowerCommand 1.1 control system

DSEULTRA DSE6000 Quick Start Guide Document Number

PowerCommand 2100 digital generator set control

Auto Mains Failure AMF Controller AE10113

ES52. Auto Start Engine Controller. Full Version. Installation and User Manual for the ES52 Auto Start Engine Controller.

Starting System DS-102 Series 200. Elmatik AS P.O.Box 309 NO-3471, Slemmestad T F

HGM501 Gen-set Controller USER MANUAL. Smartgen Technology

REVISION HISTORY REVISION HISTORY

OPERATING INSTRUCTION: DGC-6D/6D1I

DEEP SEA ELECTRONICS PLC

Deep Sea Electronics Plc

XCITE Owner s Manual. Reso-not TM Damping System XCITE 1502C HYDRAULIC POWER SUPPLY

Diesel generator set C17D5T series

ECU. Speed Switch Manual. Contents. ECU is a registered trademark of Engineering Concepts Unlimited Inc.

Energy Division

Te 803 Electronic Controller. Service, Operation & Technical Information Manual

Manual and Remote Start Unit with Key Switch, 72x72 DIN Size

GENERATOR START CONTROL MODULE

GSC300 Auto Start Engine Controller

EPM72 Engine Protection Module

R-200A R-200B Digital Controller TECHNICAL MANUAL. A new standard of reliability. This manual should remain with the unit.

HP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control

R & D SPECIALTIES ROTROL I USER'S MANUAL

GPU Equipment Operating Instructions Table of Contents

Generator Start Control Module

HGM1750 Genset Security Module USER MANUAL Smartgen Technology

OTEC Transfer switch open transition

DEEP SEA ELECTRONICS PLC DSE3210 Configuration Suite Software Manual

Phoenix Inverter

Dash8-200/300 - Auxiliary Power Unit APU CONTROLS AND INDICATORS. Page 1

Application Engineering

Commander 15i Container and Pallet Loader. Property of American Airlines

GENERATOR START CONTROL MODULE

IMI vibration switch USER MANUAL INSTALLATION - OPERATION - MAINTENANCE

R-200A R-200C Digital Controller TECHNICAL MANUAL. A new standard of reliability. This manual should remain with the unit.

AUTOMATIC STAND-BY AND PEAK-LOAD CONTROL

R-200A Digital Controller TECHNICAL MANUAL. A new standard of reliability. This manual should remain with the unit.

DG SYNCHRONIZING &AMF PANEL

4.2 Component Identification

Transfer switch OTEC and OTECSE open transition

C.E. Niehoff & Co. C703/C703A and C706 Alternators Troubleshooting Guide CAUTION. Testing Guidelines. Hazard Definitions WARNING.

Generator Sets Controller 210. Operation Manual. Ver1.0

Application Engineering Europe

Transfer switch GTEC open or delayed transition

C.E. Niehoff & Co. C505, C527, C531, and C534 Alternators Troubleshooting Guide CAUTION. Testing Guidelines. Hazard Definitions WARNING

REVISED ATM72 Auto Transfer Module

Energetech LLC 7427 S. Main (P.O. Box 400) Midvale, Utah (801) Ph. (801) Fx.

AUTO-EC-3-E-PLC Electric Filter Backwash Controller Operation & Maintenance Manual

Operator s Series 300 Generator Paralleling System

MB A 12V/24V DC PROGRAMMABLE DUAL BATTERY ISOLATOR

Generator Controller Manual

DKG-215 MANUAL AND REMOTE START UNIT

Section 3 Technical Information

INSTALLATION MANUAL ACL 5500 COMBUSTION SAFETY CONTROLLER

C.E. Niehoff & Co. C840D Alternator Troubleshooting Guide CAUTION. Testing Guidelines. Hazard Definitions WARNING.

PowerCommand Digital generator set control

HGM6320T AUTOMATIC GENERATOR CONTROLLER USER MANUAL

Users Manual. Defender 1 8.0KW to 14.0KW Online Emergency Lighting Inverter. Technical Manual # Revision B

TROUBLE SHOOTING FOR NEGATIVE GROUND TRUCKS

OPERATING INSTRUCTIONS MCP-MT1

DGC-2020 DIGITAL GENSET CONTROLLER

Digital generator set control PowerCommand 3100

Tekleen GB6 & GB7 USERS AUTOMATIC FILTERS, INC. MANUAL

GTEC Transfer switch open transition

Transcription:

Technical Data Sheet GENSET CONTROL MODULE LEVEL 0 A120A Features: One model for both spark ignition and diesel engines. 4-alarm light outputs with automatic lamp-test provision. Overspeed adjustment not required. (Overspeed trip point pre-programmed in firmware.) Factory selectable starting mode: single-cycle crank limiter (standard), or full cycle-cranking (optional). A120A Control Module Shown with industrial compression-type terminal blocks. Industrial vertical plug-in type header also available. User selectable time delays for engine start and engine stop (cool down). Loss of speed signal protection for crank motor circuit. Special logic to re-establish cranking following a false start. Special logic permits re-starting of hot engine. General Description: The Genset Control Module is a microprocessor based control system which provides complete automatic control of standby generator set engines. Fuel solenoid and/or ignition control, and cranking control are via heavy duty industrial type relay contacts. Engine temperature and oil pressure monitoring are obtained from engine mounted sensor contacts. Overspeed shutdown and crank termination control are provided internally via main generator frequency monitoring input terminals.

Technical Data Sheet A120A Specifications Input Voltage: 12VDC nominal, 16VDC max; transient and reverse polarity protected. (Typical: Pickup at 10VDC, Dropout at 6VDC.) Supply Current: 0.4A maximum plus alarm light burden. Relay Load Contacts: 20A at 28VDC. Shutdown Input Contacts: 2 (See operating instructions for start-up override times.) Main Generator Frequency Input: 120VAC nominal, 150VAC maximum. Overspeed trip point is fixed at 69Hz. Crank disconnect is fixed at 16Hz. (Approximately 500 RPM) Crank Control: Standard: Single-cycle crank limiter: continuous 48 sec. crank period (non-adjustable.) Optional: Cycle cranking: 5 cycles of 12 sec. crank and 12 sec. rest (non-adjustable.) Time Delays (optional): Delay on start from remote signal: 3 sec. (non-adjustable.) Delay on shutdown from remote signal: 3 min. (non-adjustable.) Lamp Test: Alarm lights are automatically tested each time engine is started. Shielding: Internal EMI shielding provided. Ambient Temperature: -25 F to +140 F Finish: PC Board: Protected with moisture/fungus proof varnish. Chassis: Zinc plated / yellow dichromate. Cover: ABS plastic. Terminal Blocks: Standard: Industrial vertical fixed compression type terminal block. Optional: Industrial vertical plug-in type header for use with customer supplied socket connector, to ease wire harness assembly and installation: 8 point socket connector: Wieland #25.345.3853.0, Phoenix Contact #1792304 (Digikey #277-1046-ND) 5 point socket connector: Wieland #25.345.3553.0, Phoenix Contact #1792278 (Digikey #277-1043-ND) Bouchette Electronics, Inc. N11325 County Highway Y, Clintonville, WI 54929 (715) 823-7770 (715) 823-7771 Fax www.bouchette.com

Technical Data Sheet A120A Dimensions Bouchette Electronics, Inc. N11325 County Highway Y, Clintonville, WI 54929 (715) 823-7770 (715) 823-7771 Fax www.bouchette.com

Operating Instructions GENSET CONTROL MODULE LEVEL 0 A120A / B120A Control Switch Inputs The following operator panel controls are wired into the microprocessor through the frontmounted terminal blocks: 1. Run/Stop/Auto Switch. a. Run position causes the engine to start and run immediately. b. Auto position allows the unit to be controlled via any remote single-pole dry-type contact (transfer switch, remote start switch, etc.). Contact closure causes the unit to start and run, while contact opening causes the unit to shut down. Also see Time Delay Select for time delay options. c. Stop position de-energizes the control module for immediate shutdown. Lamp Test The microprocessor automatically performs a lamp test routine each time the engine starts: All lamps illuminate immediately with the start signal, then extinguish one at a time at approximately 1-second intervals. Relay Functions 1. Master Control Relay (FS). Operates the fuel solenoid and/or ignition control. 2. Cranking Control Relay (CS). Controls engine cranking functions. A120A / B120A Operating Instructions Page 1 of 4

Operating Instructions Safety Shutdown Inputs 1. Low Oil Pressure (LOP) Shutdown. Monitoring of oil pressure begins 12-seconds after the unit starts and remains in effect until the unit is shut down (except as noted in section Microprocessor Program Notes.) Except as noted, closure of this contact while engine is running results in an engine fault shutdown with alarm light indication. The LOP signal is derived from an oil pressure sensor switch mounted on the engine. 2. High Water Temperature (HWT) Shutdown. The engine coolant temperature sensor monitoring begins immediately with the start signal. However, if the water temperature is excessive prior to start, (i.e., heat soak after shutdown), the unit is permitted to start and the high temperature condition is permitted to exist for up to 60-seconds after the unit is running, before an engine fault shutdown with alarm light indication occurs. If the high temperature condition is corrected within that time period, the microprocessor circuit reverts to normal monitoring. Except as noted, closure of this contact while engine is running results in an engine fault shutdown with alarm light indication. The HWT signal is derived from a temperature sensor switch mounted on the engine. 3. Overspeed (OS) Shutdown. Overspeed shutdown protection is provided by a frequency sensing network within the control module. The OS signal is derived from a 120VAC winding of the main generator. The trip point of the frequency network is factory set at 69Hz. Exceeding this speed will result in an engine fault shutdown with alarm light indication. A120A / B120A Operating Instructions Page 2 of 4

Operating Instructions Cranking Control 1. Overcrank (OC) Protection. Two different cranking cycles are available from the factory for programming into the control modules microprocessor: a. Single-Cycle Cranking Feature (Standard). This feature provides a single, non-adjustable, crank period of 48-seconds. Failure of the engine to start within that time results in an overcrank engine fault shutdown with alarm light indication. b. Cycle Cranking Feature (Optional). This feature provide a series of five cranking cycles; each containing a 12-second crank period with a 12-second rest period. Failure of the engine to start by the end of the fifth crank period results in an overcrank engine fault shutdown with alarm light indication. 2. Cranking Disconnect. The cranking termination speed is obtained from the frequency network within the control module. The microprocessor automatically sets the cranking termination speed at approximately 500 RPM. 3. Loss of Frequency Signal. The microprocessor will detect an absence of frequency signal while cranking. After the first 12-seconds of cranking, the overcrank light begins a staggered flashing pattern to indicate there is no frequency signal input. If the cycle cranking feature (1.b above) was selected; the microprocessor automatically converts to the single-cycle cranking feature (1.a above). This conversion prevents the starter motor from re-engaging during the second crank cycle in the event the engine is already running. Also see section Microprocessor Program Notes. Time Delay Select Combination Delay-On-Start and Cool-Down timing feature: The control module may be fieldconverted to include this feature by grounding the TDI terminal on the control. This feature will delay the start-up of the engine for 3-seconds after the Remote Run contact is closed, and it will delay the shutdown of the engine for 3-minutes after the Remote Run contact is opened. This timing feature can be made active only in the Auto switch position, and still permits instantaneous manual starting in the Run switch position. Placing the selector switch in the Stop position provides instantaneous shutdown of the engine under all conditions. The start delay is intended to prevent unnecessary start-ups from momentary remote run signals, and the stop delay is intended to provide a cool-off running period for the engine after load removal. A120A / B120A Operating Instructions Page 3 of 4

Operating Instructions Microprocessor Program Notes Internal protection against loss of frequency input signal is programmed in after the unit has started normally. In the event the frequency goes to zero (engine runs out of fuel, frequency signal source fails, etc.), the LOP shutdown circuit is bypassed and a 12-second wait period is initiated. If the frequency returns within this time period, LOP monitoring resumes and operation continues normally. If frequency has not returned at the end of this time period, the engine oil pressure status is observed to determine whether the engine is actually running or stopped. If the engine has stopped, the cranking cycle will begin in an effort to re-start the engine. If the engine has not stopped (loss of input signal, etc.), the unit is shut down with an overcrank engine fault with alarm light indication. Caution: Overcrank indication can mean a loss of frequency input signal during the previous run period. Attempting to re-start the engine without any frequency input signal can destroy the starter motor, which can cause serious personal injury. The frequency signal source is a key component in this system and must be checked out thoroughly whenever an overcrank shutdown occurs, since the control module only provides an indication of loss of signal during startup. Resetting A Fault Shutdown A shutdown with alarm, due to any fault condition, will prevent any subsequent operation of the generator set. The Run/Stop/Auto switch on the operator control panel must be momentarily placed in the Stop position to reset these functions. Bouchette Electronics, Inc. N11325 County Highway Y, Clintonville, WI 54929 (715) 823-7770 (715) 823-7771 Fax www.bouchette.com

FREQUENCY SENSING FROM MAIN AC GENERATOR Bouchette Electronics, Inc.